The sizing diagram will be available later on! For sizing ... Archive/Air handling units/GOLD...

36
86 GOLD www.swegon.com We reserve the right to alter specifications. 20110601 GOLD PX, plate heat exchanger, size 04 Min. and Max. Airflows The flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter- mined by the external pressure drop. Correction factors K OK , dB Sizing, Installation, Dimensions and Weights * The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu- lated as the sum of the levels in the supply air and the extract air. Range in the diagram Octave band, No. / mid-frequency, Hz Sound path 1 2 3 4 5 6 7 8 63 125 250 500 1000 2000 4000 8000 To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -15 2 -1 -5 -8 -8 -7 -9 -13 -16 3 -1 -2 -6 -15 -14 -16 -22 -25 4 -2 -3 -5 -13 -13 -14 -20 -25 To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -38 2 -9 -16 -21 -24 -33 -36 -39 -39 3 -6 -4 -14 -27 -35 -39 -44 -43 4 -9 -11 -16 -28 -38 -41 -44 -44 To air handling unit surroun- dings** 1 -12 -20 -29 -29 -40 -40 -46 -46 2 -12 -19 -31 -29 -40 -42 -47 -47 3 -12 -16 -29 -36 -47 -49 -56 -56 4 -13 -17 -28 -34 -46 -47 -54 -56 Size Min. airflow (on airflow regulation) Max. airflow m 3 /h m 3 /s m 3 /h m 3 /s 04 288 0.08 1620 0.45 Recommended working range for commissioning. Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat- ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). The sizing diagram will be available later on! For sizing, see the ProUnit air handling unit selection program.

Transcript of The sizing diagram will be available later on! For sizing ... Archive/Air handling units/GOLD...

86

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 04

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25

To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44

To air handling unit surroun-dings**

1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s04 288 0.08 1620 0.45

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be available later on!For sizing, see the ProUnit air handling unit selection

program.

87

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

Sizing, Installation, Dimensions and Weights

GOLD PX, plate heat exchanger, size 04

Size A B C D F G H L Ø Weight, kg

04 800 825 240 345 230 460 920 2000 315 291-337

Power connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A

Rated data per fanMotor shaft power: 0.8 kW (0.41 kW)* motor control system, 1 x 230 V, 50 Hz *The motor control system limits the power of the take-off to the value specified.

Clear Space for InspectionA clear space of 1,000 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.

Right-hand version

Left-hand version

Delivery and Transport within the SiteThe GOLD PX 04 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for trans-porting the unit within the building site.

Base frame/BaseThe GOLD PX 04 is supplied on a base frame with integrated openings for the forks of a fork-lift truck.

The stand is available as an accessory.

Installation/duct connection optionsA: Specify right-hand or left-hand version when ordering!

Outside air Supply air Extract air Exhaust air

Power connection

5252

32 32

80

180

80

50 50

16 52*

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

88

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 05

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25

To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44

To air handling unit surroun-dings**

1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s05 288 0.08 2340 0.65

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be available later on!For sizing, see the ProUnit air handling unit selection

program.

89

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 05

Sizing, Installation, Dimensions and Weights

Clear Space for InspectionA clear space of 1,000 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.

Delivery and Transport within the SiteThe GOLD PX 05 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

Base frame/BaseThe GOLD PX 05 is supplied on a base frame with integrated open-ings for the forks of a fork-lift truck.

The stand is available as an accessory.

Installation/duct connection optionsA: Specify right-hand or left-hand version when ordering!

Power connection

5252

32 32

80

180

80

50 50

16 52*

Size A B C D F G H L Ø Weight, kg

05 800 825 240 345 230 460 920 2000 315 291-337

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Right-hand version

Left-hand version

Outside air Supply air Extract air Exhaust air

Power connection1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2) or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A

Rated data per fanMotor shaft power: 0.8 kW alt. 1.15 kW, motor control system: 1 x 230 V, 50 Hz

90

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 07

Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors, KOK , dB.

Sizing, installation, dimensions and weights

* The integral attenuation of filters and plate heat exchanger has been taken into account.** Total sound power level emitted to the surroundings is calculated as the sum of the levels in the supply air and the extract air.

Rangein

diagram

Octave band, no./mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To the outletduct

1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25

To the inletduct*

1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44

To unit’s surroundings**

1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56

Size Min. airflow (for airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s07 288 0.08 2700 0.75

Recommended working range for sizing.

Permissible operating range when the fan is controlled to operate at a lower speed. The black broken line in the diagram indicates the lower limit for the airflow when the unit is operating in the airflow regulation mode. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be available later on!For sizing, see the ProUnit air handling unit selection

program.

91

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 07

Sizing, installation, dimensions and weights

Size A B C D F G H L Ø Weight, kg

07 915 995 277.5 440 271 543 1085 2230 400 360-419

Power connectionCapacity variant 1: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 10 A or 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A

Capacity variant 2: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 16 A or

3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A

Rated data per fanCapacity variant 1: Motor shaft power: 0.8 kW, motor control system: 1 x 230 V, 50 Hz

Capacity variant 2: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz

Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.

Delivery and transport within the siteThe GOLD PX 07 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

Base frame/BaseThe GOLD PX 07 is supplied on a base frame with integrated openings for the forks of a fork-lift truck.

The stand is available as an accessory.

Installation/duct connection optionsA: Specify right-hand or left-hand version when ordering.

Power connection

5252

32 32

80

180

80

50 50

16 52*

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Right-hand version

Left-hand version

Outdoor air Supply air Extract air Exhaust air

92

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 08

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -254 -2 -3 -5 -13 -13 -14 -20 -25

To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -434 -9 -11 -16 -28 -38 -41 -44 -44

To air handling unit surroun-dings**

1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -564 -13 -17 -28 -34 -46 -47 -54 -56

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s08 720 0.20 3600 1.00

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be available later on!For sizing, see the ProUnit air handling unit selection

program.

93

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 08

Sizing, Installation, Dimensions and Weights

Size A B C D F G H L Ø Weight, kg

08 915 995 277,5 440 271 543 1085 2230 400 369-428

Clear Space for InspectionA clear space of 1,000 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.

Delivery and Transport within the SiteThe GOLD PX 08 is produced in one single variant. All of its com-ponents are arranged at their given physical locations inside the air handling unit.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

Base frame/BaseThe GOLD PX 08 is supplied on a base frame with integrated open-ings for the forks of a fork-lift truck.

The stand is available as an accessory.

Installation/duct connection optionsA: Specify right-hand or left-hand version when ordering!

Power connection

5252

32 32

80

180

80

50 50

16 52*

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Right-hand version

Left-hand version

Outside air Supply air Extract air Exhaust air

Power connectionCapacity variant 1: 1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 A or 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW, motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz

94

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 11

Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, installation, dimensions and weights

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Rangein

diagram

Octave band, no./mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To the outletduct

1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -25

To the inletduct*

1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -43

To unit’s surroundings**

1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -56

Size Min. flow (for airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s11 720 0.20 3960 1.10

Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The black broken line in the diagram indicates the lower limit for the airflow when the unit is operating in the airflow regulation mode. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be specified later on!For sizing, see the ProUnit air handling unit selection

program.

95

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

D

E E 5252

16 52*

50 J

K

50 50J

K

8050

GOLD PX, plate heat exchanger, size 11

Sizing, installation, dimensions and weights

Power connection

Delivery and transport within the siteThe GOLD PX 11 is produced in one single variant. All of its components are arranged at their given physical loca-tions inside the air handling unit.

The GOLD PX 11 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors.

The air handling unit is delivered on wooden beams.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

Duct connection optionsA: Specify right-hand or left-hand version when ordering.

Right-hand version

Left-hand version

Outdoor air Supply air Extract air Exhaust air

Size A B C D E F G H J K L Ø Weight, kg

11 655 1199 324 1200 397 324 647 1295 935 551 2510 500 552-646

Power connectionCapacity variant 1: 1-phase, 3-conductor, 230 V -10/+15%, 50 Hz, 16 A or

3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Capacity variant 2: 3-phase, 5-conductor, 400 V -10/+15%, 50 Hz, 10 A Rated data per fanCapacity variant 1: Motor shaft power: 1.15 kW,

motor control system: 1 x 230 V, 50 Hz Capacity variant 2: Motor shaft power: 1.6 kW, motor control system: 3 x 400 V, 50 Hz

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 141-167 kg, D = 270-312 kg.

Division into sections for transport

A AD + 19 mm

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.

96

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 12

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -1 -6 -6 -8 -7 -7 -12 -152 -1 -5 -8 -8 -7 -9 -13 -163 -1 -2 -6 -15 -14 -16 -22 -25

To inlet duct* 1 -8 -15 -16 -28 -35 -38 -40 -382 -9 -16 -21 -24 -33 -36 -39 -393 -6 -4 -14 -27 -35 -39 -44 -43

To air handling unit surroun-dings**

1 -12 -20 -29 -29 -40 -40 -46 -462 -12 -19 -31 -29 -40 -42 -47 -473 -12 -16 -29 -36 -47 -49 -56 -56

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s12 720 0.20 5040 1.40

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be specified later on!For sizing, see the ProUnit air handling unit selection

program.

97

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

D

E E 5252

16 52*

50 J

K

50 50J

K

8050

GOLD PX, plate heat exchanger, size 12

Sizing, Installation, Dimensions and Weights

Power connection

Delivery and Transport within the SiteThe GOLD PX 12 is produced in one single variant. All of its components are arranged at their given physical locations inside the air handling unit.

The GOLD PX 12 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The air handling unit is delivered on wooden beams.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for trans-porting the unit within the building site.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

Right-hand version

Left-hand version

Outside air Supply air Extract air Exhaust air

Size A B C D E F G H J K L Ø Weight, kg

12 655 1199 324 1200 397 324 647 1295 935 551 2510 500 574-668

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 152-178 kg, D = 270-312 kg.

A AD + 19 mm

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A

Rated data per fanMotor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz

98

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 14

Sizing, Installation, Dimensions and Weights

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Correction factors KOK , dB

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s14 720 0.20 5940 1.65

Range in dia-gram chart

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34

2 -6 -9 -14 -28 -35 -39 -43 -39

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be specified later on!For sizing, see the ProUnit air handling unit selection

program.

99

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 14

Sizing, Installation, Dimensions and Weights

Delivery and Transport within the SiteThe GOLD PX 14 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The air handling unit is delivered on wooden beams.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for trans-porting the unit within the building site.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units).

Outside air Supply air Extract air Exhaust air

Clear Space for InspectionA clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A

Rated data per fanMotor shaft power: 1.6 kW alt. 2.4 kW, motor control system: 3 x 400 V, 50 Hz

Power connection

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 175-209 kg, D = 317-355 kg.

A AD + 19 mm

80

D

E E

M M

52 5050

52

N

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.

Size A B C D E F G H I J K L M N Weight, kg

14 765 1400 1136 1300 450 400 1000 1395 298 188 200 2830 208 109 667-773

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Right-hand version

Left-hand version

Division into sections for transport

100

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 20

Sizing, Installation, Dimensions and Weights

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s20 1080 0.30 7560 2.10

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34

2 -6 -9 -14 -28 -35 -39 -43 -39

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be specified later on!For sizing, see the ProUnit air handling unit selection

program.

101

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 20

Sizing, Installation, Dimensions and Weights

Delivery and Transport within the SiteThe GOLD PX 20 is always supplied as one unit. The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The air handling unit is delivered on wooden beams.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for trans-porting the unit within the building site.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units).

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 193-227 kg, D = 317-355 kg.

A AD + 19 mm

Power connection

80

D

E E

M M

52 5050

52

N

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Size A B C D E F G H I J K L M N Weight, kg

20 765 1400 1136 1300 450 400 1000 1395 298 188 200 2830 208 109 703-809

Outside air Supply air Extract air Exhaust air

Right-hand version

Left-hand version

Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 A (capacity variant 1) alt. 16 A (capacity variant 2)

Rated data per fanMotor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz

102

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 25

Sizing, Installation, Dimensions and Weights

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s25 1080 0.30 9000 2.50

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34

2 -6 -9 -14 -28 -35 -39 -43 -39

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be specified later on!For sizing, see the ProUnit air handling unit selection

program.

103

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 25

Sizing, Installation, Dimensions and Weights

Delivery and Transport within the SiteThe GOLD PX 25 is supplied as two units. The one unit con-sists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.The air handling unit is delivered on wooden beams.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for trans-porting the unit within the building site.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units).

Clear Space for InspectionA clear space of 900 mm must be provided in front of the unit and at least 200 mm must be provided above the junction hood.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 A

Rated data per fanMotor shaft power: 2.4 kW alt. 3.4 kW, motor control system: 3 x 400 V, 50 Hz

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 225-265 kg, D = 455-528 kg.

A AD + 19 mm

Power connection

80

D

E E

M M

52 5050

52

N

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Size A B C D E F G H I J K L M N Weight, kg

25 835 1600 1336 1550 575 500 1200 1595 298 203 200 3220 193 94 905-1058

Outside air Supply air Extract air Exhaust air

Right-hand version

Left-hand version

Division into sections for transport

104

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 30

Sizing, Installation, Dimensions and Weights

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s30 1800 0.50 11520 3.20

* The integral attenuation of filters and plate heat exchanger has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -11 -16 -14 -27 -33 -37 -38 -34

2 -6 -9 -14 -28 -35 -39 -43 -39

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The sizing diagram will be specified later on!For sizing, see the ProUnit air handling unit selection

program.

105

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD PX, plate heat exchanger, size 30

Sizing, Installation, Dimensions and Weights

Delivery and Transport within the SiteThe GOLD PX 30 is supplied as two units. The one unit con-sists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.The air handling unit is delivered on wooden beams.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for trans-porting the unit within the building site.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: Specify whether the unit shall have an air intake from above for outdoor air and/or extract air when placing orders (not for outdoor units).

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 245-285 kg, D = 455-528 kg.

A AD + 19 mm

Power connection

80

D

E E

M M

52 5050

52

N

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accessories) can be used for this purpose.

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Size A B C D E F G H I J K L M N Weight, kg

30 835 1600 1336 1550 575 500 1200 1595 298 203 200 3220 193 94 945-1098

Outside air Supply air Extract air Exhaust air

Right-hand version

Left-hand version

Division into sections for transport Clear space for inspectionA clear space of 900 mm should be provided in front of the unit and at least 200 mm should be provided above the junction hood.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 A (capacity variant 1) alt. 20 A (capacity variant 2)

Rated data per fanMotor shaft power: 4.0 kW alt. 5.0 kW, motor control system: 3 x 400 V, 50 Hz

106

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 35

Sizing, Installation, Dimensions and Weights

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Correction factors KOK , dB

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s35 2700 0.75 14040 3.90

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Fan motor, 6.5 kW.

75dB 80 85Lw,tot

75dB 80 85Lw,tot

2.5

2.0

1.5

12

12

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

107

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

250

M

5250

50250

M

5050 52

N

N

GOLD CX, coil heat exchangers, size 35

Sizing, Installation, Dimensions and Weights

Size A B C D E F G H I J K L M N Weight, kg

35 948 1990 1726 680 200 600 1400 1985 392 153 295 2575 600 240 1355

Delivery and Transport within the SiteThe GOLD CX 35 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.

The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The air handling unit is delivered on wooden beams.

The coil heat exchanger system is filled with liquid from the factory.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!

C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors).

Right-hand version

Left-hand version

Upward UpwardForwardForward

Fan arrangement 1 Fan arrangement 2

Fan arrangement 1 Fan arrangement 2

Upward Upward

ForwardForward

Outside air Supply air Extract air Exhaust air

Clear Space for InspectionA clear space of 900 mm should be provided in front of the unit.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 A

Rated data per fanMotor shaft power: 6.5 kW (3.9 kW)* motor control system, 3 x 400 V, 50 Hz *The motor control system limits the power of the take-off to the value

specified.

Power connection

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 404 kg, D = 547 kg.A AD+19 mm

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accesso-ries) can be used for this purpose. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1:The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted.

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Division into sections for transport

108

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 40

Sizing, Installation, Dimensions and Weights

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s40 2700 0.75 18000 5.00

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Fan motor, 6.5 kW.

2.5

2.0

1.5

12

12

75dB 80 85 90Lw,tot

75dB 80 85 90Lw,tot

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

109

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 40

Sizing, Installation, Dimensions and Weights

Delivery and Transport within the SiteThe GOLD CX 40 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.

The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The air handling unit is delivered on wooden beams.

The coil heat exchanger system is filled with liquid from the factory.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!

C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors).

Clear Space for InspectionA clear space of 900 mm should be provided in front of the unit.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 32 A

Rated data per fanMotor shaft power: 6.5 kW, motor control system, 3 x 400 V, 50 Hz

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 404 kg, D = 547 kg.

Size A B C D E F G H I J K L M N Weight, kg

40 948 1990 1726 680 200 600 1400 1985 392 153 295 2575 600 240 1355

250

M

5250

50250

M

5050 52

N

N

Power connection

If a water trap (accessory) is fitted, the air handling unit must be raised at least 50 mm to provide space for the water trap. Support feet (accesso-ries) can be used for this purpose. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1:The dimension print shows the connection configuration for fan arrangement 1. For fan arrangement 2 the connections are mirror-inverted.

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

A AD+19 mm

Right-hand version

Left-hand version

Upward UpwardForwardForward

Fan arrangement 1 Fan arrangement 2

Fan arrangement 1 Fan arrangement 2

Upward Upward

ForwardForward

Outside air Supply air Extract air Exhaust air

Division into sections for transport

110

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 50

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s50 3600 1.00 18000 5.00

Fan motor: 2 x 4.0 kW

75dB 80 85

90

Lw,tot

75dB 80 85

90

Lw,tot

2.5

2.0

1.5

12

12

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

111

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

28

28*

76254

M76

GOLD CX, coil heat exchangers, size 50

Sizing, Installation, Dimensions and Weights

Size A B D E F G H I J K L M Weight, kg

50 1050 2318 760 150 800 1600 2253 423 115 360 2860 650 2045

Delivery and Transport within the SiteThe GOLD CX 50 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.

The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The unit is supplied on 100 mm high support feet made of steel.

The coil heat exchanger system is filled with liquid from the factory.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!

C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors).

Upward Upward

ForwardForward

Upward Upward

ForwardForward

Right-hand version

Left-hand version

Fan arrangement 1 Fan arrangement 2

Fan arrangement 1 Fan arrangement 2

Outside air Supply air Extract air Exhaust air

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 542 kg, D = 961 kg.

Clear Space for InspectionA clear space of 1,100 mm should be provided in front of the unit.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 25 A

Rated data per fanMotor shaft power: 2 x 4.0 kW (2 x 2.4 kW)* motor control system, 3 x 400 V, 50 Hz *The motor control system limits the power of the take-off to the value

specified.

Power connection

Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory).

A AD

* The air handling unit

is supplied without end

connection panel if a

duct accessory housed in

an insulated casing will

be connected.

Division into sections for transport

112

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 60

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s60 3600 1.00 23400 6.50

75dB 80 85 90Lw,tot

75dB 80 85 90Lw,tot

2.5

2.0

1.5

12

12

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

Fan motor: 2 x 4.0 kW, capacity variant 1 Fan motor: 2 x 6.5 kW, capacity variant 2

75dB 80 85 90

95

Lw,tot

2.5

2.0

1.5

75dB 80 85 90

95

Lw,tot

12

12

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The diagram shows the air handling unit including the end connection panels.

113

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 60

Sizing, Installation, Dimensions and Weights

Size A B D E F G H I J K L M Weight, kg

60 1050 2318 760 150 800 1600 2253 423 115 360 2860 650 2045

Delivery and Transport within the SiteThe GOLD CX 60 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.

The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The unit is supplied on 100 mm high support feet made of steel.

The coil heat exchanger system is filled with liquid from the factory.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!

C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors).

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 542 kg, D = 961 kg.A AD

28

28*

76254

M76

Power connection

Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory).

* The air handling unit

is supplied without end

connection panel if a

duct accessory housed in

an insulated casing will

be connected.

Upward Upward

ForwardForward

Upward Upward

ForwardForward

Right-hand version

Left-hand version

Fan arrangement 1 Fan arrangement 2

Fan arrangement 1 Fan arrangement 2

Outside air Supply air Extract air Exhaust air

Division into sections for transport Clear space for inspectionA clear space of 1,100 mm should be provided in front of the unit.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 A (capacity variant 1) alt. 50 A (capacity variant 2)

Rated data per fanMotor shaft power: 2 x 4.0 kW alt. 2 x 6.5 kW, motor control system: 3 x 400 V, 50 Hz

114

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 70

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s70 5400 1.50 27000 7.50

Fan motor: 2 x 6.5 kW

75dB 80 85

90

Lw,tot

75dB 80 85

90

Lw,tot

2.5

2.0

1.5

12

12

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

115

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

254

M7676

52

52*

27

Size A B D E F G H I J K L M Weight, kg

70 1275 2637 760 164 1000 1800 2640 319 161 419 3310 800 3030

Delivery and Transport within the SiteThe GOLD CX 70 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.

The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The unit is supplied on 100 mm high support feet made of steel.

The coil heat exchanger system is filled with liquid from the factory.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!

C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors).

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 866 kg, D = 1,298 kg.

Clear Space for InspectionA clear space of 1,100 mm should be provided in front of the unit.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 32 A

Rated data per fanMotor shaft power: 2 x 6.5 kW (2 x 3.9 kW)* motor control system, 3 x 400 V, 50 Hz *The motor control system limits the power of the take-off to the value

specified.

Power connection

GOLD CX, coil heat exchangers, size 70

Sizing, Installation, Dimensions and Weights

Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory).

* The air handling unit

is supplied without end

connection panel if a

duct accessory housed in

an insulated casing will

be connected.

Upward Upward

ForwardForward

Upward Upward

ForwardForward

Right-hand version

Left-hand version

Fan arrangement 1 Fan arrangement 2

Fan arrangement 1 Fan arrangement 2

Outside air Supply air Extract air Exhaust air

Division into sections for transport

A AD

116

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 80

Min. and Max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Correction factors KOK , dB

Sizing, Installation, Dimensions and Weights

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, No. / mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s80 5400 1,50 34200 9,50

2.5

2.01.5

75dB 80 85 90Lw,tot

75dB 80 85 90Lw,tot

12

12

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Recommended working range for commissioning.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

Fan motor: 2 x 6.5 kW, capacity variant 1 Fan motor: 2 x 10 kW, capacity variant 2

2.5

2.01.5

12

12

75dB 80 85 90Lw,tot

75dB 80 85 90Lw,tot

95

95

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

Supply air fan

Extract air fan

117

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 80

Sizing, Installation, Dimensions and Weights

Size A B D E F G H I J K L M Weight, kg

80 1275 2637 760 164 1000 1800 2640 319 161 419 3310 800 3030

Delivery and Transport within the SiteThe GOLD CX 80 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is mounted in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.

The air handling unit can be split into three sections to facilitate transporting it within the building site.

The three sections are joined together by bolts and the electri-cal and control cables have quick connectors.

The unit is supplied on 100 mm high support feet made of steel.

The coil heat exchanger system is filled with liquid from the factory.

Duct connection optionsA: Specify right-hand or left-hand version when ordering!

B: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders!

C: Specify upper fan outlet for upward air discharge when ordering. (not for units installed outdoors).

The unit can be divided into three sections at the building site.Dimensions: See A and D in the table above.Weight: A = 866 kg, D = 1,298 kg.

Clear Space for InspectionA clear space of 1,100 mm should be provided in front of the unit.

Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 50 A (capacity variant 1) alt. 80 A (capacity variant 2)

Rated data per fanMotor shaft power: 2 x 6.5 kW alt. 2 x 10 kW, motor control system: 3 x 400 V, 50 Hz

254

M7676

52

52*

27

Supplied on 100 mm high support feet. They can be removed or kept as they are when the unit is in place. Applicable to the right-hand version, fan arrangement 2 and the left-hand version, fan arrangement 1: If a water trap is fitted, in addition to the base beams, the air handling unit must be raised at least 50 mm to provide space for the water trap. It is advisable to let these support feet remain on the unit. Or you can remove them and fit adjustable feet (accessory).

* The air handling unit

is supplied without end

connection panel if a

duct accessory housed in

an insulated casing will

be connected.

Upward Upward

ForwardForward

Upward Upward

ForwardForward

Right-hand version

Left-hand version

Fan arrangement 1 Fan arrangement 2

Fan arrangement 1 Fan arrangement 2

Outside air Supply air Extract air Exhaust air

Division into sections for transport

A AD

118

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

2.5

2.0

1.5

12

12

80dB 85 90Lw,tot

80dB 85 90Lw,tot

GOLD CX, coil heat exchangers, size 100

Sizing, installation, dimensions and weights

Min. and max. AirflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s100 9000 2.50 39 600 11.0

Correction factors, KOK , dB.

Fan motor: 3 x 6.5 kW

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, no./mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

119

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 100

Sizing, installation, dimensions and weights

Delivery and transport within the siteThe GOLD CX 100 is supplied as six separate sections: Two fan sections, two filter sections and two coil heat ex-changer sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are sup-plied in unassembled condition for floor or wall mounting (see TBXZ pipework package under Accessories).

The three sections are to be jointed together by bolts and the electrical and control cables are simple to connect.

Duct connection optionsA: Specify right-hand or left-hand version when ordering.

B: The arrangement of the functional sections can vary. To be specified when ordering as fan arrangement 1, 2, 4 or 5. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level.

C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). N.B.! Duct connec-tion size: 2500 x 800 mm.

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Upward UpwardForwardForward

Upward Upward

ForwardForward

Right-hand version

Fan arrangement 1 Fan arrangement 2

Outdoor air Supply air Extract air Exhaust air

Filter and fan sections See dimensions A and P in the table above. Weight: fan section = 875 kg, filter section = 529 kg.

Heat exchanger sectionsSee dimensions D and P in the table above. Weight: Heat exchanger section = 880 kg.

Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 50 ARated data per fanMotor shaft power: 3 x 6.5 kW (3 x 3.9 kW)*, motor control system: 3 x 400 V, 50 Hz *The motor control system limits the output power to the value speci-fied.

Transport at building site, dim. and weights

Fan arrangement 5, supply air – upper level

Fan arrangement 5, supply air - lower level

Upward UpwardForwardForward

Upward UpwardForward

Forward

Left-hand version

Fan arrangement 1 Fan arrangement 2

Fan arrangement 4, supply air – upper level

Fan arrangement 4, supply air - lower level

Size A B D E F G H I J K L M N O P Weight, kg

100 1126 3340 1070 191 1200 2400 3440 520 210 470 3322 800 170 2500 1720 4568

56*

56

M

P

P

N O N

137

77 3186 77

1048 1000 10481048122

45

Power connectionIf extract air flows through the lower level: The air handling unit must be raised at least 50 mm (higher than the upper edge of the base beams) to provide space for the water trap. This can be done by mounting adjust-able feet (accessories).

120

GOLD

www.swegon.comWe reserve the right to alter specifications. 20110601

2.5

2.01.5

12

12

80dB 85 90 95Lw,tot

80dB 85 90 95Lw,tot

12

12

80dB 85 90 95Lw,tot

80dB 85 90 95Lw,tot

2.5

2.01.5

GOLD CX, coil heat exchangers, size 120

Sizing, installation, dimensions and weights

Min. and max. airflowsThe flows specified refer to those that can be preset in the hand-held micro terminal. The practical flow limits are deter-mined by the external pressure drop.

Size Min. airflow (on airflow regulation)

Max. airflow

m3/h m3/s m3/h m3/s120 9000 2.50 50 400 14.0

Correction factors, KOK , dB.

Fan motor: 3 x 6.5 kW, capacity variant 1

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

Recommended working range for sizing.Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operat-ing in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).

The diagram shows the air handling unit including the end connection panels.

The lower limit for the airflow when the unit is operating in the airflow regulation mode.

Fan motor: 3 x 10 kW, capacity variant 2

Supply air fan

Extract air fan

SFPv

Airflow, m3/s

Ava

ilab

le t

ota

l pre

ssu

re r

ise,

Pa

Airflow, m3/h

* The integral attenuation of filters and coil heat exchangers has been taken into account. ** Total sound power level emitted to the surroundings is calcu-lated as the sum of the levels in the supply air and the extract air.

Range in the

diagram

Octave band, no./mid-frequency, Hz

Sound path 1 2 3 4 5 6 7 8

63 125 250 500 1000 2000 4000 8000

To outlet duct 1 -4 -9 -7 -5 -8 -9 -11 -11

2 2 -4 -7 -7 -10 -12 -16 -17

To inlet duct* 1 -10 -10 -8 -21 -28 -30 -35 -32

2 -5 -3 -8 -22 -30 -32 -40 -37

To air handling unit surroun-dings**

1 -15 -23 -30 -26 -41 -42 -45 -42

2 -9 -18 -30 -28 -43 -45 -50 -48

121

GOLD

GO

LD

www.swegon.comWe reserve the right to alter specifications. 20110601

GOLD CX, coil heat exchangers, size 120

Sizing, installation, dimensions and weights

Filter and fan sections See dimensions A and P in the table above. Weight: fan section = 875 kg, filter section = 529 kg.

Heat exchanger sectionsSee dimensions D and P in the table above. Weight: Heat exchanger section = 880 kg.

Clear space for inspectionA clear space of 1,000 mm should be provided in front of the unit.Power connection3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 A (capacity variant 1) alt. 125 A (capacity variant 2)Rated data per fanMotor shaft power: 3 x 6.5 kW alt 3 x 10 kW, motor control system: 3 x 400 V, 50 Hz

Transport at building site, dim. and weights

Delivery and transport within the siteThe GOLD CX 120 is supplied as six separate sections: Two fan sections, two filter sections and two coil heat ex-changer sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are sup-plied in unassembled condition for floor or wall mounting (see TBXZ pipework package under Accessories).

The three sections are to be jointed together by bolts and the electrical and control cables are simple to connect.

Duct connection optionsA: Specify right-hand or left-hand version when ordering.

B: The arrangement of the functional sections can vary. To be specified when ordering as fan arrangement 1, 2, 4 or 5. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level.

C: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). N.B.! Duct connec-tion size: 2500 x 800 mm.

Upward UpwardForwardForward

Upward Upward

ForwardForward

Right-hand version

Fan arrangement 1 Fan arrangement 2

Outdoor air Supply air Extract air Exhaust air

Power connection

Fan arrangement 5, supply air – upper level

Fan arrangement 5, supply air - lower level

Upward UpwardForwardForward

Upward UpwardForward

Forward

Left-hand version

Fan arrangement 1 Fan arrangement 2

Fan arrangement 4, supply air – upper level

Fan arrangement 4, supply air - lower level

Size A B D E F G H I J K L M N O P Weight, kg

120 1126 3340 1070 191 1200 2400 3440 520 210 470 3322 800 170 2500 1720 4568

56*

56

M

P

P

N O N

137

77 3186 77

1048 1000 10481048122

45

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

If extract air flows through the lower level: The air handling unit must be raised at least 50 mm (higher than the upper edge of the base beams) to provide space for the water trap. This can be done by mounting adjust-able feet (accessories).