POWER NETWORK IN THE LOOP: SUBSYSTEM TESTING USING A SWITCHING AMPLIFIER A Thesis by Publication Submitted in Partial Fulfilment of the Requirements for the Degree of Master of Engineering Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and Engineering School of Systems Engineering Queensland University of Technology Queensland, Australia February 2009

Transcript of Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6....

Page 1: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

POWER NETWORK IN THE LOOP: SUBSYSTEM

TESTING USING A SWITCHING AMPLIFIER

A Thesis by Publication Submitted in

Partial Fulfilment of the Requirements for the

Degree of

Master of Engineering

Sachin Goyal

B.Tech (Electrical Engineering)

Faculty of Built Environment and Engineering

School of Systems Engineering

Queensland University of Technology

Queensland, Australia

February 2009

Page 2: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

ii

Dedicated to the lotus feet of

‘Sai’

Page 3: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

iii

Acknowledgements

I take this opportunity to express my deep gratitude and regards to

Prof. Gerard Ledwich and Prof. Arindam Ghosh, my thesis supervisors, for their

incomparable guidance, supervision, constant encouragement and active participation

throughout the course of this research. Their meticulous and valuable suggestions

encouraged me to complete this work ahead of time. It has been a great privilege for

me to work with them.

I would like to acknowledge my sincere gratitude to Dr. Firuz Zare for his valued

suggestions and advices during the course of this research. The administrative and

technical staffs at the Faculty of Built Environment & Engineering, QUT, have

generously provided support and assistance during the course of my study.

Moreover, I wouldn’t have been able to complete this research without the financial

assistance provided by the Faculty of BEE.

Further thanks are due to many colleagues at the Faculty of BEE for their stimulating

discussions and friendly working environment, especially Mr. Ritwik Majumder,

Mr. Arash, Mr. Alireza Nami, Mr. Zafar, Mr. Manjula, Ms. Tania and Ms. An Le.

Achievements in life do not come alone by one’s own efforts, but by the blessings of

Omnipresent God and parents. I express my deep sense of reverence and profound

gratitude to my parents Mrs. Shakuntala Goyal and Mr. Yogesh Goyal and my sisters

for the pain and sufferings they have undergone to bring me up to this stage. I

acknowledge with utmost warmth their sacrifice, unconditional support, love and

affection.

I am indebted to my college teacher Dr. Rajesh Kumar who always encouraged me to

pursue a career in higher degree research. Also I am thankful to my friends especially

Mr. Aishwarya Bose, Mr. Mohit Gupta and Mr. Praveen Data for their constant

support and motivation.

Sachin Goyal

Page 4: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

iv

Abstract

“Hardware in the Loop” (HIL) testing is widely used in the automotive industry. The

sophisticated electronic control units used for vehicle control are usually tested and

evaluated using HIL-simulations. The HIL increases the degree of realistic testing of

any system. Moreover, it helps in designing the structure and control of the system

under test so that it works effectively in the situations that will be encountered in the

system.

Due to the size and the complexity of interaction within a power network, most

research is based on pure simulation. To validate the performance of physical

generator or protection system, most testing is constrained to very simple power

network. This research, however, examines a method to test power system hardware

within a complex virtual environment using the concept of the HIL.

The HIL testing for electronic control units and power systems protection device can

be easily performed at signal level. But performance of power systems equipments,

such as distributed generation systems can not be evaluated at signal level using HIL

testing. The HIL testing for power systems equipments is termed here as ‘Power

Network in the Loop’ (PNIL). PNIL testing can only be performed at power level and

requires a power amplifier that can amplify the simulation signal to the power level.

A power network is divided in two parts. One part represents the Power Network

Under Test (PNUT) and the other part represents the rest of the complex network.

The complex network is simulated in real time simulator (RTS) while the PNUT is

connected to the Voltage Source Converter (VSC) based power amplifier. Two way

interaction between the simulator and amplifier is performed using analog to digital

(A/D) and digital to analog (D/A) converters. The power amplifier amplifies the

current or voltage signal of simulator to the power level and establishes the power

level interaction between RTS and PNUT.

In the first part of this thesis, design and control of a VSC based power amplifier that

can amplify a broadband voltage signal is presented. A new Hybrid Discontinuous

Control method is proposed for the amplifier. This amplifier can be used for several

Page 5: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

v

power systems applications. In the first part of the thesis, use of this amplifier in

DSTATCOM and UPS applications are presented. In the later part of this thesis the

solution of network in the loop testing with the help of this amplifier is reported. The

experimental setup for PNIL testing is built in the laboratory of Queensland

University of Technology and the feasibility of PNIL testing has been evaluated

using the experimental studies. In the last section of this thesis a universal load with

power regenerative capability is designed. This universal load is used to test the DG

system using PNIL concepts.

This thesis is composed of published/submitted papers that form the chapters in this

dissertation. Each paper has been published or submitted during the period of

candidature. Chapter 1 integrates all the papers to provide a coherent view of wide

bandwidth switching amplifier and its used in different power systems applications

specially for the solution of power systems testing using PNIL.

Page 6: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

vi

Table of Contents

Acknowledgements .....................................................................................................iii

Abstract ....................................................................................................................... iv

Table of Contents ........................................................................................................vi

List of Figures ...........................................................................................................viii

List of Tables...............................................................................................................xi

Keywords ...................................................................................................................xii

List of Publications by Candidate .............................................................................xiii

Statement of Original Authorship .............................................................................xiv

CHAPTER 1 Introduction.......................................................................................1

1.1 Description of the Research Problem .............................................................1

1.2 Literature Review............................................................................................2

1.3 Account of Research Progress Linking the Research Papers .........................6

References ..............................................................................................................10

CHAPTER 2 A Hybrid Discontinuous Voltage Controller For DSTATCOM

Applications ..............................................................................................................15

2.1. Introduction...................................................................................................16

2.2. Voltage Control Structure .............................................................................17

2.2.1. The DSTATCOM model........................................................................18

2.2.2. The Reference generation.......................................................................19

2.3. Strategy for Hybrid Discontinuous Control..................................................20

2.4. Compensator Performance............................................................................26

2.5. Conclusions...................................................................................................36

Acknowledgement..................................................................................................37

References ..............................................................................................................37

CHAPTER 3 Active Power Flow Control In A Distribution System Using

Discontinuous Voltage Controller...........................................................................38

3.1. Introduction...................................................................................................39

3.2. Power Flow Control ......................................................................................41

3.2.1. The UPS model ......................................................................................41

3.2.2. Reference Generation.............................................................................42

3.3. Control Strategies..........................................................................................44

3.3.1. Hybrid Discontinuous Control ...............................................................44

Page 7: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

vii

3.3.2 State Feedback Control .......................................................................... 52

3.4. UPS Performance Evaluation ....................................................................... 53

3.5. Conclusions................................................................................................... 62

Appendix - A.......................................................................................................... 63

References .............................................................................................................. 63

CHAPTER 4 Power Network In Loop: A Paradigm For Real-Time Simulation

and Hardware Testing ............................................................................................. 65

4.1 Introduction................................................................................................... 66

4.2. The Hardware-Software Concept ................................................................. 68

4.3. Amplifier Structure ....................................................................................... 69

4.4. Hybrid Discontinuous Voltage Control ....................................................... 71

4.5. Experimental Results ................................................................................... 75

4.6. Power Network In Loop Of A Complex System......................................... 84

4.7. Conclusions.................................................................................................. 90

References .............................................................................................................. 90

Appendix - B.......................................................................................................... 91

CHAPTER 5 Testing of A Distributed Generation System With A Virtual Grid

.................................................................................................................................... 94

5.1. Introduction................................................................................................... 95

5.2. The Concept.................................................................................................. 96

5.3. The Scheme................................................................................................... 98

5.3.1. The UPS Model.................................................................................... 100

5.3.2. The Amplifier Model ........................................................................... 102

5.4. Reference Generation ................................................................................. 102

5.5. Control Strategy.......................................................................................... 104

5.5.1. Control of UPS: Hybrid Discontinuous Control .................................. 104

5.5.2. Control of Current Amplifier (Universal load): ................................... 106

5.6. Conclusions................................................................................................. 114

References ............................................................................................................ 114

CHAPTER 6 Conclusions and Future Research .............................................. 116

Page 8: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

viii

List of Figures

Figure 1. 1 Hardware-In-the-Loop Definition [40]......................................................3

Figure 2.1 Single-line diagram of shunt compensation of a load through a feeder. ..17

Figure 2.2. Compensator structure used in which three separate VSCs are supplied

from a common dc storage capacitor...................................................................18

Figure 2.3. VSC scheme to control capacitor voltage................................................21

Figure 2.4. Two zones for voltage control. ................................................................21

Figure 2.5. (a) Capacitor voltage and (b) Inductor current during DC tracking. .......23

Figure 2.6. Four regions of one cycle of a sinusoidal wave.......................................23

Figure 2.7. (a)Capacitor voltage and (b) Inductor current for AC voltage tracking. .24

Figure 2.8. (a) Capacitor voltage and (b) Inductor current for Example 2.1 .............25

Figure 2.9. Compensation of the unbalanced nonlinear load without precharged

capacitor...............................................................................................................28

Figure 2.10. Schematic diagram of the compensation scheme to pre-charge the dc

capacitor...............................................................................................................29

Figure 2.11. (a) DC capacitor voltage, (b) voltage angle at PCC, (b) PCC voltage and

(c) load currents when the dc capacitor is pre-charged. ......................................31

Figure 2.12. (a) PCC voltages, (b) voltage angle and (c) source currents for Example

2.3. .......................................................................................................................32

Figure 2.13. (a) PCC voltages and (b) voltage angle for Example 2.4. .....................33

Figure 2.14. (a) PCC voltages (b) voltage angle (c) and source currents for Example

2.5. .......................................................................................................................34

Figure 2.15 PCC Feeder switching scheme for Example 2.6.....................................35

Figure 2.16 (a) PCC voltage angle, (b) PCC voltages and (c) source currents for

Example 2.6. ........................................................................................................36

Figure 3. 1. Single-line diagram of the distribution system containing a UPS. .........41

Figure 3. 2. UPS structure containing three VSCs that are supplied from a common

source...................................................................................................................42

Figure 3. 3. VSC scheme to control capacitor voltage...............................................45

Figure 3. 4. The two zones voltage control scheme. ..................................................46

Figure 3. 5. Four regions of one cycle of a sinusoidal wave......................................46

Page 9: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

ix

Figure 3. 6. (a) Capacitor voltage and (b) inductor current for Example 3.1............. 49

Figure 3. 7. Inductor current with diode state and VSI output voltage...................... 50

Figure 3. 8. Inductor current and switching. .............................................................. 50

Figure 3. 9. Three-level modulation with state feedback control. ............................. 52

Figure 3. 10. UPS performance during load transient with Mode-1 control.............. 55

Figure 3. 11. System performance at the time of asymmetrical sag in source voltage

for Example 3.3 ................................................................................................... 57

Figure 3. 12. Mode-2 control at the time of sag and swell in the source voltage for

Example 3.4......................................................................................................... 58

Figure 3. 13. Mode-2 control during power reference change................................... 59

Figure 3. 14. Control switching at the time of mode shifting. ................................... 59

Figure 3. 15. System performance during mode switching and load change. ........... 60

Figure 3. 16. System performance during islanding and reclosing............................ 61

Figure 4. 1 Conceptual hardware-software simulation diagram: Voltage control. .... 68

Figure 4. 2 Power amplifier Structure........................................................................ 70

Figure 4. 3. Simple network under study. .................................................................. 70

Figure 4. 4. Voltage controlled VSC amplifier connection with the test side. .......... 70

Figure 4. 5. The two zones voltage control scheme................................................... 71

Figure 4. 6. Four regions of one cycle of a sinusoidal wave...................................... 72

Figure 4. 7 (a) Voltages vp1 and vp2 and (b) voltage tracking error............................ 74

Figure 4. 8. (a) Currents i1 and i2 and (b) the error between these two currents........ 75

Figure 4. 9. The test circuit of Example 4.2............................................................... 76

Figure 4. 10. Schematic diagram of the hardware setup for Example 4.2. ................ 76

Figure 4. 11. Experimental and simulation result for PCC voltage (vp) .................... 77

Figure 4. 12. Experimental and simulation result for i l.............................................. 77

Figure 4. 13. Simulation result for i l .......................................................................... 78

Figure 4. 14. Experimental result for i l during capacitor switching........................... 78

Figure 4. 15. Circuit under test for two generators interaction. ................................. 78

Figure 4. 16. Current at network tearing point (i l). .................................................... 79

Figure 4. 17. Line current passing through R2 (i l1)..................................................... 80

Figure 4. 18. Phase difference between i l1 and v2. ..................................................... 80

Figure 4. 19. Tearing point (PCC) voltage vp. ........................................................... 80

Figure 4. 20. v1 and v2 with 20° phase difference. ..................................................... 81

Page 10: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

x

Figure 4. 21. Current at network tearing point (i l). ....................................................81

Figure 4. 22. Tearing point (PCC) voltage vp.............................................................81

Figure 4. 23. Circuit under test for Example 4.4........................................................82

Figure 4. 24. Initial transients in is: (a) simulated waveform and (b) experimental

waveform. ............................................................................................................83

Figure 4. 25. Transients in is during power change: (a) simulated waveform and (b)

experimental waveform. ......................................................................................84

Figure 4. 26. The complex study system....................................................................85

Figure 4. 27. Voltage, current and their errors in Example 4.5..................................87

Figure 4. 28. Voltage, current and their errors in Example 4.6..................................88

Figure 4. 29. Voltage tracking of a complex system at the time of faults..................89

Figure 4. 30. The network considered for stability studies. .......................................91

Figure 4. 31. The test side current containing high frequency ripple components. ...92

Figure 4. 32. The distorted PCC voltage....................................................................92

Figure 4. 33. System structure with LPF....................................................................92

Figure 4. 34. Stable PCC voltage with LPF. ..............................................................93

Figure 5. 1 Conceptual hardware-software simulation diagram: Current control. (a)

The Un-torn Network (b) Torn Network.............................................................97

Figure 5. 2. Distributed Generation scheme under test ..............................................99

Figure 5. 3 Network Tearing Scheme ......................................................................100

Figure 5. 4. UPS structure used in which three separate VSCs are supplied from a

common dc storage capacitor. ...........................................................................101

Figure 5. 5 The Structure of Universal Load ...........................................................102

Figure 5. 6. VSC scheme to control capacitor voltage.............................................104

Figure 5. 7. The two zones voltage control scheme. ................................................105

Figure 5. 8 Performance of UPS in torn Network....................................................108

Figure 5. 9 Performance of UPS during load change in torn network .....................109

Figure 5. 10 Performance evolution during sag .......................................................110

Figure 5. 11 Performance evolution during Mode II operation ...............................111

Figure 5. 12 Scheme for utility feeder change .........................................................111

Figure 5. 13 UPS performance during utility feeder change....................................112

Figure 5. 14 Performance of torn network during mode change .............................112

Figure 5. 15 Fault evolution using torn network..................................................................113

Page 11: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

xi

List of Tables

TABLE 1. 1 COMPARISION OF DIFFERENT AMPLIFIERS ................................ 7

TABLE 2. 1. SYSTEM PARAMETERS................................................................... 27

TABLE 3. 1. COMPARISON OF STATE FEEDBACK AND DISCONTINUOUS

CONTROL .......................................................................................................... 55

TABLE 3. 2. DATA SHEET OF TOSHIBA SILICON N CHANNEL IGBT,

MG400J1US51.................................................................................................... 63

TABLE 4. 1: SYSTEM PARAMETERS FOR EXAMPLE-4.3. .............................. 79

TABLE 4. 2: PARAMETERS OF THE SYSTEM OF FIG. 4.24. ............................ 85

Page 12: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

xii

Keywords: DSTATCOM, Discontinuous Current, Hybrid Control, LC Output

Filter, UPS, Power Flow Control, Real-Time Simulator, Hardware-Software

Simulation, VSC, Harmonics, Bandwidth, Virtual Grid and Universal Load.

Page 13: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

xiii

List of Publications by Candidate

The following publications have been produced as a result of this thesis:

Peer Reviewed Journal Papers

1. S. Goyal, A. Ghosh and G. Ledwich, “Active Power Flow Control in a

Distribution System Using Discontinuous Voltage Controller”, Electric

Power Systems Research, 2008. pp. 255-264.

Peer Reviewed International Conference Papers

1. S. Goyal, A. Ghosh, and G. Ledwich, "A hybrid discontinuous voltage

controller for DSTATCOM applications," in Power and Energy Society

General Meeting - Conversion and Delivery of Electrical Energy in the 21st

Century, 2008 IEEE, 2008, pp. 1-8.

Journal papers under Review

1. S. Goyal, G. Ledwich and A. Ghosh, “Power Network in Loop: A Paradigm

for Real-Time Simulation and Hardware Testing”, IEEE Transaction on

Power Delivery, 2008.

2. S. Goyal, A. Ghosh and G. Ledwich, “Testing of A Distributed Generation

System With A Virtual Grid”, Electric Power Systems Research, 2008.

(Expected Submission 7 November 2008)

Page 14: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

xiv

Statement of Original Authorship

The work contained in this thesis has not been previously submitted for a degree or

diploma at any other higher education institutions. To the best of my knowledge and

belief, the thesis contains no material previously published or submitted for

publication by another person except where due reference has been made.

Signed:

(Sachin Goyal)

Date:

Page 15: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

1

CHAPTER 1

INTRODUCTION

1.1 Description of the Research Problem

Most research has been based on pure simulation due to the size and the complexity

of interaction within a power network. To validate the performance of a physical

generator or protection system, most testing is constrained to a very simple power

network. This research examines a method to test power system hardware within a

complex virtual environment.

Integration of real-time simulation with physical system gives an opportunity to test

a small system interacting with large power network. According to this concept, a

complex power network is simulated in real time digital simulators and with the help

of a high bandwidth switching amplifier; the physical system is connected in the loop

with the simulation.

Digital computer simulations have been used extensively in power systems studies

for both design and testing. However, this form of evaluation tool is often not

suitable for testing of protective devices like relays or testing real life controllers. To

alleviate this problem, real-time digital simulators have been developed, which use

high speed parallel processors to simulate a complex power network within

microseconds. These simulators can be interfaced with a physical controller on-line

and this form of operation is often termed as “hardware-in-the-loop” (HIL) testing

The aim of this research is to broaden the “hardware in the loop” concept to include

testing of power network components. For the simulation of large systems, Kron’s

method of tearing the network into two or more segments offers possibilities to test

physical hardware system with real time simulation.

Page 16: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

2

To interface the hardware model with a computer simulation and to transfer high

frequency disturbances of power network, a high bandwidth amplifier is required that

can transfer signals between simulated model and the hardware. This amplifier is

basically an inverter that can generate high frequency current or voltage component.

For testing of faults or transients, the amplifier must be capable of providing high

frequency current components.

The bandwidth of an amplifier can be increased using higher and variable switching

frequency. But variable frequency causes high switching losses and makes designing

of an output filter complex.

In this thesis, a method of amplifier control is proposed that amplifies the wide

bandwidth voltage signals with minimum number of switching events. The same

amplifier is used in DSTATCOM to supply harmonic current with large bandwidth.

Also, with the help of the amplifier, a UPS is designed that can supply a part of the

load power with power quality solution.

The main focus of this research is to provide a solution for HIL testing for power

systems which is termed here as ‘Power Network in the Loop’, with the help of high

bandwidth amplifier. Simulation and experimental studies of hardware-software

integration are shown. In the final part of this research a method is proposed to test a

distributed generation system with universal load which has the power re-generation

capacity.

1.2 Literature Review

Hardware in the loop: The terminology of “Hardware in the Loop” (HIL) is very

common in the automotive industry. The sophisticated electronic control units which

are used for vehicles are usually tested and evaluated using HIL-simulation [1-3].The

HIL testing leads to designs that function effectively in situations that will be

encountered by the electronic control unit. The concept of HIL testing for motor

controller is reported in [4, 5]. The interface of real-time controller with a simulated

circuit is reported in [6]. Controller output is sent to real time virtual test bed

Page 17: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

3

(RTVTB) through an A/D card while the simulation output is sent to micro-

controller. Here, the communication occurs at low voltage. To test the power

electronics equipments HIL concept is used in [7]. In all of the above testing the

interaction between real time simulation and hardware is done at a low voltage level.

Therefore the hardware which is under test is directly connected to simulation output.

Figure 1.1 [40] shows the basic concept of HIL, in which an engine is simulated in

the digital simulator and a physical hardware controller is interfaced with the digital

simulator.

Figure 1. 1 Hardware-In-the-Loop Definition The concept of HIL testing opens the wide area of highly realistic testing for power

systems. But power systems equipments can not be directly interfaced with real time

simulation because of its high voltage level. A small testing of power system

equipment with the concept of HIL is reported in [8]. But it does not describe the

network tearing concept. To test the power systems network with HIL concept, the

total network is torn in two parts. One part is simulated in the real time simulator and

the hardware under test represents the second part of the network.

The network tearing aspect has been studied in a two part paper [9, 10]. In Part 1 [9],

different methods of tearing are presented and compared against their performance.

This paper discusses power hardware in loop (PHIL) concept through a two way

interaction. But it does not discuss the hardware feasibility. The frequency response

Page 18: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

4

of different simulation/hardware interface schemes has been presented in [10].

However, it does not present the stability analysis aspects of the tearing.

As stated earlier, the power systems equipments can not be directly interfaced with

real time simulation. Therefore a power amplifier is required to interface power

equipment with real time simulation that can amplify the voltage or current signal of

the simulator to the level of the power equipment. An operational amplifier based

amplifier can not serve the purpose because of its power limitation. A voltage source

converter based amplifier is required to integrate the real time simulation with the

power equipment. The VSC is controlled in close loop to generate high voltage

reference signals. The control scheme of active power filters is helpful in designing

the control structure of power amplifier.

Active power filter: The primary objective of this part of literature review is to find

recent control techniques of Active Power Filters for both single and three phase.

Active Power Filters (APF) are power electronic inverters connected to the power

system for harmonic correction or to provide reactive power to correct the

fundamental voltage [11, 12]. In single phase APF, the H bridge voltage source

inverter is used and sliding mode close loop control was used to control the active

wave shaping function of the active filter[13]. This control methodology is able to

compensate for multiple nonlinear loads in parallel. But its switching frequency is

very high and not constant. This increases the switching losses and makes

suppression of switching frequency components difficult. For the three phase active

filter simple hysteretic current control is not suitable because the presence of LCL

filter generates stability issues [14-16]. It presents LQR and hysteresis control for

generating switching pulses, which is a stable control. Here, positive sequence of

fundamental Point of Common Coupling (PCC) voltage is calculated for reference

voltage. But in this case switching frequency is not constant, so it makes elimination

of this higher frequency component difficult. If switching frequency can be filtered

out, then the calculation of positive sequence of fundamental is not required.

Inverter Control: This section is to familiarise with the control techniques which

are used to control the inverter as an amplifier for active filter[17-19]. Different kind

of hysteresis current controls are discussed; based on the benefits and limitations of

Page 19: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

5

each technique, a proper method can be determined. To reduce switching frequency

losses[20] and constant switching frequency operation[21], a variable band

Hysteresis Current Control [HCC] is presented [15, 22-24]. It provides constant

switching frequency operation of APF. But to filter out this switching frequency

component, a simple R-L type filter is used. For better suppression, a capacitor is

used. Because of this capacitor, a simple hysteresis control gives stability issues so a

close loop stable control is required. A simple method to achieve constant switching

frequency by adding auxiliary signal in error signal is presented[25, 26]. But using

this technique, low switching frequency can not be achieved. This is effective only at

high frequency. The impact of addition of low frequency auxiliary signal is not

presented. An optimal voltage vector based hysteresis current control method with

constant switching frequency for APF is presented[27]. However, in this case online

position on space vector is required that could increase computation. A three level

hysteretic current control is presented to reduce the switching frequency component

in output current and voltage[28]. These switching frequency component and

switching losses can be further reduced by five level hysteretic current control[29].

But this technique increases the number of switches in the power circuit. At a

constant switching frequency, if an inverter is able to supply higher order harmonic

current then there would be some phase lag in tracked current. That increases higher

order harmonic terms in error. Simple feed-forward method is presented to overcome

this issue [30, 31]. But if load is not known then in that case simple feed-forward

method can not be used to provide harmonic current to the load.

Passive Filter: To eliminate the switching frequency component from output voltage

and current, a passive filter is used at the output of the inverter[32, 33]. Type of this

filter may vary[34]. Simple R-L type filter needs simple control but can not filter the

high frequency switching components from output voltage and current. A LCL filter

eliminates switching frequency components effectively. But it requires advance

control to operate in stable condition.

Stability: When an inverter is used as an amplifier in active filter to supply harmonic

current, stability is one of the main concern. To operate system in stable condition at

different loads, a robust control is required[35]. Fuzzy controlled APF is presented in

[36]. A comparison of different controllers with PI controller is also presented[37,

Page 20: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

6

38]. LQR control of active filter is described with hysteresis control [14, 39]. Study

of stability at resonance frequency of filter is required.

A solution for power systems equipments testing can be found using HIL concept

with the help of high bandwidth amplifier. An advance control is required for

amplifier control and the network tearing concept can be used for HIL testing for

power systems.

1.3 Account of Research Progress Linking the Research Papers

Hardware-In-the-Loop is a form of real-time testing. Hardware-In-the-Loop differs

from pure real-time simulation by the addition of a “real” component in the loop with

real time simulation. The purpose of a Hardware-In-the-Loop system is to provide all

of the electrical stimuli needed to fully exercise the hardware which is under test. In

effect, “fooling” the testing hardware into thinking that it is indeed connected to a

real plant. This concept has been used for controllers or relay testing for a long time.

Hardware can be connected to the real time simulation only if the voltage level of

both the signals (simulation and physical hardware) is same. But because of the

difference in voltage levels of simulation signal (5 volt) and power equipments (240

volt), this concept can not be used directly to test the power systems equipments. To

implement this concept in power systems testing, the simulation signal is amplified

to the level of physical hardware and the signal of physical hardware (voltage or

current) is scaled down to the level of simulation signal.

Current or voltage of physical power systems equipment can be easily scaled down

to the level of simulation signal with the help of current or voltage sensors. But to

amplify the simulation current or voltage signal to the level of physical equipment, a

power amplifier is required which can amplify the signal level to the power level.

There are some good quality analog amplifiers are available in the market that can

amplify the wide range of frequency signals. But these amplifiers can supply only

small amount of current, therefore they can not help in testing the power systems

equipments.

Page 21: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

7

To solve this problem an inverter based wide bandwidth amplifier is designed. The

amplifier is made of a voltage source converter (VSC) and a filter. The filter is used

to filter out the switching frequency components from output current or output

voltage. A comparative study of different type of control and filter structures for

current amplifier has been performed. The comparison is made based on the

following criterion:

• The average error in output current should be less than 10% of the reference.

• Each Harmonic component in current error (FFT of error) should be less than

10% of the reference.

• Switching frequency components in output point of common coupling (PCC)

voltage should be less than 5% of the fundamental component.

• Switching events should be less than 200 in one fundamental cycle (0.02s).

Using the above criterion, the following outcome is noted for 5 types of amplifier

structures:

TABLE 1. 1 COMPARISION OF DIFFERENT AMPLIFIERS

Type Filter Type

Control Switching Edges per

cycle

Order of harmonic that can be amplified

1. L Simple Hysteretic Current

control 191

Fundamental (50 Hz)

2. LC 2 Level HCC with state

feedback control. 206 9th (450 Hz)

3. LC 2 Level adaptive band HCC with state feedback control.

200 11th (550 Hz)

4. LC Fixed frequency sampled

control 200

Fundamental (50 Hz)

5. LC 3 Level HCC with state

feedback control. 205 21st (1050Hz)

From the above comparison it is clear that an amplifier with LC filter and 3 level

HCC with state feedback control can amplify the maximum range signals. All control

schemes which are described above can be used for voltage amplifier as well. For

voltage amplifier, a new hybrid discontinuous control is proposed that gives better

performance than a 3-level hysteresis band control in terms of both switching and

tracking.

Page 22: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

8

The design and control of the hybrid discontinuous controller is described in details

through chapters 2 and 3. This amplifier can be used for several power systems

applications. To investigate the efficiency of the hybrid discontinuous controller

based voltage amplifier, the amplifier is tested for the distribution static compensator

(DSTATCOM) application. Chapter 2 (A Hybrid Discontinuous Voltage Controller

For DSTATCOM Applications) describes the use of the hybrid discontinues voltage

controller in DSTATCOM application. The DSTATCOM controls PCC voltage.

Installation of a DSTATCOM at consumer premises is an effective solution to power

quality problems that originate in the distribution system.

Chapter 3 (Active Power Flow Control In A Distribution System Using

Discontinuous Voltage Controller) describes the use of hybrid discontinuous voltage

control methodology for a voltage source converter (VSC), which is used in a

Distributed Generation (DG) system which overcomes the power quality problem,

while supplying power from DGs at the same time. In case of emergency, when there

is no power from the grid, DG can supply the total load, due to this function, the total

DG system is termed as uninterruptible power supply (UPS) in this chapter. The UPS

controls the voltage at the point of common coupling (PCC). This UPS can

compensate the load at the time of sag or swell in source voltage. Also it can

compensate the load at the time of change in feeder load conditions.

The chapter 2 and 3 together describes the use of voltage amplifier in power systems.

In the later part of this thesis this amplifier is used for hardware in loop testing of

power system equipments which is termed here as ‘Power Network in the Loop’.

Chapter 4 and 5 demonstrate the feasibility of network in loop.

Chapter 4 (Power Network in Loop: A Paradigm for Real-Time Simulation and

Hardware Testing) discusses a new paradigm of real-time simulation of power

systems in which an equipment can be interfaced with a real-time simulator. The

physical system is driven by a voltage source converter (VSC) that is mimicking the

power system simulated in the real-time simulator. In this chapter, the VSC is

operated in a voltage control mode with the help of hybrid discontinuous controller

to track the PCC voltage supplied by the simulator. This type of splitting a network

into two parts and running a real-time simulation with a physical system in parallel is

Page 23: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

9

termed here as a hardware-software simulation. This opens up the possibility of the

study of interconnection of one or several distributed generators to a complex power

network. The proposed implementation is verified through simulation studies using

PSCAD/EMTDC and through hardware implementation on a TMS320F2812 DSP.

After the successful experimental testing of “Power Network In the Loop”, a testing

method for distributed generation system (DGs) is proposed with the concept of

network in loop. Chapter 5 (Testing Of A Distributed Generation System With A

Virtual Grid) provides the solution for testing of a DGs with a computer simulated

grid. The computer simulated grid is referred as a virtual grid in this paper.

Integration of DG with the virtual grid provides a broad area of testing of power

supplying capability and dynamic performance of a DG. It is shown that a DG is

supplying a part of load power while keeping PCC voltage magnitude constant. To

represent the actual load, a universal load along with power regenerative capability is

designed with the help of voltage source converter (VSC) that mimics the load

characteristic for DG. The overall performance of the proposed scheme is verified

using computer simulation studies.

Altogether chapters 2, 3, 4 and 5 illustrate the concept of an amplifier with new

control structure which can be used for several power systems applications. This

amplifier is used to provide a solution for hardware in loop testing of power systems

applications.

This thesis is based on published/submitted papers as listed below:

Chapter 2: S. Goyal, A. Ghosh and G. Ledwich, “A Hybrid Discontinuous Voltage

Controller for DSTATCOM Applications”, IEEE PES General Meeting, USA, 2008.

Chapter 3: S. Goyal, A. Ghosh and G. Ledwich, “Active Power Flow Control in a

Distribution System Using Discontinuous Voltage Controller”, Electric Power

Systems Research, 2008.

Chapter 4: S. Goyal, G. Ledwich and A. Ghosh, “Power Network in Loop: A

Paradigm for Real-Time Simulation and Hardware Testing”, IEEE Transaction on

Power Delivery, 2008.

Page 24: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

10

Chapter 5: S. Goyal, A. Ghosh and G. Ledwich, “Testing of A Distributed

Generation System With A Virtual Grid”, Electric Power Systems Research, 2008.

References

[1] S.Shaoyou, G. Feng ands. Ke, “Model of Intelligent Vehicle Cruise and

Hardware-in-the-loop Test”, IEEE International Conference on Vehicular

Electronics and Safety, 2006, PP. 329 – 332, 13-15 Dec. 2006.

[2]. E. F. Stefatos, T. Arslan, D. Keymeulen, and I. Ferguson, "Integrating the

Electronics of the Control-Loops of the JPL/Boeing Gyroscope Within an

Evolvable Hardware Architecture," in Field Programmable Logic and

Applications, 2006. FPL '06. International Conference on, 2006, pp. 1-4.

[3]. S. M. Shah and M. Irfan, "Embedded hardware/software verification and

validation using hardware-in-the-loop simulation," in Emerging

Technologies, 2005. Proceedings of the IEEE Symposium on, 2005, pp. 494-

498.

[4]. P. K. Gujarathi and M. V. Aware, "Hardware-in-Loop Simulation of Direct

Torque Controlled Induction Motor," in Power Electronics, Drives and

Energy Systems, 2006. PEDES '06. International Conference on, 2006, pp. 1-

5.

[5] S. Ayasun, S. Vallieu, R. Fischl, and T. Chmielewski, "Electric machinery

diagnostic/testing system and power hardware-in-the-loop studies," in

Diagnostics for Electric Machines, Power Electronics and Drives, 2003.

SDEMPED 2003. 4th IEEE International Symposium on, 2003, pp. 361-366.

[6] Z. Jiang, R, Leonard, R. Dougal, H, Figueroa and A. Monti, “Processor-in-

the-loop simulation, real-time hardware-in-the-loop testing, and hardware

validation of a digitally-controlled, fuel-cell powered battery-charging

station,” IEEE Power Electronics Specialists Conference, pp. 2251-2257,

Aachen, 2004.

[7] L. Bin, A. Monti, and R. A. Dougal, "Real-time hardware-in-the-loop testing

during design of power electronics controls," in Industrial Electronics

Society, 2003. IECON '03. The 29th Annual Conference of the IEEE, 2003,

pp. 1840-1845 Vol.2.

Page 25: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

11

[8] M. Steurer, "PEBB based high-power hardware-in-loop simulation facility for

electric power systems," in Power Engineering Society General Meeting,

2006. IEEE, 2006.

[9] X. Wu and A. Monti, "Methods for partitioning the system and performance

evaluation in power-hardware-in-the-loop simulations. Part I," in Industrial

Electronics Society, 2005. IECON 2005. 31st Annual Conference of IEEE,

2005, pp.251-256

[10] X. Wu and A. Monti, "Methods for partitioning the system and performance

evaluation in power-hardware-in-the-loop simulations - Part II," in Industrial

Electronics Society, 2005. IECON 2005. 31st Annual Conference of IEEE,

2005, pp.257-262

[11] A. Ghosh and G. Ledwich, Power Quality Enhancement Using Custom

Power Devices: Kluwer Academic Publishers, 2002.

[12] B. Singh, K. Al-Haddad, and A. Chand b ra, "A Review of Active Filters for

Power Quality Improvement," IEEE Transactions on Industrial Electronics,

Vol. 46, pp. 960-971, 1999.

[13] D. A. Torrey and M.A.M.Al-Zamel, "Single-phase active power filters for

multiple nonlinear loads," IEEE Transaction on Power Electronics, Vol. 10,

pp. 263-271, May 1995.

[14] A. Ghosh and G. Ledwich, "Load compensating DSTATCOM in weak AC

Systems," IEEE Transaction on Power Delivery, Vol. 18, pp. 1302-1309,

October 2003.

[15] P.Rodriguez, R.Pindado, and J.Bergas, "Alternative topology for three-phase

four-wire PWM converters applied to a shunt active power filter," in IECON

02 2002, pp. 2939 - 2944

[16] B. Singh, K. Al-Haddad, and A. Chandra, "A New Control Approach to

Three-phase Activt: Filter for Harmonics and Reactive Power

Compensation," IEEE Transactions on Power Systems, vol. 13, pp. 133-138,

February 1998.

[17] G. Ledwich and P. Doulai, "Control techniques for active power filters," in

IEE International Conference on Advances in Power System Control,

Operation and Management, Hong Kong, 1991, pp. 582 - 58.

Page 26: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

12

[18] X. Dianguo, G. Jianjun, L. Hankui, and G. Maozhong, "Improved Hysteresis

Current Control for Active Power Filter," in IEEE International Symposium

on Industrial Electronics, ISIE '03., 2003, pp. 836 - 840

[19] A. B. Rey, S. de Pablo, J. M. Ruiz, and J. A. Ravelo, "A novel current control

strategy for PWM inverters using the sliding mode techniques," in Power

Electronics Congress, 2000. CIEP 2000. VII IEEE International, 2000, pp.

276-279.

[20] S. Zabihi and Firuz Zare, "Active Power Filters with Unipolar Pulse Width

Modulation to Reduce Switching Losses," in International Conference on

Power System Technology: IEEE, 2006

[21] L. Malesani and P. Tenti, "A novel hysteresis control method for current-

controlled voltege-source PWM inverters with constant modulation

frequency," IEEE Transactions on Industry Applications, Vol. 26, pp. 88-92,

Jan/Feb 1990.

[22] H. Pinheiro, A. S. Martins, and J. R. Pinherio, "A sliding mode controller in

single phase voltage source inverters," in 20th International Conference on

Industrial Electronics, Control and Instrumentation, IECON '94, 1994, pp.

394-397.

[23] P. S. Ninkovic, "A Novel Constant-frequency hysteresis current control of

PFC converters.," in IEEE International Symposium on Industrial Electronics

( ISIE 2002), 2002, pp. 1059-1064.

[24] S. Buso, S. Fasolo, L. Malesani, and P. Mattavelli, "A Dead-Beat Adaptive

Hysteresis Current Control," IEEE Transactions on Industry Applications,

Vol. 36, pp. 1174-1180, July/Aug 2000.

[25] B. Nicolas, M. Fadel, and Y. Cheron, "Fixed-frequency sliding mode control

of a single phase voltage cource inverter with input filter," in IEEE

International Symposium on Industrial Electronics, (ISIE '96) 1996, pp. 470-

475.

[26] T. Noguchi, H. Kodachi, and I. Saito, "Performance improvement of current-

controlled PWM inverter by means of dithering," in Power Electronics and

Drive Systems, 2001. Proceedings., 2001 4th IEEE International Conference

on, 2001, pp. 390-395 vol.1.

Page 27: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

13

[27] J. Zeng, C. Yu, Q. Qi, Z. Yan, Y. Ni, B.L.Zhang, S. Chen, and F. F. Wu, "A

novel hysteresis current control for active power filter with constant

frequency," Electric power systems research, vol. 68, pp. 75-82, 2 August

2003.

[28] G. H. Bode and D. G. Holmes, "Implementation of Three Level Hysteresis

Current Control for a Single Phase Voltage Source Inverter," in Power

Electronics Specialists Conference, 2000, pp. 33-38.

[29] F. Zare and G. Ledwich, "A hysteresis current control for single-phase

multilevel voltage source inverters: PLD implementation," IEEE Transaction

on Power Electronics, Vol. 17, pp. 731 - 738 September 2002.

[30] L.Malesani, P.Mattavelli, and P.Tomasin, "Improved constant-frequency

hysteresis current control of VSI inverters with simple feed-forward

bandwidth prediction," in Industry Applications Conference, Thirtieth IAS

Annual Meeting, IAS '95, 1995, pp. 2633-2640.

[31] L. Malesani, P. Mattavelli, and P. Tomasin, "High-performance hysteresis

modulation technique for active filters," IEEE Transaction on Power

Electronics, Vol. 12, pp. 876-884, September 1997.

[32] Z. Chen, F. Blaabjerg, and J. K. Pedersen, "A study of parallel operations of

active and passive filters," in Power Electronics Specialists Conference,

2002. pesc 02. 2002 IEEE 33rd Annual, 2002, pp. 1021-1026 vol.2.

[33] S. Bhattacharya, D. M. Divan, and B. B. Banerjee, "Control and reduction of

terminal voltage total harmonic distortion (THD) in a hybrid series active and

parallel passive filter system," in Power Electronics Specialists Conference,

1993. PESC '93 Record., 24th Annual IEEE, 1993, pp. 779-786.

[34] J. C. Das, "Passive filters-potentialities and limitations," in Pulp and Paper

Industry Technical Conference, 2003. Conference Record of the 2003

Annual, 2003, pp. 187-197.

[34] H. Komurcugil and O. Kukrer, "A robust current control strategy for single-

phase shunt active power filters," in Industrial Electronics Society, IECON

'03. , 2003, pp. 2277 - 2281.

[35] C.N.Bhende, S.Mishra, and S.K.Jain, "TS-fuzzy-controlled active power

filter for load compensation," IEEE Transaction on Power Delivery, vol. 21,

pp. 1459-1465, July 2006.

Page 28: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

14

[36] A. Hamadi, K. Al-Haddad, S. Rahmani, and H. Kanaan, "Comparison of

Fuzzy logic and Proportional Integral ControlIer of Voltage Source Active

Filter Compensating Current Harmonics and Power Factor," in IEEE

International Conference on Industrial Technology (ICIT), 2004, pp. 645 -

650

[37] A. Jaya Laxmi, G. Tulasi Ram Das, K. Uma Rao, and K. Rayudu,

"Comparison of PI and ANN control strategies of unified shunt series

compensator," in Power India Conference India, 2006.

[39] E. Arango, J. Calvente, R. Giral, A. E. Aroudi, and L. Martínez-Salamero,

"LQR Control of an Asymmetrical Interleaved Dual Boost Converter

Working in Inherent DCM," in ISIE 2005, Dubrovnik, Croatia: IEEE, 2005.

[40] Hardware-In-the-Loop Definition, from the website,

"http://www.precisionmba.com/hardware_in_the_loop.htm" on 28 october

2008.

[41] F. Zare, "Multilevel Converter Structure and Control", PhD thesis,

Queensland University of Technology, Brisbane, Australia, 2001.

[42] L. Dawes, " Role of Soil Physical and Chemical Characteristics and

Landscape Factors in Defining Soil Behaviour Under Long Term Wastewater

Dispersal", Queensland University of Technology, Brisbane, Australia, 2006.

Page 29: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

15

CHAPTER 2

A HYBRID DISCONTINUOUS VOLTAGE CONTROLLER FOR DSTATCOM APPLICATIONS

SACHIN GOYAL, ARINDAM GHOSH AND GERARD LEDWICH

School of Engineering Systems

Queensland University of Technology

Published: IEEE PES General Meeting, USA, 2008.

Page 30: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

16

Abstract −−−− This paper proposes a hybrid discontinuous control methodology for a

voltage source converter (VSC) based distribution static compensator (DSTATCOM)

connected to a 3-phase distribution system. It is assumed that the DSTATCOM

controls the point of common coupling (PCC) voltage. An LC output filter is

connected at the output of the VSC. With the help of both filter inductor current and

filter capacitor voltage control, the voltage across the filter capacitor is controlled.

Based on the voltage error, the control is switched between voltage and current

control mode. In this scheme, an extra diode state is used that makes the VSC output

current discontinuous. This diode state reduces the switching losses because half of

the total switching occurs at nearly zero converter current. The effects of different

source conditions on voltage at PCC are studied. Voltage angle at PCC is controlled

using a PI controller. Simulation studies are performed using PSCAD to validate the

efficacy of the proposed controller.

Keywords − DSTATCOM, discontinuous current, hybrid control, LC output filter.

2.1. Introduction

Power quality is a concern for sensitive loads (consumers) like semiconductor

manufacturing plants, hospitals, financial institutes or food processing plants as a

voltage dip for even short duration can cost them a substantial amount of money.

Most of the power quality problems originate in distribution system. Installation of a

distribution static compensator (DSTATCOM) at consumer premises is an effective

solution of these problems [1]-[2]. A DSTATCOM is a voltage source converter

(VSC) based shunt device, usually supported by short-time energy stored in the dc

capacitor(s). Various kinds of structure and control methods are used for

compensators [3]. In this paper, voltage at point of common coupling (PCC) is

controlled and made balanced so that source current can be balanced, even when the

load is unbalanced and nonlinear. To prohibit the switching frequency components of

the VSC to the PCC voltage, an LC filter is connected at the output of VSC. A

simple hysteresis current control (HCC) will fail to track the capacitor voltage

reference. Hence a hybrid discontinuous feedback control law is proposed for the

combined VSC-LC filter system.

Page 31: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

17

In this paper, the discussion is based on the structure and control of a DSTATCOM

that is suitable to compensate the load at the time of sag or swell in source voltage.

Also it can compensate the load at the time of feeder change. To control the power

flow from source, voltage angle at PCC is controlled using a PI controller. This angle

control gives a jump in voltage angle when compensator is connected to the grid. A

solution to avoid this jump is proposed in this paper.

The control strategy described in this paper uses both voltage and current controls. In

voltage control mode modified concept of 3-level HCC is used [4]-[5]. Generally in a

3-level HCC, the output of the inverter is either + Vdc, 0 or − Vdc. In the zero state, a

short circuit path is provided through inverter. In this paper the zero state is modified

by a diode state. In the diode state, all four switches of single phase inverter are

turned off. Filter inductor current is made zero with the help of diodes.

2.2. Voltage Control Structure

Figure 2.1 Single-line diagram of shunt compensation of a load through a feeder.

The scheme of DSTATCOM is shown in Fig. 2.1. In this system, a load that can be

active, passive, unbalanced or nonlinear is connected with a balance voltage source

(Vs) through a feeder. Resistance and inductance of feeder are R and L. A

DSTATCOM that contains a VSC and an LC filter at the output of VSC is used to

Page 32: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

18

compensate the load. The VSC is supplied by the dc storage capacitor Cdc. The LC

filter inductance and capacitance are denoted by Lf and Cf respectively and the

resistance Rf indicates the circuit losses. It can be seen from Fig. 2.1 that the voltage

across the filter capacitor Cf is the PCC voltage vt. The aim of this scheme is to

balance the three phase PCC voltages.

2.2.1. The DSTATCOM model

Fig. 2.2 shows the structure of DSTATCOM. It contains three H-Bridge VSCs. All

three VSCs are connected to common DC storage capacitor Cdc. Each VSC is

connected to grid through single phase transformer and a capacitor. The three single

phase transformers are used to provide isolation [2]. Leakage inductance of

transformer Lf and the filter capacitor Cf constitute the LC filter for each phase. All

three transformers are connected in star and neutral point is connected to the neutral

of the load or it may be grounded if neutral point of load is not available.

Figure 2.2. Compensator structure used in which three separate VSCs are supplied from a common dc storage capacitor.

As far as structure of single phase converter is concern, it has four switches with

anti-parallel freewheeling diode. In the later part of this paper, we shell see that

output current of the converter, i.e., filter inductor current may be discontinuous. So

the diodes’ rating must be same as the IGBTs’ rating.

Page 33: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

19

2.2.2. The Reference generation

The aim the scheme is to balance the PCC voltages. Note that the compensator

(DSTATCOM) is supplied by a dc storage capacitor, which can only provide

temporary ride through during transients. Hence the power demanded by the load and

the losses in the compensation circuit must be supplied by the source. The voltage

angle at PCC − δ is set in such a manner that the source supplies the total power and

loss requirements.

Let us define

δ−∠=°∠= 21 and 0 VVVV ts (2.1)

Then from Fig. 2.1, we get the following expression for the power entering the PCC

from the source

( )[ ]δδ sincos 121222 XVVVRXR

VP +−

+= (2.2)

where X = ωL. If V1 ≈ V2, the first term inside the bracket on the right hand side of

(2) is negative. However, its influence on the positive valued second term is

negligible as R << X. Now suppose a voltage sags occurs causing V1 to drop. If the

DSTATCOM holds V2 constant, the first term becomes more negative. Let us

stipulate that the power to the load must remain unchanged. Hence δ must increase

not only to offset the first term, but also to maintain the power flow constant.

Similarly during a voltage swell in V1, the angle δ must reduce in order to hold the

power constant.

For example, let us assume that V1 = V2 = 11 kV (L-L), R = 6.05 Ω, X = 36.2854 Ω

and δ = 20°. Then the three-phase power, calculated from (1.2) is 1.077 MW. Now

suppose a symmetrical sag in supply voltage reduces V1 to 9 kV (L-L). Then in order

to maintain the power flow constant, δ must be equal to 27.5°. Similarly if V1

becomes 12 kV (L-L), δ should be around 17.3° to hold the power constant.

Page 34: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

20

Therefore in order to keep the power constant, δ must be controlled. If the power

flow is constant, the dc capacitor voltage Vdc remains constant since it is absorbing

the required amount of power to replenish the losses. A drop in the capacitor voltage

indicates as voltage sag as it tries to supply power to the load. The capacitor voltage

increases during a voltage swell as the increased power from the source is drawn by

the DSTATCOM. Therefore the power drawn from the source can be controlled by

regulating the capacitor voltage around its reference value. This gives the following

capacitor voltage control loop

∫+= edtKeK Ipδ (2.3)

where e = Vcref − Vdc, Vcref being reference voltage for the dc capacitor. Using this δ

and reference peak voltage at PCC (V2m), three phase reference voltages are

generated for voltage controller. These references are

( )( )( )

°+−=

°−−=

−=

120sin

120sin

sin

2

2

2

δωδωδω

tVv

tVv

tVv

mcref

mbref

maref

(2.4)

With the help of voltage controller, the voltage at the PCC is kept balanced.

2.3. Strategy for Hybrid Discontinuous Control

If our source voltages are balanced sinusoids and we make PCC voltage also balance

then source current will also be balance. The harmonic and unbalanced components

of the load currents will be supplied by compensator. However any unbalance or

distortion in the source voltages will be reflected in the source currents since the

PCC voltages will remain balanced sinusoidal. In this section, we shall introduce a

new control methodology to track the PCC voltage references (1.4). This control

requires fewer of switching events, thereby incurring lower switching losses

compared to hysteretic control.

This control is a combination of voltage and current control in which all the three

states (+ 1, − 1 and 0) of inverter are used. In + 1 and − 1 states, the output voltages

Page 35: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

21

of inverter are + Vdc and − Vdc respectively and the 0-state is the diode state where all

four switches are turned off. In the diode state, with the help of diode, the inductor

current is forced to zero. This state introduces discontinuity in the converter output

current.

1S 2S

3S 4S

lkR cfv

Figure 2.3. VSC scheme to control capacitor voltage.

Let us consider a single phase H-bridge converter with an LC filter as shown in Fig.

2.3. The leakage in the capacitor is denoted by a high resistance Rlk. It is desired that

the VSC tracks a reference capacitor voltage with the help of current and voltage

control. For this, two zones are defined as shown in Fig. 2.4. If capacitor voltage is in

Zone 1, the VSC is operated in current control mode and if the voltage is in Zone 2

then it is operated in voltage control mode. Both these variables are controlled in

hysteresis bands. In Zone 1, a hysteresis band limit is set for the inductor current (i f)

and in Zone 2, hysteresis band is set for the capacitor voltage (vcf).

Figure 2.4. Two zones for voltage control.

DC Voltage Tracking: If the reference of the capacitor voltage is positive, then

switching in Zone 1 will be defined as

0 then If 41 =≥ −Shi if (2.5)

Page 36: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

22

where hi is the current hysteresis band. This implies that if the current i f is greater

than or equal to hi, turn all the switches off. However, if this current is less than zero,

apply positive voltage at the VSC output, i.e.,

0 and 1 then 0If 3,24,1 =+=< SSi f (2.6)

Let the upper and lower voltage hysteresis bands be denoted by huv and hlv

respectively. Then for Zone 2, we have the following switching logic

0 then If 41 =+≥ −Shvv uvrefcf (2.7)

0 and 1 then If 3,24,1 =+=−≤ SShvV lvrefcf (2.8)

For example, let assume vref = 8 kV (dc), hi = 0.4 kA, huv = 0.02 kV and hlv = 0.1 kV.

Value of huv should be less then hlv because even if all four switches are turned off,

the capacitor voltage increase until i f becomes zero and the capacitor voltage

becomes more then vref + huv. If huv and hlv are same, a steady state error will always

be there. To eliminate this error huv should be less then hlv. Fig. 2.5 shows the

tracking of capacitor voltage when vref is positive. It can be seen that that when the

voltage rises to its reference, the control is in Zone 1, where the current is switched

rapidly. Once the voltage reaches the reference value, the control is switched to zone

2 to maintain the output voltage. During this time, the current switching will be

dependent on the leakage resistance of the capacitor. If the resistance is small, the

leakage will be more, resulting in higher current switching. The same scheme can

also be applied when vref is negative. This is not shown here.

AC Voltage Tracking: To track a sinusoidal capacitor voltage reference, one cycle

is divided in four parts as shown in Fig. 2.6. Regions 1 and 3 can be tracked using the

switching schemes explained above. However for Regions 2 and 4 separate

switching scheme needs to be implemented because the capacitor discharges in these

regions.

Page 37: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

23

0 0.005 0.01 0.015 0.02 0.025 0.030

2

4

6

8

10

Time (s)V

olta

ge

(KV

)

Capacitor Voltage

Voltage control mode

Current control mode

(a)

0 0.005 0.01 0.015 0.02 0.025 0.03-0.1

0

0.1

0.2

0.3

0.4

0.5

0.6

Time (s)

Cu

rren

t (K

A)

Inductor Current

(b)

Figure 2.5. (a) Capacitor voltage and (b) Inductor current during DC tracking.

0 0.005 0.01 0.015 0.02-1.5

-1

0

1

1.5

Time

Mag

. Region 1 Region 2

Region 3 Region 4

Figure 2.6. Four regions of one cycle of a sinusoidal wave.

Two zones are also defined for Regions 2 and 4 − one for current control and the

other for voltage control. For Region 2, switching in Zone 1 is

0 and 1 then 0If 4,13,2 =+=≥ SSi f (2.9)

0 then If 41 =≤ −Shi if (2.10)

The switching for Zone 2 are:

Page 38: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

24

0 and 1 then If 4,13,2 ==+≥ SShvv lvrefcf (2.11)

0 then If 41 =−≤ −Shvv uvrefcf (2.12)

Fig. 2.7 shows the sinusoidal tracking of capacitor voltage and inductor current. The

tracking is discontinuous in nature.

Example 2.1: In this example, a passive load is connected to the VSC through an LC

filter. For a passive load, a diode state is required for all the regions shown in Fig.

2.6. In Regions 1 and 4, only + Vdc is required, while in Regions 2 and 3, only − Vdc

is required. Note that there is no need to utilize − Vdc in Regions 1 and 4 and + Vdc in

Regions 2 and 3 (load should not provide rapid discharging path to capacitor).

0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-10

-5

0

5

10

Time (s)

Vol

tage

(K

V)

Reference and Capacitor Voltage

(a)

0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-5

-2.5

0

2.5

5

Time (s)

Cu

rren

t (K

A)

Inductor Current

(b)

Figure 2.7. (a)Capacitor voltage and (b) Inductor current for AC voltage tracking. Hence the scheme described above produces very accurate tracking. However when

the load is active or when a passive load provide a rapid discharging path for the

capacitor, the − Vdc state may also be required in Regions 1 and 4 while the + Vdc

state may be required in Regions 2 and 3 depending on the relative phase difference

Page 39: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

25

between the VSC output voltage and the system internal emf. This may increase the

switching frequency of the VSC and lead to continuous conduction mode of the

inductor current. Fig. 2.8 shows the load voltage and inductor current for a passive

load.

0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-1.5

-1

-0.5

0

0.5

1

1.5

Time (s)

Vo

ltag

e (K

V)

Capacitor Voltage

(a)

0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-4

-2

0

2

4

Time (s)

Cu

rren

t (K

A)

Inductor Current

(b)

Figure 2.8. (a) Capacitor voltage and (b) Inductor current for Example 2.1

For tracking in Region 1 with an active load, the switching control is defined as

follows. If capacitor voltage is in Zone 1, then

0 then If 41 =≥ −Shi if (2.13)

0 and 1 then 0If 3,24,1 ==< SSi f (2.14)

But if the capacitor voltage is in Zone 2, then

0 and 1 then If 3,24,1 ==−≤ SShvv lvrefcf (2.15)

0 then and If 41 =+<−> −Shvvhvv uvrefcflvrefcf (2.16)

Page 40: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

26

1 and 0 then If 3,24,1 ==+≥ SShvv uvrefcf (2.17)

The switching for Region 3 will be the same as above except that − Vdc state will be

chosen instead of + Vdc state.

The switching for Region 2 is defined as follows. Switching in Zone 1 is

0 and 1 then 0If 4,13,2 ==≥ SSi f (2.18)

0 then If 41 =≤ −Shi if (2.19)

For Zone 2,

0 and 1 then If 4,13,2 ==+≥ SShvv lvrefcf (2.20)

0 then andIf 41 =−>+< −Shvvhvv uvrefcflvrefcf (2.21)

1 and 0 then If 4,13,2 ==−≤ SShvv uvrefcf (2.22)

Switching for Region 4 can be obtain in the same way as in Region 2, the only

difference being the capacitor discharges from negative to zero instead of positive to

zero.

2.4. Compensator Performance

Once the reference for PCC voltage is computed from (1.4), the PCC voltage can be

tracked using the controller described in Section III. This is illustrated with the help

of the following example.

Example 2.2: Consider the system shown in Fig. 2.1. The system and DSTATCOM

parameters chosen are given in Table 2.1. It is assumed that the source voltage is

balanced. The load is both unbalanced (passive RL) and nonlinear (three-phase

rectifier supplying an RL). The compensator is connected to grid at time t = 0. The

source currents, load currents, PCC voltages and the angle of the PCC voltage are

shown in Figs. 2.9 (a-d) respectively. The initial transient lasts about 0.1 s. During

this time, the dc capacitor charges. Once the dc capacitor voltage reaches its desired

Page 41: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

27

level, the angle of the PCC voltage settles to its steady state level and the initial

transient dies out. This is evident from all the plots of Fig. 2.9.

TABLE 2. 1. SYSTEM PARAMETERS

System Quantities Values

Systems Frequency (ω) 100π rad/s (50 Hz)

Source voltage (Vs) 11 kV rms (L-L)

Feeder impedance (Rs + jXs) 6.05 + j36.26 Ω

Unbalanced Load

The subscripts a, b and c

denote the three phases.

Zla = 48.2 + j94.2 Ω

Zlb = 12.2 + j31.4 Ω

Zlc = 24.2 + j60.47 Ω

Nonlinear Load

Contains a three-phase

rectifier that supplies

100 + j31.4 Ω

DSTATCOM

Loss (Rf)

Filter capacitor (Cf)

Three single-phase

transformers are rated at

3 Ω

50 µF

1 MVA, 3 kV/11 kV,

leakage inductance (Lf)

of 2.5%

Capacitor Control Loop

DC capacitor

Reference voltage (vcref)

Proportional gain (KP)

Integral gain (KI)

10000 µF

3.5 kV

-0.7

0.1

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Curr

ent (K

A)

Three Phase Source Currents

(a)

Page 42: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

28

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Curr

ent (K

A)

Load Currents

(b)

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2-10-9

-5

0

5

910

Time (s)

Volta

ge (K

V)

PCC Voltages

(c)

0 0.05 0.1 0.15 0.2 0.25-140

-120

-100

-80

-60

-40

-20

Time (s)

Deg

ree

PCC Voltage Angle

(d)

Figure 2.9. Compensation of the unbalanced nonlinear load without precharged capacitor.

Once the load and the compensator are connected to the grid at time t = 0, the PCC

voltage angle starts changing as shown in Fig. 2.9 (d). This angle changes

significantly in the transient period. Such a rapid change in angle may not be

desirable to some loads. To overcome this problem, the dc capacitor should be pre-

charged before connecting the DSTATCOM to the grid. To charge the dc capacitor,

the same VSC that is used as the compensator is used. At the time of pre-charging,

the controller is switched off and anti-parallel diodes of the VSC are used as an un-

controlled rectifier. This pre-charging scheme is shown in Fig. 2.10, which contains

Page 43: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

29

two circuit breakers. The load is connected to the grid through the circuit breakers

CB1 and filter capacitor is connected to the rest of the DSTATCOM through CB2.

Initially controller is switched off to charge the dc capacitor. During this time, CB1

and CB2 are kept open. To limit the charging current of dc capacitor a resistance is

connected in series with dc capacitor. Once the capacitor voltage reaches the desired

value, the series resistance is bypassed (short-circuited) with the help of switch SC1

and CB1 and CB2 are closed subsequently.

Figure 2.10. Schematic diagram of the compensation scheme to pre-charge the dc capacitor.

Using the above pre-charging scheme, capacitor is charged for initial 0.35 s and

during this time CB1, CB2 and switch SC1 is kept open. It can be seen from the dc

capacitor voltage of Fig. 2.11 (a) that the capacitor voltage attains a near steady state

value at t = 0.35 s and hence further pre-charging is not possible. However once

CB1, CB2 and SC1 are closed, the capacitor voltage and PCC voltage angle settle

quickly without deviating much from their pre-charged values as evident from Fig.

2.11 (a) and ( b). During the charging, phase-a of the PCC voltage is shown in Fig.

2.11 (c). It can be seen that this voltage does not collapse during this period. Hence,

the loads that may be connected upstream from the PCC will not get affected much.

Also note that the output of the angle controller (1.3) changes rapidly from − 140°

towards its steady state value due to the controlled charging of the dc capacitor.

However since the PCC voltage is not controlled by the DSTATCOM during the pre-

charging time, the angle change does not have any effect on the load or the PCC

voltage. Once the breakers CB1 and CB2 are closed, the load currents start flowing

Page 44: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

30

(Fig. 2.11 d) and the PCC voltages quickly attain its steady state magnitude (Fig.

2.11 c). The advantage of this pre-charging method is that it does not require any

extra hardware other than the switch SC1 and the resistor connected in series with

the dc capacitor. The presence of the resistor will increase losses. However it will not

have much consequence since the charging time is very small.

Example 2.3: To investigate the behavior of the controller at the time of a voltage

sag in the source voltage, let us consider the same system as given in Table 2.1. A

voltage sag occurs at t = 0.25 sec in which the source voltage drops to 7 kV (L-N,

peak) from the nominal value of 9 kV. The sag is removed at t = 0.45 sec. It is

desired that the PCC voltage is maintained at 8 kV (L-N, peak). The three-phase

PCC voltage is shown in Fig. 2.12 (a). It can be seen from this figure that there is no

appreciable change in the magnitude of the PCC voltage during the sag or its

removal. From (1.2), it is clear that if source voltage

Time (s)Capacitor Pre-chargingDSTATCOM Connection to Grid

0 0.1 0.2 0.3 0.35 0.4 0.5 0.6 0.70

0.5

1

1.5

2

2.5

3

Time (s)

Volta

ge (k

V)

DC Capacitor Voltage

Capacitor Pre-charging

DSTATCOM Connection to Grid

(a)

0 0.1 0.2 0.3 0.35 0.4 0.5 0.6 0.7-140

-120

-100

-80

-60

-40

-20

Time (s)

Deg

ree

Output of Angle Controller

DSTATCOM Connection Point

(b)

Page 45: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

31

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-10

-5

0

5

10

Time (s)Volta

ge

(kV)

PCC Voltage (Phase A)

(c)

0.33 0.34 0.35 0.36 0.37 0.38 0.39 0.4-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Cur

rent

(kA)

Load Currents

(d)

Figure 2.11. (a) DC capacitor voltage, (b) voltage angle at PCC, (b) PCC voltage and (c) load currents when the dc capacitor is pre-charged.

reduces then δ should increase to maintain the same level of power flow. Fig. 2.12

(b) shows the PCC voltage angle. It starts decreasing at t = 0.25 s, resulting in

increase in δ. The angle returns to its original value once the sag is removed. The

three-phase source currents are shown in Fig. 2.12 (c). It can be seen these currents

increase during the voltage sag to maintain the constant amount of power flow.

Example 2.4: The behavior of the system is investigated for a swell in the source

voltage, which occurs at t = 0.25 s. The swell is removed at t = 0.45 s. The same

system as given in Table 2.1 is considered here also. During the swell, the source

voltage rises to 11 kV (L-N, peak). It can be seen from Fig 2.13 that magnitude of

PCC voltage remains constant while its angle increases to maintain constant power

flow.

Page 46: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

32

0.2 0.25 0.3 0.35 0.4 0.45 0.5-10

-8

-6

-4

-2

0

2

4

6

8

10

Time (s)

Volta

ge

(KV

)

PCC Voltages

(a)

0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6-120

-100

-80

-60

-40

-20

0

Time (s)

Deg

ree

Voltage Angle at PCC

Sag StartSag End

(b)

0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Curr

ents

(K

A)

Three Phase Source Current

(c)

Figure 2.12. (a) PCC voltages, (b) voltage angle and (c) source currents for Example 2.3.

0.2 0.25 0.3 0.35 0.4 0.45 0.5-10

-5

0

5

10

Time (s)

Voltag

e (K

V)

PCC Voltages

(a)

Page 47: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

33

0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6

-100

-80

-60

-40

-20

0

Deg

ree

Voltage Angle at PCC

Swell EndSwell Start

Time (s)

(b)

Figure 2.13. (a) PCC voltages and (b) voltage angle for Example 2.4.

Example 2.5: Unsymmetrical sag/swell is a common occurrence in power systems.

In this example, we shall investigate the system behavior during such an occurrence.

Let us consider the same system as given in Table 2.1. However the peak of the

instantaneous source voltages are changed as 10kV, 9kV and 8kV (L-N, peak) for the

phases a, b and c respectively at t = 0.3s and 8kV, 9kV and 10kV (L-N, peak) for the

phases a, b and c respectively at t = 0.5sec. It is desired that the DSTATCOM

maintains the peak of the PCC voltage at 9 kV. These voltages are shown in Fig. 2.14

(a). The PCC voltage angle is shown in Fig. 2.14 (b). It can be seen that it almost

remains unchanged. Since the PCC voltages are held constant, the power requirement

of the load remains unchanged. Also since the changes in the source voltages are

symmetrical (the dip in one phase is equal to the rise in the other), the angle must

remain constant for constant power. The source currents are shown in Fig. 2.14 (c). It

can be seen that they are unbalanced in sympathy with the source voltages.

0.3 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38 0.39 0.4-10

-5

0

5

10

Time (s)

Voltag

e (k

V)

PCC Voltages

(a)

Page 48: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

34

0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6-55

-50

-45

-40

-35

-30

-25

-20

Time (s)

Deg

ree

PCC Voltage Angle

Voltage Change Points

(b)

0.3 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38 0.39 0.4-0.2

-0.15

-0.1

-0.05

0

0.05

0.1

0.15

0.2

Time (s)

Curr

ent (k

A)

Three Phase Source Currents

(c)

Figure 2.14. (a) PCC voltages (b) voltage angle (c) and source currents for Example 2.5.

Example 2.6: Let us now consider the case when there is a change in the feeder

impedance. To investigate this case, the system in Table 2.1 is altered by introducing

a 3-phase phase rectifier that is connected half between the source and the PCC as

shown in Fig. 2.15. This load is connected to the feeder through a circuit breaker

(CB1), which is closed at time t = 0.3 s. The results are shown in Fig. 2.16. With the

introduction of the rectifier load, some amount of power is supplied by the source to

it. However since the load power has to remain constant, the PCC voltage angle must

recede to maintain the power flow to the load. This is evident from Fig. 2.16 (a). The

magnitude of the PCC voltage remains constant as evident from Fig. 2.16 (b).

However the currents (is) supplied by the source are now distorted, but balanced due

to the rectifier load as shown in Fig. 2.16 (c).

Page 49: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

35

Figure 2.15 PCC Feeder switching scheme for Example 2.6

0.2 0.25 0.3 0.35 0.4 0.45 0.5-100

-90

-80

-70

-60

-50

-40

-30

-20

Time (s)

Deg

ree

PCC Voltage Angle

Feeder Switch

(a)

0.25 0.3 0.35 0.4 0.45-10

-8

-6

-4

-2

0

2

4

6

8

10

Time (s)

Volta

ge

(KV

)

PCC Voltages

(b)

Page 50: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

36

0.48 0.482 0.484 0.486 0.488 0.49 0.492 0.494 0.496 0.498 0.5-0.3

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Cur

rent

(kA

)

Three Phase Source Currents

(c)

Figure 2.16 (a) PCC voltage angle, (b) PCC voltages and (c) source currents for Example 2.6.

2.5. Conclusions

This paper presents a new switching control strategy for voltage control in the

presence of an LC filter. The use of the LC filter removes the effects of switching

frequency components on the output voltage better than the traditional L filter.

However a simple hysteretic band control is not suitable in this situation as it will

lead to instability. To overcome this situation, a discontinuous hybrid control strategy

is proposed here which reduces the switching losses. Due to the use of the diode

state, half of the switching events occur when the inverter current is zero or nearly

zero, which makes half of the switching lossless. Because of this advantage, a higher

switching frequency can be chosen, which will result in better tracking of higher

frequency waveforms. Alternatively, the size of the inverter can be reduced.

This improved control strategy has been applied to a DSTATCOM operating in a

voltage control mode. The advantage of the proposed control method is that it is

robust to LC parameter variations and does not need a redesign for the changes in the

remainder of the power system, DSTATCOM parameters and operating conditions.

It has been shown that the DSTATCOM is able to hold the PCC voltage constant in

the face of various system disturbances and load changes. A simple angle control has

been used for the DSATACOM and a pre-charging scheme to avoid a phase jump

has been designed.

Page 51: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

37

Acknowledgement

The authors thank the Australian Research Council (ARC) for the financial support

for this project through the ARC Discovery Grant DP 0774092.

References

[1] A. Ghosh and G. Ledwich, Power Quality Enhancement Using Custom Power

Devices: Kluwer Academic Publishers, 2002.

[2] A. Ghosh and G. Ledwich, "Load compensating DSTATCOM in weak AC

Systems," IEEE Transaction on Power Delivery, vol. 18, pp. 1302-1309, October

2003.

[3] B. Singh, K. Al-Haddad, and A. Chandra, "A Review of Active Filters for Power

Quality Improvement," IEEE Transaction on Industrial Electronics, vol. 46, pp.

960-971, 1999.

[4] G. H. Bode and D. G. Holmes, "Implementation of Three Level Hysteresis

Current Control for a Single Phase Voltage Source Inverter," in Power

Electronics Specialists Conference, PESC’00, pp. 33-38, 2000.

[5] F. Zare and G. Ledwich, "A Hysteresis Current Control for Single-Phase

Multilevel Voltage Source Inverters: PLD implementation," IEEE Transaction

on Power Electronics, vol. 17, pp. 731-738, September 2002.

[6] Z. Chen, F. Blaabjerg, and J. K. Pedersen, "A study of parallel operations of

active and passive filters," in Power Electronics Specialists Conference,

PESC’02, pp. 1021-1026, 2002.

[7] L. Malesani, P. Mattavelli, and P. Tomasin, "High-performance hysteresis

modulation technique for active filters," IEEE Transaction on Power Electronics,

vol. 12, pp. 876-884, September 1997.

[8] S. I. Hamasaki and A. Kawamura, "A Novel Method for Active Filter Current

Regulation Using Deadbeat Control," Electrical Engineering in Japan, vol. 145,

pp. 67-77, 2003.

Page 52: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

38

CHAPTER 3

ACTIVE POWER FLOW CONTROL IN A DISTRIBUTION SYSTEM USING DISCONTINUOUS

VOLTAGE CONTROLLER

SACHIN GOYAL, ARINDAM GHOSH AND GERARD LEDWICH

School of Engineering Systems

Queensland University of Technology

Published: Electric Power Systems Research, 2008.

Page 53: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

39

Abstract – This paper proposes a hybrid discontinuous control methodology for a

voltage source converter (VSC), which is used in an uninterrupted power supply

(UPS) application. The UPS controls the voltage at the point of common coupling

(PCC). An LC filter is connected at the output of the VSC to bypass switching

harmonics. With the help of both filter inductor current and filter capacitor voltage

control, the voltage across the filter capacitor is controlled. Based on the voltage

error, the control is switched between current and voltage control modes. In this

scheme, an extra diode state is used that makes the VSC output current

discontinuous. This diode state reduces the switching losses. The UPS controls the

active power it supplies to a three-phase, four-wire distribution system. This gives a

full flexibility to the grid to buy power from the UPS system depending on its cost

and load requirement at any given time. The scheme is validated through simulation

using PSCAD.

Keywords −−−− UPS, discontinuous current, hybrid control, LC output filter and power

flow control.

3.1. Introduction

The power quality issues such as harmonics, unbalancing, voltage sag/swell have

gained considerable attention over the last few years. In addition, the concern for

global warming has seen considerable development in the distributed generation

(DG) technology in the recent time. An uninterruptible power supply (UPS) can

provide solution for the power quality problem, while supplying clean power from

DGs at the same time.

Usually UPSs are used to provide battery back up to computers and other data

processing devices. They can be off-line type in which they remain idle until power

failure occurs and start supplying power thereafter. The on-line type UPS

continuously powers the protected load from its reserve while simultaneously

replenishing the reserve by drawing power from the utility supply. A bi-mode UPS

uses the ac-dc rectification for battery charging [1]. It then seamlessly picks up the

load once a power failure occurs. Various configurations of UPS are reported in [2].

Page 54: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

40

In [3], the design of an LC filter that is connected at the output of the UPS is

discussed.

In this paper, the function of the UPS has been extended. It is assumed that the UPS

is supplied by a distributed generator. The DG can be a PV stack or fuel cell stack [4]

or battery which supplies the dc bus of the VSC connecting the UPS to the ac grid. It

is also possible to use PV or fuel cell to charge batteries that constitute the dc bus [5].

It is assumed that the UPS is connected at the point of common coupling (PCC) of

the utility and a major load center. The UPS is then can be controlled in two different

modes. In Mode-1, the utility supplies a constant power to the load and the remaining

power comes from the UPS. In Mode-2, the UPS supplies a constant power to the

load and the remaining power comes from the utility. An interchange between the

modes can occur instantaneously. However, in both the modes, the UPS provides a

balanced voltage at the PCC [6], thereby cancelling out any unbalance and harmonic

content of the load and therefore enhancing the power quality of the distribution

system.

Two different VSC control strategies are considered in this paper. The first strategy,

proposed in this paper, uses both voltage and current control modes. In the voltage

control mode, the modified concept of 3-level hysteretic current control (HCC) given

in [7, 8] is used. Generally in a 3-level HCC, the output of the converter is either +

Vdc, 0 or − Vdc. In the zero state, a short circuit path is provided through converter. In

this paper, the zero state is modified by a diode state. In the diode state, all four

switches of a single phase converter are turned off. Filter inductor current is made

zero with the help of the diodes. The switching between the current and voltage

control modes is based on the error in PCC voltage. If the error is large, the VSC

operates in the current control mode and it is switched to the voltage control mode as

the error reduces.

The performance of the proposed control strategy is compared with a 3-level state

feedback controller [9, 10] for comparison of total harmonic distortion (THD) of

PCC voltage, conduction and switching losses. Extensive simulation studies are

performed using PSCAD and some of the results are presented in the paper.

Page 55: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

41

3.2. Power Flow Control

The single-line diagram of a distribution system containing the UPS is shown in

Fig. 3.1. For simplicity, it is assumed that the UPS is supplied from a battery with a

dc voltage of Vdc. The load is assumed to be unbalanced and nonlinear. The load is

connected at the far end of a feeder with an impedance of R + jωL, which is supplied

by a source (vs). An LC filter is connected at the output of VSC, the inductance and

the capacitance of which are denoted by Lf and Cf respectively, while the resistance

Rf indicates the circuit losses. The PCC voltage is denoted by vt.

Figure 3. 1. Single-line diagram of the distribution system containing a UPS.

3.2.1. The UPS model

Fig. 3.2 shows the structure of the UPS. It contains three H-Bridge VSCs. All three

VSCs are connected to common DC storage source Vdc. Each VSC is connected to

grid through single phase transformer and a capacitor. The three single phase

transformers are used to provide isolation [7]. Leakage inductance of transformer Lf

and the filter capacitor Cf constitute the LC filter for each phase. All three

transformers are connected in star and neutral point is connected to the neutral of the

load or it may be grounded if neutral point of load is not available. As far as structure

of single phase converter is concern, it has four switches with anti-parallel

Page 56: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

42

freewheeling diode. In the later part of this paper, we shall see that output current of

the converter, i.e., filter inductor current may be discontinuous. So diodes’ rating

must be same as IGBTs’ rating.

The main purpose of the UPS is to maintain a balanced PCC voltage (vt) irrespective

of unbalance and distortion in the load currents. It also controls the magnitude of the

PCC voltage to a pre-specified value even when there is a sag or swell in the source

voltage. To control the power flow according to the modes described in the previous

section, the angle of the PCC voltage must be controlled. Therefore the reference for

the PCC voltage contains a pre-specified magnitude and an angle that is based on

power requirements. The VSC then will have to track this reference voltage in order

to achieve the desired performance.

faC fbC fcC

Figure 3. 2. UPS structure containing three VSCs that are supplied from a common source.

3.2.2. Reference Generation

Let us define the rms source and PCC voltages as

δ−∠=°∠= ttss VVVV and 0 (3.1)

Page 57: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

43

Then from Fig. 3.1, we get the following expression for the active and reactive power

entering the PCC from the source

( )[ ]δδ sincos22 sts

ts VXVVR

XR

VP +−

+= (3.2)

( )[ ]δδ sincos22 sts

ts VRVVX

XR

VQ −−

+= (3.3)

where X = ωL. If |Vs| ≈ |Vt|, the first term inside the bracket on the right hand side of

(2.2) is negative. However, its influence on the positive valued second term is

negligible as R << X. It is clear from (2.2) that real power flow can be controlled

using δ. Because if δ is increased or decreased, the amount of real power can be

increased or decreased accordingly. Therefore the reference PCC voltages are given

by

( )( )( )

°+−=

°−−=

−=

120sin

120sin

sin

δωδωδω

tVv

tVv

tVv

tmrefc

tmrefb

tmrefa

(3.4)

where Vtm is a pre-specified magnitude and δ is controlled according to the power

control mode.

3.2.2.1. Mode-1 Control

In this mode, a fixed amount of active power is drawn from the source and the UPS

supplies the balance amount of load requirement. As mentioned before, this can be

achieved by controlling δ. This gives the following power control loop

dt

deKdteKeK s

dssissps ++= ∫δ (3.5)

where es = Psref − Ps, Psref is the reference power which is drawn from the source.

As mentioned earlier, the UPS must regulate the PCC voltage even during changed

source voltage condition. Suppose a voltage sags occurs causing source voltage (|Vs|)

Page 58: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

44

to drop. As per requirement, the PCC voltage |Vt| is still held constant. Hence from

(2.2), it is evident that δ must increase in order to maintain the power flow constant.

On the contrary, the angle δ must reduce during swell in the source voltage.

Also, it can be seen from (3.3) that reactive power (Qs) is function of δ. Furthermore,

since |Vs| cos δ < |Vt|, Qs is negative. This means that the UPS supplies reactive

power to the grid. As described above that at the time of sag in source voltage, δ is

increased to maintain Ps constant. This will cause the first term of (3.3) to become

more negative. It means source will draw more reactive power from the UPS during

this condition.

3.2.2.2. Mode-2 Control

In this mode, a fixed amount of power is drawn from the UPS and the source

supplies the balance amount of load requirement. Hence the δ control loop is given

by

dt

deKdteKeK u

duuiuupu ++= ∫δ (3.6)

where eu = Puref − Pu , Puref being the reference power that is required from the UPS.

This controller works in a similar fashion as Mode-1 controller and adjusts the angle

δ to regulate the power flow from the UPS.

3.3. Control Strategies

Many control methodologies are available to track the PCC voltage. In this section,

we shall introduce a new control method and compare with an existing method.

These two methods are discussed below.

3.3.1. Hybrid Discontinuous Control

This control scheme is useful, when an LC filter is connected to the output of a single

phase converter and the instantaneous output voltage of filter capacitor (vcf) needs to

Page 59: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

45

be controlled. Fig. 3.3 shows the circuit configuration of a single-phase H-bridge

converter with the LC filter. In this control method, the converter switching decision

is made based on both filter inductor current (i f) and filter capacitor voltage. The

control is switched from one stage that is based on inductor current to second stage

which is based on capacitor voltage according to zones.

1S 2S

3S 4S

cfv

Figure 3. 3. VSC scheme to control capacitor voltage.

The zonal scheme is shown in Fig. 3.4 for a sinusoidal reference voltage with zones

and hysteresis band. The controller is assumed to be in Zone-1 when the error is

large and it is in Zone-2, when the error is small (within the hysteresis band). In

Zone-1, the control decision is made based on filter inductor current. When the error

reduces as a result of the control action of Zone-1, the controller switches to Zone-2,

where the decision will be made depending on filter capacitor voltage. However, in

both the zones, all three states (+1, -1 and 0) of converter are used based upon the

reference voltage. In + 1 state, the converter output becomes + Vdc, which is achieved

by turning on the switches S1 and S4 and turning off the switches S2 and S3 of

Fig. 3.3. Similarly in − 1 state, the converter output becomes − Vdc that can be

achieved by turning on the switches S2 and S3 and turning off the switches S1 and S4.

Usually the 0-state is defined when output voltage of converter is 0 V which is

achieved by closing the pair S1-S2 or S3-S4. But in this paper, the 0-state is modified

be a diode state where all the four switches S1-S4 of the converter are turned off.

During this time, the anti-parallel diodes conduct to bring filter inductor current (i f)

to zero. Once i f becomes zero, the diodes stop conducting and the converter output

voltage becomes equal to filter capacitor voltage (vcf). Because of the major

involvement of the diodes, this state is termed as the diode state in this paper. This

state introduces discontinuity in the converter output current (i f). Since the converter

Page 60: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

46

current (i f) becomes zero in the diode state, the next switching for either + 1 or − 1

state, occurs at zero current resulting in a loss free switching.

Figure 3. 4. The two zones voltage control scheme.

To track a sinusoidal capacitor voltage reference, one cycle is divided in four regions

as shown in Fig. 3.5 where each region is divided into two zones explained above.

For each zone, the hysteresis band is defined separately. In Zone-1, the hysteresis

band is defined for the inductor current and in Zone-2 the band is defined for the

capacitor voltage. In Regions 1 and 3, the capacitor is charged for positive and

negative voltage respectively. Thus the switching control logic is very much similar

in Regions 1 and 3. Only reference changes from positive to negative.

0 0.005 0.01 0.015 0.02-1.5

-1

0

1

1.5

Time

Mag

. Region 1 Region 2

Region 3 Region 4

Figure 3. 5. Four regions of one cycle of a sinusoidal wave.

If the reference of the capacitor voltage is in Region 1, then switching in Zone 1 will

be defined as

0 then If 41 =≥ −Shi if (3.7)

Page 61: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

47

where hi is the upper current hysteresis band. This implies that if the current i f is

greater than or equal to hi, turn all the switches off. However, if this current is less

than zero which is lower current band limit, apply positive voltage at the VSC

output, i.e.,

0 and 1 then 0If 3,24,1 =+=< SSi f (3.8)

Let the upper and lower voltage hysteresis bands (for Zone-2) be denoted by huv and

hlv respectively. Then for Zone-2, we have the following switching logic

0 then If 41 =+≥ −Shvv uvrefcf (3.9)

0 and 1 then If 3,24,1 =+=−≤ SShvv lvrefcf (3.10)

The switching for Region 3 can also be defined similarly. Since in this region, the

inductor current would be negative, the switching in Zone-1 for Region 3 is defined

as

0 then If 41 =−≤ −Shi if (3.11)

1 and 0 then 0If 3,24,1 =+=> SSi f (3.12)

The switching in Zone-2 would be

0 then If 41 =−≤ −Shvv uvrefcf (3.13)

1 and 0 then If 3,24,1 =+=+≥ SShvv lvrefcf (3.14)

For Regions 2 and 4, a separate switching scheme needs to be implemented because

the capacitor discharges in these regions. While In Region 2, the capacitor discharges

from positive to zero, it discharges from negative to zero in Region 4. The two zones

mentioned above are also defined for Regions 2 and 4, one for current control and

the other for voltage control. For Region 2, switching in Zone-1 is

0 and 1 then 0If 4,13,2 =+=≥ SSi f (3.15)

0 then If 41 =≤ −Shi if (3.16)

Page 62: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

48

The switching for Zone-2 is

0 and 1 then If 4,13,2 ==+≥ SShvv lvrefcf (3.17)

0 then If 41 =−≤ −Shvv uvrefcf (3.18)

Similarly the switching in Zone-1 for Region 4 is defined as

1 and 0 then 0If 4,13,2 =+=≤ SSi f (3.19)

0 then If 41 =≥ −Shi if (3.20)

The switching for Zone 2 is

0 then If 41 =+≥ −Shvv uvrefcf (3.21)

1 and 0 then If 4,13,2 ==−≤ SShvv lvrefcf (3.22)

It is to be noted that, in Region 1, even if all four switches are turned off, the

capacitor voltage increases until i f becomes zero forcing the capacitor voltage to

become more than vref + huv. If huv and hlv are chosen to be the same, a steady state

error will always exist. To eliminate this error, huv should be chosen less than hlv.

The filter parameters Lf and Cf, a small value of Lf is chosen for discontinuous mode

of operation until it hits the current limit of the VSC. Small value of inductor helps in

charging the capacitor rapidly. However small value of inductor increases the filter

current, but it can be controlled with the help of controller algorithm. Large inductor

will lead to more and more continuous current at switching and less controlled

capacitor voltage. Large inductor will have more energy stored in it and after closing

the all four switch it will dissipate this energy to capacitor that will result unwanted

voltage rise of capacitor and this voltage rise is uncontrolled which is undesirable. It

must be ensured that the filter inductance Lf and the capacitor Cf do not resonate at

the fundamental frequency. If the filter capacitor resonates with the filter inductance

at a frequency ωr , then we get,

Cfr = 1/ωr2*L f (3.23)

Page 63: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

49

Let us assume that this value is equal to Cfo when ωr is equal to the fundamental

frequency (ω). The filter capacitor Cf should never be chosen near Cfo. This can be

achieved by either Cf_>>Cfo or Cf_<<C fo . However, if Cf is very large, the

impedance between the PCC and ground becomes very small resulting in excessive

currents through filter capacitors. Therefore the choice of Cf_>>C fo is invalid. We

must therefore restrict Cf to be much smaller than Cfo.

Example 3.1: In this example, a passive load is connected to the VSC through an LC

filter and it is desired that capacitor voltage tracks the reference voltage

1.0(sin (100πt)). For a passive load, a diode state is required for all the regions

shown in Fig. 3.5. In addition to the 0-state, only + Vdc is required in Regions 1 and

4, while in Regions 2 and 3, only − Vdc is required. Note that there is no need to

impress − Vdc in Regions 1 and 4 and + Vdc in Regions 2 and 3. But if the passive

load is small and it discharges the capacitor rapidly, then + Vdc may be required in

Regions 2 and 3. Hence the scheme described above produces very accurate tracking.

However when the load is active in nature, − Vdc may also be required in Regions 1

and 4 + Vdc may be required in Regions 2 and 3 depending on the relative phase

difference between the VSC output voltage and the back emf.

0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-1.5

-1

-0.5

0

0.5

1

1.5

Time (s)

Vol

tag

e (K

V)

Capacitor Voltage

(a)

0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-3

-2

-1

0

1

2

3

Time (s)

Cur

rent

(kA

)

Inductor Current

(b)

Figure 3. 6. (a) Capacitor voltage and (b) inductor current for Example 3.1.

Page 64: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

50

This may increase the switching frequency of the VSC and lead to continuous

conduction mode of the inductor current. Fig. 3.6 shows the load voltage and

inductor current which is discontinuous in nature for a passive load. Fig. 3.7 shows

the filter inductor current with switching signals for switches S1 and S4. It is clear

from the figure that when switches S1 and S4 are on, the output voltage of VSC is

+Vdc and when these two switches are turned off, all four switches are off because the

switches S2 and S3 were already off. Thus the inductor current reduces and becomes

zero with the help of diode conduction. During the diode conduction, the output

voltage becomes − Vdc and as inductor current becomes zero, the output voltage

becomes equal to filter capacitor voltage (vcf). Since every + 1 or − 1 state is

followed by a diode state, it results in alternate switching at zero current. Hence half

of the total switching is free of losses. Fig. 3.8 shows that one switching edge (either

rising or falling) occurs at almost zero current.

-1

0

1

2

4.29 4.3 4.31 4.32 4.33 4.34 4.35 4.36 4.37 4.38

x 10-3

-20

-10

0

10

20

Time (s)

Vo

ltag

e (k

V)

Inductor Current

Switching S1,4

VcfVcf+Vdc

Diode state

-Vdc

Diodeconducts

Figure 3. 7. Inductor current with diode state and VSI output voltage.

0.2867 0.2868 0.2869 0.287 0.2871 0.2872 0.2873 0.2874-1

-0.5

0

0.5

1

1.5

2

Time (s)

Filter Inductor Current and Switching

S2S1

Inductor Current (kA)Switching at zero current

Figure 3. 8. Inductor current and switching.

Page 65: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

51

For tracking in Region 1 with an active load, the switching control is defined as

follows. If capacitor voltage is in Zone-1, then

0 then If 41 =≥ −Shi if (3.24)

0 and 1 then 0If 3,24,1 ==< SSi f (3.25)

But if the capacitor voltage is in Zone-2, then

0 and 1 then If 3,24,1 ==−≤ SShvv lvrefcf (3.26)

0 then and If 41 =+<−> −Shvvhvv uvrefcflvrefcf (3.27)

1 and 0 then If 3,24,1 ==+≥ SShvv uvrefcf (3.28)

The switching for Region 3 will be the same as above except that − Vdc state will be

chosen instead of + Vdc state.

The switching for Region 2 two is defined as follows. The switching in Zone-1 is

0 and 1 then 0If 4,13,2 ==≥ SSi f (3.29)

0 then If 41 =≤ −Shi if (3.30)

For Zone-2,

0 and 1 then If 4,13,2 ==+≥ SShvv uvrefcf (3.31)

0 then andIf 41 =−>+< −Shvvhvv lvrefcfuvrefcf (3.32)

1 and 0 then If 4,13,2 ==−≤ SShvv lvrefcf (3.33)

Switching for Region 4 can be obtain in the same way as in Region 2, the only

difference being the capacitor discharges from negative to zero instead of positive to

zero.

Page 66: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

52

3.3.2 State Feedback Control

From Fig. 3.3, the state space equation of the system is given by

cBuAxx +=& (3.34)

where

=

−−

=

=

0,

01

1

,f

dc

f

ff

f

cf

fL

VB

C

LL

R

Av

ix

The state feedback control law is then given by

−−

−=refcf

fHP

c vv

iKu

0 (3.35)

where K is the feedback gain matrix and i fHP is obtained by passing i f through a high

pass filter. Since it is rather difficult to obtain a reference for i f, it is safer to enforce

that the high frequency components of this signal should be zero. The gain matrix K

is obtained using a linear quadratic regulator (LQR) design, where the maximum

weightage is given to vcf. Once uc is obtained, the switching logic is generated using a

three-level HCC control as shown in Fig. 3.9. In this figure, two hysteresis bands are

chosen. Suppose uc starts at 0 and crosses the upper band h1 and reaches point A.

Then the switches S1 and S4 are turned on such that the output voltage is + Vdc. When

uc reaches − h1 at point B, the output voltage is made 0.

Figure 3. 9. Three-level modulation with state feedback control.

Subsequently, when uc reaches h1 at point C, the output voltage is made + Vdc.

Thereafter when uc reaches − h1 at point D, the output voltage is made 0. If uc

Page 67: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

53

continues in the same direction and overshoots − h1 to reach point D, then the output

voltage is made − Vdc. Thereafter when uc reaches h1 at point F, the output voltage is

made 0. This logic is applied depending on the current and previous state of uc.

3.4. UPS Performance Evaluation

Once the reference for PCC voltage is computed from (3.4), the PCC voltage can be

tracked using the controllers described in Section 3.3. Application of hybrid

discontinuous controller is illustrated with the help of the following example where a

comparison is also made with the state feedback controller.

Example 3.2: Consider the system shown in Fig. 3.1. It is assumed that the source

voltage vs is balanced and has a magnitude of 11 kV (L-L, rms), which is equal to

about 9 kV (L-N peak). The load is an unbalanced nonlinear load, whose unbalanced

RL components are

Zla = 48.2 + j94.2 Ω, Zlb = 12.2 + j31.4 Ω and Zlc = 24.2 + j60.47 Ω

where the subscripts a, b and c denote the three phases. In addition, a three-phase

rectifier is also connected to the PCC with an output of 100 + j31.4 Ω. The feeder

impedance is R + jωL = 3.025 + j18.13 Ω. The UPS parameter are Vdc = 3.5 kV, Rf =

1.5 Ω and Cf = 50 µF. The single-phase transformers are rated 1 MVA, 3 kV/11 kV

with a leakage inductance of 2.5%. The UPS is connected to grid at time t = 0 where

it is required to maintain the PCC voltage at 11 kV (L-L rms). At t = 0.3 s, one more

balanced three phase load with 50 + j94.2 Ω (per phase) is connected. It is assumed

that the source power remains constant (Mode-1 control) such that balance power

comes from the UPS. The additional load is turned off at t = 0.5 s. The active power

flowing through the circuit is shown in Fig 3.10 (a). It can be seen that the source

real power remains constant during the load transients. The PCC voltage angle is

shown in Fig. 3.10 (b). Note from (2.4) that the PCC voltage angle is − δ. Hence in

the figure and in all the subsequent figures, the PCC voltage angle indicates − δ. This

also remains constant all through the load changes, as expected. From (2.3), it is

Page 68: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

54

obvious that if the voltage and angle δ remain constant, the reactive power drawn

from the source should also remain constant. This is shown in Fig. 3.10 (c) where the

UPS reactive power changes in sympathy with that of the load, while maintaining the

source reactive power constant. The three-phase PCC voltage during the load

increase is shown in Fig. 3.10 (d). It can be seen that this voltage does not get

disturbed during the load transient. The controller parameters chosen are Kps =

−0.025, Kis = −10.0 and Kds = −10×10−6.

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7-0.5

0

0.5

1

1.5

2

2.5

3

3.5

4

Time (s)

Pow

er (M

W)

Real Power

Source PowerLoad Decreases

Load Power

Load Increases

UPS Power

(a)

0 0.1 0.2 0.3 0.4 0.5 0.6-50

-40

-30

-20

-10

0

Time (s)

Deg

ree

PCC Voltage Angle

(b)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7-2

-1

0

1

2

3

4

5

Time (s)

Pow

er (M

VAR)

Reactive Power

Load Increase Load Decrease

Load QLoad QLoad QLoad Q

Source QSource QSource QSource Q

UPS QUPS QUPS QUPS Q

(c)

Page 69: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

55

0.25 0.26 0.27 0.28 0.29 0.3 0.31 0.32 0.33 0.34 0.35-10

-5

0

5

10

Time (s)Volta

ge (kV

)

Three Phase PCC Voltage

(d)

Figure 3. 10. UPS performance during load transient with Mode-1 control.

To compare the results obtained with the hybrid discontinuous control, the same test

is repeated with the state feedback control. The results obtained are very similar and

hence are not shown here. However the switching and conduction losses and the

THD of the PCC voltages are computed for both these methods. To compute the

switching losses, it is assumed that the VSC is made of Toshiba GTR Module Silicon

N Channel IGBT (MG400J1US51) IGBTs, the specifications for which are given in

Appendix A. The comparative results are listed in Table 3.1. It can be seen that the

switching edges in the discontinuous control is only 31% of those in the state

feedback control. The current through switches in the discontinuous mode is higher

than that in the state feedback control. Hence the switching losses in the

discontinuous control are 56% of the state feedback control and the conduction

losses are higher in the discontinuous control. It can therefore to be concluded that

the high current through switches in the discontinuous control somewhat nullifies the

benefit of less switching edges.

TABLE 3. 1. COMPARISON OF STATE FEEDBACK AND DISCONTINUOUS CONTROL

Switching

Edges in

one cycle

(0.02s)

THD

(PCC

Voltage)

Conduction

Losses in

Switches

(0.02 s)

Switching

losses (0.02s)

State Feedback 914 2.4% 7.41 J 166.14 J

Discontinuous

Control 286 0.68% 10.47 J 93.18 J

Page 70: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

56

The state feedback controller is not used in the remaining part of the paper. Only the

results with the hybrid discontinuous controller are presented subsequently.

Example 3.3: To investigate the behavior of the UPS controller at the time of sag in

source voltage, we consider the same system as given in Example 3.2. There is

unsymmetrical voltage sag at t = 0.3 s where the source voltage of phase a, b and c

decreases to 7 kV, 6 kV and 8 kV (L-N, peak) respectively with an angle jump of -10

degree. Voltage at PCC is maintained at 9 kV (L-N, peak). The results are shown in

Fig. 3.11. Fig. 3.11 (a) shows the three phase source voltage with an asymmetrical

sag at t = 0.3 s. Fig 3.11 (b) shows the three-phase PCC voltage at the occurrence of

the sag. It can be seen that its magnitude remains constant. From (2.2), it is clear that

if source voltage reduces then angle should increase to maintain the same level of

power flow. Fig 3.11 (d) shows that the angle δ increases at t = 0.3 s. The active

power is shown in Fig. 3.11 (c). It can be seen that real power remain constant

barring transients, the results with a swell in the source voltage are very similar and

hence are not shown here.

0.29 0.3 0.31 0.32 0.33 0.34-10

-8

-6

-4

-2

0

2

4

6

8

10

Time (s)

Vol

tage

(kV

)

Three Phase Source Voltage

Sag with angle jump

(a)

0.29 0.3 0.31 0.32 0.33 0.34-10

-8

-6

-4

-2

0

2

4

6

8

10

Time (s)

Vol

tage

(kV

)

Three Phase PCC Voltage

(b)

Page 71: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

57

0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.60

0.5

1

1.5

2

2.5

3

3.5

Time (s)Pow

er (M

W)

Real Power

Load PowerSource PowerUPS Power

(c)

0.25 0.3 0.35 0.4 0.45 0.5-50

-45

-40

-35

-30

-25

-20

Time (s)

Deg

ree

PCC Voltage Angle

(d)

Figure 3. 11. System performance at the time of asymmetrical sag in source voltage for Example 3.3

Example 3.4: Let us now consider Mode-2 control. This control mode can be

beneficial when running cost of the UPS is cheaper than the grid power. At this time

maximum constant power (based upon the UPS rating) is supplied by the UPS. In

other words, we can say that the UPS is operated at full load and rest of the power or

change in load power is supplied by the source. However the unbalanced and non-

linear portion of the load is still supplied by the UPS such that source current can be

maintained balanced sinusoidal. The controller parameters are chosen as Kpu = 0.025,

Kiu = 10.0 and Kdu = 10×10−6. To investigate the behavior of Mode-2 control during

sag and swell in the source voltage, it is assumed that a sag occurs at t = 0.3 s where

it reduces to 6.98KV (L-N, peak) and a voltage swell occurs at t = 0.5 s where it

increases to 10.98KV (L-N, peak). The results are shown in Fig. 3.12. It shows the

real powers through the different parts of the circuit. Since the load power remains

constant, the powers supplied by the UPS and the source also remain constant.

However the angle δ changes to accommodate this as evident from Fig. 3.12 (b).

Page 72: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

58

0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.5

0

0.5

1

1.5

2

2.5

3

3.5

Time (s)

Pow

er (M

W)

Real Power

Load PowerSource powerUPS Power

(a)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9-20

-15

-10

-5

0

5

10

Time (s)

Deg

ree

PCC Voltage Angle

Sag

Swell

(b)

Figure 3. 12. Mode-2 control at the time of sag and swell in the source voltage for Example 3.4.

Additionally to test the power tracking behavior of the controller, the reference

power from the UPS is changed from 2 MW to 1 MW at t = 0.3 s. The additional

power must come from the source. This is evident from Fig. 3.13 (a). The angle δ is

shown in Fig. 3.13 (b). It can be seen that the angle quickly settles to a new value to

increase the power flow from the source.

Example 3.5: In this example, we explore the mode shifting behavior of the total

system. This can be useful for economic operation the system in which the maximum

power is drawn from the cheaper source. The mode shifting is achieved by

controlling δ with the help of two PID controllers as shown in Fig 3.14. Both the

controllers are run simultaneously irrespective of the control mode. For example,

suppose the control is running in Mode-1 with the power reference of Psref. Then δ is

computed from (2.5) with the switches Sw1 and Sw3 connected in the upper position.

In order to avoid any large transient in case of a mode switch, Mode-2 controller is

also run at this time. However, the reference for Mode-2 controller is computed from

the balance power, i.e., PL − Psref. Therefore the switch Sw2 is also in the upper

Page 73: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

59

position. However since the switch Sw3 is in the upper position, the angle δ computed

from Mode-2 controller is given to the system for the computation of the voltage

reference (2.4). Once the mode shift to Mode-2 control is desired, all the three

switches are connected to the lower position. In this case the output angle of Mode-2

with the reference of Puref is used in (2.4) and Mode-1 controller runs off-line with a

reference of PL − Puref.

0 0.1 0.2 0.3 0.4 0.5 0.6-1

0

1

2

3

4

Time (s)

Pow

er (M

W)

Real Power

Load PowerSource PowerUPS Power

(a)

0 0.1 0.2 0.3 0.4 0.5 0.6-80

-60

-40

-20

0

20

Time (s)

Deg

ree

PCC Voltage Angle

(b)

Figure 3. 13. Mode-2 control during power reference change.

Figure 3. 14. Control switching at the time of mode shifting.

Page 74: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

60

The results are shown in Fig. 3.15. It is assumed that the system is operating in

Mode-1 when a load increase occurs at t = 0.2 s. The load is reduced back to its

nominal value at t = 0.3 s. Subsequently the control is switched to Mode-2 at t = 0.4

s. Following this, the load again increases at t = 0.6 s and reduces at t = 0.8 s.

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80

0.5

1

1.5

2

2.5

3

3.5

4

Time (s)

Pow

er (M

W)

Real Power

Load PowerSource PowerUPS Power

Mode Change

(a)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-100

-50

0

50

100

Time (s)

Deg

ree

PCC Voltage Angle

Mode Change

(b)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-0.25

-0.2

-0.15

-0.1

-0.05

0

0.05

0.1

0.15

0.2

0.25

Time (s)

Curr

ent (k

A)

Phase A Source Current

(c)

Figure 3. 15. System performance during mode switching and load change.

Fig 3.15 (a) shows the three active powers. It is evident that the control scheme

works in a desired manner. The angle δ is shown in Fig. 3.15 (b). It does not have

any significant transient barring a momentary jump at the switching point. The

source current of phase-a is shown in Fig. 3.15 (c). It can be seen that it remains

Page 75: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

61

constant for Mode-1 control and changes according to the load requirement in Mode-

2 when the UPS supplies a constant power.

Example 3.6: In this example, the system performance during islanding is

investigated when the UPS is operating under Mode-2 control. With the system

operating in the steady state, the breaker connecting the supply side with the PCC

opens inadvertently at t = 0.2 s. When there is no power from source at that time total

load power is supplied by the UPS provided that total load power does not exceed the

UPS rating. The breaker recloses at t = 0.4 s.

0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6-1

0

1

2

3

4

Time (s)

Pow

er (M

W)

Real Power

Source PowerUPS PowerLoad Power

Islanding

(a)

0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6-140

-120

-100

-80

-60

-40

-20

0

20

40

60

Time (s)

Deg

ree

PCC Voltage Angle

(b)

0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Curr

ent (k

A)

Load and Source Currents for Phase A

Source CurrentLoad Current

(c)

Figure 3. 16. System performance during islanding and reclosing.

Page 76: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

62

Fig 3.16 (a) shows the source, load and UPS power variation during islanding and

reclosing. It can be seen that the UPS power becomes equal to the load power during

islanding, as expected. During islanding, however, the angle of the PCC voltage is

irrelevant since the total power is supplied by the UPS and zero power is drawn from

the source. Also since the source power is zero, the output of the PID controller

keeps on increasing. This is cause severe angle transient during reclosing. To avoid

this, the angle controller is turned off at the onset of island detection and the angle is

held constant at its pre-islanded value. The angle is shown in Fig. 3.16 (b). Phase-a

of the source and load currents are shown in Fig. 3.16 (c). It can be seen that load

current does not undergo any substantial transient during islanding or reclosing.

3.5. Conclusions

This paper presents a new control methodology to balance the source currents and

real power sharing between the grid and a UPS. Since the PCC voltages are

balanced, the current drawn from the source are balanced irrespective of the nature of

the load. The use of an LC filter with the UPS removes the effect of switching

frequency components at PCC voltage.

A new control strategy for the control of the PCC voltage is proposed in this paper.

In this, a diode state is used instead of the common 0-state. This results in

discontinuity in the VSC output current (i.e., the inductor current of the LC filter). In

comparison to 3-level state feedback control, the proposed method gives much less

switching and the switching loss is almost half compared to the state feedback

control. Furthermore, the new control scheme generates less THD in PCC voltage

than the 3-level state feedback control. In discontinuous control, the peak inductor

current of the LC filter is higher than the 3-level state feedback control. But

average/rms currents in both the controls are in the same order of magnitude. The

saturation current rating of an inductor is frequently designed to be higher than the

heating/average current rating, hence the same inductor can often work in both

discontinuous and 3-level state feedback (continuous) controls. In worse case we

might have to go for some higher rating inductors. In discontinuous control, it is not

necessary that the inductor current will always be discontinuous. Control logic tries

Page 77: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

63

to make it discontinuous but, if next switching event occurs before inductor current

reaches to zero then inductor current doesn’t becomes discontinuous. If inductor

value is high then chances of discontinuity in current is less. Thus there will be

periods of discontinuous current and other periods of continuous. The extent of the

discontinuous mode determines the overall gain of switching losses for the new

control.

The PCC voltage angle (δ) is controlled using a simple PID controller. Mode shifting

between grid and UPS with the help of two PID controllers is discussed along with

switching of these two controllers.

Appendix - A

The characteristics of Toshiba MG400J1US51 module is listed in Table 3.2. These

ratings are used for loss computation of Example 3.2.

TABLE 3. 2. DATA SHEET OF TOSHIBA SILICON N CHANNEL IGBT, MG400J1US51

S.No Characteristic Rating

1 Collector Emitter Voltage 600V

2 Gate Emitter Voltage 20V

3 Forward Current 400A

4 Turn on Time (Max) 1.2µs

5 Rise Time (Max) 0.3µs

6 Turn on Delay (Max) 0.4µs

7 Turn off Time (Max) 1.0µs

8 Turn off Delay (Max) 0.4µs

9 Fall Time (Max) 0.3µs

References

[1] W. Bower and G. O'Sullivan, “Bimode uninterruptible power supply

compatibility in renewable hybrid energy systems,” IEEE Aerospace and

Electronic Systems Magazine, Vol. 5, No. 8, pp. 16-22, August 1990.

Page 78: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

64

[2] K. Hkachi, M. Sakane, T. Matsui, A. Kojima and M. Nakaoka, “Cost-

effective practical developments of high-performance and multi-functional

ups with new system configurations and their specific control

implementations,” IEEE Power Electronics Specialist Conference (PESC),

Vol. 1, pp. 480-485, June 1995.

[3] F. Kamran, and T. G. Habetler, “ A novel on-line ups with universal filtering

capabilities,” IEEE Trans. on Power Electronics, Vol. 13, No. 3, pp. 410-418,

May 1998.

[4] C. Wang and M. H. Nehrir, "Distributed Generation Applications of Fuel

Cells," Power Systems Conference: Advanced Metering, Protection, Control,

Communication, and Distributed Resources, 2006. PS '06, 2006, pp. 244-248.

[5] Z. Jiang and R. A. Dougal, “ Control strategies for active power sharing in a

fuel-cell-powered battery-charging station,” IEEE Trans. on Industry

Applications, Vol. 40, No. 3, pp. 917-924, May/June 2004.

[6] M. K. Mishra, A. Ghosh and A. Joshi, “Operation of a DSTATCOM in

Voltage Control Mode,” IEEE Trans. on Power Delivery, vol. 18, pp. 258-

264, January 2003

[7] G. H. Bode and D. G. Holmes, "Implementation of Three Level Hysteresis

Current Control for a Single Phase Voltage Source Converter," in Power

Electronics Specialists Conference, pp. 33-38, 2000.

[8] F. Zare and G. Ledwich, "A Hysteresis Current Control for Single-Phase

Multilevel Voltage Source Converters: PLD implementation," IEEE

Transaction on Power Electronics, vol. 17, pp. 731-738, September 2002.

[9] A. Ghosh and G. Ledwich, "Load compensating DSTATCOM in weak AC

Systems," IEEE Transaction on Power Delivery, vol. 18, pp. 1302-1309,

October 2003.

[10] A. Ghosh and G. Ledwich, Power Quality Enhancement Using Custom Power

Devices: Kluwer Academic Publishers, 2002.

[11] Toshiba GTR Module Silicon N Channel IGBT, MG400J1US51, from the

website,

http://www.datasheetcatalog.com/datasheets_pdf/M/G/4/0/MG400J1US51.sht

ml.

Page 79: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

65

CHAPTER 4

POWER NETWORK IN LOOP: A PARADIGM FOR REAL-TIME SIMULATION AND HARDWARE

TESTING

SACHIN GOYAL, GERARD LEDWICH AND ARINDAM GHOSH

School of Engineering Systems

Queensland University of Technology

Submitted: IEEE Transaction on Power Delivery.

Page 80: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

66

Abstract −−−− The paper discusses a new paradigm of real-time simulation of power

systems in which equipment can be interfaced with a real-time digital simulator. In

this scheme, one part of a power system can be simulated using a real-time simulator,

while the other part is implemented as a physical system. The only interface of the

physical system with the computer based simulator is through data acquisition

system. The physical system is driven by a voltage source converter (VSC) that is

mimicking the power system simulated in the real-time simulator. In the paper, the

VSC is operated in a voltage control mode to track the PCC voltage signal supplied

by the digital simulator. This type of splitting a network in two parts and running a

real-time simulation with a physical system in parallel is termed as a power network

in loop here. This opens up the possibility of the study of interconnection of one or

several distributed generators to a complex power network. The proposed

implementation is verified through simulation studies using PSCAD/EMTDC and

through hardware implementation on a TMS320F2812 DSP.

Index Terms − Real-time simulator, power network in loop simulation, VSC,

control bandwidth.

4.1 Introduction Digital computer simulations have been used extensively in power systems studies

for both design and testing. However, this form of evaluation tool is often not

suitable for testing of protective devices like relays or testing real life controllers. To

alleviate this problem, real-time digital simulators have been developed, which use

high speed parallel processors to simulate a complex power network within

microseconds [1-3]. These simulators can be interfaced with a physical controller on-

line and this form of operation is often termed as “hardware-in-the-loop” testing.

While testing protection devices, the real-life system components interact with a

digital simulation of a power network running in real time. The hardware is sent

signals to represent the currents or voltages in a network with small amplifiers to

make the signals compatible with the output expected from VT’s and CT’s. The trip

signal from the protecting device is then passed to the simulator which can then

Page 81: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

67

open/close circuit breakers in the simulated network. The advantage of the approach

is that limitations of the hardware implementation can be evaluated within a realistic

environment.

The aim of this paper is to broaden the “hardware in the loop” concept to include

testing of network components. For many consumer devices, the mains supply can be

treated as an ideal voltage source, and hence, the component testing only requires

finding a near-ideal source for evaluating performance. This paper aims to develop

the theory for on-line interaction between power network components and simulation

using an inverter interface. For the simulation of large systems, Kron’s method of

tearing the network into two or more segments offers possibilities [4,5]. The

difficulty is that the theory is developed with similar network solution processes in

both sections without the interface issues.

The interface of real-time controller with a simulated circuit is reported in [6].

Controller output is sent to real time virtual test bed (RTVTB) through an A/D card

and simulation output is sent to micro-controller. Here the communication is at low

voltage. No amplification is required. Communication is carried out through a serial

port.

The network tearing aspect has been studied in a two part paper [7,8]. In Part 1 [7],

different methods of tearing are presented and compared against their performance.

This paper discusses power hardware in loop (PHIL) concept through a two way

interactions. But however does not discuss the hardware feasibility. The frequency

response of different simulation/hardware interface schemes has been presented in

[8]. It however does not present the stability analysis aspects of tearing.

We begin our discussion with an introduction to the hardware-software simulation

concept. This will be followed a discussion of closed-loop VSC control employed in

the paper for voltage control. The associated filtering issues will also be discussed.

The proposed structure will be verified through extensive PSCAD simulation and

also through an experimental setup prepared around a TMS320F2812 DSP processor.

Page 82: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

68

4.2. The Hardware-Software Concept

The conceptual diagram of the hardware-software simulation system is shown in Fig.

4.1. In this diagram, the power network, simulated in a real-time simulator, is termed

as the supply side, while the equipment to be tested is termed as the test side. In

general the test side is assumed to contain a separate generator, which often can be a

disturbed generator (DG). The supply side is represented by its Thevenin equivalent

v1, Z1. The test side may contain a DG, feeder and any local load, which have a

Thevenin equivalent of v2, Z2. In this figure, the voltage vf of the test side is

generated by a voltage source converter (VSC).

Figure 4. 1 Conceptual hardware-software simulation diagram: Voltage control.

In Fig. 4.1, the voltage vp measurement is tracked by the VSC to produce vf of the

test side. The current-controlled current source i f is controlled by the output of the

low-pass filter (LPF). The function of the LPF is to suppress the high frequency

switching components generated by the VSC of the test side current. Moreover, it

also has an impact on the stability of the system, as we shall discuss later. The

voltage and current are transferred from one part (supply side) of the network to the

other part (test side) of the network in the form of low voltage signals with the help

of voltage and current sensors. A current sensor measures the current i2, which is

then sampled and converted by an A/D converter. This signal can then be scaled to

be of the same magnitude as that in the simulated circuit. The LPF is realized in the

form of an averaging process in software itself. The voltage feedback from supply

side to test side is amplified by the VSC, which acts as a power amplifier. The design

of this amplifier is described in Section 4.3. It is to be noted that the connection

between the supply side and the test side is only through signal level through digital-

Page 83: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

69

to-analog converter (DAC) and analog-to-digital converter (ADC). Power level

signals are not exchanged.

Depending on the network complexity and parallel processing hardware availability,

a real-time simulator can solve the supply side dynamic equations in as little as 2

microseconds. A VSC, however, cannot be operated at this speed. Therefore a much

lower switching frequency of the VSC can be chosen, provided that it is sufficient to

track the desired voltage.

In Fig. 4.1, the VSC mimics the supply side for the test side and it is supposed to

generate same voltage waveform as vp. But when VSC tracks supply side voltage for

test side, it generates high frequency switching components along with desired

voltage. These high frequency components reflect in current (i2) flowing at test side.

Since these high frequency switching components are not part of network therefore

elimination of these components are necessary. If this current (i2), containing high

frequency components, is fed to supply side directly, total deterioration of the system

performance will occur. Hence low pass filter is used to eliminate undesired high

frequency components. The effect of the LPF on the system stability is discussed in

Appendix A.

4.3. Amplifier Structure

Fig. 4.2 shows the structure of VSC based power amplifier. It contains one H-Bridge

voltage source converter and an LC filter with inductance of Lf1 and capacitance of Cf

at the output of converter. This filter prevents the high frequency switching

components from entering the test side. VSC is connected to DC storage Vdc. Output

voltage vcf is controlled using a voltage control scheme. Voltage signals of vp from

supply side is considered as a reference for the voltage control scheme.

To discuss the VSC control strategy used in the paper, let us consider a simple power

system, as shown in Fig. 4.3. The network tearing line is also shown in this figure. In

this, the supply side contains the voltage source v1, while source impedance is being

represented by R1 + jωL1. The test side voltage source v2 has a source impedance

Page 84: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

70

jωLs. It also contains a passive R-L load (Rl, Ll) and a feeder with an impedance of R2

+ jωL2. The test side equivalent circuit is shown in Fig. 4.4.

Figure 4. 2 Power amplifier Structure

Figure 4. 3. Simple network under study.

Figure 4. 4. Voltage controlled VSC amplifier connection with the test side.

Ideally, vp1 should be equal to vp2 and i1 should be equal to i2. However with the

network being torn, this will not be so. The main idea of the VSC control is force

them to be nearly equal. The success of the scheme will depend on the closed-loop

Page 85: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

71

control of the VSC, which enables it to track the reference voltage accurately.

Closed-loop voltage tracking in the presence of a filter, however, is a nontrivial task.

In this paper, a strategy of close loop voltage control is discussed.

4.4. Hybrid Discontinuous Voltage Control

In this control scheme, the converter switching decision is made based on inductor

current (i f1) and capacitor voltage (vcf) of LC filter to control the output voltage of

amplifier. All the three states (+ 1, − 1 and 0) of inverter are used here. In + 1 and − 1

states, the output voltages of converter are + Vdc and − Vdc respectively and the 0-

state is the diode state where all four switches are turned off. In the diode state, with

the help of the free-wheeling diode, the inductor current is forced to zero. This state

introduces discontinuity in the converter output current (i f1).

Based on zones, control action between inductor current control and capacitor

voltage control is switched as shown in Fig. 4.5. If error between reference voltage

and capacitor voltage is high then control action is assumed in Zone-1 where

converter decision is made based on filter inductor current and it is controlled inside

a band. Once error reduces due to the control action of Zone-1, control action is

switched to Zone-2, where converter switching decision is made based on filter

capacitor voltage.

Figure 4. 5. The two zones voltage control scheme.

To track a sinusoidal capacitor voltage reference, one cycle is divided in four regions

as shown in Fig. 4.6, where each region is divided into two zones explained above.

Page 86: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

72

For each zone, the hysteresis band is defined separately. In Zone-1, the hysteresis

band is defined for the inductor current and in Zone-2, the band is defined for the

capacitor voltage. In Regions 1 and 3, the capacitor is charged for positive and

negative voltage respectively. Thus the switching control logic is very much similar

in Regions 1 and 3. Only reference changes from positive to negative.

0 0.005 0.01 0.015 0.02-1.5

-1

0

1

1.5

Time

Mag

. Region 1 Region 2

Region 3 Region 4

Figure 4. 6. Four regions of one cycle of a sinusoidal wave

If the reference of the capacitor voltage is in Region 1, then switching in Zone-1 will

be defined as

0 then If 411 =≥ −Shi if (4.1)

where hi is the upper current hysteresis band. This implies that if the current i f1 is

greater than or equal to hi, turn all the switches off. However, if this current is less

than zero, which is lower current band limit, apply positive voltage at the VSC

output, i.e.,

0 and 1 then 0If 4,32,11 =+=< SSi f (4.2)

Let the upper and lower voltage hysteresis bands (for Zone-2) be denoted by huv and

hlv respectively. Then for Zone-2, we have the following switching logic

0 and 1 then If 4,32,1 ==−≤ SShvv lvrefcf (4.3)

0 then and If 41 =+<−> −Shvvhvv uvrefcflvrefcf (4.4)

1 and 0 then If 4,32,1 ==+≥ SShvv uvrefcf (4.5)

Page 87: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

73

The switching for Region 3 will be the same as above except that − Vdc state will be

chosen instead of + Vdc state.

The switching for Region 2 two is defined as follows. The switching in Zone-1 is

0 and 1 then 0If 2,14,3 ==≥ SSi f (4.6)

0 then If 41 =≤ −Shi if (4.7)

Similarly for Zone-2, we have

0 and 1 then If 2,14,3 ==+≥ SShvv uvrefcf (4.8)

0 then andIf 41 =−>+< −Shvvhvv lvrefcfuvrefcf (4.9)

1 and 0 then If 2,14,3 ==−≤ SShvv lvrefcf (4.10)

Switching for Region 4 can be obtain in the same way as in Region 2, the only

difference being the capacitor discharges from negative to zero instead of positive to

zero.

Example 4.1: To demonstrate the voltage tracking ability of the VSC, let us consider

the system of Fig. 4.3. Here it is assumed that network is torn in two parts (supply

and test) from network tearing line as shown in Fig. 4.3. The torn network is

interfaced with the help of VSC amplifier as shown in Fig. 4.4. Efficiency of

amplifier can be judged with the help of error between voltage (vp1) at tearing point

in actual network (Fig. 4.3) and voltage vp2 at test side in the torn network. Ideally

these two voltages should be identical. The system parameters chosen for the study

are:

System Frequency = 50 Hz,

v1 = 9 sin (ωt ) kV, v2 = 9 sin (ωt − 30°) kV,

L1 = 60 mH, Ls = 5 mH, R1 = 0.94 Ω,.

Feeder & Load: R2 = 1.25 Ω, L2 = 80 mH, Rl = 50 Ω,

Ll = 100 mH.

VSC & Filter: Vdc = 15 kV, Lf1 = 10 µH, Cf = 2500 µF.

Page 88: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

74

( )20000

20000LPF

+=

ss

The system is simulated using PSCAD with a simulation step size of 10 µs. Voltage

tracking results of hybrid discontinues voltage control is shown in Fig. 4.7 (a) which

shows reference voltage vp1 of the total (real) network (Fig. 4.3) and output voltage

of amplifier (vp2). Since the difference between the two voltages is not visible from

this figure, the error between them is plotted in Fig. 4.7 (b). The average error is less

than 0.55%.

(a)

(b)

Figure 4. 7 (a) Voltages vp1 and vp2 and (b) voltage tracking error.

Fig. 4.8(a) shows the reference current i2 of the total (real) network (Fig. 4.3) and the

current flowing in torn network (i2′). The error between these two currents is plotted

in Fig. 4.8 (b). The steady state average and maximum errors in current are about

0.58% and 1.56%.

Page 89: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

75

(a)

(b)

Figure 4. 8. (a) Currents i1 and i2 and (b) the error between these two currents.

4.5. Experimental Results

A hardware setup is built to test and verify the practical feasibility of the power

network-in-loop concept. One H-Bridge single phase inverter is used for amplifier.

Texas instrument DSP board TMS320F2812 is used to control the VSC and is also

used to simulate the test side network. LEM current sensor is used to measure the

filter inductor current. For the capacitor voltage of the LC filter of the amplifier,

voltage is scaled down and measured with the help of an operational amplifier. The

PCC voltage (vp) was used as reference voltage for amplifier. Test side current is

sensed using LEM current sensor and A/D converter which is inbuilt in this DSP.

Example 4.2: Here, a simple circuit, as shown in Fig. 4.9, is tested. The tearing line

is as shown in this figure. Since supply side circuit is simulated and the amplifier

control is computed in the same DSP chip, the reference voltage (vp) for amplifier is

directly passed and no DAC is required here. The supply side is simulated using

discrete time state equation with a time step of 40 µs. The schematic diagram of the

hardware setup for this example is shown in Fig. 4.10.

Page 90: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

76

Figure 4. 9. The test circuit of Example 4.2.

Figure 4. 10. Schematic diagram of the hardware setup for Example 4.2.

The state equations for supply side circuit are represented as follow:

( )

=−−

=

s

i

s

s

is

L

RL

BL

RRA

0

01

, (4.11)

The discrete-time equivalent of the circuit for a sampling time (Ts = 40 µs) is given

by

( ) ( ) ( )kGukFxkx c+=+1 (4.12)

where ( ) [ ]lsTcs ivuikx == and .

The system parameters are: Rl = 10 Ω, RL = 200Ω, Ll = 20mH and LL = 54mH. The

supply voltage is chosen with a peak of 20 V and a frequency of 50 Hz. The load

current (i l) is taken to the supply side using current sensor and A/D card. It is then

filtered using an averaging process.

Page 91: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

77

The entire (complete) network without tearing is simulated in PSCAD. This is then

compared with the experimental results obtained with torn network, as per the

experimental set up discussed. Fig 4.11 shows the PCC voltage (vp), while Fig. 4.12

depicts the test side current (i l). It is clear that the experimental results with network

tearing are similar to simulation results with the complete network. These results

prove that the testing of power system network is practically feasible using power

network-in-loop concept.

0.2 0.205 0.21 0.215 0.22 0.225 0.23 0.235 0.24 0.245 0.25-30

-20

-10

0

10

20

30

Time (s)

Vol

tage

(V

)

PCC Voltage

Experimental ResultSimulation Result

Figure 4. 11. Experimental and simulation result for PCC voltage (vp)

1.2 1.21 1.22 1.23 1.24 1.25 1.26 1.27 1.28 1.29

-0.1

-0.05

0

0.05

0.1

0.15

Time(s)

Cur

rent

(A

)

Test Side Current

Experimental resultSimulation Result

Figure 4. 12. Experimental and simulation result for i l

In the next step of this test, a 30 µF capacitor is connected in series with RL and LL

and value of RL was reduced to 10 Ω. The capacitor is switched to examine the

transient behaviour of torn network. With the circuit being in steady state, the

capacitor is bypassed (short circuited) in the simulation studies. Fig. 4.13 shows the

current i l. Note that the reactance of the capacitor is much larger than that of the

inductor. Hence the load impedance reduces as the capacitor is bypassed. This results

in an increase in the current as is evident from Fig. 4.13. The experimental waveform

is shown in Fig. 4.14. The transient behaviours are not identical since the dynamics

of the switch and the instant of bypass switch closing could not be matched.

Page 92: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

78

0.16 0.17 0.18 0.19 0.2 0.21 0.22 0.23 0.24 0.25

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

Time(s)

Cur

rent

(A)

Load Switch (Simulation Result)

Load Change

Figure 4. 13. Simulation result for i l

Figure 4. 14. Experimental result for i l during capacitor switching.

Example 4.3: In this example, the feasibility of power network tearing is extended

by testing the interaction of two generators. Fig. 4.15 shows the network under test in

which the network tearing line is also indicated. The supply side network is

simulated in the DSP using state equations of (4.11) and (4.12) since the supply side

remains unchanged from Example 4.2.

Figure 4. 15. Circuit under test for two generators interaction.

The grid voltage is scaled down using an auto-transformer and used as the voltage

source v2. Synchronization between v2 and v1 must be established to avoid a

Page 93: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

79

frequency mismatch. Generally, a phase lock loop (PLL) is used to establish

synchronization between two sources. To avoid complexity, the grid voltage is scaled

down and passed to the DSP through an ADC. We can then set the frequency of the

voltage source v1 to that of the mains. The voltage magnitude and phase difference

(Φ) can be created using software program in the DSP by storing one cycle data at a

40 µs sampling rate. The study system parameters are shown in Table-4.1.

TABLE 4. 1: SYSTEM PARAMETERS FOR EXAMPLE-4.3. System

Quantities

Value

v1 )sin(5.32 tω×

v2 )sin(10 φω +× t

Rl 10Ω

Ll 20mH

Ri 5Ω

RL 200Ω

LL 54mH

R2 5Ω

L2 9mH

1.76 1.78 1.8 1.82 1.84 1.86 1.88 1.9-2.5

-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

2.5

Time(s)

Cur

rent

(A)

Experimental ResultsSimulation Results

Figure 4. 16. Current at network tearing point (i l).

For this test, again the PSCAD simulation of the complete network is compared with

the experimental results. First the network is tested with zero phase difference

between v1 and v2. Fig. 4.16 shows the current at network tearing point (i l). Fig. 4.17

shows the comparison between the line currents (i l1). It is clear from these figures

Page 94: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

80

that the currents in the torn network are similar to those in the simulated entire

network. Fig. 4.18 shows the phase difference between i l1 and v2, obtained

experimentally. The PCC voltage is shown in Fig. 4.19.

1.78 1.79 1.8 1.81 1.82 1.83 1.84 1.85

-1.5

-1

-0.5

0

0.5

1

1.5

Time(s)

Cur

rent

(A

)

Line Current

Experimental ResultSimulation Result

Figure 4. 17. Line current passing through R2 (i l1).

5.24 5.26 5.28 5.3 5.32 5.34 5.36 5.38 5.4 5.42-25

-20

-15

-10

-5

0

5

10

15

20

25

Time(s)

Current

Voltage

Figure 4. 18. Phase difference between i l1 and v2.

Figure 4. 19. Tearing point (PCC) voltage vp. In the next stage of this test, a phase difference of 20° was created between v1 and v2

in which the phase of v1 is advanced by 20° vis-à-vis that of v2 in the software

program. Fig. 4.20 shows the voltage v1 and v2. Fig. 4.21 shows the current at

network tearing point (i l). Since the case magnitude of i l is very small, the noise to

signal ratio of the current sensor is high. Therefore the current i l is significantly

Page 95: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

81

distorted. However, the performance of the system does not get affect due to the

small magnitude of the current. This is evident from the PCC voltage shown in Fig.

4.22.

1 1.002 1.004 1.006 1.008 1.01 1.012 1.014 1.016 1.018 1.02-40

-30

-20

-10

0

10

20

30

40

Time(s)

Vol

tage

(V)

v1

v2

Figure 4. 20. v1 and v2 with 20° phase difference.

1.12 1.14 1.16 1.18 1.2 1.22 1.24 1.26 1.28 1.3

-0.5

0

0.5

Time(s)

Cur

rent

(A)

Experimental ResultsSimulation Results

Figure 4. 21. Current at network tearing point (i l).

Figure 4. 22. Tearing point (PCC) voltage vp.

Example 4.4: To study the two way interaction of power network in loop, the

network shown in Fig. 4.23 is considered, where the voltage source v2 is the utility

bus. The voltage source v1 is simulated in the DSP and its angle (δ) is varied

according to the swing equation.

Page 96: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

82

Figure 4. 23. Circuit under test for Example 4.4.

The swing equation is solved in discrete time domain at sampling rate of 40µs. It can

be represented as follow:

( )em PPHf

H

D

dt

d −

+

−=

02

1

02

02 δ

ω

πδω

(4.13)

The discrete-time equivalent of the swing equation at the sampling frequency of 1/Ts

is given by

( ) ( ) ( )kGukFxkx c+=+1 (4.14)

The parameters chosen for the study are

R=15 Ω, L=20mH, f=50Hz, D=6 and H=0.5

)sin(121 δω +×= tv and )sin(102 tv ω×=

To calculated the instantaneous electrical power (Pe), is is sensed using A/D card and

multiplied with v1. The angle δ is calculated using (4.14) by the DSP. To overcome

the problem of frequency mismatch between v1 and v2, mains grid voltage is sensed

using A/D card and scaled to form the magnitude of v1, while a phase lead is

provided according the calculated value of δ as per (4.14).

Initially Pm is set to 2 watts. Fig. 4.24 (a) and (b) show the simulation and

experimental results, respectively, of the initial transient in is. It is clear from these

that the initial transients are similar.

Page 97: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

83

0 0.2 0.4 0.6 0.8 1 1.2 1.4

-1

-0.6

-0.2

0

0.2

0.6

1

Time(t)

Cur

rent

(A)

Siumulation result

(a)

0.2 0.4 0.6 0.8 1 1.2 1.4

-1

-0.6

-0.2

0

0.2

0.6

1

Time(t)

Cur

rent

(A)

Experimental Results

(b)

Figure 4. 24. Initial transients in is: (a) simulated waveform and (b) experimental waveform.

The value of Pm is now suddenly changed from 2 to 5 watts. It is well-known that as

Pm increases; both the values of δ and is will increase. Fig. 4.25 (a) shows the

simulation result of change in Pm, while Fig. 4.25 (b) shows the waveform obtained

experimentally. It can be seen that the magnitudes and trends are similar for both

these waveforms.

2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

Time(t)

Cur

rent

(A)

Simulation Result

(a)

Page 98: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

84

2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

Time(t)

Cur

rent

(A)

Experimental Result

(b)

Figure 4. 25. Transients in is during power change: (a) simulated waveform and (b) experimental waveform.

Hence this experiment proves that the transient study of power system network can

be performed using the proposed power network in loop concept. For study of big

power network, high speed real time digital simulators are required so that the supply

side network can be simulated in lesser time.

4.6. Power Network In Loop Of A Complex System

So far we have demonstrated the proposed concept of power network in loop for

simple systems and have verified it through simulations and experiments. In this

section, we shall show that this concept of tearing is valid even in the case of more

complex networks. The dynamic interaction will be verified through simulation

studies only. The system is considered to be single phase.

Example 4.5: Let us consider the system as shown in Fig. 4.26. In this figure,

different feeder sections are denoted by the subscript ‘f’, while the loads are denoted

the subscript ‘l’. The system parameters for the network are listed in Table 4.2. It is

assumed that the circuit on the left of the network tearing line (the supply side) is

simulated in a digital simulator, while the circuit on the right (test side) consists of

physical systems with the interface driven by an amplifier. Both these systems are

simulated in PSCAD. The amplifier is controlled with discontinuous hybrid voltage

control. The network tearing line is also indicated in this figure. This network has 2

buses and 5 feeders. Voltage sources v1 and v2 are connected to Bus-1 and Bus-2

Page 99: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

85

through feeders one and five respectively. There is a rectifier load connected to Bus-

1 through feeder 3 that injects the harmonics to the system.

The PCC voltage of the complete network without tearing and the torn network with

the VSC amplifier are shown in Fig. 4.27 (a), while the error between these two

voltages is shown in Fig. 4.27 (b). The average voltage error is 2%. The currents

flowing in the test side for the two networks (without tearing and torn) are shown in

Fig. 4.27 (c), while the error between these two quantities is shown Fig. 4.27 (d). The

average current error is 3%.

Figure 4. 26. The complex study system.

TABLE 4. 2: PARAMETERS OF THE SYSTEM OF FIG. 4.24. System quantities Values

System frequency 50 Hz

Voltage Source v1, v2 9 sin (ω t)

Feeder (Rf1, Lf1) 0.4032 Ω, 12.8

mH

Feeders (Rf2, Lf2), (Rf3, Lf3),

(Rf4, Lf4),

0.2016 Ω, 6.4 mH

Source inductance (Ls) 5 mH

Load (Rl1, Ll1), (Rl3, Ll3), 50 Ω, 100 mH

Page 100: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

86

(Rl4, Ll4)

Feeders Rf5, Lf5 1.25 Ω, 6.4 mH

Load (Rl2, Ll2) 10 Ω, 100 mH

Filter capacitance Cl2 50 µF

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

-10

-5

0

5

10

Time (s)

Vol

tage

(kV

)

PCC Voltage in Real & Torn Network

TornReal

(a)

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1-0.5

-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

0.5

Time (s)

Vol

tage

Err

or (kV

)

(b)

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1-0.5

-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

0.5

Time (s)

Cur

rent

(kA

)

Current in Real & Torn Network

TornReal

(c)

Page 101: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

87

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1-0.015

-0.01

-0.005

0

0.005

0.01

0.015

Time (s)

Cur

rent

Err

or (k

A)

(d)

Figure 4. 27. Voltage, current and their errors in Example 4.5.

Example 4.6: In this example, we investigate the behavior due to voltage sag and

swell in the source voltage of the supply side of the system of Fig. 4.26 and Table

4.2. A sag in the source voltage is created at 0.5 s, where the source voltage is

decreased to 7 kV (L-N Peak). This is followed by a swell in this voltage at 0.6 s,

where the voltage becomes 11 kV (L-N Peak). The voltage returns to its nominal

value (9 kV) at 0.7 s.

Fig. 4.28 (a) shows the PCC voltage of the complete and the torn networks, while the

voltage error is shown in Fig. 4.28 (b). The average voltage error is less than 2%.

However at the points of the occurrence of voltage transients, the error shoots up to

about 3.5%. Fig. 4.28(c, d) shows the current in the actual and torn networks and

error between these two currents. It is clear from Fig. 4.28(d) that the current error is

less than 5%.

0.45 0.5 0.55 0.6 0.65 0.7 0.75-15

-10

-5

0

5

10

15

Time (s)

Vol

tage

(kV

)

PCC Voltage in Real and Torn Network

TornReal

Sag Swell

(a)

Page 102: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

88

0.45 0.5 0.55 0.6 0.65 0.7 0.75

-0.4

-0.2

0

0.2

0.4

0.6

Time (s)

Volta

ge E

rror

(kV)

(b)

0.45 0.5 0.55 0.6 0.65 0.7 0.75-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

Time (s)

Cur

rent

(kV

)

Current in real and Torn Network

TornRealSag Swell

(c)

0.45 0.5 0.55 0.6 0.65 0.7 0.75-0.02

-0.015

-0.01

-0.005

0

0.005

0.01

0.015

0.02

Time (s)

Cur

rent

Err

or (kA

)

(d)

Figure 4. 28. Voltage, current and their errors in Example 4.6.

Example 4.7: In this example effect of line to ground faults at buses 1 and 2 is

examined. At t = 0.5 s, the fault is created at Bus 1 and it is removed at t = 0.6 s.

Again at t = 0.7 s, a fault is created at Bus 2, which is removed at t = 0.8s. Due to

either of these faults, the PCC voltage decreases and test side current increases. Fig.

4.29 (a) shows the PCC voltage in the actual and torn networks. It is clear from

figure that the amplifier is able to track the voltage closely even when it reduces due

to the faults. Fig. 4.29 (b) shows error in the PCC voltages. It is clear from this figure

that except for the spikes at the instants of voltage change, the error is less than 3.5%.

Fig. 4.29 (c) shows the current in the actual and torn networks, while their error is

plotted in Fig. 4.29 (d). The average current tracking error is less than 2.5%.

Page 103: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

89

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85

-10

-5

0

5

10

Time (s)

Vol

tage

(kV

)

PCC Voltage in Real and Torn Network

TornReal

Fault at Bus A

Fault at Bus B

(a)

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85-3

-2

-1

0

1

2

3

4

5

6

Time (s)

Vol

tage

Err

or (k

V)

(b)

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85-3

-2

-1

0

1

2

3

Time (s)

Cur

rent

(kA

)

Crrent in Real and Torn Network

TornReal

Fault at Bus A

Fault at Bus B

(c)

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85

-0.1

-0.05

0

0.05

0.1

Time (s)

Cur

rent

Err

or (k

A)

(d)

Figure 4. 29. Voltage tracking of a complex system at the time of faults

Page 104: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

90

4.7. Conclusions

In this paper a new concept has been proposed. This Power Network in Loop

provides a new method for testing of power system components. This paper shows

how this can be applied to general power networks through simulation and

experimental studies. The research shows that a subsystem of a power network can

be interfaced with a real-time simulation using the switching amplifier. The amplifier

is capable of amplifying the voltage signal received from the real-time simulation.

This can represent the effect of the simulated network, which can be complex. This

amplified voltage can then be interfaced with a small physical subsystem. Using this

concept, the effect of different faults and other conditions in the simulated network

can be evaluated on the subsystem under test.

References

[1] R. Kuffel et al, “RTDS – a fully digital power system simulator operating in real-

time,” Digital Power System Simulators, ICDS’95, 1995.

[2] G. Sybille and P. Giroux, “Simulation of FACTS controllers using the MATLAB

power system blockset and Hypersim real-time simulator,” IEE PES Panel

Session on Digital Simulations of FACTS and Custom Power Controllers, Winter

Meeting, New York, 2002.

[3] C. A. Rabbath, M. Abdoune and J. Belanger, “Effective real-time simulations of

event-based systems,” Proceedings of the 2000 Winter Simulation Conference,

2000.

[4] B. Han, B. Bae and Y. Jeong, “Load simulator with power recovery capability

based on voltage source converter-inverter set,” Proc. IEE Electric Power

Application, Vol. 153, No. 6, pp. 891-897, 2006.

[5] G. Kron, Tensor Analysis of Networks, John Wiley, N.Y., 1939.

[6] Z. Jiang, R, Leonard, R. Dougal, H, Figueroa and A. Monti, “Processor-in-the-

loop simulation, real-time hardware-in-the-loop testing, and hardware validation

of a digitally-controlled, fuel-cell powered battery-charging station,” IEEE

Power Electronics Specialists Conference, pp. 2251-2257, Aachen, 2004.

Page 105: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

91

[7] X. Wu and A. Monti, "Methods for partitioning the system and performance

evaluation in power-hardware-in-the-loop simulations. Part I," in Industrial

Electronics Society, 2005. IECON 2005. 31st Annual Conference of IEEE, 2005,

pp.251-256

[8] X. Wu and A. Monti, "Methods for partitioning the system and performance

evaluation in power-hardware-in-the-loop simulations - Part II," in Industrial

Electronics Society, 2005. IECON 2005. 31st Annual Conference of IEEE, 2005,

pp.257-262

Appendix - B

This appendix discusses the numerical stability issue and provides a guideline for the

remedial action. Consider the network shown in Fig. 4.30, for which the following

parameters are chosen: R1 = 1 Ω, L1 = 1 mH, R2 = 0.1 Ω, L2 = 0.1mH, C = 10 µF Ri =

2 Ω and v1 = √2×10 sin (ω t) V. The network tearing line is also shown in the figure.

Let us assume that the current i1 is directly supplied from test side to the supply side

without passing it through the LPF. For the parameters chosen, the complete network

without tearing is stable. However, the power network in the loop simulation

becomes unstable as shown in Fig. 4.31. It can be seen from Fig. 4.7 (b) that the

voltage error contains the high frequency components, which is then passed to the

current i1. A direct feedback of this current to the supply side will result in the

distortion of the PCC voltage as shown in Fig. 4.32. The distorted PCC voltage

further distorts the current, which then distorts the PCC voltage further. Thus the

distortions shown in Figs. 4.31 and 32 are due to these cumulative effects.

Figure 4. 30. The network considered for stability studies.

Page 106: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

92

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

Time (s)

Cur

rent

(A)

Test Side Current (il)

Figure 4. 31. The test side current containing high frequency ripple components.

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04-15

-10

-5

0

5

10

15

Time (s)

Volta

ge (V

)

PCC Voltage

Figure 4. 32. The distorted PCC voltage.

To alleviate the problem, the current i1 is first passed through a low pass filter (LPF)

before passing it to the supply side as shown in Fig. 4.33. The LPF prevents the

injection of the high frequency components of i1 to the supply side and hence PCC

voltage does not get distorted. This results in the stable tracking as shown in Fig.

4.34. A more formal proof of the effect of the LPF is beyond the scope of this paper.

Figure 4. 33. System structure with LPF.

Page 107: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

93

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04-10

-8

-6

-4

-2

0

2

4

6

8

10

Time (s)Volta

ge (V

)

PCC Voltage

Figure 4. 34. Stable PCC voltage with LPF.

Page 108: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

94

CHAPTER 5

TESTING OF A DISTRIBUTED GENERATION SYSTEM WITH A VIRTUAL GRID

SACHIN GOYAL, ARINDAM GHOSH AND GERARD LEDWICH

School of Engineering Systems

Queensland University of Technology

Submitted: Electric Power Systems Research.

Page 109: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

95

Abstract – The paper provides the solution for testing of a distributed generation

system (DGs) with a computer simulated grid. The computer simulated grid is

referred as virtual grid in this paper. Integration of DG with the virtual grid provides

broad area of testing of power supplying capability and dynamic performance of a

DG. It is shown that a DG is supplying a part of load power while keeping PCC

voltage magnitude constant. To represent the actual load, a universal load along with

power regenerative capability is designed with the help of voltage source converter

(VSC) that mimics the load characteristic for DG. The overall performance of the

proposed scheme is verified using computer simulation studies.

Keywords −−−− UPS, Virtual grid, Universal Load, LC output filter.

5.1. Introduction

Because of size and the complexity of interaction within a power network, most

power system research is based on pure simulation. To validate the performance of

physical generator or protection system, most testing is constrained to very simple

power networks. This paper examines a method to test power system hardware

within a complex virtual environment. Integration of simulation with a physical

system gives an opportunity to test a small distributed generation system with in a

large power network. According to this concept, the total power network is torn in

two parts. One part represents the physical system that needs to be tested and the

other part represents the rest of the complex network. The complex power network is

simulated in a real time simulator [1-3] and with the help of analog-to-digital (A/D)

and digital to analog (D/A) converter cards signals (voltage and current) are

transferred from simulated network to physical system and vice versa. Since there is

a voltage level difference between the simulation signals and the physical system, an

amplifier is required to bring simulation signal to the level of physical system. A

high bandwidth switching amplifier (VSC based) is used to connect the physical

system in a loop with the simulation.

While testing protection devices [4], the real-life system components interact with a

digital simulation of a power network running in real time. The hardware is sent

Page 110: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

96

signals to represent the currents or voltages in a network with small amplifiers to

make the signals compatible with the output expected from VT’s and CT’s. The trip

signal from the protecting device is then passed to the simulator which can then

open/close circuit breakers in the simulated network. The advantage of the approach

is that limitations of the hardware implementation can be evaluated within a realistic

environment

In this paper, the concept of “Hardware in loop” is explored to test a DG system with

a power network. The DG is connected to the main grid with a VSC and a LC filter.

The LC filter is used to bypass the switching frequency components of VSC output

voltage. The control and structure of the total DG system is designed in such a way

so that it overcome the power quality problem, while supplying clean power from

DGs at the same time. In case of emergency, when there is no power from the grid, it

can supply the total load and that is why in this paper this total DG system is termed

as uninterruptible power supply (UPS). This UPS can compensate the load at the

time of sag or swell in source voltage. Also it can compensate the load at the time of

feeder change [5]. For the simulation of large systems, Kron’s method of tearing the

network into two or more segments offers possibilities [6]. The difficulty is that the

theory is developed with similar network solution processes in both sections without

the interface issues. The load simulator with power recovery unit has been studied in

[7-9]. Here the concept of back to back inverter is used for power recovery at AC

side with PLL which requires extra hardware and control.

We start our discussion with an introduction to the hardware – software integration

concept. This will be followed by the UPS and its testing scheme with power

recovery scheme. We will also discuss the control of amplifier with power recovery

capability. The proposed scheme and control will be verified through extensive

PSCAD simulation.

5.2. The Concept

The conceptual diagram of the hardware-software interface system is shown in Fig.

5.1. In this diagram, the complex power network, simulated in a real-time simulator

Page 111: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

97

(RTS), is termed as the supply side, while the equipment to be tested is termed as the

test side. In general the test side is assumed to contain a separated generator, which

often can be a distributed generator (DG). The supply side can be a set of generators

and a complex network. The test side may contain a DG, feeder and any local load.

For the simplicity a small network as shown in Fig. 5.1 (a) is considered to explain

the concept. Here the supply side contains a generator v1 and a feeder with the

impedance of Z1 and the test side contains another generator v2 and a feeder with the

impedance of Z2. The network is torn along the network tearing line as shown in Fig.

5.1 (a). After tearing a voltage controlled voltage source is connected at supply side

and a current controlled current source is connected at supply side as shown in Fig.

5.1 (b).

(a)

(b)

Figure 5. 1 Conceptual hardware-software simulation diagram: Current control. (a) The Un-torn Network (b) Torn Network

In Fig. 5.1 (b), the current i1 measurement from the supply side controls the current-

controlled current source i f of the test side. Similarly the voltage-controlled voltage

source vf is controlled by the point of common coupling (PCC) voltage vt.

Page 112: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

98

It is to be noted that the connection between the supply side and the test side is

through digital-to-analog converter (DAC) and analog-to-digital converter (ADC).

For example, consider the system of Fig. 5.1. The current signal i1 is passed through

a low pass filter (LPF) and using a DAC sets the reference for i f. Similarly, the

measured voltage vp is passed through a LPF and given as the input vf through an

ADC. There are some stability issues in the system because of the bandwidth

mismatch between the supply side voltage controlled voltage source and the test side

current controlled current source which is an amplifier. LPF1 and LPF2 are used to

overcome the stability problem of the whole system.

Since output signal of the RTS is a low voltage signal and it can not supply any

amount of power to the physical power network therefore the RTS can not be

directly connected to the physical power network. To integrate the RTS and the

physical power network, an amplifier is required that amplifies the RTS output signal

from signal level to power level so that it can interact with physical power network.

In later part of this paper design of a current amplifier will be discussed.

5.3. The Scheme

The single-line diagram of the scheme under test is shown in Fig. 5.2. It is a

distribution system containing the UPS for reliability and power quality

enhancement. It is assumed that the UPS is supplied from a DG with a dc voltage of

Vdc. The load is assumed to be unbalanced and nonlinear. The load is connected at

the far end of a feeder with an impedance of R + jωL, which is supplied by a source

(vs). An LC filter is connected at the output of VSC, the inductance and the

capacitance of which are denoted by Lf and Cf respectively, while the resistance Rf

indicates the circuit losses. The PCC voltage is denoted by vt.

The main purpose of the UPS is to maintain a balanced PCC voltage (vt) irrespective

of unbalance and distortion in the load currents and to share a specific amount of the

load power. It also controls the magnitude of the PCC voltage to a pre-specified

value even when there is a sag or swell in the source voltage. To control the power

flow either from the grid or from the UPS, the angle of the PCC voltage must be

Page 113: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

99

controlled. Therefore the reference for the PCC voltage contains a pre-specified

magnitude and an angle that is based on power requirements. The VSC then will

have to track this reference voltage in order to achieve the desired performance. The

amount of power shared by the UPS depends on capability of DG system and

different mode of the UPS operation. In later part of this paper these different modes

will be described.

Figure 5. 2. Distributed Generation scheme under test

The aim is to test this UPS in real time frame in different network condition. This

network is torn along the network tearing line as shown in Fig. 5.2. The portion of

network which is above the tearing line is simulated inside the computer which is

referred here as the supply side. A VSC based current amplifier is connected to the

UPS at PCC’, which amplifies the current signal of RTS and mimics the supply side

network for the UPS. Sine the UPS shares the certain amount of the load power

therefore power flows from UPS to amplifier. To minimize the losses at the time of

testing, this amplifier was designed with power regeneration capability so that the

amplifier can supply back the power to the UPS. The PCC’ voltage is measured with

the help of voltage sensor and fed in to RTS with the help of A to D card. Current i f

from computer simulation is taken out for the reference of amplifier and amplifier

tracks this reference current.

Page 114: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

100

When VSC based amplifier tracks this reference current, power is fed from the UPS

to the DC side of the VSC. This power is fed back to the DC bus of UPS. Therefore

only the power required for circuit losses in the whole system is consumed

effectively.

vs

+

RL

is Unbalanced

Non-Linear

load

if*

il

vt

Ps, Qs PL, QL

PCC

VSC

Rf

Lf

CfPU, QU

PCC’

VSC

(Mimicking Load)

if

Power

Feed Back

vt*

Lf1

if*

Reference

A/D Card

D/A Card

Vdc

The Operating

DGVdg

Figure 5. 3 Network Tearing Scheme

5.3.1. The UPS Model

Fig. 5.4 shows the structure of the UPS. It contains three H-Bridge VSCs. All three

VSCs are connected to common DC storage source Vdc. Each VSC is connected to

grid through single phase transformer and a capacitor. The three single phase

transformers are used to provide isolation [7]. Leakage inductance of transformer Lf

and the filter capacitor Cf constitute the LC filter for each phase. All three

Page 115: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

101

transformers are connected in star and neutral point is connected to the neutral of the

load or it may be grounded if neutral point of load is not available. As far as structure

of single phase converter is concern, it has four switches with anti-parallel

freewheeling diode.

The main purpose of the UPS is to maintain a balanced PCC voltage (vt) irrespective

of unbalance and distortion in the load currents. It also controls the magnitude of the

PCC voltage to a pre-specified value even when there is a sag or swell in the source

voltage. To control the power flow according to the modes described in the previous

section, the angle of the PCC voltage must be controlled. Therefore the reference for

the PCC voltage contains a pre-specified magnitude and an angle that is based on

power requirements. The VSC then will have to track this reference voltage in order

to achieve the desired performance.

Figure 5. 4. UPS structure used in which three separate VSCs are supplied from a common dc storage capacitor.

Page 116: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

102

5.3.2. The Amplifier Model

Figure 5. 5 The Structure of Universal Load

Fig. 5.5 shows the structure of the current amplifier. It contains three H-Bridge

VSCs. All three VSCs are connected to the same DC storage source Vdc where UPS

is connected. Each VSC is connected to PCC through single phase transformer.

Leakage inductance of transformer Lfl constitute the L filter for each phase. All three

transformers are connected in star and neutral point is connected to the neutral of the

load or it may be grounded if neutral point of load is not available. However this

current amplifier is amplifying the current signals of RTS but it is not supplying any

amount of power to the system. Because power flow is from USP to the rest of the

system. Therefore this power has to consume by some load. The current amplifier

works as a load for the UPS and can be termed as universal load. But the power

consumed by universal load can be fed back to the DC bus of the UPS to minimize

the power losses. Here this power is fed back to the UPS by making a common DC

bus as shown in Fig. 5.3.

5.4. Reference Generation

Let us define the rms source and PCC voltages as

δ−∠=°∠= ttss VVVV and 0 (5.1)

Page 117: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

103

Then from Fig. 5.2, we get the following expression for the active and reactive power

entering the PCC from the source

( )[ ]δδ sincos22 sts

ts VXVVR

XR

VP +−

+= (5.2)

( )[ ]δδ sincos22 sts

ts VRVVX

XR

VQ −−

+= (5.3)

where X = ωL. If |Vs| ≈ |Vt|, the first term inside the bracket on the right hand side of

(5.2) is negative. However, its influence on the positive valued second term is

negligible as R << X. It is clear from (5.2) that real power flow can be controlled

using δ. Because if δ is increased or decreased, the amount of real power can be

increased or decreased accordingly. Therefore the reference PCC voltages are given

by

( )( )( )

°+−=

°−−=

−=

120sin

120sin

sin

δωδωδω

tVv

tVv

tVv

tmrefc

tmrefb

tmrefa

(5.4)

where Vtm is a pre-specified magnitude and δ is controlled according to the power

control mode.

Power Control:

A fixed amount of active power is drawn from the source and the UPS supplies the

balance amount of load requirement. As mentioned before, this can be achieved by

controlling δ. This gives the following power control loop

dt

deKdteKeK s

dssissps ++= ∫δ (5.5)

where es = Psref − Ps, Psref is the reference power which is drawn from the source.

As mentioned earlier, the UPS must regulate the PCC voltage even during a changed

source voltage condition. Suppose a voltage sags occurs causing source voltage (|Vs|)

Page 118: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

104

to drop. As per requirement, the PCC voltage |Vt| is still held constant. Hence from

(2), it is evident that δ must increase in order to maintain the power flow constant.

On the contrary, the angle δ must reduce during swell in the source voltage.

Also, it can be seen from (3) that reactive power (Qs) is function of δ. Furthermore,

since |Vs| cos δ < |Vt|, Qs is negative. This means that the UPS supplies reactive

power to the grid. As described above that at the time of sag in source voltage, δ is

increased to maintain Ps constant. This will cause the first term of (5.3) to become

more negative. It means source will draw more reactive power from the UPS during

this condition.

The UPS can be operated in a different mode where the UPS is responsible to supply

the constant power and the source supplies the balance amount of load requirement

[5]. Here in this paper, this second mode of operation is named Mode II operation.

5.5. Control Strategy

5.5.1. Control of UPS: Hybrid Discontinuous Control

A hybrid discontinuous control is used to operate the UPS [5, 10]. This control is

useful, when an LC filter is connected to the output of a single phase converter and

the instantaneous output voltage of filter capacitor (vcf) needs to be controlled.

1S 2S

3S 4S

cfv

Figure 5. 6. VSC scheme to control capacitor voltage.

Fig. 5.3 shows the circuit configuration of a single-phase H-bridge converter with the

LC filter. In this control method, the converter switching decision is made based on

Page 119: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

105

both filter inductor current (i f) and filter capacitor voltage. The control is switched

from one stage that is based on inductor current to second stage which is based on

capacitor voltage according to zones. The zonal scheme is shown in Fig. 5.4 for a

sinusoidal reference voltage with zones and hysteresis band. The controller is

assumed to be in Zone-1 when the error is large and it is in Zone-2, when the error is

small (within the hysteresis band). In Zone-1, the control decision is made based on

filter inductor current. When the error reduces as a result of the control action of

Zone-1, the controller switches to Zone-2, where the decision will be made

depending on filter capacitor voltage. However, in both the zones, all three states

(+1, -1 and 0) of converter are used based upon the reference voltage. In + 1 state,

the converter output becomes + Vdc, which is achieved by turning on the switches S1

and S4 and turning off the switches S2 and S3 of Fig. 5.3. Similarly in − 1 state, the

converter output becomes − Vdc that can be achieved by turning on the switches S2

and S3 and turning off the switches S1 and S4. Usually the 0-state is defined when

output voltage of converter is 0 V which is achieved by closing the pair S1-S2 or S3-

S4.

Figure 5. 7. The two zones voltage control scheme.

But in this paper, the 0-state is modified to be a diode state where all the four

switches S1-S4 of the converter are turned off. During this time, the anti-parallel

diodes conduct to bring filter inductor current (i f) to zero. Once i f becomes zero, the

diodes stop conducting and the converter output voltage becomes equal to filter

capacitor voltage (vcf). Because of the major involvement of the diodes, this state is

termed as the diode state in this paper. This state introduces discontinuity in the

Page 120: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

106

converter output current (i f). Since the converter current (i f) becomes zero in the

diode state, the next switching for either + 1 or − 1 state, occurs at zero current

resulting in a loss free switching.

5.5.2. Control of Current Amplifier (Universal load):

Since PCC’ voltage is controlled by the UPS. Hence VSC (amplifier) is responsible

to control the current i f. Reference for this current is taken from the computer

simulation with the help of D to A card. This current can be tracked with simple

hysteresis current control (HCC).

( )dctf

f vuvLdt

di×−=

1

1 (5.6)

1

1

=−≤

−=+≥∗

uthenhiielseif

uthenhiiif

ff

ff (5.7)

Usually a Simple HCC results in high switching frequency component in the PCC

voltage. To overcome this problem a capacitor is connected to bypass the switching

frequency ripple in the PCC voltage and it needs a special form of control because of

instability. In this design the capacitor Cf helps to filter out switching frequency

component of both VSC and UPS. Hence the amplifier does not need any special

control, the simple HCC work fine to control the current i f.

Example 5.1: Consider the system shown in Fig. 5.2. It is assumed that the source

voltage vs is balanced and has a magnitude of 11 kV (L-L, rms), which is equal to

about 9 kV (L-N peak). The load is an unbalanced nonlinear load, whose unbalanced

RL components are

Zla = 48.2 + j94.2 Ω, Zlb = 12.2 + j31.4 Ω and Zlc = 24.2 + j60.47 Ω

where the subscripts a, b and c denote the three phases. In addition, a three-phase

rectifier is also connected to the PCC with DC side load of 100 + j31.4 Ω. The feeder

impedance is R + jωL = 3.025 + j18.13 Ω. The UPS parameter are Vdg = 2.8 kV (L-L

Page 121: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

107

rms), Rf = 1.5 Ω and Cf = 50 µF. The single-phase transformers are rated 1 MVA, 3

kV/11 kV with a leakage inductance of 2.5%. The UPS is connected to grid at time t

= 0 where it is required to maintain the PCC voltage at 11 kV (L-L rms). It is

assumed that the source power remains constant (Mode-1 control) such that balance

power comes from the UPS. The controller parameters chosen are Kps = −0.025, Kis =

−10.0 and Kds = −10×10−6 in (5.5).

To test this system network was torn according to figure 5.2. Three 1 MVA,

11kV/3kV with 10% leakage inductance, step down single phase transformers are

used for the universal load. The PCC’ voltage is maintained at 11 kV (L-L rms), δ is

controlled according to equation (5.5) based on power requirement from source. This

PCC’ voltage is fed in to computer simulation with the help of A/D cards and the

universal load is controlled to draw current i f.

The active power flowing through the circuit is shown in Fig 5.8(a). The error

between power supplied by UPS in actual network and the torn network is shown in

Fig 5.8(b). Since there is a small error in current tracking of amplifier and also there

is some voltage tracking difference between actual and torn network which is bigger

than current error, therefore there is small error in real power between the actual

network and the torn network. It is clear from Fig. 5.8 (b) that average error in real

power between the actual network and the torn network is less than 6%. For the

power recovery, DC bus of the universal load is connected to the DC bus of the UPS

and it boosts the DC bus voltage by small amount. Although the same controller is

used in both the network yet because of the different DC bus voltages of the actual

and the torn network there is a tracking difference between the actual and the torn

network. Fig 5.8(c) shows the tracking capability of current amplifier. Since the

universal load feed the power back to the UPS therefore only the total losses in

whole circuit is supplied by DG. Fig 5.8(d) shows the total power supplied by DG. It

is clear from the Fig 5.8(d) that the net power supplied by the DG is very small

which is equal to total losses in whole system.

Page 122: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

108

0 0.05 0.1 0.15 0.2 0.25-0.5

0

0.5

1

1.5

2

2.5

3

3.5

Time (s)

Power (M

W)

Real Power

LoadSourceUPS

(a)

0 0.05 0.1 0.15 0.2 0.250

0.02

0.04

0.06

0.08

0.1

0.12

Time (s)

Error (M

W)

Error in Real Power

(b)

0 0.05 0.1 0.15-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Current (k

A)

Current Tracking of Universal Load

ActualReference

(c)

0 0.1 0.2 0.250

1

2

3

Time (s)

Power (M

W)

Power Consumed in Total Losses

(d) Figure 5. 8 Performance of UPS in torn Network

To test the performance of UPS (DG) and to investigate the behavior of the torn

network at the time of load change, an extra unbalanced load is connected at t=0.15.

It is clear from Fig 5.9(a) that extra amount of power is supplied by UPS and source

Page 123: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

109

power remains constant in torn network as desired. Fig 5.9(b) shows the error

between response of UPS in torn network and actual network. This is clear from the

Fig 5.9(b) that error in transient and steady state responses of UPS is about 5%.

0.14 0.16 0.18 0.2 0.22 0.24 0.261

1.5

2

2.5

3

3.5

4

4.5

Time (s)

Pow

er (M

W)

Real Power

LoadSourceUPS

(a)

0.15 0.2 0.25 0.30.04

0.05

0.06

0.07

0.08

0.09

0.1

Time (s)

Error (M

W)

Error in Real Power

(b) Figure 5. 9 Performance of UPS during load change in torn network

Example 5.2: Here we test the UPS performance at the time of asymmetrical sag in

the utility voltage. With the system operating in steady state, an unsymmetrical

voltage sag is created at t= 0.2 s, where the source voltage of the phases a, b and c

decrease to 7 kV, 6 kV and 8 kV (L-N, peak) respectively. The angles of all the

phase voltages also make a jump of −10°. The UPS however regulates the PCC

voltage at 9 kV (L-N, peak). Fig. 5.11 (a) shows the three phase source voltage with

the asymmetrical sag. It is clear from Fig 5.10 (b) that current amplifier is able to

mimic the rest of the power system network which was simulated inside the RTS. Fig

5.10 (c) shows the power supplied by the UPS in actual and torn network. This figure

explains that the performance of UPS is same torn and actual network.

Page 124: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

110

(a)

0.16 0.18 0.2 0.22 0.24 0.26 0.28 0.3-0.5

-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

0.5

Time (s)

Current (

kA)

ActualReference

(b)

0.15 0.2 0.25 0.3 0.35 0.40

0.5

1

1.5

2

2.5

3

3.5

4

Time (s)

Power (M

W)

Real Power Supplied by UPS

Actual NetworkTorn Network

(c) Figure 5. 10 Performance evolution during sag

Example 5.3: In this example the performance of torn network is examined in Mode

II operation where the UPS is responsible to supply the constant power. Here at

t=0.25s an extra load is connected and this extra load is removed at t=0.45s. It is

clear from Fig 5.11 that response of torn network follows the response of actual

network in both transient and steady state.

Page 125: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

111

0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.551

1.5

2

2.5

3

3.5

4

4.5

Time (s)

Real Power

LoadSourceUPS

(a)

0.2 0.25 0.3 0.35 0.4 0.45 0.50

0.5

1

1.5

2

2.5

3

3.5

4

Time (s)

Power (M

W)

Real Power

Actual NetworkTorn Network

(b) Figure 5. 11 Performance evolution during Mode II operation

Example 5.4: Using this network tearing concept we can test the effect of utility

feeder change on UPS in Mode II if a nonlinear load is connected in between the

feeder at t=0.2s. As soon as the nonlinear load is connected, the source current

becomes distorted but UPS keeps PCC voltage undistorted which is clear from Fig

5.13(c).

Figure 5. 12 Scheme for utility feeder change

Fig 5.13(a) shows the power supplied by UPS in torn network and in the actual

network. Universal load is capable to track the current supplied by UPS in actual

network as shown in Fig 5.13(b).

Page 126: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

112

0.15 0.2 0.25 0.3 0.350

0.5

1

1.5

2

2.5

3

3.5

4

Time (s)

Power (M

W)

UPS Power

Torn NetworkActual Network (Reference)

(a)

0.16 0.18 0.2 0.22 0.24 0.26 0.28 0.3 0.32-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Current (

kA)

Curent Traccking of Universal Load

ActualReference

(b)

(c) Figure 5. 13 UPS performance during utility feeder change

Example 5.5: In this example performance of UPS is evaluated during change of

modes. As explained before, in Mode I, constant power is taken from utility and any

variation in load power is supplied by UPS.

0.15 0.2 0.25 0.3 0.350

0.5

1

1.5

2

2.5

3

Time (s)

Power (M

W)

Real Power During Mode Change

Mode Change

UPS Power

Source Power

........ Reference_____ Torn network

Figure 5. 14 Performance of torn network during mode change

Page 127: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

113

In Mode II, the constant power is taken from the UPS and the variation in load power

is supplied by utility. In this example the reference for constant power is set at 2

MW. It is clear from Fig. 5.14 that at t=0.2s the Mode is changed from I to II and

UPS starts supplying 2MW power to load. Fig 5.11 shows the power responses in

real and torn network both. It is clear from this figure that response of source and

UPS power is very much similar in real and torn network.

Example 5.6: Here we examine the testing of UPS if there is a fault near to PCC.

However if there is a fault near to PCC, UPS will not be able to maintain the

sinusoidal voltage profile at PCC, because the source current and a major part of

UPS current feed the fault current until the fault is removed. Once the faulty portion

is isolated with the help of circuit breaker, UPS supplies the total load power and

maintains sinusoidal voltage profile at PCC. But this network tearing scheme is still

able to test the UPS system when there is fault at utility side.

0.13 0.15 0.17 0.19 0.21-10

-8

-6

-4

-2

0

2

4

6

8

10

Time (s)

Volta

ge (kV

)

Phase A Voltage

Torn NetworkActual

Fault Occurence

CB Opens

(a)

0.15 0.16 0.17 0.18 0.19 0.2-1.5

-1

-0.5

0

0.5

1

Time (s)

Current (

kA)

Phase A UPS Current

Torn N/WActual

(b) Figure 5. 15 Fault evolution using torn network

In this test it is recommended not to have power recovery. Because at the time of

power recovery, DC bus voltage is disturbed slightly. This disturbance in DC bus

voltage reflects to the PCC voltage when there is a fault near to PCC. There for to

match voltage profile during fault it is recommended to disconnected power recovery

Page 128: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

114

unit and feed universal load with separate load. However power losses in this case

will not be severe because fault duration is always very small. Once fault is removed,

power recovery unit is connected again.

5.6. Conclusions

This paper provides a solution for testing of distributed generation system with the

help of hardware in loop concept. This testing opens the way to designs the structure

and control of DG system so that it works effectively in the situations that will be

encountered by DG while connected to main grid. The effect of the change in utility

side can also be tested.

A current amplifier in the form of universal load with power regeneration capability

is designed that can mimic any kind of load for DG. Since the universal load has the

power regeneration capability therefore, there are small power losses during the

testing.

References

[1] R. Kuffel et al, “RTDS – a fully digital power system simulator operating in real-

time,” Digital Power System Simulators, ICDS’95, 1995.

[2] G. Sybille and P. Giroux, “Simulation of FACTS controllers using the MATLAB

power system blockset and Hypersim real-time simulator,” IEE PES Panel

Session on Digital Simulations of FACTS and Custom Power Controllers,

Winter Meeting, New York, 2002.

[3] C. A. Rabbath, M. Abdoune and J. Belanger, “Effective real-time simulations of

event-based systems,” Proceedings of the 2000 Winter Simulation Conference,

2000.

[4] C. Zhang, V. K. Vijapurapu, A. K. Srivastava, N. N. Schulz and J. Bastos, “

Hardware-in-the-Loop Simulation of Distance Relay Using RTDS”, Summer

Computer Simulation Conference, San Diego, California, pp. 149-154, 2007.

Page 129: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

115

[5] S. Goyal, A. Ghosh and G. Ledwich, “Active Power Flow Control in a

Distribution System Using Discontinuous Voltage Controller”, Electric Power

Systems Research, 2008.

[6] G. Kron, Tensor Analysis of Networks, John Wiley, N.Y., 1939.

[7] B. Han, B. Bae and Y. Jeong, “Load simulator with power recovery capability

based on voltage source converter-inverter set,” Proc. IEE Electric Power

Application, Vol. 153, No. 6, pp. 891-897, 2006.

[8] L. S. Czamecki, G. Chen, H. Ginn and J. Hu, “Phantom Load: A Simulator of

Non-Periodic Currents,” IEEE PES Summer Meeting, Seattle, USA, pp. 988-993,

2000.

[9] I. Ando, I. Takahashi, Y. Tanaka and M. Ikehara, “Electric Load Controlled by

Computer Simulator having Power Regeneration Ability,” Power Conversion

Conference, Nagaoka, Vol. 2, pp. 925-930, 1997.

[10] S. Goyal, A. Ghosh and G. Ledwich, “A Hybrid Discontinuous Voltage

Controller for DSTATCOM Applications”, IEEE PES General Meeting, USA,

2008.

Page 130: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

116

CHAPTER 6

CONCLUSIONS AND FUTURE RESEARCH

“Power Network in the Loop” testing opens a new method for testing of power

system networks using the concept of hardware in the loop. This methodology

provides a more realistic testing of power systems network than pure simulation

testing. A solution for power network in the loop testing has been proposed based on

a high bandwidth switching amplifier.

The structure and control of a high bandwidth switching amplifier has been

demonstrated. A new hybrid discontinuous control method is proposed for the

switching amplifier. Simulation and experimental results confirm that the controller

is computationally feasible in real-time control. As a result of comparative study of

different controllers, it has been verified that hybrid discontinuous control provides

the best performance in terms of voltage tracking and minimum switching events per

fundamental cycle among the all controllers tested.

Because of the good tracking capability of this amplifier, it can be used in several

power system applications. The use of this amplifier in different power system

applications has been demonstrated. The efficiency of this amplifier is shown in

DSTATCOM operating in a voltage control mode where DSTATCOM is able to

hold the PCC voltage constant in the face of various system disturbances and load

changes. The study shows that hybrid discontinuous control is comparatively robust

to LC parameter variations and does not need a redesign for the changes in the

remainder of the power system, DSTATCOM parameters and operating conditions.

The application of this amplifier in distributed generation system has been analyzed.

If a DC power source is connected to the DC bus of the amplifier then it can be used

in real power sharing in a distribution system. Again because of amplifier’s good

voltage tracking capability, it mitigates the power quality problems in a distribution

Page 131: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

117

system. This amplifier can be easily controlled to operate the DG system utilizing the

most economic source.

A solution for testing the power network subsystem has been proposed using this

novel switching amplifier. The research shows that a subsystem of a power network

can be interfaced with a real-time simulation using the switching amplifier. The

amplifier is capable of amplifying the voltage signal received from the real-time

simulation and represents the effect of the simulated big network to the subsystem.

Using this concept, the effect of different faults and other conditions in the simulated

network can be evaluated on the subsystem under test.

A testing method for distributed generation system is illustrated on a system of a

universal load with power recovery capability. This testing opens the way to design

the structure and control of a DG system so that it works effectively in the situations

that will be encountered by a DG while connected to main grid. The effect of the

change in utility side can also be tested. A current amplifier in the form of universal

load with power regeneration capability is designed that can mimic any kind of load

for DG. Since the universal load has a power regeneration capability, therefore, there

are low power losses during the testing. Extensive case studies have been included to

show that concept of power network in the loop can be effectively used for

subsystem testing.

Some suggestions for future work are:

1. In this research, a solution for “power network in the loop” is presented where a

big network is torn in two parts. One is simulated in the real-time and other is

interfaced with it using a switching amplifier. This work can be extended for the

testing of more than one subsystem with the same big power network. In such

cases, the total power network can be torn in more than two parts and subsystems

can be interfaced with the single simulated network using multiple numbers of

amplifiers.

2. When the voltage signal is transferred to the test side and current signal is

transferred to the supply side, this tearing is called V-I type of tearing and if the

Page 132: Thesis Sachin Goyal - QUT ePrintseprints.qut.edu.au/26521/1/Sachin_Goyal_Thesis.pdf · 2010. 6. 9. · Sachin Goyal B.Tech (Electrical Engineering) Faculty of Built Environment and

118

current signal is transferred to the test side and voltage signal is transferred to the

supply side then this tearing is called I-V type of tearing. In this research

simulation study of both types of tearing (Chapter 4 and 5) is shown but the

experimental validation is established only for V-I type of tearing. An

experimental setup for I-V type of tearing can be established.

3. In this research, to test the feasibility of power network in the loop, only a simple

system is simulated in real-time using a DSP. But in the future, a large system

can be simulated in a real time system and tested with the same concept and the

full bandwidth performance can be evaluated.

4. In discontinuous control, if the inductor of the LC filter is very small with respect

to capacitor then the peak current in inductor could be very high which could

result high di/dt and hence EMI issues. This inductor current could be reduced by

increasing the size of the inductor and correspondingly reduce the capacitor to

give the same cutoff frequency. A detailed study of EMI issues and core losses in

discontinuous control would be of interest but is beyond the scope of this

research.