TCB thermal circuit breaker - SEW EurodriveTCB thermal circuit breaker2 Installation Instructions...
Transcript of TCB thermal circuit breaker - SEW EurodriveTCB thermal circuit breaker2 Installation Instructions...
*23514450_0317*Drive Technology \ Drive Automation \ System Integration \ Services
Installation Instructions
TCB thermal circuit breaker
Edition 03/2017 23514450/EN
SEW-EURODRIVE—Driving the world
1General information
Installation Instructions – TCB thermal circuit breaker 3
1 General information
INFORMATIONOther applicable documentationThe following installation notes are only applicable in addition to the operating in-structions of the inverter.Observe the safety notes in the applicable operating instructions.
2351
4450
/EN
– 0
3/20
17
2 TCB thermal circuit breaker
Installation Instructions – TCB thermal circuit breaker4
2 TCB thermal circuit breakerIf a TCB thermal circuit breaker is used, the following connection applies.
Connection
1 3 5
2 4 6
12
24
23
11
+R
-R
23 245 2 1 4 3 6[1]
[2]
11 121) 2)
[3]
[4]
20144535819
[1] TCB thermal circuit breaker
[2] Braking resistor
[3] Inverter
[4] Control knob
1) Opens in case of thermal overload
2) Closes in case of thermal overload
• If the thermal circuit breaker trips, the signal contact is set (23-24 connection isopened, 11-12 connection is closed).
• The connection between inverter and braking resistor is disconnected.• This does not require a response by the PLC.• It is not required to disconnect the supply system connection with an external
switching device.• Set the control knob [4] of the thermal circuit breaker TCB to the tripping current IF
of the connected braking resistor. For doing so, set scaling to 40 °C.• After all cables are connected, the 3 upper screw holes must be covered with 3
touch guard caps. The touch guard caps are included in the delivery.
2351
4450
/EN
– 0
3/20
17
SEW-EURODRIVE—Driving the world
SEW-EURODRIVE GmbH & Co KGP.O. Box 302376642 BRUCHSALGERMANYPhone +49 7251 75-0Fax +49 7251 [email protected]