THERMAL MANAGEMENT SYSTEMS
Concept 6/2
Selection guide 6/6
VFVentilation systems 6/8
ICL-AI/ICT-AIAir/air exchangers 6/30
ICL-AG/ICT-AGAir/water exchangers 6/36
CLL/CLTCLLMP/CLTMPCooling units 6/40 - Mechanical control - Electronic control
RCResistance heaters 6/64 - Insulated - Standard
TSControl devices 6/80
Thermal management for electrical panels 6/95
Support service for the PROclima 4.0 softwarecalculation 6/100
06_000_001_EN.indd 306_000_001_EN.indd 3 2/4/08 13:29:072/4/08 13:29:07
6/2
Thermal management for electrical and electronic switchboards: a need
06_002_013_EN.indd 206_002_013_EN.indd 2 2/4/08 13:14:012/4/08 13:14:01
6/3
What is temperature control?
Technological evolutionThe miniaturisation of components, the generalisation of electronics, the appearance of new products based on power electronics mean that temperature management is a need that must increasingly be taken into account in the design of electrical and/or electronic switchboards.
What are the advantages of good temperature control?Temperature control in electrical switchboards is one of the important factors of good industrial maintenance.The risks involved through failure to have a suitable thermal solution are multiple, affecting the life of components and the performance of installations to such an extent that they may halt production.The service life of the components themselves is a function of the temperature and humidity conditions in the enclosure. Ideal are values from +15…+35 ºC for temperature and from 30 to 90% relative humidity (RH).
Cooling, Heating, controllingJust like the degrees of IP/IK protection suited to each installation, the equipment installed inside an enclosure needs suitable thermal protection.There are different solutions to these problems, depending on environmental conditions, the nature of the components of the electrical switchboard, etc.In some cases it is suffi cient to oversize the enclosure, use fans or air-air exchangers. In other, more extreme cases, in which the ambient temperature is higher, air-water heat exchangers or cooling units must be used.
A solution for every needWith this objective in mind, Himel proposes a comprehensive Thermal Offer to secure your installation.
Cooling 1. Forced ventilation system 2 . Air/air exchangers 3 . Air/water exchangers 4. Cooling unitsHeating 5. Resistance heatersControl 6. Thermal control systemsCalculation 7. PROclima 4.0 software
06_002_013_EN.indd 306_002_013_EN.indd 3 2/4/08 13:14:092/4/08 13:14:09
6/4
System Natural ventilation Forced ventilation Air-air exchangers
Natural convection helps to reduce the
temperature inside the enclosure, whereby
installing (without fi lter) outlet grilles or raising
the enclosure tops may be a suitable solution.
Fans with a Himel fi lter have been designed to
evacuate a large amount of heat economically.
They have an aluminium exchange battery that
separates the two air circuits (inside and outside)
and stops dust from getting inside.
When to use them
This solution is only feasible in cases where the
power that has to be dissipated is weak, and in
atmospheres with low dust levels.
When you need to evacuate greater dissipated
power, and when the outside environment is
polluted.
In highly polluted atmospheres or when large
amounts of heat must be evacuated without
bringing the outside and inside atmospheres
into contact.
Ta: ambient temperature
Td: temperature required
The inside and outside air circuits are
independent.
Advantages
c Economic solution.
c Maintenance-free.
c Easy and quick to install.
c Economic solution.
c Easy maintenance.
c Easy and quick to install.
c Even temperature inside the enclosure.
c High protection degree (IP54 or IP55).
c They do not bring the atmospheres inside and
outside the enclosure into contact.
c Easy maintenance.
c High protection degree (IP54).
Drawbacks
c The amount of heat evacuated is weak.
c Reduction in protection degree.
c Dust penetration.
c The temperature inside the enclosure is always
higher than the outside.
c They bring the atmospheres inside and outside
the enclosure into contact.
c Maintenance is required: fi lter change.
c The temperature inside the enclosure is
always higher than the outside.
Solutions
Ta < Td Ta < Td Ta < Td
NO NO YES
Outlet grilles Air-air exchangersFans and outlet grills
06_002_013_EN.indd 406_002_013_EN.indd 4 2/4/08 13:14:102/4/08 13:14:10
6/5
Air-water exchangers Cooling Heating
They cool the enclosure by means of a water-cooled exchange
battery.
The regulation of the temperature in the enclosure is performed
by means of a thermostat that closes or opens an
electro-valve.
They are cooling unit devices that guarantee effective and
independent cooling from the outside environment, and avoid
the appearance of heat sources.
Resistance heaters avoid problems of condensation inside the
enclosure and guarantee maintenance of the ideal temperature
for the correct operation of the electronic components.
c When a large amount of heat has to be evacuated and a
water cooling installation stable in temperature and fl ow is
available.
c Particularly suitable for diffi cult and highly polluted
atmosphere, since there is no outside air circuit.
c Our cooling units can be used in the severest atmospheres,
where the temperature can reach up to 55 ºC.
c Our cooling units feature the temperature adjustment
function, as well as an indication of any anomalies by
means of an alarm.
Resistance heaters are used to heat the electrical switchboard
when the ambient temperature is too low, or to prevent the
formation of condensation water.
c The inside temperature of the enclosure does not depend on
the outside.
c They do not bring the atmospheres inside and outside the
enclosure into contact.
c It has a leak detection device.
c Even temperature inside the enclosure.
c High protection degree (IP54).
c They use ecological gas.
c Small size.
c Fitted with a PTC-type heating element that stabilises the
surface temperature of the aluminium section.
c In two versions: insulated, with low surface temperature
and in aluminium with a surface temperature below
< 75 ºC.
c The fan-equipped resistance heaters guarantee the
temperature inside the enclosure and prevent hot spots.
c They need cold water.
c They need a specifi c plumbing installation.
c The installation of a drain is recommended.
c Maintenance is required: fi lter change.
Ta > Td Ta > Td Ta < Td
YES YES
Air-water exchangers Cooling units Resistance heaters
06_002_013_EN.indd 506_002_013_EN.indd 5 2/4/08 13:14:332/4/08 13:14:33
6/6
Ventilation systems with fi lter
Particularly suited for installations in which:
c The temperature expected outside the enclosure may be lower than the maximum required inside it.
c A high degree of protection must be maintained (IP54/IP55).
c The outside environment is not too dusty.
Broad range of solutions:
c 42 models.
c In RAL-7032 and RAL-7035.
c From 38 to 850 m3/h.
c In 5 voltages:AC: 400/440 V, 230 V, 115 V (50/60 Hz). DC: 48 V and 24 V.
A thermal solution for every environment
Air-air exchangers
Particularly suited for installations in which:
c The temperature expected outside the enclosure may be lower than the maximum required inside it.
c Maintaining good watertightness is important (IP54/IP55).
c The outside environment is highly polluted.
Broad range of solutions:
c 4 models.
c Top- and side-mounting versions.
c Performance from 15 to 70 W.
c Voltage: 230 V (50/60 Hz).
Air-water exchangers
Particularly suited for installations in which:
c The temperature required inside the enclosure must be lower than the maximum expected outside.
c In corrosive atmospheres, the outside and inside air circuit never come into contact.
c Very polluted atmospheres, since they are water-cooled and there is no outside air circuit.
c When the heat needs to be extracted from the confines of the building.
Broad range of solutions:
c 3 models.
c Top- and side-mounting versions.
c Cooling power from 2100 W and 3000 W.
c Voltage: 230 V (50/60 Hz).
THERMAL MANAGEMENT Selection guide
06_002_013_EN.indd 606_002_013_EN.indd 6 2/4/08 13:15:002/4/08 13:15:00
6/7
Cooling units
They give the equipment installed in the enclosure the temperature it needs to operate correctly:
Regardless of the outside temperature.
They do not bring the inside and outside air circuit into contact.
They reduce humidity in the enclosure.
Range of solutions:
c 19 models.
c Top- and side-mounting versions.
c Cooling power from 240 up to 3.100 W.
c Tension: 230 V (50/60 Hz); 3 � 400/440 V (50/60 Hz).
Calculation assistance software: PROclima
We provide our clients and users with this software to help them select their temperature control equipment.
The program calculates the thermal balance in the enclosure and suggests the best ventilation or cooling solution.
Control devices
Thermostats: they maintain the temperature inside the enclosure and send a signal when certain defi ned values are exceeded:
c Maximum value (cooling action).
c Minimum value (heating action).
Range of solutions:
c 16 models.
c Two versions: adjustable or preset temperature.
c Hygrostat: relative humidity regulators. They are used together withresistance heaters or fans.
c Hygrometer: relative humidity control with a double-function device: hy-grostat-thermostat.
Resistance heaters
With a twofold objective:
c They avoid condensation problems inside the enclosure.
c They guarantee maintenance of the ideal temperature for the correct operation of the electronic components.
Range of solutions:
c 30 models.
c Insulated or aluminium versions.
c Convection or circulation fan versions.
c Heating power from 10 up to 550 W.
c Tension: from 12 to 450 V AC/DC.
THERMAL MANAGEMENT Selection guide
06_002_013_EN.indd 706_002_013_EN.indd 7 2/4/08 13:15:222/4/08 13:15:22
Ventilation systems VFWide range of ventilation products
6/8
1
3
2
4
5
6
7
8
9
06_002_013_EN.indd 806_002_013_EN.indd 8 2/4/08 13:15:372/4/08 13:15:37
1 Minimum pressure loss. Better air fl ow. The angles of walls, the tilting of slats, the fi xing distance of the motor and the sizing of the unit have been studied to guarantee the best possible air conduction and minimise pressure loss.
2 Fixing guide (2.1). Exclusive device (patented) that centres the fan body with the machining carried out on the enclosure wall. This system corrects possible defects in sizing and in the precision of machining. It also facilitates the operation of the “multiple fixing clips”.
Multiple thickness fi xing clips system (2.2). This exclusive patented device guarantees easy and reliable fi xing of the ventilation system on 0.8 mm to 4.5 mm thick walls without the need for any other screws. It also guarantees a perfect joint compression on the cut outline. Protection between the grille and the wall is guaranteed for all materials: steel, stainless steel, polyester, aluminium, etc.
Tilted profi le of the grill (2.3). This innovating profile increases the protection of the filter against vertical exposure:c Each slat is protected by the slat above it.c The external size remains small.
3 IP54-55. Designed (patented) especially to evacuate any water that might be retained by the fi lter blanket for applications that may be splashed under pressure.
7 Strong, reliable and effortless fi xing that is evident upon installation, made possible by the set of “guide devices” and the “multiple fi xing clips”.It also allows traditional enclosures to be fi xed with fasteners.
9 Motor selection. State-of-the-art motors have been selected from leading manufacturers in the sector, with a view to achieving:c Higher flow rate.c Longer useful life.The largest range of voltages is available in the standard motor selection, both in alternating (50/60 Hz) and direct current.
Self-extinguishing. Self-extinguishing according to the UL94 VO regulation.
8 Fast replacement of the fi lter blanket.Fast, easy and secure replacement of the fi lter blanket, even with the fan operating.
Reversibility.The rotation of the fan motor can be easily changed on all models (extraction/discharge).
6 Selection of plastic materials.The materials (ASA/PC) selected give the system: c Good behaviour (long service life) with regard to
UV rays.c Excellent mechanical behaviour.c The colours of the grills in the standard supply are
RAL-7032 and 7035.c Grill colour can be changed by mould injection
(check with the sales network).
5 Environment.c Recyclable plastic
materials and filters.c Motors compliant with
the ROHS legislation.c Lower electrical
consumption for greater air flow.
4 Wide offer of fi lters.c For application in
greasy atmospheres (OEMs).
c Anti-insect filters.c Small fine filter (when
greater dust protection is required).
ENVIRONMENTALLY friendly
6/9
4.5 mm
0.8 mm
2.1
2.2
2.3
06_002_013_EN.indd 906_002_013_EN.indd 9 2/4/08 13:15:442/4/08 13:15:44
6/10
SYSTEMS Selection guide
VENTILATION SYSTEMS WITH FILTER
Free fl ow(fan with fi lter)
Flow rate (m3/h)
Voltage Type of connection
(*)
Dimensions(mm)
Fan + 1 outlet grill Fan + 2 outlet grills
50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 HzTotal
(external) (mm)Cut-out
(mm)
38 39 25 26 33 34 230 V C
137 � 117 92 � 92
38 39 27 28 35 36 115 V C
58 39 47 24 DC C
44 34 41 48 DC C
85 98 63 72 71 83 230 V F
170 � 150 125 � 125
79 92 65 74 73 79 115 V F
80 57 77 24 DC F
79 59 68 48 DC F
165 193 153 171 161 175 230 V F
268 � 248 223 � 223
164 192 153 171 161 174 115 V F
188 171 179 24 DC F
193 171 179 48 DC F
302 350 260 307 268 311 230 V F
302 348 263 305 271 314 115 V F
262 221 229 24 DC F
247 210 218 48 DC F
562 586 473 477 481 485 230 V B
336 � 316 291 � 291
582 583 485 475 494 477 115 V B
838 803 718 568 728 585 230 V B
983 944 843 642 854 667 115 V B
931 803 798 568 809 585 400/440 V B
NEW Fans with type of connection F include a fan connection cable (L = 2 m)
(*) C = by cable, F = by connector, B = by terminal block.
06_002_013_EN.indd 1006_002_013_EN.indd 10 2/4/08 13:16:142/4/08 13:16:14
6/11
Reference
IPFan with fi lter Outlet grille Fan with fi lter Outlet grille
RAL-7032 RAL-7032 RAL-7035 RAL-7035
VF38
FS38
VF38R35
FS38R35 54
VF38/115 VF38/115R35
VF38/24DC VF38/24DCR35
VF38/48DC VF38/48DCR35
VF85
FS85
VF85R35
FS85R35 54
VF85/115 VF85/115R35
VF85/24DC VF85/24DCR35
VF85/48DC VF85/48DCR35
VF165
FS165
VF165R35
FS165R35 54
VF165/115 VF165/115R35
VF165/24DC VF165/24DCR35
VF165/48DC VF165/48DCR35
VF300 VF300R35
VF300/115 VF300/115R35
VF300/24DC VF300/24DCR35
VF300/48DC VF300/48DCR35
VF560
FS560
VF560R35
FS560R35 54
VF560/115 VF560/115R35
VF850 VF850R35
VF850/115 VF850/115R35
VF850/400 VF850/400R35
06_002_013_EN.indd 1106_002_013_EN.indd 11 2/4/08 13:16:232/4/08 13:16:23
6/12
VENTILATION SYSTEMS Selection guide
Reference Concept For fans and grilles with dimensions (mm)
F38
Standard fi lter (G2 class conforming to EN 779)
137 � 117
F85 170 � 150
F165 268 � 248
F560 336 � 316
F85OEM
“Greasy environments” OEM fi lter
170 � 150
F165OEM 268 � 248
F560OEM 336 � 316
FF85Fine fi lter (G3 class conforming
to EN 779)
170 � 150
FF165 268 � 248
FF560 336 � 316
FAIN38
“Anti-insect” fi lters
137 � 117
FAIN85 170 � 150
FAIN165 268 � 248
FAIN560 336 � 316
ReferenceDimensions
(mm)IP
RAL-7032 RAL-7035 Total (outside) Cut-out
FS38 FS38R35 137 � 117 92 � 92 54
FS85 FS85R35 170 � 150 125 � 125 54
FS165 FS165R35 268 � 248 223 � 223 54
FS560 FS560R35 336 � 316 291 � 291 54
OUTLET GRILLES
FILTERS
Reference Dimensions(mm)
Set of
RAL-7011
ANVF 137 � 177 2
ANVF 170 � 150 2
ANVF 268 � 248 2
ANVF 336 � 316 2
VANDAL PROOF SYSTEM
Reference Length (mm)
CBMV100 1000
CBMV200 2000
POWER CONNECTION CABLE FOR FANS
06_002_013_EN.indd 1206_002_013_EN.indd 12 2/4/08 13:16:232/4/08 13:16:23
6/13
Reference For fans and grilles with dimensions (mm)
VF85/KITIPCEM 170 � 150
VF165/KITIPCEM 268 � 248
VF560/KITIPCEM 336 � 316
For grilles and fans (mm)
Aluzinc RAL-7032
AluzincRAL-7035
Stainless steelReplacement
fi lters
170 � 150 VF85/KITIPALZ32 VF85/KITIPALZ35 VF85/KITIP F85/KITIP
268 � 248 VF165/KITIPALZ32 VF165/KITIPALZ35 VF165/KITIP F165/KITIP
336 � 316 VF560/KITIPALZ32 VF560/KITIPALZ35 VF560/KITIP F560/KITIP
EMC EXTERNAL KIT IP55
PROTECTION KIT IP55
Natural ventilation
Forced ventilation
The movement of air inside the enclosure with the aid of a fan makes it possible to:
1 Increase thermal dissipation through the enclosure walls and, as a result, reduce the inside temperature.
2 Avoid hot spots in the enclosure (even temperature) harmful to some components.
Solution 2Solution 1
VENTILATION SYSTEMS Selection guide
The provision of fresh air from the outside by means of ventilation grills improves the dissipation of heat by natural convection. However, this solution is feasible in cases where the power to be dissipated is weak and in atmospheres with low dust levels. There are 4 ways of ventilating, with a common principle: entry of cold air through the bottom of the enclosure by means of an accessory and the exit of hot air through the top of the enclosure by means of an accessory:
1 By elevating the ceiling of the enclosures (only in Spacial 6000 models) and adding a fi lterless bottom air inlet (solution 1).
2 By means of a ceiling ventilation device, adding a fi lterless air inlet at the bottom (solution 1).
3 By means of inlet and outlet grills (fi lterless) (solution 2).
4 By means of ventilation lugs (Solution for insulating enclosures).
06_002_013_EN.indd 1306_002_013_EN.indd 13 2/4/08 13:16:262/4/08 13:16:26
6/14
VFForced ventilation systemIP54 (EN 60529)
General features:
c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining dust particles.
c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements.
c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling.
Conditions of use:
c The outside temperature Te should be 5 °C below the temperature required Ts in the enclosure.
c The filters the fans are equipped with must be cleaned or replaced periodically.
c The environment should be relatively “clean” and over-frequent filter replacement should be avoided.
c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.
Characteristics Reference
Colour RAL-7032 VF38 VF38/115 VF38/24DC VF38/48DC
Colour RAL-7035 VF38R35 VF38/115R35 VF38/24DCR35 VF38/48DCR35
Flow rate with fi lter (m3/h) (50/60 Hz) 38/39 38/39 58 44
Flow rate with 1 outlet grill (m3/h) (50/60 Hz) 25/26 27/28 39 34
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC
Voltage range 150...250 V 75...125 V 10...27.6 V 24...55 V
Absorbed power (50/60 Hz) 4.5/4.8 W 3.3/3.5 W 3.6 W 4.6 W
Intensity max. (50/60 Hz) 0.16/0.17 A 0.16/0.16 A 0.18 A 0.074 A
Noise level 40/41 dB (A)
Bearing Balls
IP Degree of protection (with standard fi lter) 54
External dimensions (mm) 137 � 117 � 49
Cut-out dimensions (mm) 92 � 92
Weight 0.220 kg 0.230 kg
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –10 a +70 °C –10 a +70 °C
Storage temperature –40 a +70 °C
100% operating factor 100%
Maximum static pressure (0 m3/h airfl ow) 20 Pa
Characteristics Reference
Colour RAL-7032 FS38
Colour RAL-7035 FS38R35
Degree of protection IP54 54
External dimensions (mm)
(height � length � depth)137 � 117 � 18
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Operating temperature –20 a +70 °C
Outlet grilles
Replacement fi lter
Characteristics Reference
Standard fi lter (G2 class conforming to EN 779) F38
VF38 Fans…
06_014_029_EN.indd 1406_014_029_EN.indd 14 2/4/08 13:27:272/4/08 13:27:27
137
117 9
13
49
80
91.8
5
92 � 92
6/15
VFForced ventilation systemIP54 (EN 60529)
Fans VF38-VF38/115
FIG. 1
“Pressure/Flow” Diagram
FIG. 2
Diff
eren
ce in
sta
tic p
ress
ure
(SP
)
Flow rate m3/h
VF38�Pa
Dimensions (mm)
06_014_029_EN.indd 1506_014_029_EN.indd 15 2/4/08 13:27:282/4/08 13:27:28
6/16
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
General features:
c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles.
c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements.
c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations.
c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling.
Conditions of use:
c The outside temperature Te should be 5 °C below the temperature required Ts in the enclosure.
c The filters the fans are equipped with must be cleaned or replaced periodically.
c The environment should be relatively “clean” and over-frequent filter replacement should be avoided.
c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.
Characteristics Reference
Colour RAL-7032 VF85 VF85/115 VF85/24DC VF85/48DC
Colour RAL-7035 VF85R35 VF85/115R35 VF85/24DCR35 VF85/48DCR35
Flow rate with fi lter (m3/h) (50/60 Hz) 85/98 79/92 80
Flow rate with 1 outlet grill (m3/h) (50/60 Hz) 63/72 65/74 60
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC
Voltage range 175...253 V 75...126 V 10...27.6 V 25...55.2 V
Absorbed power (50/60 Hz) 17/15 W 16/15 W 7.6 W 8 W
Intensity max. (50/60 Hz) 0.12/0.097 A 0.21/0.179 A 0.30 A 0.173 A
Noise level 46/49 dB (A)
Bearing Balls
IP Degree of protection (with standard fi lter) 54
External dimensions (mm) 170 � 150 � 62
Cut-out dimensions (mm) 125 � 125
Weight 0.780 kg 0.480 kg
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –20 a +60 °C –10 a +70 °C
Storage temperature –40 a +70 °C
100% operating factor 100%
Maximum static pressure (0 m3/h airfl ow) 50 Pa
Characteristics Reference
Standard fi lter (fi ltration capacity: G2 conforming to EN 779) F85
OEM fi lter (oily environment) F85OEM
Fine fi lter FF85
Anti-insect fi lter FAIN85
Replacement fi lter
Outlet grills
Characteristics Reference
Colour RAL-7032 FS85
Colour RAL-7035 FS85R35
IP 54
Outside dimensions (mm)
(height � width � depth)170 � 150 � 18
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –20 a +70 °C
VF85 Fans…
06_014_029_EN.indd 1606_014_029_EN.indd 16 2/4/08 13:27:292/4/08 13:27:29
150
170
125 x 125125 � 125
119
62
15
9
124.
85
6/17
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
Fans
FIG. 1
“Pressure/Flow” Diagram
FIG. 2
Diff
eren
ce in
sta
tic p
ress
ure
(SP
)
Flow rate m3/h
�Pa VF85
Dimensions (mm)
06_014_029_EN.indd 1706_014_029_EN.indd 17 2/4/08 13:27:302/4/08 13:27:30
6/18
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
Characteristics Reference
Colour RAL-7032 VF165 VF165/115 VF165/24DC VF165/48DC
Colour RAL-7035 VF165R35 VF165/115R35 VF165/24DCR35 VF165/48DCR35
Flow rate with fi lter (m3/h) (50/60 Hz) 165/193 190
Flow rate with 1 outlet grill (m3/h) (50/60 Hz) 153/171 171
Flow rate with 2 outlet grills (m3/h) (50/60 Hz) 161/175 179
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC
Voltage range 175...253 V 75...126 V 10...27.6 V 25...55.2 V
Absorbed power (50/60 Hz) 16.3/14.3 W 15.5/14.4 W 8 W 8.7 W
Intensity max. (50/60 Hz) 0.12 A/0.94 A 0.20 A/0.18 A 0.3 A 0.18 A
Noise level 50/51 dB (A)
Bearing Balls
IP Degree of protection (with standard fi lter) 54
External dimensions (mm) 268 � 248 � 104
Cut-out dimensions (mm) 223 � 223
Weight 1.140 kg 0.810 kg
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –20 a +60 °C –10 a +70 °C
Storage temperature –40 a +70 °C
100% operating factor 100%
Maximum static pressure (0 m3/h airfl ow) 50 Pa
General features:
c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles.
c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements.
c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations.
c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling.
Conditions of use:
c The outside temperature Te should be 5 °C below the temperature required Ts in the enclosure.
c The filters the fans are equipped with must be cleaned or replaced periodically.
c The environment should be relatively “clean” and over-frequent filter replacement should be avoided.
c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.
Characteristics Reference
Standard fi lter (fi ltration capacity: G2 conforming to EN 779) F165
OEM fi lter (oily environment) F165OEM
Fine fi lter FF165
Anti-insect fi lter FAIN165
Replacement fi lter
Characteristics Reference
Colour RAL-7032 FS165
Colour RAL-7035 FS165R35
IP 54
Outside dimensions (mm)
(height � width � depth)268 � 248 � 18
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –20 a +70 °C
Outlet grills
VF165 Fans…
06_014_029_EN.indd 1806_014_029_EN.indd 18 2/4/08 13:27:312/4/08 13:27:31
268
248
223 x 223223 � 223
18
9.5104
119
222.
7
VF165
Diff
eren
ce in
sta
tic p
ress
ure
(SP
)
�Pa
Flow rate (m3/h)
6/19
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
Fans VF165-VF165/115
FIG. 1
“Pressure/Flow” Diagram
FIG. 2
Dimensions (mm)
06_014_029_EN.indd 1906_014_029_EN.indd 19 2/4/08 13:27:322/4/08 13:27:32
6/20
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
Characteristics Reference
Colour RAL-7032 VF300 VF300/115 VF300/24DC VF300/48DC
Colour RAL-7035 VF300R35 VF300/115R35 VF300/24DCR35 VF300/48DCR35
Flow rate with fi lter (m3/h) (50/60 Hz) 300/350 262
Flow rate with 1 outlet grill (m3/h) (50/60 Hz) 260/307 221
Flow rate with 2 outlet grills (m3/h) (50/60 Hz) 268/311 229
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC
Voltage range 145...253 V 75...126 V 12...30 V 25...60 V
Absorbed power (50/60 Hz) 36/37 W 36/36 W 13 W 11 W
Intensity max. (50/60 Hz) 0.17/0.16 A 0.35/0.32 A 0.53 A 0.24 A
Noise level 55/56 dB (A)
Bearing Balls
IP Degree of protection (with standard fi lter) 54
External dimensions (mm) 268 � 248 � 116 268 � 248 � 103,4
Cut-out dimensions (mm) 223 � 223
Weight 1.3 kg 1.1 kg
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –10 a +70 °C –10 a +70 °C
Storage temperature –40 a +70 °C
100% operating factor 100%
Maximum static pressure (0 m3/h airfl ow) 158 Pa
Characteristics Reference
Colour RAL-7032 FS165
Colour RAL-7035 FS165R35
IP 54
Outside dimensions (mm)
(height � width � depth)268 � 248 � 18
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –20 a +70 °C
Characteristics Reference
Standard fi lter (fi ltration capacity: G2 conforming to EN 779) F165
OEM fi lter (oily environment) F165OEM
Fine fi lter FF165
Anti-insect fi lter FAIN165
General features:
c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles.
c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements.
c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations.
c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling.
Conditions of use:
c The outside temperature Te should be 5 °C below the temperature required Ts in the enclosure.
c The filters the fans are equipped with must be cleaned or replaced periodically.
c The environment should be relatively “clean” and over-frequent filter replacement should be avoided.
c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.
Replacement fi lter
Outlet grills
VF300 Fans…
06_014_029_EN.indd 2006_014_029_EN.indd 20 2/4/08 13:27:332/4/08 13:27:33
172
222.
7
18
9.5116
268
248
223 x 223223 � 223
6/21
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
VF300
Diff
eren
ce in
sta
tic p
ress
ure
(SP
)
�Pa
Flow rate m3/h
Fans VF300-VF300/115
FIG. 1
“Pressure/Flow” Diagram
FIG. 2
Dimensions (mm)
06_014_029_EN.indd 2106_014_029_EN.indd 21 2/4/08 13:27:342/4/08 13:27:34
6/22
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
Characteristics Reference
Colour RAL-7032 VF560 VF560/115 VF850 VF850/115 VF850/400
Colour RAL-7035 VF560R35 VF560/115R35 VF850R35 VF850/115R35 VF850/400R35
Flow rate with fi lter (m3/h) (50/60 Hz) 562/586838 (50 Hz)
803 (60 Hz)
983 (50 Hz)
944 (60 Hz)
931 (50 Hz)
803 (60 Hz)
Flow rate with 1 outlet grill (m3/h) (50/60 Hz) 473/477718 (50 Hz)
568 (60 Hz)
843 (50 Hz)
642 (60 Hz)
798 (50 Hz)
568 (60 Hz)
Flow rate with 2 outlet grills (m3/h) (50/60 Hz) 481/485728 (50 Hz)
585 (60 Hz)
854 (50 Hz)
667 (60 Hz)
809 (50 Hz)
585 (60 Hz)
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 230 V (50/60 Hz) 115 V (50/60 Hz) 400 V (50/60 Hz)
Voltage range 207...244 V 103...122 V 207...244 V 103...122 V 396...466 V
Absorbed power (50/60 Hz) 68/85 W 65/83 W 150/195 W 145/182 W 40/40 W
Intensity max. (50/60 Hz) 0.52/0.37 A 0.60/0.72 A 0.65/0.85 A 0.13/1.6 A 0.22/0.23 A
Noise level 59/59 dB (A) 76/75 dB (A) 78/77 dB (A) 77/75 dB (A)
Bearing Balls
IP Degree of protection (with standard fi lter) 54
External dimensions (mm) 336 � 316 � 161 336 � 316 � 162
Cut-out dimensions (mm) 291 � 291
Weight 3.2 kg 4.1 kg
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –15 a +60 °C
Storage temperature –40 a +50 °C
100% operating factor 100%
Maximum static pressure (0 m3/h airfl ow) 140 Pa 170 Pa
Characteristics Reference
Standard fi lter (fi ltration capacity: G2 conforming to EN 779) F560
OEM fi lter (oily environment) F560OEM
Fine fi lter FF560
Anti-insect fi lter FAIN560
Characteristics Reference
Colour RAL-7032 FS560
Colour RAL-7035 FS560R35
IP 54
Outside dimensions (mm) (height � width � depth) 336 � 316 � 18
Material Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0
Service temperature –20 a +70 °C
General features:
c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles.
c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements.
c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations.
c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling.
Conditions of use:
c The outside temperature Te should be 5 °C below the temperature required Ts in the enclosure.
c The filters the fans are equipped with must be cleaned or replaced periodically.
c The environment should be relatively “clean” and over-frequent filter replacement should be avoided.
c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.
Replacement fi lter
Outlet grills
VF560... and VF850... Fans
06_014_029_EN.indd 2206_014_029_EN.indd 22 2/4/08 13:27:342/4/08 13:27:34
336
316
291 x 291291 � 291
225
290.
7
18
9.5160.5
336
316
291 x 291291 � 291
280
290.
7
18
9.5162
VF560 VF850
Diff
eren
ce in
sta
tic p
ress
ure
(Pa)
�Pa
Flow rate m3/h
Diff
eren
ce in
sta
tic p
ress
ure
(Pa)
�Pa
Flow rate m3/h
6/23
VFForced ventilation systemIP54 (EN 60529) / IP55 (with IP55 protection kit)
VF560-VF560/115 Fans
FIG. 1
“Pressure/Flow” Diagram
FIG. 3
VF650-VF650/115 Fans
FIG. 2
FIG. 4
Dimensions (mm)
06_014_029_EN.indd 2306_014_029_EN.indd 23 2/4/08 13:27:352/4/08 13:27:35
6/24
VF Accessories for forced and natural ventilation systems
EMC external kit IP55
c They are directly mounted onto the fans and grilles to protect the equipment from electromagnetic interference.
Circulation fan
c To circulate the air inside the enclosures.
c Fixing with screws.
c User protection according to DIN 31001.
ReferenceFlow rate
(m3/h)Tension
Electrical power (W)
Weight(kg)
VC150 150 230 V 50 Hz 17 0.82
ReferenceFlow rate
(m3/h)Tension Electrical power (W)
Weight(kg)
Dimensions(mm)
Outlet grilles Standard fi lter
V65 65 230 V - 50 Hz 17 0.69 124 � 124 � 55 FS65 F65
V65/115 65 115 V - 50 Hz 17 0.69 124 � 124 � 55 FS65 F65
IP20 Fans
c For uses where a high degree of protection is not required (IP20).
c Self-extinguishing thermoplastic grille with a black fi nish.
c Fixing to the enclosure with four M4 screws.
Reference For fans and grilles with dimensions (mm)
VF85/KITIPCEM 170 � 150
VF165/KITIPCEM 268 � 248
VF560/KITIPCEM 336 � 316
06_014_029_EN.indd 2406_014_029_EN.indd 24 2/4/08 13:27:362/4/08 13:27:36
6/25
VF Accessories for forced and natural ventilation systems
Reference Flow rate (m3/h)NoisedB (A)
Tension (V/Hz)Electrical power
(W)
VTR300 300 53 230/50-60 37
Reference Specifi cationsFlow rate*
(m3/h)Noise dB (A)
Tension(V/Hz)
Electrical power (W)
VR312With 3 fans with a depth of 180 mm With thermostat and indicator light
312 50 230/50-60 34
VR400 With 3 fans with a depth of 180 mm 400 50 230/50-60 36
VR624With 3 fans with a depth of 180 mm With thermostat and indicator light
624 50 230/50-60 68
VR800 With 6 fans with a depth of 310 mm 800 52 230/50-61 72
VR1200 With 9 fans with a depth of 445 mm 1200 55 230/50-62 108
*Flow measured without counter-pressure.
Fans for 19” racks
c Height: 1 U.
c Connection cable.
References:CBMV100 (L = 1 m).CBMV200 (L = 2 m).
19” 2 U tangential fan
c Fan with air drawn in from the front and vertically channelled through the 19” rack.
c Height: 2 U.
06_014_029_EN.indd 2506_014_029_EN.indd 25 2/4/08 13:27:392/4/08 13:27:39
6/26
VF Accessories for forced and natural ventilation systems
Fans
c Turbine-type fan motor for ventilation/extraction.
ReferenceFlow(m3/h)
Tension(V/Hz)
Power absorbed(W)
Noise(dB) (A)
External dimensions (mm)
Filter Grille
MV156 156 230/50-60 17/15 42 120 � 120 � 38 FS156 RV156
MV156/115 156 120/50-60 17/15 42 120 � 120 � 38 FS156 RV156
MV35 35 230/50-60 16/14 32 80 � 80 � 25 FS35 RV35
MV35/115 35 120/50-60 16/14 32 80 � 80 � 25 FS35 RV35
Ventilation fi lters
c Outlet fi lter unit for enclosure ventilation. For fi tting to MV fans.
Protective grille
c Protective grille for enclosure fan motors. For fi tting to MV fans.
Power connection cable for fans
c For fi tting to the connection terminal of the fan motors.
References:CBMV100 (L = 1 m).CBMV200 (L = 2 m).
06_014_029_EN.indd 2606_014_029_EN.indd 26 2/4/08 13:27:402/4/08 13:27:40
228
190
228
66
ø7
290.
5
90
68 22
6
270
270
270
340
340
270
270
340
340 90
68 22
6
270
290.
5
VMT340 VFT400
6/27
VF Accessories for forced and natural ventilation systems
Ceiling ventilation
c Ventilation accessories to be mounted on the top of OLN enclosures..
External dimensions (mm)
Reference Description Height Width Depth Flow rate (m3/h) Tension (V/Hz) Electrical power (W)
VMT340 Natural airing device 93 340 340 - - -
VFT400Forced ventilation device(supplied with electric fan)
90 340 340 400 230/50-60 85
06_014_029_EN.indd 2706_014_029_EN.indd 27 2/4/08 13:27:472/4/08 13:27:47
Reference Dimensions(mm)
Set of
RAL-7011
ANVF 137 � 177 2
ANVF 170 � 150 2
ANVF 268 � 248 2
ANVF 336 � 316 2
VANDAL PROOF SYSTEM
Reference Length (mm)
CBMV100 1000
CBMV200 2000
POWER CONNECTION CABLE FOR FANS
6/28
VF Accessories for forced and natural ventilation systems
Outlet grilles with filter IP54
c Injected thermoplastic, self-extinguishing, conforming to UL94 V0.
c Operating temperature from –10 to +60 °C.
c IP55 with IP55 watertightness protection kit.
ReferenceDimensions
(mm)
RAL-7032 RAL-7035 Total (exterior) Machined
FS38 FS38R35 137 � 117 92 � 92
FS85 FS85R35 170 � 150 125 � 125
FS165 FS165R35 268 � 248 223 � 223
FS560 FS560R35 336 � 316 291 � 291
Filters
Protection kit IP55
For grilles and fans (mm)
AluzincRAL-7032
Aluzinc RAL-7035
Stainless steelReplacement
fi lter
170 � 150 VF85/KITIPALZ32 VF85/KITIPALZ35 VF85/KITIP F85/KITIP
268 � 248 VF165/KITIPALZ32 VF165/KITIPALZ35 VF165/KITIP F165/KITIP
336 � 316 VF560/KITIPALZ32 VF560/KITIPALZ35 VF560/KITIP F560/KITIP
Reference Concept For fans and grilles with dimensions (mm)
F38
Standard fi lter (G2 class conforming to EN 779)
137 � 117
F85 170 � 150
F165 268 � 248
F560 336 � 316
F85OEM“Greasy environments” OEM fi lter
170 � 150
F165OEM 268 � 248
F560OEM 336 � 316
FF85Fine fi lter (G3 class conforming
to EN 779)
170 � 150
FF165 268 � 248
FF560 336 � 316
FAIN38
“Anti-insect” fi lters
137 � 117
FAIN85 170 � 150
FAIN165 268 � 248
FAIN560 336 � 316
06_014_029_EN.indd 2806_014_029_EN.indd 28 2/4/08 13:27:482/4/08 13:27:48
AF F
DE
BC
==
Ø5.3
6/29
VF Accessories for forced and natural ventilation systems
Ventilation devices
c To connect the inside of the enclosure with the exterior atmosphere and prevent condensation. Can be fixed onto the outside (references VM25 and VN27) or onto the internal sides connected with the rear self-ventilating windows of the POLYMEL enclosures (reference VM35).
Reference Specifi cations
VM25 For coupling to the exterior of all polyester enclosures
VM27 For coupling to the exterior of all polyester enclosures
VM35 For coupling to the interior of POLYMEL enclosures
Reference A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)
TR1 144 62 36 110 - -
TR2 208 90 72 94 190 -
TR3 244 90 72 130 226 -
TR4 345 118 100 231 237 115.5
TR5 345 148 130 231 327 115.5
TR6 445 148 130 297 427 148.5
Lifting screws
c Lifting screws for the top of the OLN enclosures to improve ventilation
c Reference: VET12.
Ventilation slots
c Natural ventilation. Guarantee air circulation inside the enclosure. Texturised RAL-7032 colour
VM35
VM27VM25
06_014_029_EN.indd 2906_014_029_EN.indd 29 2/4/08 13:27:522/4/08 13:27:52
6/30
1
2
34
5
Air/air exchangersIn details
AIR/AIR EXCHANGERS
Reference Performance Voltage MountingDimensions (mm)
Integratedthermostat
Height Width Depth
ICL15AI 15 W/°K 230 V 50/60 Hz Side 700 270 144 Yes
ICL35AI 35 W/°K 230 V 50/60 Hz Side 780 325 144 Yes
ICL35AILC 35 W/°K 230 V 50/60 Hz Side 780 325 144 No
ICL35AIN 35 W/°K 230 V 50/60 Hz Side 780 325 144 Yes
ICL60AI 70 W/°K 230 V 50/60 Hz Side 1480 450 144 Yes
ICT50AI 50 W/°K 230 V 50/60 Hz Top 340 600 360 Yes
See the accessories on pages 6/33 and 6/35.
06_030_039_EN.indd 3006_030_039_EN.indd 30 2/4/08 13:29:452/4/08 13:29:45
6/31
1 Available in two versions: c Side-mounting.c Top-mounting.
Performance from 15 to 70 W/°K that allows you to install the equipment best suited to your needs in each case.
5c Fast access to
the interior makes unit cleaning and maintenance easy.
c The special configuration of the exchange battery makes it easy to clean.
The spaces between the slats make it possible to access the inside aluminium walls for easy and fast cleaning.
2 The exchangers come equipped with an adjustable thermostat that controls the interior temperature of the enclosure:c An auxiliary control
thermostat does not need to be installed.
c It guarantees the correct reading of the interior temperature of the enclosure.
Temperature control range from +20 to +50 ºC.
3 The air-air exchangers do not need inlet fi lters, thus reducing periodic maintenance.
4 The interior and exterior air circuits are perfectly separated and maintain the IP54 watertightness of the enclosure.
Two fans guarantee air circulation in each of the circuits:
c Circulation fan for air inside the enclosure.
The internal circuit fan is always on, thereby maintaining a uniform temperature inside the enclosure and preventing hot spots.
c Circulation fan for air outside the enclosure.
The interior thermostat controls the fan and starts it when the temperature of the air inside the enclosure is above the required temperature.
06_030_039_EN.indd 3106_030_039_EN.indd 31 2/4/08 13:29:502/4/08 13:29:50
6/32
ICT / ICL / AI Air/air exchangers
General features:
c Main components: thermostatic adjustment system, exchange battery, circulation
c The temperature required in the enclosure may be adjusted from +25 ºC to +50 ºC.
c The interior and exterior air circuits are perfectly separated (IP54). Two fans guarantee air circulation in each one of the circuits; the inside circuit (that moves the enclosure air) is permanently on, which makes it possible to avoid hot spots in the electric circuits or the components.
c The equipment is delivered with a drilling template, an installation guide, and a water and air-tightness gasket to be inserted between the exchanger and the enclosure.
Conditions of use:
c The exchangers can only be used when the outside temperature is 5 °C below the temperature required inside the enclosure.
c The enclosure should be airtight to avoid the penetration of outside air(IP54 minimum).
Reference
ICL15AI ICL35AI ICL35AILC ICL35AIN
(internal mounting)ICL60AI
Cooling specifi cations
Specifi c power (1) 15 W/°K 35 W/°K 35 W/°K 35 W/°K 70 W/°K
Exterior circuit airfl ow 200 m3/h 450 m3/h 450 m3/h 450 m3/h 450 m3/h
Inside circuit airfl ow 200 m3/h 450 m3/h 450 m3/h 450 m3/h 450 m3/h
Exchange surface 1.23 m2 1.5 m2 1.5 m2 1.5 m2 6.6 m2
Adjustment Yes Yes No Yes Yes
Type Thermostatic Thermostatic - Thermostatic Thermostatic
Temperature control range 25-50 °C 25-50 °C - 25-50 °C 25-50 °C
Nature of the fl uid Air Air Thermostatic Air Air
Electrical specifi cations
Power supply voltage 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz
Start-up/rated intensity 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A
Electrical power absorbed 150 W 150 W 150 W 150 W 150 W
Physical features
External dimensions A � B � C (mm)
700 � 270 � 144 780 � 325 � 144 780 � 325 � 144 780 � 325 � 144 1480 � 450 � 144
Internal IP circuit IP54 IP54 IP54 IP54 IP54
External IP circuit IP22 IP22 IP22 IP22 IP22
Weight 12 kg 15 kg 15 kg 15 kg 35 kg
Noise level 64 dB (A) 64 dB (A) 64 dB (A) 64 dB (A) 64 dB (A)
Side-mounting
(1) Power in W is obtained by formula: specifi c power � temperature difference between interior and exterior of enclosure.Example: for exchanger ref. ICL35AI for a difference of 10 °C, the system power is 35 � 10 = 350 W.
06_030_039_EN.indd 3206_030_039_EN.indd 32 2/4/08 13:30:042/4/08 13:30:04
A
I
F
G
J
E
25
H
80
25
B144(C)26
D
K
ø 30
136
=
==
=
A
I
F
G
J
E
80
B
144(C)28 26
D
K
136
H
==
(1)
(1)
6/33
ICT / ICL / AI Air/air exchangers
Accessories (side mounting)
c Optional grille to mount the exchangers inside the enclosure.
ICL15AI ICL35AI
ICL35AILCICL35AIN
ICL60AI
A 700 780 1480
B 270 325 450
C 144 144 144
D 220 294 420
E 167 183.5 183.5
F 82 77.5 77.5
G 13 35.5 35.5
H 366 413 1113
I 226 266 393
J 40 52 115
K 4 � 8 Ø 4 � 8 Ø 6 � 8 Ø
Installation (internal mounting)
Reference For mounting with the exchanger
RPF15AI ICL15AI
RPF35AI ICL35AI/ICL35AILC
RPF70AI ICL60AI
External mounting
FIG. 1
(1) Filter grilles.
Ref.: RPF (not included in the standard supply).
Internal mounting
FIG. 2
Dimensions (mm)
06_030_039_EN.indd 3306_030_039_EN.indd 33 2/4/08 13:30:052/4/08 13:30:05
6/34
ICT / ICL / AI Air/air exchangers
General features:
c Main components: thermostatic adjustment system, exchange battery, circulation fans for air from the inside and outside circuits.
c The temperature required in the enclosure may be adjusted from +25 ºC to +50 ºC.
c The interior and exterior air circuits are perfectly separated (IP54). Two fans guarantee air circulation in each one of the circuits; the inside circuit (that moves the enclosure air) is permanently on, which makes it possible to avoid hot spots in the electric circuits or the components.
c The equipment is delivered with a drilling template, an installation guide, and a water and air-tightness gasket to be inserted between the exchanger and the enclosure.
Conditions of use:
c The exchangers can only be used when the outside temperature is 5 °C below the temperature required inside the enclosure.
c The enclosure should be airtight to avoid the penetration of outside air.
Reference
ICT50AI
Cooling specifi cations
Specifi c power (1) 50 W/°K
Exterior circuit airfl ow 450 m3/h
Interior circuit airfl ow 450 m3/h
Exchange surface 3.3 m2
Adjustment Yes
Type Thermostatic
Temperature control range 20-50 °C
Nature of the fl uid Air
Electrical specifi cations
Power supply voltage 230 V 50/60 Hz
Start-up/rated intensity 2.1/0.7 A
Electrical power absorbed 150 W
Physical features
External dimensions A � B � C (mm) 390 � 600 � 365
Internal IP circuit IP54
External IP circuit IP22
Weight 19 kg
Noise level 64 dB (A)
ICT50AI
Top mounting
(1) Power in W is obtained by formula: specifi c power � temperature difference between inferior and exterior of enclosure.
06_030_039_EN.indd 3406_030_039_EN.indd 34 2/4/08 13:30:062/4/08 13:30:06
600
300
115 370
31070 7020
ø 8
290360
340
600 36026
36026
6/35
ICT / ICL / AI Air/air exchangers
Accessories (top mounting)
c Intermediate frame for coupling the MMI64 exchanger to the 600 mm wide and 400 mm deep enclosures.
c Ref. MMI64.
Top mounting: dimensions
FIG. 1
Dimensions (mm)
Frame MMI64
06_030_039_EN.indd 3506_030_039_EN.indd 35 2/4/08 13:30:072/4/08 13:30:07
6/36
1
2
3
4
5
AIR/WATER EXCHANGERS
ReferencesCooling power L35/W
10/200 l/hVoltage
Dimensions (mm)Mounting
Height Width Depth
ICL1800AG 1800 W 230 V 50/60 Hz 830 360 113 Side
ICT1800AG 1800 W 230 V 50/60 Hz 310 600 365 Top
Air/water exchangersIn details
06_030_039_EN.indd 3606_030_039_EN.indd 36 2/4/08 13:30:072/4/08 13:30:07
6/37
ANTI-LEAKdetection system
1 Available in two versions: Top and side mounting.
5 Comfortable and easy to assemble and disassemble. Fast access to the inside makes for easy cleaning and maintenance of the unit.Because it is water cooled, there is no outside air circuit, and no fi lters are needed, thus reducing periodical maintenance.
2 The exchangers come with an adjustable thermostat that controls the inside temperature of the enclosure:c It avoids the installation of an auxiliary control thermostat.c It guarantees the correct reading of the inside temperature of the enclosure.
Temperature adjustment range: +20 to +50 ºC.
4 The IP54 watertightness is guaranteed.The recirculation fan of the enclosure inside air is on permanently, which maintains an even temperature inside the enclosure and thus avoids the appearance of hot spots.
3 It has an electrically-operated valve in the water inlet which, controlled by the thermostat, adjusts temperature and avoids possible condensation.It has an anti-leak detection system that cuts off the water supply if it detects a loss in the circuit.
Maximum Safety
06_030_039_EN.indd 3706_030_039_EN.indd 37 2/4/08 13:30:152/4/08 13:30:15
6/38
ICT / ICL / AG Air/water exchangers
General features:
c Main components: control system, exchange cassette, circulation fans for internal circuit.
c The temperature required in the enclosure can be controlled within a range of +25 to +50 ºC.
c The alarm which detects an interruption in the water circuit triggers closing of an N/O contact. This contact can be used to actuate a pilot light or siren, or it can be connected to a PLC input. In the event of the alarm being triggered, the water supply is automatically cut off.
c System to evacuate condensation water to the outside.
Conditions of use:
c The air-water exchangers can be used even if the external temperature is superior to the temperature required within the enclosure.
c The enclosure should be airtight in order to prevent entry of external air, IP54 minimum.
Reference
ICT1800AG ICL1800AG
Cooling specifi cations
Specifi c power A 35 W 10-200 l/h 1800 W 1800 W
Max. water pressure 1 MPa 1 MPa
Exterior circuit airfl ow 250 m3/h 350 m3/h
Adjustment Yes Yes
Type Thermostatic Thermostatic
Temperature control range 25-50 °C 25-50 °C
Nature of the fl uid Water Water
Electrical specifi cations
Power supply voltage 230 V 50/60 Hz 230 V 50/60 Hz
Start-up/rated intensity 1/0.5 A 1/0.5 A
Electrical power absorbed 90 W 90 W
Type of alarm Dry contact Dry contact
Physical features
External dimensions A � B � C (mm) 310 � 600 � 365 830 � 355 � 110
IP (EN 60529) IP54 IP54
Weight 26 kg 19 kg
Noise level 64 dB (A) 62 dB (A)
Mounting Top Side
Top and side mounting
06_030_039_EN.indd 3806_030_039_EN.indd 38 2/4/08 13:30:362/4/08 13:30:36
600
310
497
430
332
=
61.540.5
280268 236
236
=
=
=
Front of the enclosure
830
300
105
20
750
410
150
360113
300
ø 8
180
6/39
ICT / ICL / AG Air/water exchangers
FIG. 1
Included with unit:
c Drilling template.
c Installation accessories.
c Installation and operating instructions.
Top mounting Ref.: ICT1800AG
Included with unit:
c Drilling template.
c Installation accessories.
c Installation and operating instructions.
c For internal or external mounting.
Side mounting Ref.: ICL1800AG
FIG. 2
Power absorbed at a water fl ow rate for 100 l/h Power absorbed at a water fl ow rate for 200 l/h Power absorbed at a water fl ow rate for 300 l/h
3500
Td=50°CTd=45°CTd=40°CTd=35°CTd=30°CTd=25°CTd=20°C
3000
2500
2000
1500
1000
500
0
Temperatura del agua °C
Td = Temperatura deseada en el interior del armario
Pote
ncia
dis
ipad
a po
r el i
nter
cam
biad
or (W
)
5 10 15 20 25 30
Td=50°CTd=45°CTd=40°CTd=35°CTd=30°CTd=25°CTd=20°C
Temperatura del agua °C
Pote
ncia
dis
ipad
a po
r el i
nter
cam
biad
or (W
)
5 10 15 20 25 30
3500
3000
4000
2500
2000
1500
1000
500
0
Temperatura del agua °C
Pote
ncia
dis
ipad
a po
r el i
nter
cam
biad
or (W
)
Td=50°CTd=45°CTd=40°CTd=35°CTd=30°CTd=25°CTd=20°C
5 10 15 20 25 30
3500
3000
4000
2500
2000
1500
1000
500
0
Curves
FIG. 3
Water inlet-outlet
Condensation water outlet
Dimensions
Water temperature ºC Water temperature ºCWater temperature ºC
Top mounting exchanger
Side mounting exchanger
Example: for water at 100 l/h at 15 ºC with a preferred temperature of 35 ºCPower = 1400 W
Pow
er e
xcha
nged
by
the
exch
ange
rs (W
)
Pow
er e
xcha
nged
by
the
exch
ange
rs (W
)
Pow
er e
xcha
nged
by
the
exch
ange
rs (W
)
06_030_039_EN.indd 3906_030_039_EN.indd 39 2/4/08 13:30:422/4/08 13:30:42
6/40
Cooling unitsCLL/CLT standard control
06_040_043_EN.indd 4006_040_043_EN.indd 40 2/4/08 13:31:132/4/08 13:31:13
ENVIRONMENTALLY friendly
6/41
c Available in two versions: top and side mounting versions.
c The power of mechanically regulated cooling units ranges from 240 to 3100 W. There is always equipment which is suited to your needs.
c Comfortable and easy to assemble and disassemble.
c The side installation models can be semi-recessed with the use of the specific accessory.
Easy access to the condenser allows simplifi ed cleaning through blowing.
Disassemble of the cooling units is not necessary for the high temperature compressor and external fan maintenances.
The inside and outside air circuits are perfectly separated and maintain IP54 watertightness of the enclosure.
Two fans guarantee air circulation in each one of the circuits:
c Internal circuit fan. It is on permanently, which maintains an even temperature inside the enclosure, avoids the appearance of hot spots and guarantees a correct reading of the inside temperature of the enclosure by the set-point thermostat.
c External circuit fan. The inside thermostat controls the fan and starts it up when the temperature of the air inside the enclosure is above the maximum value displayed.
The air conditioning units come with an adjustable thermostat that controls the inside temperature of the enclosure: c It avoids the installation
of an auxiliary control thermostat.
c It guarantees the correct reading of the inside temperature of the enclosure.
Temperature adjustment range: +20 ºC to +50 ºC (supplied factory-adjusted to 35 ºC).
c The top mounting models feature a condensation water automatic evaporation system with an exclusive safety system that switches off the apparatus or issues an alarm if the condensation water level is exceeded.
c They also feature an exclusive voluntary unloading system that makes it possible to empty the water from the condensation tray.
They are equipped with an automatic reset pressostat and a contact thermostat that detects the overpressure in the compressor circuit and interrupts it and the outside circuit fan, thus avoiding possible faults.
Fitted with a fault warning relay, it provides the possibility of operating an alarm indicator, shutting down the apparatus.
Fitted with high pressure compressors that allow them to work at outside temperatures of up to +55 ºC.
Environmentally friendly.
Use of R134a ecological gas.
06_040_043_EN.indd 4106_040_043_EN.indd 41 2/4/08 13:31:192/4/08 13:31:19
6/42
COOLING UNITS Selection guide
SIDE-MOUNTING
ReferencesPower EN 14511
L35 - L35Voltage in V-Hz Dimensions (mm) Adjustment
CLL240 240 W (819 Btu/h) 230-50/60 450 � 350 � 140 Thermostat
CLL370 370 W (1260 Btu/h) 230-50/60 620 � 300 � 170 Thermostat
CLL760 760 W (2594 Btu/h) 230-50/60 800 � 350 �195 Thermostat
CLL1050 1050 W (3584 Btu/h) 230-50/60 900 � 400 � 195 Thermostat
CLLMP1100 1100 W (3755 Btu/h) 230-50/60 1010 � 400 � 240 Microprocessor
CLLMP1400 1400 W (4780 Btu/h) 230-50/60 1010 � 400 � 240 Microprocessor
CLLMP1400T 1400 W (4780 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
1010 � 400 � 240 Microprocessor
CLL1650 1650 W (5631 Btu/h) 230-50/60 1000 � 400 � 220 Thermostat
CLL1650T 1800 W (6143 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
1000 � 400 � 220 Thermostat
CLLMP1800T 1800 W (6145 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
1010 � 400 � 240 Microprocessor
06_040_043_EN.indd 4206_040_043_EN.indd 42 2/4/08 13:31:282/4/08 13:31:28
6/43
COOLING UNITS Selection guide
TOP-MOUNTING
ReferencesPower EN 14511
L35 - L35Voltage in V-Hz Dimensions (mm) Adjustment
CLT760 760 W (2.594 Btu/h) 230-50/60 340 � 600 � 350 Thermostat
CLT1050 1050 W (3.584 Btu/h) 230-50/60 400 � 700 � 400 Thermostat
CLTMP1400 1400 W (4.780 Btu/h) 230-50/60 415 � 750 � 412 Microprocessor
CLT1460 1460 W (4.984 Btu/h) 230-50/60 400 � 700 � 400 Thermostat
CLT1650 1650 W (5.631 Btu/h) 230-50/60 430 � 700 � 400 Thermostat
CLTMP1800T 1800 W (6.145 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
415 � 750 � 412 Microprocessor
CLT1650T 2000 W (6.826 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
430 � 700 � 400 Thermostat
CLT2450T 2450 W (8.368 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
470 � 800 � 450 Thermostat
CLT3100T 3100 W (10.583 Btu/h)3 � 400 V 50 Hz/3 � 440 V 60 Hz
470 � 800 � 450 Thermostat
06_040_043_EN.indd 4306_040_043_EN.indd 43 2/4/08 13:31:302/4/08 13:31:30
6/44
CLL Cooling units
Cooling units for electronic switchboards:
c Respect for the environment by using the ecological gas R134a.
c Cooling power of 240 W to 3100 W.
c Possibility of partial flush mounting for all side mounting models.
General features:
c Temperature setting can be adjusted from +20 to +50 ºC.
c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actua-tes compressor and external fan switch-off.
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c The equipment is fitted with switches enabling an alarm report.
c Cooling power of 240 W to 3100 W.
c Possibility of partial flush mounting.
Reference CLL240 CLL370 CLL760
Voltage 230 V 50/60 Hz
Cooling power (50/60 Hz) acording to EN 14511L35 - L35 L35 - L50
240 W (819 Btu/h)190 W (649 Btu/h)
370/390 W (1263/1331 Btu/h) 300/310 W (1024/1058 Btu/h)
760/810 W (2594/2765 Btu/h) 610/640 W (2082/2184 Btu/h)
Dimensions Height WidthDepth
450 mm 350 mm
140 mm + (15 mm inside)
620 mm 300 mm 170 mm
800 mm350 mm195 mm
Current Start-up Nominal
2.8 A0.7 A
5.8/6.7 A 1.5/1.8 A
7.7/8.8 A2/2.3 A
Electrical power absorbedL35 - L35L35 - L50
140 W 160 W
290/330 W 330/380 W
380/440 W440/500 W
EER energetic performance L35 - L35 1.7 1.3/1.2 2.0/1.8
Temperature regulator Thermostat
Temperature setting range 20 - 45 °C 20 - 50 °C
Maximum external temperature 50 °C 55 °C
Noise level 58 dB (A) 65 dB (A) 67 dB (A)
Airfl ow Internal circuitExternal circuit
160 m3/h 320 m3/h
160/175 m3/h 210/230 m3/h
350/385 m3/h 350/385 m3/h
Alarm type contact free power Inverter contact
Weight 15 kg 21 kg 33 kg
Cooling gas R134a (0.25 kg) R134a (0.3 kg) R134a (0.5 kg)
Internal IP circuit 54 54 54
External IP circuit 34 34 34
External circuit fi lter Optional Yes
Mounting model Side
Recommended protection (fuse curve) T1.6 A T3 A T3 A
CLL760
Side mountingMechanical control
06_044_063_EN.indd 4406_044_063_EN.indd 44 2/4/08 13:32:012/4/08 13:32:01
400
350
300
250
200
150
100
20 25 30 35 40 45 50 55
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50/60 Hz
700
600
500
400
300
200
100
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 60 Hz
1400
1200
1000
800
600
400
200
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 60 Hz
700
600
500
400
300
200
100
1400
1200
1000
800
600
400
200
Pf
[ W ]
P26
H
A
C
E
G
Q
60
B
D
F
N
LR30
M
ø S
K
= =
6/45
CLL Cooling units
FIG. 1
CLL240 50/60 Hz CLL370 50 Hz CLL370 60 Hz
CLL760 50 Hz CLL760 60 Hz
Curves
Dimensions in mm CLL370 CLL760
A 260 266
B 0 52
C 80 116
D 40 193,5
E 300 375
F 540 413
G 60 80
H 620 800
K 136 136
L 300 350
M 240 294
N - -
P 170 195
Q 35 149
R 0 24
S 8 8
CLL240: Dimensions Cut-out dimensions
External mounting Partial fl ush mounting
Ref. CLL370 and CLL760
Ref. CLL240
FIG. 3
Side mounting: dimensions
FIG. 2
Dimensions (mm)
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 4506_044_063_EN.indd 45 2/4/08 13:32:032/4/08 13:32:03
6/46
CLL Cooling units
Cooling units for switchboards:
c Respect for the environment by using the ecological gas R134a.
c Automatic evaporation of condensation water on all top mounting models.
c Cooling power of 240 W to 3100 W.
c Possibility of partial flush mounting for all side mounting models.
General features:
c Temperature setting can be adjusted from +20 to +50 ºC.
c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) activates compressor and external fan switch-off.
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c The equipment is fitted with switches enabling an alarm report.
c Cooling power of 240 W to 3100 W.
c Possibility of partial flush mounting.
Reference CLL1050 CLL1650 CLL1650T
Voltage 230 V 50/60 Hz 3 � 400 V 50 Hz / 3 � 440 V 60 Hz
Cooling power (50/60 Hz) according to EN 14511L35 - L35L35 - L50
1050/1100 W(3584/3755 Btu/h)
840/890 W (2867/3038 Btu/h)
1650/1700 W (5631/5802 Btu/h)1300/1400 W (4438/4779 Btu/h)
1800/1900 W (6143/6485 Btu/h) 1400/1500 W (4779/5121 Btu/h)
Dimensions HeightWidthDepth
900 mm400 mm 195 mm
1000 mm400 mm220 mm
CurrentStart-upNominal
10.1/11.6 A 2.7/3 A
16.1/18.5 A 4.2/4.9 A
6.8/7.9 A 2.1/2.5 A
Electrical power absorbedL35 - L35L35 - L50
550/580 W 580/660 W
800/920 W 920/1100 W
1200/1400 W1400/1600 W
EER energetic performance L35 - L35
2.1/1.9 2.1/1.9
1.5/1.4
Temperature setting range Thermostat
Control range 20 - 50 °C
Max. external ambient temperature 55 °C
Noise level 67 dB (A) 67 dB (A) 69 dB (A)
Airfl ow Internal circuitExternal circuit
350/385 m3/h510/560 m3/h
550/600 m3/h620/680 m3/h
Alarm contact Potential-free
Weight 39 kg 42 kg 46 kg
Cooling gas R134a (0.7 kg) R134a (0.75 kg)
Internal IP circuit 54 54 54
External IP circuit 34 34 34
External circuit fi lter Yes
Mounting model Side
Recommended protection (fuse curve) T4 A T6 A T3 A
CLL1650
Side mounting
06_044_063_EN.indd 4606_044_063_EN.indd 46 2/4/08 13:32:042/4/08 13:32:04
H
A
C
E
G
Q
60
B
D
F
N
LR30
M
ø S
K
= =
P26
1800
1600
1400
1200
1000
800
600
400
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
3000
2600
2200
1800
1400
1000
600
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
3000
2600
2200
1800
1400
1000
600
3200
2800
2400
2000
1600
1200
600
3200
2800
2400
2000
1600
1200
600
1800
1600
1400
1200
1000
800
600
400
6/47
CLL Cooling units
FIG. 1
Curves
FIG. 2
Dimensions in mm CLL1050 CLL1650 CLL1650T
A 300 300 300
B 0 0 0
C 135 135 135
D 30 30 30
E 465 475 475
F 840 840 840
G 100 100 100
H 900 1000 1000
K 180 180 180
L 400 400 400
M 320 320 320
N - 470 470
P 195 220 220
Q 35 25 25
R 195 195 195
S 0 10 10
CLL1050 50 Hz CLL1050 60 Hz CLL1650 50 Hz
CLL1650 60 Hz CLL1650T 50 Hz CLL1650T 60 Hz
Side mounting: dimensions
Dimensions (mm)
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 4706_044_063_EN.indd 47 2/4/08 13:32:052/4/08 13:32:05
6/48
CLT Cooling units
Cooling units for electrical switchboards:
c Respect for the environment by using the ecological gas R134a.
c Automatic evaporation of condensation water.
c Cooling power of 760 W to 3100 W.
General features:
c Temperature setting can be adjusted from +20 to +50 ºC.
c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off.
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c The equipment is fitted with switches enabling an alarm report.
c System of automatic recovery and evaporation of condensates.
Reference CLT760 CLT1050 CLT1460
Voltage 230 V 50/60 Hz
Cooling power (50/60 Hz) according to EN 14511L35 - L35L35 - L50
760/810 W (2594/2765 Btu/h) 610/640 W (2082/2184 Btu/h)
1050/1100 W (3584/3755 Btu/h) 840/890 W (2867/3038 Btu/h)
1460/1500 W (4983/5121 Btu/h)1200/1200 W (4096/4096 Btu/h)
Dimensions Height Width Depth
340 mm 600 mm 350 mm
400 mm700 mm 400 mm
Current Starting currentRated current
7.7/8.8 A 2/2.3 A
10.1/11.6 A 2.7/3 A
14.1/16.2 A3.7/4.3 A
Electrical power absorbedL35 - L35L35 - L50
380/440 W 440/500 W
550/580 W 580/660 W
730/810 W810/930 W
EER energetic performance L35 - L35 2.0/1.8 2.1/1.9 2.1/1.9
Control type thermostatic Thermostat
Temperature setting range 20 - 50 °C
Maximum external temperature 55 °C
Noise level 67 dB (A) 69 dB (A)
Airfl owInternal circuit External circuit
350/385 m3/h 350/385 m3/h
400/440 m3/h620/680 m3/h
Alarm type free power Inverter contact
Weight 33 kg 41 kg 45 kg
Cooling gas R134a (0.5 kg) R134a (0.7 kg) R134a (0.75 kg)
Internal IP circuit 54 54 54
External IP circuit 34 34 34
External circuit fi lter Yes
Mounting model Top
Recommended protection (fuse curve) T3 A T4 A T6 A
CLT1050
Top mounting
06_044_063_EN.indd 4806_044_063_EN.indd 48 2/4/08 13:32:052/4/08 13:32:05
M*
J26
K
H
250
A
F
B
ø 8
G
300C
ED
6/49
CLT Cooling units
FIG. 1
Top-mounting Ref.: CLT760-CTL1050-CTL1460
Reference A B C D E F G H I K M
CLT760 108 350 350 40 136 292 80 600 600 340 600
CLT1050 118 420 400 45 180 328 90 700 700 400 700
CLT1460 118 420 400 45 180 328 90 700 700 400 700
Drilling template for top mounting without intermediate frame
1400
1200
1000
800
600
400
200
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
1800
1600
1400
1200
1000
800
600
400
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
1800
1600
1400
1200
1000
800
600
400
2400
2100
1800
1500
1200
900
600
1400
1200
1000
800
600
400
200
2400
2100
1800
1500
1200
900
600
Curves
FIG. 2
CLT760 50 Hz CLT760 60 Hz CLT1050 50 Hz
CLT1050 60 Hz CLT1460 50 Hz CLT1460 60 Hz
Dimensions (mm)
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 4906_044_063_EN.indd 49 2/4/08 13:32:062/4/08 13:32:06
6/50
CLT Cooling units
Cooling units for electrical switchboards:
c Respect for the environment by using the ecological gas R134a.
c Automatic evaporation of condensation water.
c Cooling power of 760 W to 3100 W.
General features:
c Temperature setting can be adjusted from +20 to +50 ºC.
c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off.
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c The equipment is fitted with switches enabling an alarm report.
c System of automatic recovery and evaporation of condensates.
Reference CLT1650 CLT1650T
Voltage 230 V 50/60 Hz 3 � 400 V 50 Hz / 3 � 440 V 60 Hz
Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50
1650/1700 W (5631/5802 Btu/h)1300/1400 W (4438/4779 Btu/h)
1650/2100 W (6826/7169 Btu/h)1600/1700 W (5462/5803 Btu/h)
DimensionsHeightWidth Depth
430 mm700 mm400 mm
CurrentStarting currentRated current
16.1/18.5 A4.2/4.5 A
6.8 /7.9 A2.1/2.5 A
Electrical power absorbed L35 - L35L35 - L50
800/920 W 920/1100 W
1200/1400 W1400/1700 W
EER energetic performance L35 - L35 2.1/1.9 1.7/1.5
Temperature regulator Thermostat
Temperature setting range 20 - 50 °C
Maximum external temperature 55 °C
Noise level 67 dB (A) 69 dB (A)
Airfl owInternal circuit External circuit
550/600 m3/h 620/680 m3/h
Alarm type free power Inverter contact
Weight 47 kg 60 kg
Cooling gas R134a (1.0 kg)
Internal IP circuit 54
External IP circuit 34
External circuit fi lter Yes
Mounting model Top
Recommended protection (fuse curve) T6 A T3 A
CLT1650
Top mounting
06_044_063_EN.indd 5006_044_063_EN.indd 50 2/4/08 13:32:062/4/08 13:32:06
M*
J26
K
H
250
A
F
B
ø 8
G
300C
ED
6/51
CLT Cooling units
FIG. 1
Top mounting Ref.: CLT1650-CLT1650T
Reference A B C D E F G H I K M
CLT1650 118 420 400 45 180 328 90 700 700 430 700
CLT1650T 118 420 400 45 180 328 90 700 700 430 700
Drilling template for top mounting without intermediate frame
Dimensions (mm)
Curves
FIG. 2
CLT1650 50 Hz CLT1650 60 Hz
CLT1650T 50 Hz CLT1650T 60 Hz
3000
2600
2200
1800
1400
1000
600
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
3000
2600
2200
1800
1400
1000
600
3200
2800
2400
2000
1600
1200
600
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
3200
2800
2400
2000
1600
1200
600
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 5106_044_063_EN.indd 51 2/4/08 13:32:072/4/08 13:32:07
6/52
CLT Cooling units
Cooling units for electrical switchboards:
c Respect for the environment by using the ecological gas R134a.
c Automatic evaporation of condensation water.
c Cooling power of 760 W to 3100 W.
General features:
c Temperature setting can be adjusted from +20 to +50 ºC.
c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off.
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c The equipment is fitted with switches enabling an alarm report.
c System of automatic recovery and evaporation of condensates.
CLT3100T
Reference CLT2450T CLT3100T
Voltage 3 � 400 V 50 Hz / 3 � 440 V 60 Hz
Cooling power (50/60 Hz) according to EN 14511L35 - L35L35 - L50
2450/2600 W (8362/8876 Btu/h) 2000/2100 W (6828/7169 Btu/h)
3100/3300 W (10580/11266 Btu/h)2500/2600 W (8532/8876 Btu/h)
DimensionsHeightWidth Depth
470 mm800 mm450 mm
CurrentStart-upNominal
8.4/10.1 A 2.6/3.2 A
9.6/11.3 A3.0/3.5 A
Electrical power absorbedL35 - L35L35 - L50
1500/1800 W1800/2100 W
1700/2000 W2000/2300 W
EER energetic performance L35 - L35 1.6/1.5 1.8/1.7
Temperature regulator Thermostat
Control range 20 - 50 °C
Max. external ambient temperature 55 °C
Noise level 69 dB (A)
Internal IP circuit 750/820 m3/h
External IP circuit 1200/1310 m3/h
Alarm type contact free power Inverter contact
Weight 65 kg
Cooling gas R134a (1.5 kg) R134a (1.7 kg)
Internal IP circuit 54
External IP circuit 34
External circuit fi lter Yes
Mounting model Top
Recommended protection (fuse curve) T4 A T4 A
Top mounting
06_044_063_EN.indd 5206_044_063_EN.indd 52 2/4/08 13:32:072/4/08 13:32:07
800*
*
8002626
470
800
220
380
360
ø 10
140
300300450
14070
6/53
CLT Cooling units
FIG. 1
Top mounting Ref.: CLT2450T-CLT3100T
Curves
FIG. 2
* Maximum overall dimensions of the intermediate frame
CLT2450T 50 Hz CLT2450T 60 Hz
CLT3100T 50 Hz CLT3100T 60 Hz
Dimensions (mm)
4000
3500
3000
2500
2000
1500
1000
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
4000
3500
3000
2500
2000
1500
1000
5500
4900
4300
3700
3100
2500
1900
1300
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
5500
4900
4300
3700
3100
2500
1900
1300
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 5306_044_063_EN.indd 53 2/4/08 13:32:082/4/08 13:32:08
X Y
26
* V
T
U
* WX Y
26*20
6/54
CLL / CLT Accessories
Frames for partial fl ush mounting
c For partial flush mounting of the CLL cooling units.
Reference To fi t the units
MECL370 CLL370
MECL760 CLL760
MECL1050 CLL1050
MECL1650 CLL1650/1650T
Partial fl ush unit mounting Frame for partial mounting
Reference T V V* W* X Y
MECL370 320 635 646 346 80 90
MECL760 370 815 826 396 95 100
MECL1050 420 915 926 446 95 100
MECL1650 420 1015 1026 446 120 100
* Maximum dimensions of the frame
06_044_063_EN.indd 5406_044_063_EN.indd 54 2/4/08 13:32:082/4/08 13:32:08
36026
6/55
CLL / CLT Accessories
Intermediate frame for top mounting
c For mounting the CLT760 cooling unit on the top of enclosures width = 600 mmdepth = 400 mm
c Colour grey RAL-7032.
c Dimensions: 60 � 595 � 360 mm.
Reference Characteristics
MMI64To fi t enclosures 600 mm wide and 400 mm deep.
Replacement fi lter
Reference Characteristics
FCLIC To fi t to all cooling units
06_044_063_EN.indd 5506_044_063_EN.indd 55 2/4/08 13:32:092/4/08 13:32:09
6/56
Cooling unitsCLLMP/CLTMP electronic control
06_044_063_EN.indd 5606_044_063_EN.indd 56 2/4/08 13:32:102/4/08 13:32:10
ENVIRONMENTALLYfriendly
6/57
c Available in two versions: top- and side-mounting.
c Power from 1100 W to 1800 W allowing you to install the equipment that best suits your needs in each case.
Comfortable and easy to assemble and disassemble.
The side-mounted air conditioners feature an exclusive quick-installation system:c Two retractable
handles facilitate the installation of the air conditioner by a single operator.
c They have an exclusive quick-fixing system without screws that facilitates mounting
c Fast access to the inside makes unit cleaning and maintenance easy.
c Its design renders fi lters unnecessary in most cases. It is possible to install a fi lter in the exterior circuit for particularly polluted atmospheres.
The inside and outside air circuits are perfectly separated and maintain the enclosure’s IP54 watertightness.
Two fans guarantee air circulation in each of the circuits:
c Recirculation fan for air inside the enclosure. The internal circuit fan is always on, thereby maintaining a uniform temperature inside the enclosure and preventing hot spots.
Electronic regulation provides:
c Precise control of the operating temperature:
– Start-up of the compressor at +1 °C above the preset temperature.
– Switching off of the compressor at -5 °C below the preset temperature.
c Door contact management.
c Manual alarm reset.c Manual rearming of the
alarms.c Control of the idle and
operation times of the compressor.
Temperature adjustment range from +20 to +50 °C.
All models, side-and top-mounting, have an automatic evaporation system for the condensation water.
Use of R134 ecological gas.
c Fan to circulate the air outside the enclosure. The inside thermostat controls the fan and starts it up when the temperature of the air inside the enclosure is above the required temperature.
c The design of the aluminium slats of the condenser makes maintenance easier and less frequent.
on the enclosure and guarantees the IP54 degree of protection.
c The electrical connection is carried out with removable connectors supplied with the cooling unit.
One single machining size.The machining sizes are the same for all side-mounted cooling units.
06_044_063_EN.indd 5706_044_063_EN.indd 57 2/4/08 13:32:162/4/08 13:32:16
6/58
CLLMP Electronically-controlled cooling units
CLLMP1400
Reference CLLMP1100 CLLMP1400 CLLMP1400T CLLMP1800T
Voltage 230 V 50/60 Hz 3 � 400 V 50 Hz / 3 � 440 V 60 Hz
Cooling power (50/60 Hz) according to EN 14511L35 - L35L35 - L50
1100/1200 W (3755/4097 Btu/h)
880/930 W (3004/3175 Btu/h)
1400/1500 W (4780/5121 Btu/h)
1200/1300 W (4097/4438 Btu/h)
1400/1500 W (4780/5121 Btu/h)
1200/1300 W (4097/4438 Btu/h)
1800/1900 W (6145/6485 Btu/h)
1400/1500 W (4780/5121 Btu/h)
Dimensions Height � Width � Depth 1,010 mm � 400 mm � 240 mm
CurrentStart-up Nominal
12.1/13.9 A3.2/3.7 A
18.1/22.2 A 4.8/5.8 A
3.7/4.3 A 1.2/1.4 A
5.3/6.3 A1.8/2.1 A
Electrical power absorbed L35 - L35L35 - L50
600/690 W690/790 W
900/1,100 W1100/1300 W
700/810 W810/930 W
1000/1200 W1200/1300 W
EER energetic performance L35 - L35
1.8/1.7 1.6/1.4 2.0/1.9 1.8/1.7
Temperature regulator Microprocessor (with display and diagnosis)
Temperature setting range 20 - 50 °C
Max. external ambient temperature 55 °C
Noise level 62 dB (A) 64 dB (A) 66 dB (A) 69 dB (A)
Airfl owInternal circuit External circuit
575/600 m3/h860/900 m3/h
860/900 m3/h 860/900 m3/h
860/900 m3/h 860/900 m3/h
885/900 m3/h1050/1160 m3/h
Alarm type free power Inverter contact
Weight 45 kg 46 kg 47 kg 50 kg
Cooling gas R134a (0.85 kg) R134a (0.85 kg) R134a (0.85 kg) R134a (0.85 kg)
Internal IP circuit 54 54 54 54
External IP circuit 34 34 34 34
External circuit fi lter Optional
Mounting model Side
Recommended protection (fuse curve) T6 A T8 A T2 A T3 A
Side mountingGeneral characteristics:
c Main components: high temperature compressor, two fans mounted on removable support, two exchange cassettes, ecological cooling fluid HFC R134a, electronic control and evaporation device (with anti-corrosion finish) for side and top models.
c Temperature setting can be adjusted from +20 to +50 ºC (pre-adjustment and temperature recommended: 35 ºC).
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c Electronic control by microprocessor enables:v Adjustment of set temperature.v Door contact control.v Data is stored in the memory in the event of a power cut:
– Minimum compressor operating time.– Minimum compressor idle time.
v Compressor switch-on at set temperature +1 ºC.v Compressor switch-off at set temperature –5 ºC.v Alarm management.v Alarm reset by “acknowledgement” (manual reset).
Operating conditions:
c Operating temperature: +20 to +55 ºC.c An optional filter is required in cases of installation in the following
applications: intensive welding, hot metal forging, fibres and textiles, crushing, rubber processing and other difficult environments.
c The air conditioner incorporates two retractable handles to facilitate transport.c The air conditioner incorporates a quick attachment device. A circular screw/
cage nut assembly ensures locking of the unit from the exterior.c Electrical connection is by plug-in connectors, included with the unit.c Do not obstruct, even partially, air inlets and outlets.c The unit should be installed spaced at least 30 cm from walls and at least
10 cm from floor level.
06_044_063_EN.indd 5806_044_063_EN.indd 58 2/4/08 13:32:262/4/08 13:32:26
6/59
CLLMP Electronically-controlled cooling units
FIG. 1
Curves
FIG. 2
Drilling template for side mounting
Drilling template for side mounting
2000
1800
1600
1400
1200
1000
800
600
400
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 50 Hz
2200
2000
1800
1600
1400
1200
1000
800
600
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
2200
2000
1800
1600
1400
1200
1000
800
600
Pf
[ W ]
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ]
2200
2000
1800
1600
1400
1200
1000
800
600
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
2000
1800
1600
1400
1200
1000
800
600
400
2200
2000
1800
1600
1400
1200
1000
800
600
CLLMP1100 50 Hz CLLMP1100 60 Hz CLLMP1400T 50 Hz
CLLMP1800T 60 HzCLLMP1800T 50 Hz
CLLMP1400 50 Hz CLLMP1400 60 HzCLLMP1400T 60 Hz
Dimensions (mm)
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 5906_044_063_EN.indd 59 2/4/08 13:32:292/4/08 13:32:29
6/60
CLTMP Electronically-controlled cooling units
Reference CLTMP1400 CLTMP1800T
Voltage 230 V 50/60 Hz 3 � 400 V 50 Hz / 3 � 440 V 60 Hz
Cooling power (50/60 Hz) according to EN 14511L35 - L35 L35 - L50
1400/1500 W (4780/5121 Btu/h) 1200/1300 W (4097/4438 Btu/h)
1800/1900 W (6145/6485 Btu/h)1400/1500 W (4780/5121 Btu/h)
Dimensions Height � Width � Depth 415 mm � 750 mm � 412 mm
IntensityStarting currentRated current
18.1/22.2 A 4.8/5.8 A
5.3/6.3 A1.8/2.1 A
Electrical power absorbedL35 - L35L35 - L50
900/1100 W 1100/1300 W
1000/1200 W1200/1300 W
EER energetic performance L35 - L35
1.6/1.4 1.8/1.7
Temperature regulator Microprocessor (with display and diagnosis)
Temperature setting range 20 - 50 °C
Max. external ambient temperature 55 °C
Noise level 64 dB (A) 69 dB (A)
Airfl owInternal circuit External circuit
860/900 m3/h860/900 m3/h
885/900 m3/h1050/1160 m3/h
Alarm type free power Inverter contact
Weight 48 kg 50 kg
Cooling gas R134a (0.95 kg) R134a (0.95 kg)
Internal IP circuit 54
External IP circuit 34
External circuit fi lter Optional
Mounting model Top
Recommended protection (fuse curve) T8 A T3 A
CLTMP1400
Top mounting
General characteristics:c Main components: high temperature compressor, two fans mounted on
removable support, two exchange cassettes, ecological cooling fluid HFC R134a, electronic control and evaporation device (with anti-corrosion finish) for side and top models.
c Temperature setting can be adjusted from +20 to +50 ºC (pre-adjustment and temperature recommended: 35 ºC).
c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure.
c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure.
c Electronic control by microprocessor enables:v Adjustment of set temperature.v Door contact control.v Data is stored in the memory in the event of a power cut:
– Minimum compressor operating time. – Minimum compressor idle time.
v Compressor switch-on at set temperature +1 ºC.v Compressor switch-off at set temperature –5 ºC.v Alarm management.v Alarm reset by “acknowledgement” (manual reset).
Operating conditions:c Operating temperature: +20 to +55 ºC.c An optional filter is required in cases of installation in the following
applications: intensive welding, hot metal forging, fibres and textiles, crushing, rubber processing and other difficult environments.
c The air conditioner incorporates two retractable handles to facilitate transport.
c The air conditioner incorporates a quick attachment device. A circular screw/cage nut assembly ensures locking of the unit from the exterior.
c Electrical connection is by plug-in connectors, included with the unit.c Do not obstruct, even partially, air inlets and outlets.c The unit should be installed spaced at least 30 cm from walls and at least
10 cm from floor level.
06_044_063_EN.indd 6006_044_063_EN.indd 60 2/4/08 13:32:312/4/08 13:32:31
6/61
CLTMP Electronically-controlled cooling units
FIG. 1
Drilling template for top mounting
Drilling template for top mounting
Dimensions (mm)
Curves
FIG. 2
CLTMP1400 60 Hz CLTMP1400 50 Hz
CLTMP1800T 50 Hz CLTMP1800T 60 Hz
2200
2000
1800
1600
1400
1200
1000
800
600
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ] 2200
2000
1800
1600
1400
1200
1000
800
600
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Pf
[ W ]
Ti [ ºC ]
Te [ ºC ] f = 50 Hz20 25 30 35 40 45 50 55
50
45
40
35
30
25
20
Te [ ºC ] f = 60 Hz
Ti [ ºC ] 3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
Te: ambient air temperature (°C)
Ti: temperature inside enclosure (°C)
Pf: cooling power (W)
06_044_063_EN.indd 6106_044_063_EN.indd 61 2/4/08 13:32:322/4/08 13:32:32
6/62
CLLMP / CLTPM Accessories
Filter unit
c For installation in the outside circuit of the side cooling units. Reference CLLMP...
c Reference: CFCLL.
CFCLL
c Replacement filter.Reference: CFLL.
CFLL
06_044_063_EN.indd 6206_044_063_EN.indd 62 2/4/08 13:32:332/4/08 13:32:33
6/63
CLLMP / CLTPM Accessories
Reference Height Depth
2PLOL186CLM 1,800 600
2PLOL188CLM 1,800 800
2PLOL206CLM 2,000 600
2PLOL208CLM 2,000 800
Side panels prepared for air conditioners
c Set of 2 side panels for fixing inside or outside the enclosure. One pre-knocked panel for the direct fi xing of the CLLMP side-mounted cooling units…
06_044_063_EN.indd 6306_044_063_EN.indd 63 2/4/08 13:32:342/4/08 13:32:34
6/64
Insulated resistance heatersHeating safely
06_064_067_EN.indd 6406_064_067_EN.indd 64 2/4/08 13:33:122/4/08 13:33:12
6/65
c Protected from direct contact with the aluminium radiator.
c Electrical connection protected from direct contact by means of a plastic terminal block cover.
c Equipped with a PTC-type heating element.c Surface temperature below +70 ºC.c The configuration of the aluminium section produces
a chimney effect. High natural convection.c Low energy consumption thanks to the auto-
adjustment of the PTC resistor.
c Available in two versions: by convection and with fan. c Alternating or direct current. c Powers from 10 W to 550 W.
It has a plastic covering to prevent direct contact with the aluminium radiator.
c Small size.c Fast electrical connection by means of snap-on
terminals.c Fast and simple fixing to the 35 mm DIN rail.c Maintenance-free.
c The resistors equipped with fan guarantee air recirculation and an even temperature inside the enclosure.
c High-flow, silent fans.
c EC Marking.c Compliant with UL and VDE across the range.
Certifications
06_064_067_EN.indd 6506_064_067_EN.indd 65 2/4/08 13:33:172/4/08 13:33:17
6/66
RESISTANCE HEATERS
Selection guide
INSULATED RESISTANCE HEATERS
Reference Power W Voltage V
Type of connection
Terminal block Cable
RC10/12-36AI 10 12-36 DC X
RC10AI 10 110-250 AC X
RC20/12-36AI 21 12-36 DC X
RC20AI 21 110-250 AC X
RC50/12-36AI 55 12-36 DC X
RC50AI 55 110-250 AC X
RC50/270-420AI 55 270-420 AC X
RC100/12-36AI 102 12-36 DC X
RC100AI 102 110-250 AC X
RC100/270-420AI 102 270-420 AC X
RC150/12-36AI 147 12-36 DC X
RC150AI 147 110-250 AC X
06_064_067_EN.indd 6606_064_067_EN.indd 66 2/4/08 13:33:382/4/08 13:33:38
6/67
RESISTANCE HEATERS
Selection guide
Reference Power W Voltage V
Type of connection
Terminal block Cable
RCV170 170 230 AC X
Reference Power W Voltage V
Typo of connection
Terminal block Cable
TMV350-550/120 400/550 120 AC X
TMV350/550 400/550 230 AC X
TMV350 350 230 AC X
INSULATED RESISTANCE HEATERS WITH FAN
THERMOFANS
06_064_067_EN.indd 6706_064_067_EN.indd 67 2/4/08 13:33:432/4/08 13:33:43
6/68
RC ... AI Resistance heaters
General characteristics:
c Compact resistance heater which prevents the condensation of water and ice inside the enclosures.
c Innovative design for better natural convection and high thermal performance.
c Compact, smaller resistance heater.
c Extruded aluminium body.
c Features an insulated UL94 V0 plastic cover in light grey to avoid direct contact with the heating elements (PTC) and the aluminium radiator.
c Surface temperature limited to less than 70 °C.
c Equipped with a connection cable.
c Double safety insulated (plastic).
c PTC technology range.
c Quick clip-fixing onto the 35 mm DIN rail.
c Compliant with UL and VDE EC Marking.
Usage conditions:
c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed).
c The enclosure must be sealed in order to prevent the penetration of external air.
c The electrical protection devices must be installed between the supply source and the resistance heaters themselves.
Characteristics Reference
RC10AI RC10/12-36AI RC20AI RC20/12-36AI
Heating power at 0 °C 10 W 21 W
Power supply voltage 110-250 V AC/DC 12-36 V AC/DC 110-250 V AC/DC 12-36 V AC/DC
Heating element PTC
Surface temperature <70 °C, except for upper protection grill
Electrical connection Terminal board
Fixing By clip for the 35 mm DIN rail (EN 50022)
Cover Plastic UL94 V0
Operating position Vertical
Operating temperature –40 to +70 °C (–10 to +15 °F)
IP Protection/Class IP20II (double insulation)
Certifi cations VDE and UL in process
InsulatedRC10AI - RC20AI10 W and 20 W insulated resistance heaters
06_068_079_EN.indd 6806_068_079_EN.indd 68 11/4/08 16:09:4111/4/08 16:09:41
1 2
98
clip de fijación para carril DIN de 35 mm
75
38
12
Clip on 35 mm DIN rail
6/69
RC ... AI Resistance heaters
FIG. 1
Connections
Reference L (mm)
RC10AI 98
RC20AI 98
Dimensions (mm)
06_068_079_EN.indd 6906_068_079_EN.indd 69 11/4/08 16:09:4511/4/08 16:09:45
6/70
RC ... AI Resistance heaters
General characteristics:
c Compact resistance heater which prevents the condensation of water and ice inside the enclosures.
c Innovative design for better natural convection and high thermal performance.
c Compact, smaller resistance heater.
c Extruded aluminium body.
c Features an insulated UL94 V0 plastic cover in light grey to avoid direct contact with the heating elements (PTC) and the aluminium radiator.
c Surface temperature limited to less than 70 °C.
c Fitted with 2.5 mm2 quick-connection terminals.
c Double safety insulated (plastic).
c PTC technology range.
c Quick clip-fixing onto the 35 mm DIN rail (EN 50022).
c Certifications compliant with UL and VDE and EC Marking.
Usage conditions:
c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed).
c The enclosure must be sealed in order to prevent the penetration of external air.
c The electrical protection devices must be installed between the supply source and the resistance heaters themselves.
Characteristics Reference
RC50AI RC50/12-36AIRC50/
270-420AIRC100AI
RC100/12-36AI
RC100/270-420AI
RC 150AIRC150/12-36AI
Heating power at 0 °C 55 W 102 W 147 W
Power supply voltage110-250 V
AC/DC12-36 VAC/DC
270-420 VAC/DC
110-250 VAC/DC
12-36 VAC/DC
270-420 VAC/DC
110-250 VAC/DC
12-36 VAC/DC
Heating element PTC
Surface temperature <70 °C, except for upper protection grill
Electrical connection 4 poles terminal block, 2.5 mm2
Fixing By clip for the 35 mm DIN rail (EN 50022)
Cover Plastic UL94 V0
Operating position Vertical
Operating temperature –40 to +70 °C (–10 to +158 °F)
IP Protection /Class IP20/II (double insulation)
Certifi cations VDE and UL in process
RC50AI - RC100AI - RC150AI55 W - 100 W - 147 W insulated resistance heaters
06_068_079_EN.indd 7006_068_079_EN.indd 70 11/4/08 16:09:4511/4/08 16:09:45
6/71
RC ... AI Resistance heaters
FIG. 1
FIG. 2
RC50AI
RC100AI
RC150AI
Heating power diagram - Ambient temperature
Ambient temperature (°C)
Hea
ting
pow
er (W
)
Diagram
Dimensions (mm)
Reference L (mm)
RC50AI 110
RC50/12-36AI 110
RC50/270-420AI 110
RC100AI 110
RC100/12-36AI 110
RC100/270-420AI 150
RC150AI 150
RC150/12-36AI 150
06_068_079_EN.indd 7106_068_079_EN.indd 71 11/4/08 16:09:4911/4/08 16:09:49
6/72
RCV Resistance heaters with fan
General characteristics:
c Compact resistance heater which prevents the condensation of water and ice inside the enclosures.
c Includes an axial fan to ensure uniform heating inside the enclosure.
c Compact, smaller resistance heater.
c Extruded aluminium body.
c Features an insulated UL94 V0 plastic cover in black to avoid direct contact with the heating elements (PTC) and the aluminium radiator.
c Surface temperature limited to less than 50 °C.
c Fitted with 2.5 mm2 quick-connection terminals.
c Double safety insulated (plastic).
c PTC technology range.
c Quick clip-fixing onto the 35 mm DIN rail (EN 50022).
c Certifications compliant with UL and VDE and EC Marking.
Usage conditions:
c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed).
c The enclosure should be sealed in order to prevent the penetration of external air.
c An electrical protection device should be installed on the supply side of the unit.
Characteristics Reference
RCV170
Heating power at 0 °C 177 W
Power supply voltage 230 V AC 50-60 Hz
Heating element PTC
Surface temperature Max. of 50 ºC in the enclosure, 100 ºC in the upper protection grill (for an external temperature of 20 °C/68 °F)
Service life 40000 h to 40 °C
Airfl ow 13.8 m3/h
Electrical connection 2 poles of 2.5 mm2
Fixing Clip for the 35 mm DIN rail (EN 50022)
Cover Plastic UL94 V0
Operating position Vertical
Operating temperature –40 to +70 °C (–10 to +158 °F)
IP Protection/Class IP20II (double insulation)
Certifi cations VDE and UL in process
RCV170
06_068_079_EN.indd 7206_068_079_EN.indd 72 11/4/08 16:09:5111/4/08 16:09:51
6/73
RCV Resistance heaters with fan
FIG. 1
RCV170
Dimensions (mm)
06_068_079_EN.indd 7306_068_079_EN.indd 73 11/4/08 16:09:5611/4/08 16:09:56
6/74
Standard heating resistorsTraditional convection
06_068_079_EN.indd 7406_068_079_EN.indd 74 11/4/08 16:09:5711/4/08 16:09:57
6/75
The Himel heating resistors for electrical or electronic enclosures are equipped with PTC-type heating elements (Positive Temperature Coeffi cient). The use of these semi-conductors as heating elements means that: c The aluminium surface
temperature of the diffuser stabilises at +75 ºC (for an ambient temperature of –5 ºC).
c Electrical energy consumption is reduced.
The design of the profi le of the Himel heating resistors produces a “chimney” effect. Thus, a uniform temperature is achieved inside the enclosure.The resistors are secured by means of fast-fi xing clips on the 35 mm DIN rails.
The 10 and 20 W resistors are equipped with a 2 � 0.75 � 300 mm electrical connection cable.
Higher power resistors are equipped with fast-connection terminals.
Their broad range of powers, from 10 to 400 W, means that any solution is possible.Models from 250 and 400 W with a built-in fan.
06_068_079_EN.indd 7506_068_079_EN.indd 75 11/4/08 16:09:5911/4/08 16:09:59
6/76
RESISTANCE HEATERS
Selection guide
RESISTANCE HEATERS
Reference Power (W) Voltage (V)
Connection type
Terminal block Cable
RC10/12-36 10 12-36 DC X
RC10 10 110-250 AC X
RC20/12-36 20 12-36 DC X
RC20 20 110-250 AC X
RC20/270-420 20 270-420 AC X
RC55/12-36 55 12-36 DC X
RC55 55 110-250 AC X
RC55/270-420 55 270-420 AC X
RC100/12-36 90 12-36 DC X
RC100 90 110-250 AC X
RC100/270-420 90 270-420 AC X
RC150/12-36 150 12-36 DC X
RC150 150 110-250 AC X
RC150/270-420 150 270-420 AC X
06_068_079_EN.indd 7606_068_079_EN.indd 76 11/4/08 16:10:0611/4/08 16:10:06
6/77
RESISTANCE HEATERS
Selection guide
References Power (W) Voltage (V)
Connection type
Terminal block Cable
RCV250 250 230 AC X
RCV400 400 230 AC X
RCV200P/115 200 115 AC X
RCV200P 200 230 AC X
RESISTANCE HEATERS WITH FAN
06_068_079_EN.indd 7706_068_079_EN.indd 77 11/4/08 16:10:0611/4/08 16:10:06
6/78
RC / RCV / TMV Resistance heaters
Resistance heaters
c Range of resistance heaters from 10 to 400 W ensuring the proper heating of the enclosure to prevent condensation.
General characteristics:
c Extruded aluminium body.
c Surface temperature limited to less than 75 °C with an ambient temperature of –5 °C.
c 500 mm-long power supply cable with silicone insulation (except for the RCV400, R55, 90 and 150 models, which are equipped with a connection terminal block).
Usage conditions:
c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed).
c The enclosure should be sealed in order to prevent the penetration of exter-nal air.
c The electrical protection devices must be installed between the supply source and the resistance heaters themselves.
Reference Power (W) Voltage (V) Start-up current (A) Nominal current (A) Class Dimensions (mm)
RC10/12-36 10 12-36 DC II 25 � 50 � 50
RC10 10 110-250 AC 0.80 0.60 II 25 � 50 � 50
RC20/12-36 20 12-36 DC II 25 � 50 � 75
RC20 20 110-250 AC 1 1.05 II 25 � 50 � 75
RC20/270-420 20 270-420 AC II 25 � 50 � 75
RC55/12-36 55 12-36 DC II 70 � 50 � 140
RC55 55 110-250 AC 1.50 0.24 II 70 � 50 � 140
RC55/270-420 55 270-420 AC II 70 � 50 � 140
RC90/12-36 90 12-36 DC II 70 � 50 � 140
RC90 90 110-250 AC 2.40 0.40 II 70 � 50 � 140
RC90/270-420 90 270-420 AC II 70 � 50 � 140
RC150/12-36 150 12-36 DC II 70 � 50 � 220
RC150 150 110-250 AC 4.50 0.65 II 70 � 50 � 220
RC150/270-420 150 270-420 AC II 70 � 50 � 220
RC250 250 220-230 1.10 1.10 II 70 � 50 � 220
RC400 400 220-230 1.70 1.70 II 70 � 50 � 220
06_068_079_EN.indd 7806_068_079_EN.indd 78 11/4/08 16:10:0611/4/08 16:10:06
6/79
RC / RCV / TMV Resistance heaters
Reference Power (W) Voltage (V)Start-up
current (A)Nominal
current (A)Class Dimensions (mm)
RCV250 250 230 CA 1.20 1.20 I 180 � 85 � 95
RCV400 400 230 CA 1.80 1.80 I 80 � 80 � 248
Reference Power (W) Voltage (V)Start-up
current (A)Nominal
current (A)Class Dimensions (mm)
RCV200P 200 230 CA - 0.90 I 120 � 120 � 47
RCV200P/115 200 115 CA - 1.80 I 120 � 120 � 47
Reference Power ( W) Voltage (V) Dimensions (mm)
TMV350 350 230 CA 200 � 45 � 180
TMV350/550 400/550 230 CA 180 � 85 � 95
TMV350-550/120 400/550 120 CA 180 � 85 � 95
Resistance heaters with fan
c The fan maintains an even temperature inside the electric switchboard.
Plain resistance heater with fan
Thermofans
c This device combines a the heating power of a resistor with the operation of an axial fan, offering optimal heat distribution inside the enclosure.
c Fixing onto a DIN rail.
c Adjustable temperature from 10 to 50 °C for TMV350, and from 0 to 60 °C for TMV350/550.
c Power-on indicator lamp.TMV350
TMV350/550
06_068_079_EN.indd 7906_068_079_EN.indd 79 11/4/08 16:10:0711/4/08 16:10:07
6/80
Control devicesTemperature under control
Compact thermostats (adjustable)
NO (blue button): with normally open contact, when the temperature increases, the contact closes, activating the fan to extract the heat. NC (red button): with normally closed contact, when the temperature falls below the preset value, the contact closes, activating the resistance heater to prevent condensation.c Broad range of temperature control.c Small size.c Simple fi xing by clip onto the 35 mm DIN rail.c Easy access terminals.c High-power connection.
24 V DC electronic thermostat (adjustable)
It can control 24 V direct-current electrical equipment by means of a potential-free inverter contact. Resistors, fan, etc. may be connected.They have a PTC temperature probe for more precise control and low hysteresis.c High DC switching capacity.c Low hysteresis (greater temperature precision).c Switching by means of an inverter contact.c Simple fi xing by clip onto the 35 mm DIN/EN rail.
Dual thermostat (adjustable)
To control two units independently and simultaneously: a resistance heater and a fan.NC (red button): normally closed contact (NC) for resistance heater control. NO (blue button): normally open contact (NO) for fan control.c Double thermostats in the same housing, with separate adjustment and operation.c Easy access terminals.c Simple fi xing by clip onto the 35 mm DIN rail.
NO/NC Thermostat (adjustable)
Its NO/NC inverter contact controls a resistance heater or a fan.c Switching by means of two NO/NC contacts.c Simple fi xing by clip onto the 35 mm DIN rail.c Easy access terminals.c High-power connection.
Selection guide
06_080_083_EN.indd 8006_080_083_EN.indd 80 2/4/08 13:37:242/4/08 13:37:24
6/81
Hygrostat (adjustable)
It is used to adjust the relative humidity in the enclosure by controlling resistance heaters or fans.The hygrostat prevents condensation and the corrosion of components.c Adjustable relative humidity. c Switching by means of an inverter contact.c Simple fi xing by clip onto the 35 mm DIN rail.c Easy access terminals.c High-power connection.
Compact fi xed thermostats
c Preset factory temperature: v Red button: 5, 10 and 15 °C.v Blue button: 25, 30 and 35 °C.c Small size.c Simple fi xing by clip onto the 35 mm DIN rail.c Easy access terminals.c High-power connection.
Fixed dual thermostat
c To control two units independently and simultaneously:v NO/NC: fan and resistor.v NO/NO: fan and alarm.v NC /NC: resistance and alarm.c Preset factory values.c Double thermostats in the same housing, with separate operation.c Easy access terminals.c Simple fi xing by clip onto the 35 mm DIN rail.
Fixed hygrostat
c Factory-adjusted relative humidity: 60% RH.c Switching by means of an NO contact.c Simple fi xing by clip onto the 35 mm DIN rail.c Easy access terminals.c High-power connection.
Hygrometer (adjustable)
Combination of thermostat and hygrostat in the same unit to control relative humidity.The resistance heaters or fans are switched on when the two limit values are exceeded. c Adjustable temperature and relative humidity of the air.c High switching capacity.c Visual operation indication.c Simple fi xing by clip onto the 35 mm DIN rail.c Easy access terminals.
06_080_083_EN.indd 8106_080_083_EN.indd 81 2/4/08 13:37:372/4/08 13:37:37
6/82
CONTROL DEVICES
Selection guide
DOUBLE THERMOSTAT
ReferencesPower supply
voltage(V)
ControlContact
typeApplication
Control element
Switching power
(ohmic load)
TDS1401 - °C NC+NO
Resistance heaters and ventilation systems
Bimetal250 V AC 10 A120 V AC 15 A
ELECTRONIC THERMOSTAT
ReferencesPower supply
voltage(V)
ControlContact
typeApplication
Control element
Switching power
(ohmic load)
TSE200 24 DC °C 2 � NO
Resistance heaters and ventilation systems
ElectronicNO or NC:24 V DC 2 � 8 A
FIXED THERMOSTAT
ReferencesFixed
adjustmentContact type Application
Switching power (ohmic load)
TS140F5 5 °C/41 °F NC
Resistance heaters 250 V AC 10 A120 V AC 15 A
DC 30 WTS140F10 10 °C/50 °F NC
TS140F15 15 °C/59 °F NC
TS141F25 25 °C/77 °F NO
Ventilation systems250 V AC 10 A120 V AC 15 A
DC 30 WTS141F30 30 °C/86 °F NO
TS141F35 35 °C/95 °F NO
THERMOSTATS
ReferencesPower supply
voltage (V)
ControlContact
typeApplication
Control element
Switching power
(ohmic load)
TS140
-
°C NC Resistance heaters
Bimetal
30 W DC250 V AC 10 A120 V AC 15 A
TS140F °F NC
TS141 °C NOVentilation systems
TS141F °F NO
TS170 °C Switch
Resistance heaters or ventilation systems
250 V AC 10 A
06_080_083_EN.indd 8206_080_083_EN.indd 82 2/4/08 13:37:532/4/08 13:37:53
6/83
CONTROL DEVICES
Selection guide
FIXED DUAL THERMOSTAT
References Fixed adjustment Contact typeSwitching
power (ohmic load)
TSD1401F10/3510 °C/50 °F35 °C/95 °F
NCNO
250 V AC 10 A120 V AC 15 A
DC 30 WTSD1401F35/45
35 °C/95 °F45 °C/113 °F
NONO
TSD1401F5/155 °C/41 °F15 °C/59 °F
NCNC
HYGROMETER
ReferencesPower supply
voltage (V)
ControlContact
typeApplication
Control element
Switching power
(ohmic load)
THS3000 230 CA % RH, °C Switch
Resistance heaters and ventilation systems
Bimetal240 V AC 8 A120 V AC 8 A
FIXED HYGROSTAT
References Fixed adjustment Contact typeMax. control
current
HS300F60 60% RH Switch250 V AC 5 A
DC 20 W
HYGROSTAT
ReferencesPower supply
voltage (V)
ControlContact
typeApplication
Control element
Switching power (ohmic
load)
HS300 - % RH Switch
Resistance heaters and ventilation systems
Bimetal230 V AC 5 A
06_080_083_EN.indd 8306_080_083_EN.indd 83 2/4/08 13:37:592/4/08 13:37:59
carga
L N
2
1
V
Carga = resistencia
υ
6/84
TS Control devices
Thermostat TS140
c Thermostat (normally closed contact (NC) for the control of resistance heaters.
c Thermostat use increases service life of resistors, switching them only when required by the temperature.
c Fixing onto a DIN rail.
c IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Adjustable temperature from 0 to 60 °C.
c Connection: 2 x 2.5 mm2 terminals.
Technical specifi cations
Sensor element Bimetal
Contact type Normally closed (NC), snap action contact
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
250 V AC 10 A (ohmic load)120 V AC 15 A (ohmic load)250/120 V AC 2 A (inductive load cos � = 0.6) DC 30 W
Connection Terminals with two 2.5 mm poles
Mounting Clip for the 35 mm DIN rail , EN 50022
Cover V0 thermoplastic UL94, light grey
Dimensions 60 � 33 � 43 mm
Weight 40 g
Fitting position Non-defi ned
Operating temperature –20 to +80 °C (–4 to +176 °F)
Degree of protection IP20
Hysteresis 7 °K
Adjustable temperature From 0 to 60 °C
Reference Dimensions (mm) Max. control current
TS140 60 � 33 � 43 250 V 10 A
TS140F 60 � 33 � 43 250 V 10 A
FIG. 1
Load = resistance
load
06_084_095_EN.indd 8406_084_095_EN.indd 84 2/4/08 13:39:192/4/08 13:39:19
L N
2
1
V υ
carga
Carga = ventilador
6/85
TS Control devices
Thermostat TS141
c Thermostat (normally open – NO contact) for control of fans.
c This thermostat allows the regulation of temperature in the enclosure, starting the fan only in case fresh air is required. As a result, service life of the fan is increased and its filter stays cleaner.
c DIN rail fixing.
c Degree of protection IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Adjustable temperature from 0 to 60 ºC.
c Connection: 2 � 2.5 mm2 terminals.
FIG. 1Technical specifi cations
Sensor element Bimetal
Contact type Normally open (NO), snap action contact
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
250 V AC 10 A (ohmic load)120 V AC 15 A (ohmic load)250/120 V AC 2 A (inductive load cos � = 0.6) DC 30 W
Connection Terminals with two 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 60 � 33 � 43 mm
Weight 40 g
Fitting position Non-defi ned
Operating temperature –20 to +80 °C (–4 to +176 °F)
Degree of protection IP20
Hysteresis 7 °K
Adjustable temperature From 0 to 60 °C
Reference Dimensions (mm) Max. control current
TS141 60 � 33 � 43 250 V 10 A
TS141F 60 � 33 � 43 250 V 10 A
Load = fan
load
06_084_095_EN.indd 8506_084_095_EN.indd 85 2/4/08 13:39:212/4/08 13:39:21
6/86
TS Control devices
Load 2
Load 3
Load (2) =resistanceLoad (3) = fan
> �
L N
Thermostat TS170
c Thermostat (contact switch) to control the fan or resistance heaters.
c With this device, the internal temperature of the panel may be regulated by switching on a resistor or a fan.
c Fixing on a DIN rail.
c IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Adjustable temperature from 10 to 60 °C.
c Connection: 4 � 2.5 mm2 terminals.
FIG. 1Technical specifi cations
Sensor element Bimetal
Contact type Switch contact, snap action
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity 250 V AC 10 A (ohmic load)
Max. opening contact250 V AC 4 A (inductive load cos � = 0.6)DC 30 W
Connection Terminals with four 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 67 � 50 � 44 mm
Weight 100 g
Fitting position Non-defi ned
Operating temperature –20 to +80 °C (–4 to +176 °F)
Degree of protection IP20
Hysteresis 7 °K
Adjustable temperature From 5 to 60 °C
Reference Dimensions (mm) Max. control current
TS170 67 � 50 � 44 (NA) 5 A/(NC) 10 A
06_084_095_EN.indd 8606_084_095_EN.indd 86 2/4/08 13:39:232/4/08 13:39:23
6/87
TS Control devices
N2 L2
N1 L1 11
12
23
24
V
V
B
A
Dual thermostat TSD1401
c Dual temperature regulator.
c Two thermostats in one single enclosure.
c Separate control and operation.
c Fixing clip for the 35 mm DIN rail.
c IP20.
c Dual thermostat (two thermostats in one single box). With the red button (normally closed contact- NC), the resistance heater can be regulated. A fan, signalling system or alarm can be controlled with the blue button (normally open contact- NO).
This thermostat allows the simultaneous control of a resistance heater and a fan, making an independent temperature adjustment possible.
FIG. 1Technical specifi cations
Sensor element Bimetal
Contact type 1 normally open (NO), 1 normally closed (NC), snap action
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
250 V AC 10 A (ohmic load)120 V AC 15 A (ohmic load)250/120 V AC 2 A (inductive load cos � = 0,6)DC 30 W
Connection Terminals with six 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 67 � 50 � 44 mm
Weight 90 g
Fitting position Non-defi ned
Operating temperature –20 to +80 °C (–4 to +176 °F)
Degree of protection IP20
Hysteresis 7 °K
Adjustable temperature From 0 to 60 °C
Reference Dimensions (mm) Max. control current
TSD1401 67 � 50 � 44250 V AC 10 A120 V AC 15 A
06_084_095_EN.indd 8706_084_095_EN.indd 87 2/4/08 13:39:262/4/08 13:39:26
6/88
TS Control devices
+24 V
11
_
+
21
22
12
V
Thermostat TSE200
c Electronic temperature regulator.
c 24 V DC supply.
c Fixing by clip for 35 mm DIN rail.
c IP20.
c Thermostat with volt-free 2 dry contact switching relay.
c Allows high number of switching operations with improved temperature accuracy (± 2 °K) thanks to its PTC probe.
c The miniature communication relays installed in the thermostat are powerful (230 A) and safe.
c Possibility of having a thermostat with open-contact switches or inverted switches.
FIG. 1Technical specifi cations
Adjustable temperature From 0 to +60 °C
Hysteresis 2 °K ± 2 °K
Sensor element PTC probe
Connection Terminals with six 2.5 mm2 poles
Contact type 2 normally open (NO), snap action contact
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover ABS according to UL94 V0
Operating temperature 0 to +60 °C (–32 to +140 °F)
Degree of protection IP20
Dimensions 67 � 50 � 44 mm
Weight 80 g
Reference Dimensions (mm) Max. rated current
TSE200 67 � 50 � 44NA o NC:
24 V DC 2 � 8 A
06_084_095_EN.indd 8806_084_095_EN.indd 88 2/4/08 13:39:292/4/08 13:39:29
6/89
TS Control devices
carga
L N
2
1
V
Carga = resistencia
υ
Load = resistance
Load 1
Fixed thermostats TS140F
c Thermostat (normally closed contact - NC) to control resistance heaters.
c DIN rail fixing.
c Degree of protection IP20.
c V0 self-extinguishing thermoplastic material as per UL94.
c Factory-adjusted temperature.
c Connection: 2 � 2.5 mm2 terminals.
FIG. 1Technical specifi cations
Sensor element Bimetal
Contact typeNormally closed (NC), snap action contact Normally closed (NC), snap action contact
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
250 V AC 10 A (ohmic load)120 V AC 15 A (ohmic load)250/120 V AC 2 A(inductive load cos � = 0.6) DC 30 W
Connection Terminals with two 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail 35 mm, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 60 � 33 � 43 mm
Weight 40 g
Fitting position Non-defi ned
Operating temperature –20 to +80 °C (–4 to +176 °F)
Degree of protection IP20
Reference Fixed adjustment Max. control current
TS140F5 5 °C/41 °F250 V AC 10 A 120 V AC 15 A
DC 30 WTS140F10 10 °C/50 °F
TS140F15 15 °C/59 °F
06_084_095_EN.indd 8906_084_095_EN.indd 89 2/4/08 13:39:322/4/08 13:39:32
6/90
TS Control devices
L N
2
1
V υ
carga
Carga = ventilador
Fixed thermostats TS141F
c Thermostat (normally open - NO contact) to control fans.
c Degree of protection IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Factory-adjusted temperature.
c Connection: 2 � 2.5 mm2 terminals.
c DIN rail fixing.
FIG. 1Technical specifi cations
Sensor element Bimetal
Contact type Normally open (NO), snap action contact
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
250 V AC 10 A (ohmic load)120 V AC 15 A (ohmic load)250/120 V AC 2 A (inductive load cos � = 0.6) DC 30 W
Connection Terminals with two 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 60 � 33 � 43 mm
Weight 40 g
Fitting position Non-defi ned
Operating temperature –20 to + 80 °C (–4 to +176 °F)
Degree of protection IP20
Hysteresis 7 °K
Reference Fixed adjustment Max. control current
TS141F25 25 °C/77 °F 250 V AC 10 A 120 V AC 15 A
DC 30 WTS141F30 30 °C/86 °F
TS141F35 35 °C/95 °F
Load = fan
06_084_095_EN.indd 9006_084_095_EN.indd 90 2/4/08 13:39:352/4/08 13:39:35
6/91
TS Control devices
N2 L2
N1 L1 11
12
23
24
V
V
B
A
Fixed dual thermostat TSD1401F
c Dual temperature regulator.
c Two thermostat in one enclosure with separated setting and operation.
c 35 mm DIN rail clip fixing.
c Factory-adjusted temperature.
c This unit allows trip control of a fan and a resistance heater, independent setting and operation.
FIG. 1
Technical specifi cations
Sensor element Bimetal
Contact type Snap action
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
250 V AC 10 A (ohmic load)120 V AC 15 A (ohmic load)250/120 V AC 2 A (inductive load cos � = 0.6)DC 30 W
Connection Terminals with six 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 67 � 50 � 44 mm
Weight 90 g
Fitting position Non-defi ned
Operating temperature –20 to +80 °C (–4 to +176 °F)
Degree of protection IP20
Hysteresis 7 °K
Reference Contact type Fixed adjustment
TSD1401F10/35NC:NO:
10 ºC/50 ºF
35 ºC/95 ºF
TSD1401F35/45NO:NO:
35 ºC/95 ºF
45 ºC/113 ºF
TSD1401F5/15NC:NC:
5 ºC/41 ºF
15 ºC/59 ºF
06_084_095_EN.indd 9106_084_095_EN.indd 91 2/4/08 13:39:382/4/08 13:39:38
6/92
TS Control devices
L230 V50 Hz
T°RH
N
1 2 3 4 5
CargaLoad
Hygrometer THS3000
c The device independently measures the temperature and humidity within the electrical enclosure. The resistance heater is switched on when either of the limiting values set for the two parameters is exceeded: the temperature rises and the relative humidity RH falls. The hygrometer switch should be preferably be installed in the upper part of the enclosure at a minimum distance of 50 cm from the resistance heater.
c DIN rail fixing.
c Degree of protection IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Adjustable temperature from 0 to 60 ºC.
c Adjsutable relative humidity from 50 to 90%.
c Hysteresis: 2 °C, 3% RH.
c Service life: >100000 cycles.
FIG. 1
Technical specifi cations
Power supply voltage 230 V AC 50/60 Hz
Switching precision Temperature 2 °K (±1 °K)
Switching precision Humidity 4% (±1%)
Response time Approx. 160 sec.
Contact type Switch
Contact resistance < 10 m�
Service life > 100000 cycles
Max. switching capacity
240 V AC 8 A (ohmic load)240/120 V AC 4 A (inductive load cos � = 0.6)240 V DC 0.1 A48 V DC 0.8 A24 V DC 8 A
Connection Terminals with fi ve 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 67 � 50 � 43 mm
Weight 200 g
Fitting position Vertical
Operating temperature –20 to +60 °C (–4 to +140 °F)
Degree of protection IP20
Power-on indicator LED
Reference Dimensions (mm) Max. control current
THS3000 67 � 50 � 43 250 V AC 8 A12 V DC 8 A35 V DC 5 A
06_084_095_EN.indd 9206_084_095_EN.indd 92 2/4/08 13:39:412/4/08 13:39:41
6/93
TS Control devices
carga 1
L N
3
1
4carga 2
V
Carga 1 = resistencia (deshumidificador)Carga 2 = humidificador
ϕ
Load 1 = resistance (dehumidifi er) Load 2 = humidifi er
Load 1
Load 2
Hygrostat HS300
c This device only measures the relative humidity inside the enclosure.
c It is used to switch on the resistance heater when the humidity rises above the set value.
c DIN rail fixing.
c Degree of protection IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Adjustable relative humidity from 30 to 90%.
FIG. 1
Reference Dimensions (mm) Max. control current
HS300 67 � 50 � 37 250 V AC 5 A
Technical specifi cations
Control 35% to 95% RH
Switching precision Humidity 4% (±3%)
Permissible air velocity 15 m/sec
Contact type Switch
Contact resistance < 10 m�
Service life 50000 cycles
Min. switching power 20 V AC/DC 100 mA
Max. switching capacity
230 V AC 5 A (ohmic load)230/120 V AC 0.2 A (inductive load cos Ø = 0.650 V DC 1 A/75 V DC 0.5 A (inductive load L/R = 3 ms)
Connection Terminals with three 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail , EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 67 � 50 � 37 mm
Weight 100 g
Fitting position Non-defi ned
Operating temperature –20 to +60 °C (–4 to +140 °F)
Degree of protection IP20
06_084_095_EN.indd 9306_084_095_EN.indd 93 2/4/08 13:39:422/4/08 13:39:42
carga 1
L N
3
1
4carga 2
V
Carga 1 = resistencia (deshumidificador)Carga 2 = humidificador
ϕ
Load 1 = resistance (dehumidifi er) Load 2 = humidifi er
6/94
TS Control devices
Fixed hygrostat HS300F
c This device only measures the relative humidity inside the enclosure.
c It can be used to start up a resistance heater when this relative humidity exceeds the preset value.
c DIN rail fixing.
c Degree of protection IP20.
c V0 self-extinguishing thermoplastic as per UL94.
c Factory-adjusted relative humidity.
FIG. 1Technical specifi cations
Switching precision Humidity 4% (±3%)
Permissible air velocity 15 m/sec
Contact type Switch
Contact resistance < 10 m�
Service life 50000 cycles
Min. switching power 20 V AC/DC 100 mA
Max. switching capacity250 V AC 5 A (ohmic load)250 V AC 0,2 A (inductive load cos � = 0.6)DC 20 W
Connection Terminals with three 2.5 mm2 poles
Mounting Clip for the 35 mm DIN rail, EN 50022
Cover V0 UL94 thermoplastic, light grey
Dimensions 67 � 50 � 37 mm
Weight 100 g
Fitting position Non-defi ned
Operating temperature –20 to +60 °C (–4 to +140 °F)
Degree of protection IP20
Reference Fixed adjustment Max. control current
HS300F60 60% RH250 V AC 5 A
DC 20 W
06_084_095_EN.indd 9406_084_095_EN.indd 94 2/4/08 13:39:452/4/08 13:39:45
At = ambient temperature.Dt = internal desired temperature.
If At > Dt If At < Dt
6/95
HEAT CALCULATION Thermal management for electrical control panels
To air
Natural dissipation (through the enclosure walls).
In some cases, using a larger enclosure can solve the heating problem.
Natural ventilation
Providing fresh exterior air through ventilation outlet grilles improves heat dissipation through natural convection.
Nevertheless, this solution can only be used in low-dust environments when the power to be dissipated is low.
Due to the miniaturisation of the components, the generalisation of electronics, and the appearance of new electronically-based power products, temperature control has become an increasingly important necessity that must be taken into account when designing electrical and/or electronic control panels, as is being done with the IP degree of protection.
Reliability and the search for minimal breakdown rates are two determining factors in process industries where hourly operation costs for the installa-tions are extremely high; the smallest breakdown can immediately result in losses totalling hundreds of thousands of pesetas. The service life of the components depends on the temperature and humidity conditions in the enclosure.
The solutions to these problems are varied, and can depend on environ-mental conditions, the type of components in the electrical control panel and, of course, their cost!
In certain cases, it is enough to oversize the enclosure or to use fans. In other cases, where ambient temperatures are higher, heat exchangers or cooling units must be used.
Himel offers a wide range of solutions adapted to all situations.
06_084_095_EN.indd 9506_084_095_EN.indd 95 2/4/08 13:39:482/4/08 13:39:48
6/96
HEAT CALCULATION Thermal management for electrical control panels
Ventilation
Using a fan to circulate air within the enclosure can even out the temperature and prevent hot spots which could be harmful to certain components.
Forced ventilation
HIMEL fans are designed to remove large quantities of heat generated by electrical control panel components. This signifi cantly increases component longevity, thus ensuring the durability and correct operation of the installation.
The fans, which are easy to install and maintain, as well as economical, are an effective solution to the problem of rising temperatures in electrical control panels.
Due to their IP degree of protection, they can be used both in industrial environments and in the tertiary sector.
Air/air exchangers
HIMEL air-air exchangers combine performance and simplicity: the movement of hot air from the enclosure and cool air from the surrounding environment by means of two fans circulating on either side of sealed divider walls prevents dust and humidity from penetrating the enclosure. Warm air from the panel heats these walls, which are then cooled by the colder external air. The heat transfer always takes place from the warmer to the cooler area. For this reason, these devices can only be used if the ambient temperature is at least 5ºC lower than the required internal temperature of the enclosure.
The aluminium exchange battery is at the heart of the system. This element can be cleaned as it is easily removed.
In addition, the continuous operation of an internal fan prevents hot spots in the electrical control panel. The temperature is regulated by switching the external circuit fan on and off.
To ventilate
To cool
Undesired effects on the components installed in poorly-cooled environments.
06_096_107_EN.indd 9606_096_107_EN.indd 96 2/4/08 13:40:302/4/08 13:40:30
6/97
HEAT CALCULATION Thermal management for electrical control panels
To cool
Air/water exchangers
The operating principle of HIMEL air/water exchangers is similar to that of the air/air exchangers: the cool external air is replaced by cold water supplied by the piping of the installation itself on the industrial site.
Due to this fl uid exchange, much larger quantities of heat can be removed, and the temperature within the electrical control panel can be adjusted to below that of the ambient air.
Temperature within the panel is regulated by modulating the water fl ow.
The water circuit is protected by a supply shut-off device ensuring the safety of your electrical installation.
Cooling units
HIMEL cooling units can be used in the most severe environments, where temperatures can reach 55ºC. These units are particularly suitable when the required temperature of the enclosure must be lower than the ambient temperature, or when large quantities of heat must be removed. As in the case of the exchangers, they do not affect the IP rating of the panel.
Due to the fi lter located at the intake of the external air circuit, they can operate even when the ambient air is very dusty or greasy. This device is easy to replace and ensures that the effi ciency of the equipment is maintained throughout its entire service life.
The cooling units have an enclosure temperature control system and an alarm function which is triggered in the event of a malfunction.
Resistance heaters
There are two reasons to use resistance heaters:
c To heat the electrical control enclosure when the ambient temperature is too low for the components to operate correctly.
c To prevent water condensation from forming.
Condensation can cause short circuits, premature contact oxidation, corrosion of metal parts (particularly those of the enclosure), and it can signifi cantly reduce the service life of electrical and electronic components.
Condensation occurs when the temperature quickly drops below the dew point. This can be prevented by simply maintaining the temperature within the enclosure at a few degrees above the ambient temperature.
The design of the HIMEL heaters facilitates natural convection and ensures a both uniform and rapid heating of the enclosure.
To heat
06_096_107_EN.indd 9706_096_107_EN.indd 97 2/4/08 13:40:342/4/08 13:40:34
6/98
HEAT CALCULATION Thermal calculation and mounting suggestions
The temperature control calculation consists of comparing the power dissipated by the operating components with the power exchanged spontaneously by the enclosure walls. It enables calculation of the internal temperature in the enclosure without use of a temperature control system and therefore determination of whether or not one should be installed, taking into account the required external and internal temperatures.
The following presents a simple method of making such a selection.
Example: OLN Ref.: OLN208/40Height = 2000Width = 800Depth = 400
S = m2
Installation type: enclosure placed against a wall.
S = 4.13 m2
Enclosure position
Placement as specifi ed by IEC 890
Formula for calculation of S (m2)
(A)Height
(B)Width
(C)Depth
Accessible from all sides S = 1.8 � A � (B+C) + 1.4 � B � C
Placed against a wall. S = 1.4 � B � (A+C) + 1.8 � C � A
End, in the case of coupling S = 1.4 � C � (A+B) + 1.8 � B � A
End, in the case of coupling and placed against a wall
S = 1.4 � A � (B+C) + 1.4 � B � C
Intermediate in the case of coupling S = 1.8 3 B 3 A + 1.4 3 B 3 C + C 3 A
Intermediate in the case of coupling and placed against a wall
S = 1.4 � B � (A+C) + C � A
Intermediate in the case of coupling and placed against a wall with the upper part covered
S = 1.4 � B � A + 0.7 � B � C + C � A
1 ENCLOSURE CHARACTERISTICS
This is obtained by totalling the power dissipated by each component installed.
If the individual values are unknown, use the tables on page which provide average values.
Pd = W
Assume that the compo-nents dissipate 800 W.
Pd = 800 W
2 POWER DISSIPATED BY OPERATING COMPONENTS
These are characterised by the type of components and the characteristics of the ambient air.
Maximum internal temperature (desired).
Minimun internal temperature (desired).
4 REQUIRED INTERNAL AVERAGE TEMPERATURES
Tdmín = °C
Tdmax = °C
Tdmax = 40 °C
Tdmín = 15 °C
PdK � S
5 FINAL ENCLOSURE TEMPERATURE WITHOUT TEMPERATURE CONTROL SYSTEM
Maximum internal temperature Timax = + Temax
Minimun internal temperature Timin = Temin
(voltage-free panel).
K = 5.5 W/m2 ºK for a metal enclosure.K = 3.5 W/m2 ºK for a polyester enclosure.K = 3.7 W/m2 ºK for a stainless steel enclosure.K = 12 W/m2 ºK for an aluminium enclosure.
Cooling is required
Timín = °C
Timax = °CTimax = 70 °C
Timín = 15 °C
Maximum ambient temperature.
Minimum ambient temperature.
Average relative humidity.
Temperature conditions are as follows:
3 CHARACTERISTICS OF AMBIENT AIR
Temax = °C
Temín = °C
Temax = 35 °C
Temín = 15 °C
Determining the temperature control equipment
06_096_107_EN.indd 9806_096_107_EN.indd 98 2/4/08 13:40:392/4/08 13:40:39
6/99
HEAT CALCULATION Thermal calculation and mounting suggestions
Tdmín < Timín Tdmín > Timín Tdmax < Timax Tdmax > Timax
Temperature control system not required,
but circulation fan could be installed to
even out temperature.
Temperature control system required:
resistance heater.
1 Permanent switchboard operation
Psyst = K � S (Tdmín – Te mín) – Pd
2 Intermittent operation:
Psyst = K � S (Tdmín – Te mín)
Temperature control system required: either fan, exchanger or cooling unit.
Psis = Pd – K � S (Tdmax – Te max)
Psis = 800 – 5.5 � 4.13 � (40 – 35) ± 690 W
Temperature control system not required, but a
circulation fan could be installed to eliminate hot
spots.
Ventilating
Temperature conditions Solution Advantages of solution Constraints of solution
Avoid hot spots. Install circulation fans in the enclosure. Highly economical maintenance-free
solution. Simple installation. Installation IP
maintained.
Quantity of heat removed is relatively low.
Cooling
Temperature conditions Solution Advantages of solution Constraints of solution
Final temperature required in the enclosure
Ts (max) at least 5 °C higher than the
maximum ambient temperature Te (max).
Td max ≥ Te max + 5 °C
Oversize the enclosure. Economical maintenance-free solution.
Simple installation. Installation IP
maintained.
Quantity of heat removed is relatively low.
Increased dimensions.
Install ventilation louvres. Highly economical maintenance-free
solution. Simple installation.
Quantity of heat removed is low, depending on
arrangement of components. IP downgraded
(dust penetration).
Install fresh air inlet fans. Economical maintenance-free solution,
simple to install. Quantity of heat removed
high. Temperature control possible.
Regular fi lter maintenance. IP slightly
downgraded.
Use an air/air exchanger. Simple installation. Installation IP
maintained. Temperature control as
standard. Simple maintenance.
Regular fi lter maintenance.
Final temperature required in the enclosure
Ts (max) at least 5 ºC lower than the
maximun ambient temperature Te (max).
Td max ≤ Te max + 5 °C
Use a cooling unit. Simple installation. Enables evacuation
of large quantities of heat, even when
ambient temperature is high. Installation IP
maintain. Temperature regulation.
Regular fi lter maintenance. Can not be used
above ambient temperature 55 °C.
Use an air/water exchanger. Simple installation. Enables evacuation
of large quantities of heat, even when
ambient temperature is high. Installation IP
maintain. Temperature control as standard.
No fi lter to maintain.
Water circuit required. Water consumption cost
if mains supply used.
Heating
Temperature conditions Solution Advantages of solution Constraints of solution
External temperature lower than the
minimum temperature admissible by
components.
Condensation risk.
Heating by resistance heater. Economical, reliable.Temperature in
enclosure can be controlled.
Energy consumption. Space occupied in
enclosure.
Heating by resistance heater to maintain
temperature above the dew point
temperature.
Economical, reliable, Humidity in enclosure
can be controlled.
Energy consumption. Space occupied in
enclosure.
6 DETERMINATION OF THE TYPE OF TEMPERATURE CONTROL SYSTEM AND ITS POWER PSYST
D =Psyst
(Tsmax-Temax)� 3.1 m3/h
q =Psyst
(Tsmax-Temax)wk
06_096_107_EN.indd 9906_096_107_EN.indd 99 2/4/08 13:40:392/4/08 13:40:39
6/100
ClimaSys: calculation support servicePROclima 4.0
Results
6 Select the control system (fans, exchangers, etc.).
7 View and print the result.
Printing and drawing up of the thermal study report
Once the calculation has been made, a report can be printed, which details all the calculation data, the results obtained, as well as the equipment recommended to maintain the internal temperature of the enclosure under the conditions indicated.
The report provides the machining template to scale, as well as the dimensions and electrical characteristics of the recommended equipment.
PROclima 4.0
Data entry
Entry of the data for the installation necessary to calculate the “thermal balance”.
The steps to follow are:
1 Input of the project and customer data.
2 Input of the temperature data.
3 Input of the electrical data of the installation (voltage for selecting the solution and intensity for the calculation of the dissipation in the busbars).
4 Input of the power dissipated by the electrical components inside the enclosure; if the programme is not known, provide the means for its calculation:
– By entering the type and quantity of the installed components.
– In the case of manoeuvres during operation, by reading the interior/exterior temperature.
5 Select the enclosure model and the method of installation.
We have developed the PROclima programme to facilitate the calculation and selection of temperature control equipment for enclosures containing electrical or electronic equipment.
The programme calculates the thermal balance inside the enclosure and recommends the most suitable solution based on the values entered.
06_096_107_EN.indd 10006_096_107_EN.indd 100 2/4/08 13:40:402/4/08 13:40:40
6/101
7 View and print the result.
3 Input the electrical data of the installation (compulsory).
4 Input the power dissipated by the electrical components inside the enclosure (compulsory).
1 Input the project and customer data (optional).
2 Input the internal and external temperature data of the enclosures (compulsory).
5 Select the enclosure model and the method of installation (compulsory).
6 Select the control system (fans, exchangers, etc.) (compulsory).
06_096_107_EN.indd 10106_096_107_EN.indd 101 2/4/08 13:40:412/4/08 13:40:41
6/102
HEAT CALCULATION Calculation support software
Calculation and selection assistance software
PROclima software
c Calculation and selection programme for temperature control equipment for enclosures containing electrical or electronic equipment.
c The programme performs the calculations presented on pages 6/98 and 6/99, as well as the dissipation surface areas, based on the dimensions of the enclosure and its position with respect to the walls.
c Available on CD-ROM in two languages: Spanish and English.
c Minimum requirements: PC that is IBM PC 486 SX compatible, 33 MHz, with 8 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA graphics card (640 � 480 pixels).
c Recommended requirements: PC that is IBM Pentium 90 MHz compatible, with 16 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA graphics card (800 � 600 pixels).
c Required components: Microsoft DOS version 5.0 or later, Microsoft Windows version 3.1 or later, Microsoft Windows NT version 3.51.944 or later.
Project phases with the PROclima software
c General project data.
Customer, technical manager, name, place, and date of project.
c Selection of enclosure model.
Range, dimensions, placement.
c Temperature data:
v Minimum and maximum temperatures, possible external temperatures.
v Minimum and maximum temperatures desired inside the enclosure.
v Altitude.
v Relative humidity.
c Dissipated power assessment.
It is theoretically known or can be recreated from a database:
v Enter the dissipated power of the components.
v And/or select all the electrical and electronic elements installed inside the enclosure to then calculate an approximate value.
The thermal balance consists of comparing the energy dissipated by the components of the installation with the energy dissipated spontaneously by the walls of the enclosure.
It makes it possible to defi ne the external temperature of the enclosure without a temperature control element and to justify the installation of equipment.
c Selection of the temperature control element.
A screen makes it possible to select the control system (fan, exchanger, cooling unit, resistance heaters) to proportion with the programme.
After the calculation, the power, specifi cations, and reference numbers of the temperature control element and the respective accessories are needed.The programme provides a project summary that can be printed.
06_096_107_EN.indd 10206_096_107_EN.indd 102 2/4/08 13:40:462/4/08 13:40:46
6/103
HEAT CALCULATION Calculation example
Enclosure characteristicsc Dimensions
Height: 2000 mmWidth: 800 mmDepth: 500 mm
c Location: against a wall c Material: enclosure in painted sheet steel
c Thermal power dissipated by operating componentsPd: 950 W
c Environment and temperature data: Maximum temperature expected outside the enclosure Temax: 25 ºC Minimum temperature expected outside the enclosure Temin: 25 ºC Minimum temperature dissipated inside the enclosure Temax: 35 ºC Minimum temperature dissipated outside the enclosure Temin: 25 ºC
Atmosphere characteristics: little pollution with low dust levels
Selection and calculation: The maximum required temperature (Tsmax) inside the enclosure is 10 ºC higher
than the maximum value expected outside (Timax). It is possible to cool the enclosure using fi ltered ventilation systems.
Calculation of the fan required:
Usage formulas:Psis = Pd – (k � S � (Tsmax – Temax)Flow = f � Psis / (Tdmax – Temax)
Pd: thermal power dissipated by operating components S = 1.4 � L � (H+P) + 1.8 � P � H = 4.6 m2. Conforming to standard IEC 890.
K = Constant defi ned by the material used to construct the enclosure
K = 5.5 W/m2 � ºC for a painted steel sheet enclosureK = 3.5 W/m2 � ºC for a polyester enclosureK = 3.7 W/m2 � ºC for a stainless steel enclosure
0 to 100 m f = 3.1100 to 250 m f = 3.2250 to 500 m f = 3.3
For the calculation, it is necessary to know the altitude above sea level of the installation site:Altitude above sea level: 800 mf = Coeffi cient related to the altitude above sea level (value)
In our example:
Psis = 950 – 5.5 � 4.6 � (35 – 25) = 497 WFlow = 3.5 � 697/(35 – 25) = 244 m3/hSelecting from the quick-selection table of fans1 fan with standard VF300 fi lter + 1 outlet grille with standard FS615 + fi lter
1 thermostat TS141F35They provide a 302 m3/h fl ow rate
The minimum expected exterior temperature is less than the minimum required temperature inside the enclosure.It is necessary to install resistance heaters:
Calculation of the resistance necessary:
Usage formulas:W = 5.5 � 4.6 (15 – 10) = 127 W
In our example:
W = 5.5 � 4.6 (15 – 10) = 127 W
Data
Selecting from the quick-selection table of resistance heaters1 resistance heater Ref. RC150AI + 1 thermostat Ref. TS140F15
500 to 750 m f = 3.4750 to 1000 m f = 3.5
................
06_096_107_EN.indd 10306_096_107_EN.indd 103 2/4/08 13:40:492/4/08 13:40:49
6/104
HEAT CALCULATION
Dissipation surface area
Dissipation surface area of the metal enclosures: CRN-CRNG
Installation mode
Accessible on all sides
Against a wall
At one end of a row
Intermediate in a row, against a wall
Intermediate in a row, against a wall,closed covered top
Intermediate in a row
At one end of a row, against a wall
Enclosure model Dimensions in mm
A B C
Type of installation conforming to IEC 890
CRN / CRNG
Surface areas are expressed in m2.
■ 250 200 150 0.20 0.18 0.18 0.16 0.17 0.15 0.13
■ 300 250 150 0.27 0.24 0.25 0.22 0.23 0.20 0.18
■ 300 250 200 0.31 0.28 0.29 0.26 0.27 0.24 0.20
■ 300 300 150 0.31 0.27 0.29 0.25 0.27 0.23 0.20
■ 300 300 200 0.35 0.32 0.33 0.29 0.31 0.27 0.23
■ 300 400 200 0.44 0.39 0.41 0.40 0.39 0.34 0.28
■ 400 300 150 0.39 0.34 0.36 0.32 0.34 0.29 0.26
■ 400 300 200 0.44 0.40 0.41 0.36 0.38 0.33 0.29
■ 400 400 200 0.54 0.48 0.51 0.45 0.48 0.42 0.36
■ 400 600 250 0.82 0.73 0.78 0.69 0.74 0.65 0.54
■ 400 600 300 0.90 0.80 0.85 0.76 0.80 0.71 0.58
■ 500 400 150 0.58 0.50 0.55 0.47 0.52 0.44 0.40
■ 500 400 200 0.65 0.57 0.61 0.53 0.57 0.49 0.44
■ 500 400 250 0.73 0.65 0.68 0.60 0.63 0.55 0.48
■ 500 500 250 0.85 0.75 0.80 0.70 0.75 0.65 0.56
■ 600 400 150 0.68 0.58 0.64 0.55 0.61 0.51 0.47
■ 600 400 200 0.76 0.66 0.71 0.62 0.66 0.57 0.51
■ 600 400 250 0.84 0.75 0.78 0.69 0.72 0.63 0.56
■ 600 500 150 0.81 0.69 0.77 0.65 0.74 0.62 0.56
■ 600 500 200 0.90 0.78 0.85 0.73 0.80 0.68 0.61
■ 600 500 250 0.99 0.87 0.93 0.81 0.87 0.75 0.66
■ 600 600 250 1.13 0.98 1.07 0.92 1.01 0.86 0.76
■ 600 600 300 1.22 1.08 1.15 1.01 1.08 0.94 0.81
■ 600 800 300 1.52 1.33 1.45 1.36 1.38 1.19 1.02
■ 700 500 200 1.02 0.88 0.97 0.83 0.91 0.77 0.70
■ 700 500 250 1.12 0.98 1.05 0.91 0.98 0.84 0.75
■ 800 600 200 1.32 1.13 1.26 1.06 1.19 1.00 0.92
■ 800 600 250 1.43 1.24 1.35 1.16 1.27 1.08 0.98
■ 800 600 300 1.55 1.36 1.45 1.26 1.36 1.16 1.04
■ 800 800 200 1.66 1.41 1.60 1.34 1.54 1.28 1.17
■ 800 800 300 1.92 1.66 1.82 1.57 1.73 1.47 1.30
■ 800 1000 300 2.29 1.97 1.45 1.36 1.38 1.19 1.02
■ 1000 600 250 1.74 1.50 1.64 1.40 1.54 1.30 1.20
■ 1000 600 300 1.87 1.63 1.75 1.51 1.63 1.39 1.27
1000 800 200 2.02 1.70 1.94 1.62 1.86 1.54 1.43
■ 1000 800 250 2.17 1.85 2.07 1.75 1.97 1.65 1.51
■ 1000 800 300 2.32 2.00 2.20 1.88 2.08 1.76 1.59
■ 1000 1000 300 2.76 2.36 2.64 2.24 2.52 2.12 1.91
■ 1000 1200 300 3.20 2.72 3.08 2.75 2.96 2.48 2.23
■ 1200 800 300 2.71 2.33 2.57 2.18 2.42 2.04 1.87
■ 1200 1000 300 3.23 2.75 3.08 2.60 2.94 2.46 2.25
06_096_107_EN.indd 10406_096_107_EN.indd 104 2/4/08 13:40:492/4/08 13:40:49
6/105
HEAT CALCULATION
Dissipation surface area of the metal enclo-sures: CMO and OLN
Installation mode
Dimensions in mm
A B C
Type of installation conforming to IEC 890Enclosure reference
number
CMO1010/30 1000 1000 300 2.76 2.36 2.64 2.36 2.52 2.12 1.91
CMO128/30 1200 800 300 2.71 2.33 2.57 2.28 2.42 2.04 1.87
CMO1210/30 1200 1000 300 3.23 2.75 3.08 2.72 2.94 2.46 2.25
CMO1212/40 1200 1200 400 4.13 3.55 3.94 3.55 3.74 3.17 2.83
CMO146/30 1400 600 300 2.52 2.18 2.35 2.09 2.18 1.85 1.72
CMO146/40 1400 600 400 2.86 2.52 2.63 2.39 2.41 2.07 1.90
CMO148/30 1400 800 300 3.11 2.66 2.94 2.59 2.77 2.32 2.16
CMO148/40 1400 800 400 3.47 3.02 3.25 2.93 3.02 2.58 2.35
CMO1410/40 1400 1000 400 4.09 3.53 3.86 3.46 3.64 3.08 2.80
CMO1412/40 1400 1200 400 4.70 4.03 4.48 4.00 4.26 3.58 3.25
CMO166/30 1600 600 300 2.84 2.46 2.65 2.34 2.46 2.08 1.95
CMO166/40 1600 600 400 3.22 2.83 2.96 2.67 2.70 2.32 2.15
CMO168/30 1600 800 300 3.50 2.99 3.31 2.90 3.12 2.61 2.44
CMO168/40 1600 800 400 3.90 3.39 3.65 3.26 3.39 2.88 2.66
CMO1610/30 1600 1000 300 4.16 3.52 3.97 3.45 3.78 3.14 2.93
CMO1610/40 1600 1000 400 4.95 3.95 4.34 3.86 4.08 3.44 3.16
CMO1612/30 1600 1200 300 4.82 4.06 4.63 4.01 4.44 3.67 3.42
CMO1612/40 1600 1200 400 5.28 4.51 5.02 4.45 4.77 4.00 3.66
CMO186/30 1800 600 300 3.17 2.74 2.95 2.59 2.74 2.30 2.18
CMO186/40 1800 600 400 3.58 3.14 3.29 2.95 3.00 2.57 2.40
CMO188/30 1800 800 300 3.90 3.32 3.68 3.20 3.47 2.89 2.72
CMO188/40 1800 800 400 4.34 3.76 4.05 3.60 3.76 3.18 2.96
CMO188/50 1800 800 500 4.77 4.20 4.41 4.00 4.05 3.48 3.20
CMO188/60 1800 800 600 5.21 4.63 4.78 4.39 4.34 3.77 3.43
CMO1810/40 1800 1000 400 5.10 4.38 4.81 4.25 4.52 3.80 3.52
CMO1810/50 1800 1000 500 5.56 4.84 5.20 4.68 4.84 4.12 3.77
CMO1812/40 1800 1200 400 5.86 4.99 5.57 4.90 5.28 4.42 4.08
CMO1812/50 1800 1200 500 6.35 5.48 5.99 5.36 5.63 4.76 4.34
CMO1816/40 1800 1600 400 7.38 6.22 7.09 6.19 6.80 5.65 5.20
CMO1816/50 1800 1600 500 7.92 6.77 7.56 6.73 7.20 6.05 5.49
CMO206/30 2000 600 300 3.49 3.01 3.25 2.84 3.01 2.53 2.41
CMO206/40 2000 600 400 3.94 3.46 3.62 3.23 3.30 2.82 2.65
CMO208/30 2000 800 300 4.30 3.66 4.06 3.51 3.82 3.18 3.01
CMO208/40 2000 800 400 4.77 4.13 4.45 3.94 4.13 3.49 3.26
CMO208/50 2000 800 500 5.24 4.60 4.84 4.36 4.44 3.80 3.52
CMO208/60 2000 800 600 5.71 5.07 5.23 4.78 4.75 4.11 3.78
CMO2010/40 2000 1000 400 5.60 4.80 5.28 4.64 4.96 4.16 3.88
CMO2010/50 2000 1000 500 6.10 5.30 5.70 5.10 5.30 4.50 4.15
CMO2012/40 2000 1200 400 6.43 5.47 6.11 5.34 5.79 4.83 4.50
CMO2012/50 2000 1200 500 6.96 6.00 6.56 5.84 6.16 5.20 4.78
CMO2012/60 2000 1200 600 7.49 6.53 7.01 6.34 6.53 5.57 5.06
CMO2016/40 2000 1600 400 8.10 6.82 7.78 6.75 7.46 6.18 5.73
CMO2016/50 2000 1600 500 8.68 7.40 8.28 7.32 7.88 6.60 6.04
CMO2016/60 2000 1.600 600 9.26 7.98 8.78 7.89 8.30 7.02 6.35
Dissipation surface area
Accessible on all sides
Against a wall
At one end of a row
Intermediate in a row, against a wall
Intermediate in a row, against a wall,closed covered top
Intermediate in a row
At one end of a row, against a wall
06_096_107_EN.indd 10506_096_107_EN.indd 105 2/4/08 13:40:492/4/08 13:40:49
6/106
HEAT CALCULATION
Dissipation surface area of the metal enclosures: OLN
Dimensions in mm
A B C
Type of installation conforming to IEC 890Enclosure reference
number
OLN203/80 2000 300 600 4.30 4.06 3.66 3.51 3.02 2.78 2.61
OLN206/40 2000 600 400 3.94 3.46 3.62 3.14 3.30 2.82 2.65
OLN206/50 2000 600 500 4.38 3.90 3.98 3.50 3.58 3.10 2.89
OLN206/60 2000 600 600 4.82 4.34 4.34 3.86 3.86 3.38 3.13
OLN206/80 2000 600 800 5.71 5.23 5.07 4.59 4.43 3.95 3.62
OLN208/40 2000 800 400 4.77 4.13 4.45 3.81 4.13 3.49 3.26
OLN208/50 2000 800 500 5.24 4.60 4.84 4.20 4.44 3.80 3.52
OLN208/60 2000 800 600 5.71 5.07 5.23 4.59 4.7 4.11 3.78
OLN208/80 2000 800 800 6.66 6.02 6.02 5.38 5.38 4.74 4.29
OLN2010/40 2000 1000 400 5.60 4.80 5.28 4.48 4.96 4.16 3.88
OLN2010/40/2P 2000 1000 400 5.60 4.80 5.28 4.48 4.96 4.16 3.88
OLN2010/50 2000 1000 500 6.10 5.30 5.70 4.90 5.30 4.50 4.15
OLN2010/50/2P 2000 1000 500 6.10 5.30 5.70 4.90 5.30 4.50 4.15
OLN2010/60 2000 1000 600 6.60 5.80 6.12 5.32 5.64 4.84 4.42
OLN2010/60/2P 2000 1000 600 6.60 5.80 6.12 5.32 5.64 4.84 4.42
OLN2010/80 2000 1000 800 7.60 6.80 6.96 6.16 6.32 5.52 4.96
OLN2010/80/2P 2000 1000 800 7.60 6.80 6.96 6.16 6.32 5.52 4.96
OLN2012/40/2P 2000 1200 400 6.43 5.47 6.11 5.15 5.79 4.83 4.50
OLN2012/50/2P 2000 1200 500 6.96 6.00 6.56 5.60 6.16 5.20 4.78
OLN2012/60/2P 2000 1200 600 7.49 6.53 7.01 6.05 6.53 5.57 5.06
OLN2012/80/2P 2000 1200 800 8.54 7.58 7.90 6.94 7.26 6.30 5.63
OLN226/60 2200 600 600 5.26 4.73 4.73 4.20 4.20 3.67 3.42
OLN226/80 2200 600 800 6.22 5.69 5.51 4.98 4.81 4.28 3.94
OLN228/60 2200 800 600 6.22 5.51 5.69 4.98 5.16 4.46 4.12
OLN228/80 2200 800 800 7.23 6.53 6.53 5.82 5.82 5.12 4.67
OLN2210/60 2200 1000 600 7.18 6.30 6.65 5.77 6.12 5.24 4.82
OLN2210/80 2200 1000 800 8.25 7.37 7.54 6.66 6.84 5.96 5.40
OLN2210/80/2P 2200 1000 800 8.25 7.37 7.54 6.66 6.84 5.96 5.40
OLN2212/60/2P 2200 1200 600 8.14 7.08 7.61 6.55 7.08 6.02 5.52
OLN2212/80/2P 2200 1200 800 9.26 8.21 8.56 7.50 7.86 6.80 6.13
OLN126/40 1200 600 400 2.50 2.21 2.30 2.02 2.11 1.82 1.66
OLN126/60 1200 600 600 3.70 2.81 2.81 2.52 2.52 2.23 1.98
OLN126/80 1200 600 800 3.70 3.41 3.31 3.02 2.93 2.64 2.30
OLN128/40 1200 800 400 3.04 2.66 2.85 2.46 2.66 2.27 2.05
OLN128/60 1200 800 600 3.70 3.31 3.41 3.02 3.12 2.74 2.40
OLN128/80 1200 800 800 4.35 3.97 3.97 3.58 3.58 3.20 2.75
OLN146/40 1400 600 400 2.86 2.52 2.63 2.30 2.41 2.07 1.90
OLN146/60 1400 600 600 3.53 3.19 3.19 2.86 2.86 2.52 2.27
OLN146/80 1400 600 800 4.20 3.86 3.75 3.42 3.30 2.97 2.63
OLN148/40 1400 800 400 3.47 3.02 3.25 2.80 3.02 2.58 2.35
OLN148/60 1400 800 600 4.20 3.75 3.86 3.42 3.53 3.08 2.74
OLN148/80 1400 800 800 4.93 4.48 4.48 4.03 4.03 3.58 3.14
OLN166/60 1600 600 600 3.96 3.58 3.58 3.19 3.19 2.81 2.56
OLN166/80 1600 600 800 4.70 4.32 4.19 3.81 3.68 3.30 2.96
OLN168/60 1600 800 600 4.70 4.19 4.32 3.81 3.94 3.42 3.09
OLN168/80 1600 800 800 5.50 4.99 4.99 4.48 4.48 3.97 3.52
OLN186/40 1800 600 400 3.58 3.14 3.29 2.86 3.00 2.57 2.40
OLN186/50 1800 600 500 3.98 3.55 3.62 3.19 3.26 2.83 2.62
OLN186/60 1800 600 600 4.39 3.96 3.96 3.53 3.53 3.10 2.84
OLN186/80 1800 600 800 5.21 4.78 4.69 4.20 4.06 3.62 3.29
OLN188/40 1800 800 400 4.34 3.76 4.05 3.47 3.76 3.18 2.96
OLN188/50 1800 800 500 4.77 4.20 4.41 3.84 4.05 3.48 3.20
OLN188/60 1800 800 600 5.21 4.63 4.78 4.20 4.34 3.77 3.43
OLN1810/40 1800 1000 400 5.10 4.38 4.81 4.09 4.52 3.80 3.52
OLN1810/40/2P 1800 1000 400 5.10 4.38 4.81 4.09 4.52 3.80 3.52
OLN1810/50 1800 1000 500 5.56 4.84 5.20 4.48 4.84 4.12 3.77
OLN1810/50/2P 1800 1000 500 5.56 4.84 5.20 4.48 4.84 4.12 3.77
OLN1810/60 1800 1000 600 6.02 5.30 5.59 4.87 5.16 4.44 4.02
OLN1810/60/2P 1800 1000 600 6.02 5.30 5.59 4.87 5.16 4.44 4.02
OLN1812/40/2P 1800 1200 400 5.86 4.99 5.57 4.70 5.28 4.42 4.08
OLN1812/50/2P 1800 1200 500 6.35 5.48 5.99 5.12 5.63 4.76 4.34
OLN1812/60/2P 1800 1200 600 6.84 5.98 6.41 5.54 5.98 5.11 4.61
OLN203/50 2000 300 500 3.09 2.85 2.69 2.45 2.29 2.05 1.95
OLN203/60 2000 300 600 3.49 3.25 3.01 2.77 2.53 2.29 2.17
Dissipation surface area
06_096_107_EN.indd 10606_096_107_EN.indd 106 2/4/08 13:40:502/4/08 13:40:50
6/107
HEAT CALCULATION
PLM3025 308 255 160 0.29 0.23 0.26 0.27 0.25 0.22 0.19
PLM32 310 215 160 0.26 0.23 0.24 0.21 0.22 0.19 0.17
PLM43 430 330 200 0.50 0.45 0.47 0.41 0.43 0.38 0.33
PLM54 530 430 200 0.72 0.63 0.68 0.59 0.64 0.55 0.49
PLM64 647 436 250 0.95 0.84 0.89 0.77 0.82 0.71 0.63
PLM75 747 536 300 1.35 1.19 1.26 1.10 1.17 1.01 0.90
PLM86 847 636 300 1.69 1.48 1.59 1.38 1.49 1.28 1.14
PLM108 1056 800 350 2.46 2.14 2.32 2.00 2.18 1.86 1.67
Dimensions in mm
A B C
Type of installation conforming to IEC 890Enclosure reference
number
PLA553 500 500 320 0.96 0.86 0.90 0.86 0.83 0.73 0.62
PLA554 500 500 420 1.12 1.02 1.04 1.02 0.95 0.85 0.71
PLA573 500 750 320 1.30 1.15 1.24 1.18 1.17 1.02 0.85
PLA574 500 750 420 1.49 1.34 1.41 1.39 1.33 1.18 0.96
PLA5103 500 1000 320 1.64 1.44 1.57 1.50 1.51 1.31 1.08
PLA5104 500 1000 420 1.87 1.67 1.78 1.75 1.70 1.50 1.20
PLA5123 500 1250 320 1.97 1.72 1.91 1.82 1.85 1.60 1.32
PLA5124 500 1250 420 2.24 1.99 2.15 2.11 2.07 1.82 1.45
PLA753 750 500 320 1.33 1.18 1.24 1.15 1.14 0.99 0.88
PLA754 750 500 420 1.54 1.39 1.41 1.34 1.28 1.13 0.99
PLA773 750 750 320 1.78 1.56 1.68 1.56 1.59 1.36 1.20
PLA774 750 750 420 2.02 1.80 1.89 1.80 1.77 1.54 1.32
PLA7103 750 1000 320 2.23 1.93 2.13 1.96 2.04 1.74 1.51
PLA7104 750 1000 420 2.51 2.21 2.38 2.25 2.25 1.95 1.66
PLA7123 750 1250 320 2.68 2.30 2.58 2.37 2.49 2.11 1.83
PLA7124 750 1250 420 2.99 2.61 2.86 2.70 2.74 2.36 2.00
PLA1053 1000 500 320 1.70 1.50 1.57 1.44 1.44 1.24 1.13
PLA1054 1000 500 420 1.95 1.75 1.78 1.67 1.61 1.41 1.27
PLA1073 1000 750 320 2.26 1.96 2.13 1.93 2.01 1.71 1.54
PLA1074 1000 750 420 2.55 2.25 2.38 2.21 2.21 1.91 1.69
PLA10103 1000 1000 320 2.82 2.42 2.70 2.42 2.57 2.17 1.94
PLA10104 1000 1000 420 3.14 2.74 2.98 2.74 2.81 2.41 2.11
PLA10123 1000 1250 320 3.39 2.89 3.26 2.92 3.13 2.63 2.35
PLA10124 1000 1250 420 3.74 3.24 3.57 3.28 3.41 2.91 2.54
PLA1253 1250 500 320 2.07 1.82 1.91 1.72 1.75 1.50 1.39
PLA1254 1250 500 420 2.36 2.11 2.15 1.99 1.94 1.69 1.55
PLA1273 1250 750 320 2.74 2.37 2.58 2.30 2.42 2.05 1.88
PLA1274 1250 750 420 3.07 2.70 2.86 2.61 2.65 2.28 2.06
PLA12103 1250 1000 320 3.42 2.92 3.26 2.89 3.10 2.60 2.37
PLA12104 1250 1000 420 3.78 3.28 3.57 3.24 3.36 2.86 2.57
PLA12123 1250 1250 320 4.09 3.47 3.93 3.47 3.77 3.15 2.87
PLA12124 1250 1250 420 4.49 3.87 4.28 3.87 4.07 3.45 3.08
PLA1553 1500 500 320 2.44 2.14 2.25 2.01 2.05 1.75 1.64
PLA1554 1500 500 420 2.78 2.48 2.53 2.31 2.27 1.97 1.83
PLA1573 1500 750 320 3.23 2.78 3.03 2.68 2.84 2.39 2.22
PLA1574 1500 750 420 3.60 3.15 3.35 3.02 3.10 2.65 2.43
PLA15103 1500 1000 320 4.01 3.41 3.82 3.35 3.63 3.03 2.80
PLA15104 1500 1000 420 4.42 3.82 4.17 3.74 3.92 3.32 3.02
PLA15123 1500 1250 320 4.80 4.05 4.61 4.02 4.42 3.67 3.39
PLA15124 1500 1250 420 5.24 4.49 4.99 4.45 4.74 3.99 3.62
Dimensions in mm
A B C
Type of installation conforming to IEC 890Enclosure reference number
Dissipation surface area of the polyester enclosures: POLYMEL
Dissipation surface area of the polyesterenclosures: PLA
06_096_107_EN.indd 10706_096_107_EN.indd 107 2/4/08 13:40:502/4/08 13:40:50