TM No.1, 6 th Street, Dr. Subbarayan Nagar, Kodambakkam, Chennai - 600 024. India. Ph. No. : +91 –...
-
Upload
terrance-chapman -
Category
Documents
-
view
221 -
download
0
Transcript of TM No.1, 6 th Street, Dr. Subbarayan Nagar, Kodambakkam, Chennai - 600 024. India. Ph. No. : +91 –...
TM
No.1, 6th Street, Dr. Subbarayan Nagar,Kodambakkam, Chennai - 600 024. India.
Ph. No. : +91 – 044 – 24812420Fax No.: +91 – 044 – 24812475
TM
series….
IH 153E – IR Ember Detector
for
Coal Conveyor Fire Protection
TM
About Ourselves
1985 – M/s. Agni Controls Established as Custom Built Panel Manufacturer
1987 – Started to Manufacture Conventional Fire Alarm Panel
1988 – Started to provide Gas Based Extinguishing System as a specialized Fire Protection Engineering Company
1991 – Developed Special Infra Red Technology Spark Detectors for protecting Ducts
1993 – Developed Special Probe Type Heat Detector for Paint Booths, Kitchen Hood and Battery compartments
TM
About Ourselves
2003 – Developed Water Mist System
2003 – Developed Gas Weight Monitoring Device suitable for Gas Based Systems
2003 – Introduced the brand Name for the Gas Based Systems & Components
2003 – Developed Ultra-Violet & Infra Red type Flame & Ember Detectors
2005 – Introduced the brand Name SERIES… for all Special Application Products – Flame/Ember/Spark/Heat Detectors
2007 – Introduced Fully Integrated & Tested Cylinder Bank Assembly
TM
R
R
TM
The Systems We Offer CO2 Fire Extinguishing System & Components
Continuous Gas Weight Monitoring System & Components
Inert Gas Clean Agent System & Components
Fire Alarm System & Components
Intrinsically Safe Fire Protection System & Components
Diversion / Spark Detection System & Components
Special Application Detectors
COAL CONVEYOR PROTECTION
TM
INTRODUCTION* If a smoldering coal or embers are introduced due to spontaneous
combustion onto a conveyor during a loading and unloading operation, it
is every possibility to be conveyed to a transfer point, crusher or silo or
bunker.
* At such places hot coal may ignite combustible dust accumulations and
may lead to large scale Fire incident.
* Critical Equipment losses, production loss, property loss, loss of human
life are need not to be elaborated.
* Coal Conveyer Fire Protection is very much essential and important.
TM
WHAT IS EMBER
TM
PROTECTING COAL CONVEYOR
CONVEYOR BELT
LHS CABLE FOR PROTECTING
CONVEYOR BELT
PROTECTING COAL CARRIED IN CONVEYOR BELT
TM
DETECTION IN COAL CONVEYOR PROTECTION
DETECTORS APPLICATION
SMOKE X CANNOT BE USED AS THE AREA IS DUSTY IN ENVIRONMENT
POINT TYPE HEAT
X LESS EFFECTIVE AS THE FIRE IS NOT STATIC
LHS CABLE √ USED TO PROTECT THE CONVEYOR BELT AS THE SAME IS A COSTLY INVESTMENT
FLAME DETECTOR
X LESS EFFECTIVE AS IT CAN DETECT ONLY FIRE WITH FLAMES. COAL PRODUCES EMBER AT ITS EARLIEST STAGE.
EMBER √ VERY EFFECTIVE AS IT CAN DETECT THE COAL FIRE AT ITS EARLIEST STAGE AND
ALSO WHILE THE COAL EMBER IS MOVING ON THE CONVEYOR
IH 153E – Infra Red Ember Detector
TM
TM
BASIC CONCEPT
Infra Red Ember Detector are used to detect hot
moving spots on the conveyor before they reach
processing machinery or storage hoppers and initiate
alarm and Fire Extinguishing arrangement.
PRINCIPLE OF DETECTION
Hot Carbon Dioxide and Carbon Monoxide produced by the Coal
Ember is emitting Infra Red radiation. IR Sensor in the Detector
responds when the Ember enters the sensor filed of view.
TM
PRODUCT INTRODUCTION
• Agni Controls is pioneer in IR Technology.
• Our IR Spark & Ember are widely used in Machinery Protection especially in Textile Industries for last 18 years.
• More than 5000 Nos. of IR Spark/Ember Detectors are in operation.
• fladet - IH153E Infra Red Ember Detectors are specially designed to detect moving ember with 90 Deg. Cone view.
• Detector is designed with four independent Infra Red Sensors and special electronic logic analysis is used to give the best result.
• IH 153E IR Detector with IP 67 protection is well suitable for dusty environments.
TM
IH – 153Efladet IH 153E IR Detector with unique features makes the detector
user friendly and least maintenance requirement.
• Flashing Green LED indicates healthiness of the Detector 4 wire system 2 wire for Input Supply and 2 wire suitable to connect any Standard Fire Alarm Zone / PLC/ Annunciation.
• No Separate Control Panel is required. Any Annunciation or PLC or fire Alarm Panel can be used.
• Air Purging provision makes cleaning very simple. By connecting existing instrument air, the Glass surface can be cleaned either by
simple manual method or by automatic arrangement as per site requirement. Dedicated separate air source also can be incorporated.
• IH 323 Air Purging Unit is Stand Alone Provided with Air Blower operated on 230 V AC.
TM
IH – 153E
• The Detector is cost effective because of the above referred flexibility. • Simple mounting bracket with tilting arrangement is used to easy field erection and maintenance• Spectral Filter is 3000-14000 nm. • Because of the critical spectral range it is ineffective to sunlight, other lights.• Cone of Vision is 90 Deg. which makes wider coverage. • Wider Range of operating Temperature (-40Deg.C to 60 Deg. C) and Input supply voltage 24 V DC+/-20% ensure proper detection performance. • Non ferrous Rugged enclosure suitable for dusty and windy environment with IP 67 protection.
TMTM
TMTM
DETECTOR POSITION
RECOMMENDED MOUNTING ARRANGEMENT
FOR IH153E IR EMBER DETECTOR
TM
DETECTOR POSITION๏ Detector should be mounted on the conveyor hood or gantry structure looking down at the coal being transparent.
๏ Detector will detect 100 Sq. cm glowing coal ember at the distance of 3 ft.
๏ Detector cone of angle is 90 Deg. across the belt. It is recommend to mount the Detector at a height equal to half width of the conveyor.
๏ For increased sensitivity two Detectors are recommended if the width is more than 2 meters.
๏ It is recommended to a minimum of two Infrared Ember Detector for each conveyor.
๏ In normal practice close to the tail pulley one set of Detectors and close to Head pulley, another set of Detectors may be located.
๏ These detectors shall be wired as separate zone in the control panel.
TM
IH – 153E
IH153E SPECTRAL RESPONSE
TM
2.5 3 4 5 6 7 8 9 10 15 Micrometers
0
20
40
60
80
100 %Filter Sensitivity
TMTM
DETECTOR TYPICAL WIRING SCHEME
S S
TY PE - I
FIR
E A
LA
RM
PA
NE
LC
ON
VE
NT
ION
AL
TMTM
FIR
E A
LA
RM
PA
NE
LA
DD
RE
SS
AB
LE
TY PE - I I
DETECTOR TYPICAL WIRING SCHEME
TMTM
PA
NE
L O
R P
LC
AN
NU
NC
IAT
ION
TY PE - II I
DETECTOR TYPICAL WIRING SCHEME
TMTM
₪ Air Purging provision makes cleaning very simple.
₪ By connecting existing instrument air, the Glass surface can be cleaned either by simple manual method or by automatic arrangement as per site requirement.
₪ Dedicated separate air source also can be incorporated.
AIR PURGING
MANUAL AIR PURGING SY STEM1
TMTM
MANUAL & AUTOMATIC
AIR PURGING SY STEM2
STAND ALONE
AIR PURGING SY STEM3
AIR PURGING
TMTM
IH 323 - AIR PURGING UNIT
TMTM
STAND ALONEIH323 AIR PURGING UNIT4
For Special Detection Solutionin
Hazardous and Challenging areas
Visit us at : www.balafire.com
Please contact our Special Application Product (SAP) Division at
PhonePhone:+91-044-2481 2420
Fax: Fax: +91-044-2481 2475
Email : Email : [email protected] [email protected]
[email protected]@agnicontrols.com