Terasaki Catalogue

36
www.terasaki.co.jp Low-Voltage Circuit Breakers Selection Guide CATALOGUE No. ’05-G90E

description

Circuit Breakers Catalogue

Transcript of Terasaki Catalogue

  • www.terasaki.co.jp

    Low-Voltage Circuit BreakersSelection Guide

    CATALOGUE No. 05-G90E

  • 1Terasaki developed its original breaker for the first time in Japan in 1947.Since then, the company has been offering, as a specialized breakermanufacturer, the most advanced breakers not only to the Japanese market, butalso to the world markets.The TemBreak series of Moulded case circuit breakers, which is evaluated ashighly reliable by our customers, has been improved from time to time for betterperformance through Terasaki's advanced technologies.In 2000, the TemPower 2 series was released to replace the Tempower series ofair circuit breakers, which had received high reputations for many years. Thisnew series consists of small, high-performance air circuit breakers featuringadvanced information and communication capabilities.Terasaki is ready to meet the customers' requirements in the 21st century throughits diversified model lineup and its broad range of enhanced products.

    circuit breakers. Our mature product line supports the wide ranging needs of our customers.

    Contents

    In September 1993, Terasaki ob-tained certification for the world quali-ty assurance standard ISO9002. In 1994, we obtained certification forthe even more rigorous ISO9001which covers additional items such asManagement Responsibil i t ies,Employee Training, Design andDevelopment, and Service. In the future, we will respond to theeven higher level of global needs withinternational reliability.

    In April 2000, Terasaki was certifiedas conforming to ISO 14001, an inter-national environment-related stan-dard. The company gives priority toits commitment to the curtailment orabolishment of using environmentallyharmful substances, energy saving inthe production activities, reduction ofwastes, and effective utilization of re-sources.

    ISO9001 certificate

    ISO14001 certificate

    World Class Air Circuit BreakerEnergy saving support

    Power Monitoring Equipment

    Company profile 2

    1. TemPower 6Air Circuit Breakers AR 6Air Circuit Breakers ATAH 8Air Circuit Breakers AME 9

    2. TemBreak 10z Moulded Case Circuit Breakers 10

    Economical XE Series 10Standard XS Series 12High-fault Level XH Series 15Motor Protection XM Series 16D.C. Application Series 17Current-Limiting Breakers, TL Series 18TO/TT Series 20Mining Series 21Non-automatic Trip Breakers 22Thyrister Protection Breakers 24TB Series for Distribution Board use 25Adjustable Thermal Trip 26Marine Approval 28

    x Earth-leakage Relays 30TZS Series 30

    3. TemMeasure 314. TemPlug 325. TemDin 336. Other Electrical Distribution Equipment 34

    Special Circuit Breakers 34

  • 2TTTTEEEERRRRAAAASSSSAAAAKKKKIIIIPPPPrrrrooooffffiiii lllleeee

    Sales departmentfor marine

    Technical departmentfor marine

    Sales departmentfor industrial

    Technical departmentfor Industrial

    Imari factoryYao factory Yabakei factory

    Sales department

    Technical department

    Kami factory

    Quality assurancedepartment

    Business administrationdivision

    Accounting & financedepartment

    General affairsdepartment

    President

    Board of directors

    Section of inspector

    Board of auditors

    Industrial systems

    Marine systems Circuit brea

    kers

    Quality assurancedepartment

    Short-circuittesting station

    Division administrationdepartment

    Division administrationdepartment

    Customers

    Established: October 1,1923President: Masakazu FujitaCapital: 641 million yenNumber of employees: 813Sales: (Mar. 2004) 19,353 million yen

    Line of business

    Marine Systems Division:

    Power distribution systems, Engine monitoring & control

    systems, General instrumentation

    Industrial Systems Division:

    Power distribution system, Co-generation system,

    Independent generation plant (distributed power supply),

    System engineering, Electronic equipment and systems for

    factory automation, Monitoring & control system

    Medical tools and equipment

    Circuit Breaker Division:

    Moulded case circuit breakers, Air circuit breakers.

    Minuature circuit breakers, Power monitoring equipments

    Circuit Breaker Division

    Industrial Systems Division

    Marine SystemsDivision

  • 3TERASAKI ELECTRIC CO., LTD.Osaka, JAPANHeadquarter

    Overseas Affiliates

    q

    o

    w

    r

    t

    e

    yu

    i

    TERASAKI (EUROPE) LTD.Glasgow, SCOTLAND U. K.

    TERASAKI ITALIA s.r.l.Milano, ITALY

    TERASAKI ESPAA, S.A.U.Barcelona, SPAIN

    TERASAKI SKANDINAVISKA ABSKOGS SWEDEN

    TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.SINGAPORE

    TERASAKI ELECTRIC (M) SDN. BHD.Shah Alam, MALAYSIA

    TERASAKI DO BRASIL LTDA.Rio de Janeiro, BRAZIL

    TERASAKI ELECTRIC (CHINA) LIMITEDZengcheng, CHINA

    TERASAKI ELECTRIC CO., (FAR EAST) PTE. LTD.SINGAPORE

    q

    w

    e

    r

    t

    y

    u

    i

    o

    TERASAKI Global NetworkTERASAKI Global Network

    1 TERASAKISKANDINAVISKA AB(SWEDEN)

    2 TERASAKI (EUROPE) LTD.(U.K.)

    3 TERASAKI ESPAA, S.A.U.(SPAIN)

    4 TERASAKI ITALIA s.r.l.(ITALY)

    TERASAKI ELECTRIC CO., LTD.(JAPAN)

    5 TERASAKI ELECTRIC(M) SDN. BHD. (MALAYSIA)

    6 TERASAKI CIRCUITBREAKERS (S) PTE. LTD.(SINGAPORE)

    7 TERASAKI ELECTRIC CO.,(FAR EAST) PTE. LTD.(SINGAPORE)

    8 TERASAKI ELECTRIC(CHINA) LTD.(CHINA)

    9 TERASAKI DO BRASIL LTDA.(BRAZIL)

  • Short-circuit Testing Station

    q Short-circuit test generator No.1w Short-circuit test generator No.2e Voltage change devicer Back-up breakert Making switchy Reactors, Resistanceu Step-down 3 transformeri 800V d.c. short-circuit testing

    equipmento Pit!0 Impulse generator!1 Control room!2 Computerized control equipment

    q

    w

    e

    r

    t

    y

    u

    i

    o

    !0

    !2

    !1

    4

    Certifications, Authorizations or Approvals by World's Leading Organizations

    Air Circuit BreakersASTA/U.K.ASTA CERTIFICATION SERVICESSECV/AustraliaState Electricity Commission of VictoriaLR/U.K.Lloyds Register of ShippingBV/FranceBureau VeritasGL/GermanyGermanischer LloydAB/U.S.A.American Bureau of ShippingNK/JapanNippon Kaiji Kyokai

    Moulded Case Circuit BreakersASTA/U.K.ASTA CERTIFICATION SERVICESSECV/AustraliaState Electricity Commission of VictoriaLR/U.K.Lloyds Register of ShippingBV/FranceBureau VeritasGL/GermanyGermanischer LloydAB/U.S.A.American Bureau of ShippingNK/JapanNippon Kaiji Kyokai

    Based Standards

    Air Circuit BreakersIEC 60947-2International Electrotechnical CommissionBS EN 60947 Part 2/U.K.British StandardVDE 0660 Part 101/GermanyVerband Deutscher ElektrotechnickerNEMA PUB NO. SG3/U.S.A.National Electrical Manufacturers AssociationANSI C37. 13/U.S.A.American National Standard instituteJIS C8372/JapanJapanese Industrial StandardJEC-160/JapanJapanese Electrical Committee

    Moulded Case Circuit BreakersIEC 60947-2International Electrotechnical CommissionBS EN 60947 Part 2/U.K.British StandardVDE 0660 Part 101/GermanyVerband Deutscher ElektrotechnickerCEI EN 60947 Part 101/GeramanyItalian StandardNEMA AB-1/U.S.A.National Electrigal Manufacturers AssociationJIS C8370/JapanJapanese Industrial Standard

    Short-circuit test generator No.1

    Short-circuit test generator No.2

    TYPE TESTS on every lot

    Construction testOperation testTripping testOverload testOvershooting testTemperature rise testEndurance testInsulation resistance testWithstand voltage testShort-circuit testFlexible cord protection testShort-circuit making capacity testShort-time withstand current test

    RELIABILITY TESTS

    Vibration testMechanical operation testRust proof testMechanical impact testHeat-shock testGas proof testAging test

    Combined Short-circuit Capacity(MVA) When TwoShort-circuitTest Generators (No.1 and No.2)are Paralleled.

    Time after short-circuit (Cycle) Sym. 3 R.M.S.

    0 10601/2 9501 8603 710

    TERASAKI is always pleasedto send you the worlds top-class products.Already for many decades TERASAKI has beeninternationally minded. This is proved by the num-ber of certifications, authorizations and approvalsby the worlds leading organizations and authori-ties.TERASAKI maintains the top position.TERASAKI will exert its further efforts to attainmore international quality recognition.

  • TemBreakMoulded Case

    Circuit Breakers

    (AME series for Generator Protection)

    Power Monitoring Equipment

    Direct bus plug-in mounting base

    Air Circuit Breakers

    Earth-leakage Relays

    Air Circuit Breakers with enhanced OCR

    5

    AAAAppppppppeeeeaaaarrrraaaannnncccceeee ooooffff mmmmaaaajjjjoooorrrr pppprrrroooodddduuuuccccttttssss

  • 6Air Circuit BreakersAR Standard Series1

    AMPERE RATING(A)TYPERATED CURRENT (max) [In](A) IEC, EN, AS

    q w JISNEMA, ANSIMarine

    NEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLES e rRATED PRIMARY CURRENT OF OVERCURRENTRELEASE [ICT](A) for general feeder circuit use

    RATED CURRENT OF OVERCURRENT RELEASE(A) for generator protection use[In] is generator rated current.

    AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) tRATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) yAC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]IEC,EN,AS AC 690V u[Ics = Icu] 440VNEMA AC 600VANSI 480V

    240VJIS AC 550V

    460V220V

    o DC 600V !0250V

    NK !2 AC 690V450V

    LR, AB, !2 AC 690VGL, BV 450V

    RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV)RATED SHORT TIME WITHSTAND 1sCURRENT[Icw][kA rms] 3sLATCHING CURRENT (kA)TOTAL BREAKING TIME (s)CLOSING OPERATION TIMESPRING CHARGING TIME (s) max.CLOSE TIME (s) max.No. of operating cycles Mechanical life with maintenance

    without maintenance Electrical life without maintenance AC460V

    AC690VWEIGHT (kg) draw-out typeOUTLINE DIMENSION (mm)FIXED TYPE a

    bc

    dDRAW-OUT aTYPE !3 b

    c

    d

    800AR208S8008008008008003 4200400800

    100In200200In400400In800

    1000690

    50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

    126550650.03

    100.08

    3000015000120001000073 86

    360 44546029075354 43946034540

    1250AR212S125012501250125012503 44008001250

    200In400400In800630In1250

    1000690

    50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

    126550650.03

    100.08

    3000015000120001000073 86

    360 44546029075354 43946034540

    1600AR216S160016001540160016003 440080012501600

    200In400400In800630In1250800In1600

    1000690

    50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

    126550650.03

    100.08

    3000015000120001000076 90

    360 44546029075354 43946034540

    2000AR220S200020002000200020003 4400800125016002000200In400400In800630In1250800In16001000In20001000690

    50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

    126550650.03

    100.08

    250001200010000700079 94

    360 44546029075354 43946034540

    2500AR325S250025002500250025003 42500

    1250In2500

    1000690

    65/14385/187 i50/11565/149.585/195.565/14385/195.585/195.540/4040/4065/15385/201 i65/15385/201 i

    128565850.03

    100.08

    200001000070005000105 125

    466 58646029075460 58046034540

    3200AR332S320032003200320032003 43200

    1600In3200

    1000690

    65/14385/187 i50/11565/149.585/195.565/14385/195.585/195.540/4040/4065/15385/201 i65/15385/201 i

    128565850.03

    100.08

    200001000070005000105 125

    466 58646029075460 58046034540

    q : Values in open air at 40C (45C for marine applications).w : Values of AR208S ~ 216S for draw-out type with horizontal terminals,

    Values of AR220S ~ 440S for draw-out type with vertical terminals.e : For 2poles use both opposite ends poles of 3poles ACBs.r : 4poles ACBs without Neutral phase protection can not be applied to

    IT earthing systems.t : Rated insulation voltage depends on applied standard: 1000V AC

    according to IEC 60947-2.

    4000AR440S400037003700400040003 44000

    2000In4000

    1000690

    75/165100/22065/149.575/172.5100/23075/165100/230100/23040/4040/4075/179100/24575/179100/245

    12100851000.03

    100.08

    15000800050002500139 176

    631 80146037553

    y : Rated operational voltage depends on applied standard: 690Vaccording to IEC 60947-2.

    u : Cannot apply IT earthing system, ie, insulated from earth.i : For 500V AC.o : Please contact TERASAKI for DC application.!0 : 3poles in series should be applied for 600V DC.!2 : Applicable to only 3poles ACBs.!3 : For vertical terminals or horizontal terminals.

    a c d

    b

    a c d

    b

  • 7Air Circuit BreakersAR High Fault Series1

    AMPERE RATING(A)TYPERATED CURRENT (max) [In](A) IEC, EN, AS

    q w JISNEMA, ANSIMarine

    NEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLES e rRATED PRIMARY CURRENT OF OVERCURRENTRELEASE [ICT](A) for general feeder circuit use

    RATED CURRENT OF OVERCURRENT RELEASE(A) for generator protection use[In] is generator rated current.

    AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) tRATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) yAC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]IEC,EN,AS AC 690V u[Ics = Icu] 440VNEMA AC 600VANSI 480V

    240VJIS AC 550V

    460V220V

    o DC 600V !0250V

    NK !2 AC 690V450V

    LR, AB, !2 AC 690VGL, BV 450V

    RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV)RATED SHORT TIME WITHSTAND 1sCURRENT[Icw][kA rms] 3sLATCHING CURRENT (kA)TOTAL BREAKING TIME (s)CLOSING OPERATION TIMESPRING CHARGING TIME (s) max.CLOSE TIME (s) max.No. of operating cycles Mechanical life with maintenance

    without maintenance Electrical life without maintenance AC460V

    AC690VWEIGHT (kg) draw-out typeOUTLINE DIMENSION (mm)DRAW-OUT aTYPE !3 b

    c

    d

    1250AR212H125012501250125012503 42004008001250

    100In200200In400400In800630In1250

    1000690

    55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186

    128055650.03

    100.08

    3000015000120001000079 94

    354 43946034540

    1600AR216H160016001600160016003 41600

    800In1600

    1000690

    55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186

    128055650.03

    100.08

    3000015000120001000079 94

    354 43946034540

    2000AR220H200020002000200020003 42000

    1000In2000

    1000690

    55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186

    128055650.03

    100.08

    3000015000120001000079 94

    354 43946034540

    1600AR316H160016001600160016003 420040080012501600100In200200In400400In800630In1250800In16001000690

    85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

    1210075850.03

    100.08

    2500012000100007000105 125

    460 58046034540

    2000AR320H200020002000200020003 42000

    1000In2000

    1000690

    85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

    1210075850.03

    100.08

    200001000070005000105 125

    460 58046034540

    2500AR325H250025002500250025003 42500

    1250In2500

    1000690

    85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

    1210075850.03

    100.08

    200001000070005000105 125

    460 58046034540

    3200AR332H320032003200320032003 43200

    1600In3200

    1000690

    85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

    1210075850.03

    100.08

    200001000070005000105 125

    460 58046034540a c d

    b

    q : Values in open air at 40C (45C for marine applications).w : Values for draw-out type with vertical terminals.e : For 2poles use both opposite ends poles of 3poles ACBs.r : 4poles ACBs without Neutral phase protection can not be applied to

    IT earthing systems.t : Rated insulation voltage depends on applied standard: 1000V AC

    according to IEC 60947-2.

    y : Rated operational voltage depends on applied standard: 690Vaccording to IEC 60947-2.

    u : Contact TERASAKI for details.o : Please contact TERASAKI for DC application.!0 : 3poles in series should be applied for 600V DC.!2 : Applicable to only 3poles ACBs.!3 : For vertical terminals.

    : When the ACB is used without Instantaneous trip function MCR should be set to work. The rated breaking capacity will reduce to the level of the latching currentwithout MCR function.

  • 8Air Circuit BreakersATAH Series1

    Frame Size (A)Type RATED CURRENT [In] (A) IEC, BS, VDE, AS (Max.) q JIS

    JEC !0NEMA, ANSIMarine

    Neutral Pole Amperes Frame (A) wNumber of Poles e RATED PRIMARY CURRENT OF

    OVER-CURRENT TRIP DEVICES [ICT] (A) for general feeder circuit use RATED CURRENT OF

    OVER-CURRENT TRIP DEVICES [Io] (A) for generator protection use ([Io] is generator rated current)AC Rated insulation voltage [Ui] (V) rRated operational voltage [Ue] (V) t AC RATED BREAKING CAP.(kA sym.)/MAKING CAP.(kA peak)

    with INST AC 690V !1[Ics]=100%[Icu] 600V !1

    500VUp to 415V

    with MCR AC 690V !1600V !1

    Up to 500Vwithout INST AC 690V !1

    Up to 500Vwith INST AC 600V

    480V240V

    with MCR AC 600VUp to 480V

    without INST Up to AC 600Vwith INST AC 550V

    460V220V

    with MCR AC 550VUp to 460V

    without INST Up to AC 550Vwith INST only DC 250V uwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500V

    Rated impulse withstand voltage [Uimp] (kV)Utilization CategoryRated short time withstand current 1Srms [Icw] (kA) 3SLatching current rms (kA)Total breaking time (s)Closing operation timeSpring charging time (s) max.Close time (s) max.Weight (kg) draw-out type (Motor Charging) OUTLINE DIMENSION (mm)Fixed aType b

    cd

    Draw-out aType b

    cd

    NOTE) : noor not available.q Values in open air at 40C (45C for marine applications). w Neutral current rating is equal to the max. applicable current rating, which varies depending on applicable standards. e 2-pole type is identicalto 3-pole type except the centre pole is omitted. 4-poles type can not be applied to Marine approval. r 1000V.AC. according to IEC60947-2. t 690V.AC. according to IEC60947-2. y 1700A for JECstandard. u DC rating is of special application. i Full rated neutral pole available on request. o Values at 480V AC. !0 Ratings are the actual performance not the recommended values of the standard.!1 Cannot apply IT earthing system, ie, insulated from earth. !2 86.1/203kA at 660V.AC. !3 87.6/203kA at 660V.AC.

    IECBS

    VDEAS[Ics]

    NEMA

    JIS

    ANSI

    JEC

    NK

    AB

    LR

    BV

    GL

    a c d

    b

    50

    a c d

    b

    50

    2000AT20L200020001700

    20002000 y3 4320 1600630 20001250

    690480

    130/286

    130/325130/325

    130/322 o

    130/322 o

    130/322 o

    130/322 o

    8A1717170.02

    100.0691 115

    368 45349245892

    2500AT25L250025002300

    25002000 i3 42500

    690480

    130/286

    130/325130/325

    130/322 o

    8A1717170.02

    100.06152 188

    518 65352645882

    4000AH-40C4000400036504000400032002,3 44000

    1600Io4000

    1000690

    85/18785/187120/264120/26485/18785/187100/22060/13260/132100/230120/276120/276100/230100/23060/138100/230120/300120/300100/230100/23060/13240/40120/286100/23160/138120/286100/23160/138124/280 !2108/23962.8/144120/286100/231

    120/286100/220

    8B10070600.03

    100.04240 280

    622 782655566106

    5000AH-50C5000500046505000500050002,3 45000

    2000Io5000

    1000690

    85/18785/187120/264120/26485/18785/187100/22070/15470/154100/230120/276120/276100/230100/23070/161100/230120/300120/300100/230100/23070/15440/40120/286100/23170/153120/286100/23170/153124/280108/23976.3/170120/286100/231

    120/264100/220

    8B10070700.03

    100.04350 450

    747 937685589146

    6300AH-60C6300615053006150600063002,3 46300

    2500Io6300

    1000690

    85/18785/187120/264120/26485/18785/187120/26470/15470/154100/230120/276120/276100/230120/27670/161100/230120/300120/300100/230100/30070/15440/40120/286120/28670/153120/286120/28670/153124/280 !3124/28077.37/166120/280100/239

    120/264

    8B12070700.03

    100.04380 480

    747 937685589146

  • 9Air Circuit BreakersAME Series for Generator protection1

    NOTES: : Available. : Not available.q : With long time-delay trip and short time-delay trip.w : Cannot use UVT and SHT jointly.e : Equipped as standard.r : Used for testing instantaneous trip function (separate mounting).

    NK standard requires at least one checker per vessel.t : Used for testing tripping characteristics with secondary current.

    Frame Size [A]TypeNumber of polesRated current of overcurrent trip device [A](ln is generator rated current)

    Rated insulation voltage (Ui) [VAC]Rated frequency [Hz] AC RATED BREAKING CAPACITY [kA sym. rms.] /RATED MAKING CAPACITY [kA peak]LR, AB, GL, with INST 460VBV, NK without INST q 460VRated short-time current (lcw) [kA, rms.] OPERATIONDirect manualExternal manual (option)Motorized (option) DIMENSIONS (mm)rear-connected (RC)/plug-in (PM)

    abcd

    CONNECTIONS AND MOUNTINGSRear connected Flat bar stud RCPlug-in For switchboard PMweight Direct manual operation/(Rear connected)(kg) Direct manual operation/(Plug-in) ACCESSORIES (option)Undervoltage trip w UTVShunt trip w SHTAuxiliary switch AXAlarm switch ALHandle extension (For direct manual) EHATerminal cover for rear connected plug-in TCROCR checker rOCR adapter t PROTECTIVE FUNCTIONSElectronic type LTD STD INST

    STD INST ENDURANCE

    Number of operations with currentNumber of operations without current

    Type AME 4B( Direct manual operation ) Type AME 4B( Motorized operation )

    250AME3B316 I

    n31.5

    31.5 In63

    63 In125

    125 In250

    60050/60

    16/34.84/6.874 (150ms)

    182/161260/282121/121255/245

    6.58.2

    e

    20008000

    400AME4B3200I

    n400

    60050/60

    16/34.86/10.26 (150ms)

    182/161260/282121/121255/245

    6.58.2

    e

    10009000

    630AME6B3315I

    n630

    60050/60

    20/42.610/17.410 (150ms)

    252/231273/303121/121267/270

    1016.1

    e e

    5004500

    800AME8B3500I

    n800

    60050/60

    30/63.815/33.015 (150ms)

    252/231370/370120/138282/336

    19.530.1

    e e

    5004500

    1000AME10B3800I

    n1000

    60050/60

    30/63.815/33.015 (150ms)

    252/231370/370120/138282/336

    19.530.1

    e e

    5004500

  • 10

    TemBreakz Moulded Case Circuit BreakersEconomical XE Series2

    Frame Size [A]TypeNumber of PolesOutside view

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    3 155 2010 30(40C only)

    220

    2.5

    2.5/1.3(220V)

    A

    45.5 689652670.27 0.4

    ' e

    y

    (AXE)

    30XE30NS2 3

    3 15 405 20 5010 30

    6660

    1.52.55

    1.5/0.8 @52.5/1.3 @52.5/1.32.5/1.35/2.5

    5

    2.55

    A

    50 7513068870.48 0.74

    ' e

    u

    (AXE) (ALE)

    50XE50NB2 3

    15 40 7520 50 10030 60(40C only)6660

    257.5

    2/1 @55/2.5 @55/2.55/2.57.5/3.8

    7.5

    510

    A

    50 7513068870.48 0.74

    ' r

    (AXE) (ALE)

    100XE100CB2 3

    10 30 6015 40 7520 50 100

    6660

    7.51025

    7.5/3.8 @510/5 @510/515/7.525/13

    25

    7.515

    A

    50 7513068870.48 0.74

    ' r

    u

    (AXE) (ALE)

    100XE100NS2 3

    15 40 7520 50 10030 60

    8690

    101425

    10/5 @514/714/718/925/13

    25

    1015

    A

    60 9015568860.78 1.1

    '

    (AXE) (ALE)

    100XE100HB2 3

    125 200150 225175

    8690

    57.515

    5/2.5 @57.5/3.87.5/3.87.5/3.815/7.5

    7.515

    1010

    A

    10516060831.4

    ' (BAR)

    (AXE) (ALE)

    !2

    225XE225CS3

    125 200150 225175

    8690

    101525

    10/5 @515/7.515/7.518/925/13

    1525

    1015

    A

    10516060831.4

    ' (BAR)

    (AXE) (ALE)

    !2

    225XE225NC3

    250 400300350

    8690

    152535

    15/7.5 @518/925/1325/1335/18

    1835

    2020

    A

    1402601031314.7

    ' (BAR)

    (AX) (AX)

    !2

    400XE400NS3

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.e : Comes with conductor pressing terminal.r : Comes with conductor pressing terminal for below 50A rating.

    y : Hydraulic-magnetic type for below 5A rating.u : Hydraulic-magnetic type for below 10A rating.o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

  • 11

    TemBreakz Moulded Case Circuit BreakersEconomical XE Series2

    Frame Size [A]TypeNumber of PolesOutside view

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    600XE600NS3

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.

    o : The UVT controller is installed externally, when provided with AC UVT.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

    500600

    8690

    182535

    18/9 @520/1025/1325/1335/18

    2035

    2020

    A

    2102731031459.0

    '

    (AX) (AL)

  • 12

    TemBreakz Moulded Case Circuit BreakersStandard XS Series2

    Frame Size [A]TypeNumber of PolesOutside view

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.e : Comes with conductor pressing terminal.

    u : Hydraulic-magnetic type for below 10A rating.o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

    3 155 2010 30

    6660

    1.52.55

    1.5/0.8 @52.5/1.3 @52.5/1.32.5/1.35/2.5

    5

    2.55

    A

    50 7513068870.48 0.74

    ' e

    u

    (AXE) (ALE)

    30XS30NB2 3

    10 3015 4020 50

    6660

    57.510

    5/2.5 @57.5/3.8 @57.5/3.810/510/5

    10

    7.515

    A

    50 7513068870.48 0.74

    ' e

    u

    (AXE) (ALE)

    50XS50CB2 3

    10 3015 4020 50

    6660

    7.51025

    7.5/3.8 @510/5 @510/515/7.525/13

    25

    7.515

    A

    50 7513068870.48 0.74

    ' e

    u

    (AXE) (ALE)

    50XS50NB2 3

    60

    6660

    7.51025

    7.5/3.8 @510/5 @510/515/7.525/13

    25

    7.515

    A

    50 7513068870.48 0.74

    '

    (AXE) (ALE)

    15 40 7520 50 10030 60

    8690

    1525505/2.5 @512/6 @525/1325/1330/1550/25

    50

    1520

    A

    60 90 12015568860.78 1.1 1.4

    '

    (AXE) (ALE)

    !2

    100XS100NB2 3 4

    125 200150 225175

    8690

    2225508/4 @522/11 @525/1325/1335/1850/25222550

    4040

    A

    105 140165861071.85 2.4

    ' (BAR)

    (AXE) (ALE)

    225XS225NS3 4

    60XS60NS2 3

    FOR JAPANESE MARKET

  • 13

    TemBreakz Moulded Case Circuit BreakersStandard XS Series2

    600XS600NE3 4

    800XS800NS3 4

    800XS800CS3 4

    600XS600NS3 4

    600XS600CS3 4

    400XS400NS3 4

    400XS400NE3 4

    700800

    8690

    35508520/10 @535/18 @550/2550/2565/3385/43305085

    4040

    A

    210 2802731031459.4 12.2

    '

    !3

    (AX) (AL)

    700800

    8690

    25355016/8 @525/13 @530/1535/1845/2350/25253550

    4040

    A

    210 2802731031459.4 12.2

    '

    !3

    (AX) (AL)

    Adjustable300 500350 6004008690

    35508520/10 @535/18 @550/2550/2550/2585/4330508510

    10 (0.3sec)B

    210 2802731031459.6 12.0

    '

    !3

    (AX) (AL)

    300 6004005008690

    35508520/10 @535/18 @550/2550/2565/3385/43305085

    4040

    A

    210 2802731031459.0 11.5

    '

    !3

    (AX) (AL)

    300 6004005008690

    25355016/8 @525/13 @530/1535/1845/2350/25253550

    4040

    A

    210 2802731031459.0 11.5

    '

    !3

    (AX) (AL)

    Adjustable125 200 200 300150 225 225 350175 250 4008690

    35508518/9 @530/15 @542/2150/2550/2585/433042855

    5 (0.3sec)B

    140 1852601031314.8 6.2

    ' (BAR)

    !3

    (PTA only)

    (AX) (AL)

    !2

    125 200 300150 225 350175 250 4008690

    35508518/9 @530/15 @542/2150/2550/2585/43304285

    4040

    A

    140 1852601031314.7 6.1

    ' (BAR)

    !3

    (AX) (AL)

    !2

    125 200 300150 225 350175 250 4008690

    22305016/8 @522/11 @530/1535/1835/1850/25223050

    4040

    A

    140 1852601031314.7 6.1

    ' (BAR)

    !3

    (AX) (AL)

    !2

    400XS400CS3 4

    Frame Size [A]TypeNumber of PolesOutside view

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.

    o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!3 : Special specification.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

  • 14

    TemBreakz Moulded Case Circuit BreakersStandard XS Series2

    Frame Size [A]TypeNumber of PolesOutside view* 2 pole breaker is a 3 pole breaker with the center pole omitted.

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.

    o : The UVT controller is installed externally, when provided with AC UVT.!0 : One is supplied with every five breakers. Please specify if more are required.!3 : Special specification.!4 : Handle is supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Magnetic trip only. Contact Terasaki for details.@5 : The application on IT systems on this voltage is not available.

    2500XS2500NE3 4

    2000XS2000NE3 4

    1600XS1600NE3 4

    1000XS1000NE3 4

    1200XS1200NE3 4

    Adjustable1200 20001400 250016008690

    658513045/42 @565/49 @585/6485/64100/75125/94658512542

    42 (0.3sec)B

    320 42945018524562.5 78.2

    '

    (AX) (AL)

    !4

    Adjustable1000 16001200 18001400 20008690

    658513045/42 @565/49 @585/6485/64100/75125/94658512542

    42 (0.3sec)B

    320 42945018524554.0 67.0

    '

    (AX) (AL)

    !4

    Adjustable800 1200900 14001000 16008690

    658513045/34 @565/49 @585/6485/64100/75125/94658512520

    20 (0.3sec)B

    210 28037014019127.0 35.0

    '

    (AX) (AL) !0

    Adjustable600 1000700 12008008690

    506510025/19 @545/34 @565/4965/4985/64100/7542658515

    15 (0.3sec)B

    210 28037012017122.0 28.0

    '

    !3

    (AX) (AL) !0

    Adjustable500 800600 900700 10008690

    506510025/19 @545/34 @565/4965/4985/64100/7542658515

    15 (0.3sec)B

    210 28037012017122.0 28.0

    '

    !3

    (AX) (AL) !0

    800XS800NE3 4

    Adjustable400 600450 700500 8008690

    35508520/10 @535/18 @550/2550/2550/2585/4330508510

    10 (0.3sec)B

    210 2802731031459.7 12.5

    '

    !3

    (AX) (AL)

  • 15

    TemBreakz Moulded Case Circuit BreakersHigh-fault Level XH Series2

    15 4020 50308690

    3550858/4 @525/13 @542/2150/2550/2585/43

    85

    4040

    A

    90 120155861041.3 1.58

    '

    (AXE) (ALE)

    !2

    400XH400NE3 4

    800XH800PS3 4

    800XH800NE3 4

    600XH600NE3 4

    225XH225NE3 4

    225XH225NS3 4

    50XH50NS3 4

    100XH100NS3 4

    700800

    8690

    658513045/23 @565/33 @585/4385/43100/50125/636585125

    4040

    A

    210 2802731031459.4 12.2

    '

    !3

    (AX) (AL)

    Adjustable400 600450 700500 8008690

    506510020/10 @542/21 @565/3365/3365/33100/5042658510

    10 (0.3sec)B

    210 2802731031459.7 12.5

    '

    !3

    (AX) (AL)

    Adjustable300 500350 6004008690

    506510020/10 @542/21 @565/3365/3365/33100/5042658510

    10 (0.3sec)B

    210 2802731031459.6 12.0

    '

    !3

    (AX) (AL)

    Adjustable125 200 200 300150 225 225 350175 250 4008690

    506510020/10 @542/21 @565/3365/3365/33100/504265855

    5 (0.3sec)B

    140 1852601031314.8 6.2

    ' (BAR)

    !3

    (PTA only)

    (AX) (AL)

    !2

    Adjustable125 200150 2251758690

    35508518/9 @530/15 @542/2150/2550/2585/433042855

    5 (0.3sec)B

    140 1852601031314.8 6.2

    ' (BAR)

    !3

    (PTA only)

    (AX) (AL)

    !2

    125 200150 2251758690

    35508515/7.5 @525/13 @542/2150/2550/2585/43254285

    4040

    A

    105 1401651031242.1 2.6

    ' (BAR)

    !3

    (AXE) (ALE)

    !2

    15 40 7520 50 10030 608690

    3550858/4 @525/13 @542/2150/2550/2585/43

    85

    4040

    A

    90 120155861041.3 1.58

    '

    (AXE) (ALE)

    !2

    Frame Size [A]TypeNumber of PolesOutside view

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    NOTES: ' : Standard. This configuration is used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.

    o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!3 : Special specification.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

    FOR JAPANESE MARKET

    FOR JAPANESE MARKET

  • 16

    TemBreakz Moulded Case Circuit BreakersMotor Protection XM Series2

    200- 400-220V 440V

    [Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 2515 32

    6660

    2.552.5/1.32.5/1.35/2.5

    5A

    7513068870.74

    ' e

    i

    (AXE) (ALE)

    100- 200-110V 220V

    [Kw] [A] [A]0.1 40.2 6.3 1.40.4 10 2.60.75 16 4.21.5 7.42.2 103.7 165.5 257.5 33

    6220

    2.5

    2.5/1.3-(220V)

    A

    45.5 689652670.27 0.4

    ' e

    (AXE)

    RATINGSVoltage for motor 50/60 Hz

    Motor output and rated current at 40C(45C for marine applications)

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 460V

    220VIEC 60947-2 Icu/Ics 415VBS EN 60947-2 380V

    240VNEMA AB-1 480V

    240VUtilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSHydraulic-magnetic tripsThermal and fixed magnetic trips STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    50XM50NB3

    225XM225NS3

    100XM100NB3

    100XM100CS3

    50XM50CB3

    30XM30PB3

    30XM30CS2 3

    30XM30NB3

    200- 400-220V 440V

    [Kw] [A] [A]30 12537 15045 17555 22575 15090 175110 225

    8690

    255025/1335/1850/252550A

    105165861071.85

    ' (BAR)

    (AXE) (ALE)

    !2

    200- 400-220V 440V

    [Kw] [A] [A]3.7 165.5 257.5 32 1611 45 2515 60 3218.5 75 4022 90 4530 6037 7545 9055 100

    8690

    255025/1330/1550/25

    50A

    9015568861.1

    '

    (AXE) (ALE)

    !2

    200- 400-220V 440V

    [Kw] [A] [A]15 6318.5 7522 9030 6337 7545 9055 100

    6660

    102510/515/7.525/13

    25A

    7513068870.74

    '

    (AXE) (ALE)

    200- 400-220V 440V

    [Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 45 2515 3218.5 4022 456660

    10 !62510!6/5!715!6/7.5!725/13

    25A

    7513068870.74

    ' e

    i

    (AXE) (ALE)

    200- 400-220V 440V

    [Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 45 2515 3218.5 4022 456660

    2.552.5/1.32.5/1.35/2.5

    5A

    7513068870.74

    ' e

    i

    (AXE) (ALE)

    200- 400-220V 440V

    [Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 85.5 12

    6660

    8512585/8585/85125/125

    125A

    78147.5981171.78

    ' e

    (AXE) (ALE)

    Frame Size [A]TypeNumber of PolesOutside view

    d

    b

    ca

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.e : Comes with conductor pressing terminal.i : Hydraulic-magnetic type for below 25A rating.

    o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!6 : 7.5kA for below 8A rating.!7 : 3.8kA for below 8A rating.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.

  • 17

    TemBreakz Moulded Case Circuit BreakersD.C. Application Series2

    Frame Size [A]TypeNumber of PolesOutside view* 2 pole breaker is a 3 pole breaker with the center pole omitted.

    RATED CURRENT (In) [A]at 40C

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VDC] RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 AC 550V

    460V220V

    DC 250VIEC 60947-2 Icu/Ics AC 690VBS EN 60947-2 500V

    440V415V380V240V

    DC 250VNEMA AB-1 AC 600V

    480V240V

    Without Inst. AC 240-690VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    d

    b

    ca

    2500XS2500ND*2 3

    2000XS2000ND*2 3

    1200XS1200ND*2 3

    1600XS1600ND*2 3

    2500 @4

    8600

    40

    40/30

    A

    32045018524555.7 62.5

    '

    @4

    (AX) (AL)

    !4

    2000 @4

    8600

    40

    40/30

    A

    32045018524550.0 54.0

    '

    @4

    (AX) (AL)

    !4

    1600 @4

    8600

    40

    40/30

    A

    21037014019124.0 27.0

    '

    @4

    (AX) (AL) !0

    1200 @4

    8600

    40

    40/30

    A

    21037014019123.8 26.0

    '

    @4

    (AX) (AL) !0

    1000XS1000ND*2 3

    1000

    8600

    40

    40/20

    A

    2102731031459.2 10.3

    '

    (AX) (AL)

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.

    !0 : One is supplied with every five breakers. Please specify if more are required.!4 : Handle is supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Magnetic trip only.

  • 18

    600TL-600NE3 4

    1200TL-1200NE3 4

    1000TL-1000NE3 4

    800TL-800NE3 4

    400TL-400E3 4

    225TL-225F3

    100TL-100F3 4

    BAdjustable600 1000700 1200800690

    6512515045/34 @575/57 @5125/65125/65125/65150/113658512515

    815 (0.3sec)

    210 28037014019126.0 33.7

    '

    !3

    (AX) (AL) o !0

    Frame Size [A]TypeNumber of PolesOutside view

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.o : The UVT controller is installed externally when provided with AC UVT.!0 : One is supplied with every five breakers. Please specify if more are required.

    !3 : Special specification.!4 : Rated current shown in ( ) is for 4 poles only, and special specification.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

    BAdjustable500 800600 900700 1000690

    6512515045/34 @575/57 @5125/65125/65125/65150/113658512515

    815 (0.3sec)

    210 28037014019126.0 33.7

    '

    !3

    (AX) (AL) o !0

    Utilization Category RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.] DIMENSIONS (mm)

    abcd/e

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    BAdjustable400 600450 700500 800690

    6512515045/34 @575/57 @5125/70125/70125/70150/113658512515

    815 (0.3sec)

    210 28037014019125.8 33.5

    '

    !3

    (AX) (AL) o !0

    BAdjustable300 500350 600400690

    6512515045/34 @575/57 @5125/70125/70125/70150/113658512515

    815 (0.3sec)

    210 28037014019125.8 33.5

    '

    !3

    (AX) (AL) o !0

    A250 400 (175)300 (125) (200)350 (150) (225)!4690

    7512012045/23 @575/38 @5120/60120/60120/60120/6075120120

    40408

    160 2122601331678.5 10

    ' (BAR)

    !3

    (AX) (AL)

    (TYD)

    A125 200150 225175

    690

    6012012025/13 @560/30 @5120/60120/60120/60120/606075120

    40408

    1402601331676.0

    ' (BAR)

    (AX) (AL)

    (TYD)

    A15 40 7520 50 10030 60

    690

    4212012025/13 @560/30 @5120/60120/60120/60120/604275120

    40408

    105 1401651251433.2 3.8

    '

    (AX) (AL)

    (TYD)

    z Moulded Case Circuit BreakersCurrent-limiting Breakers, TL Series (120kA)2

    d e

    b

    ca

  • 19

    800TL-8003

    600TL-6003

    400TL-4003

    100TL-100C3

    225TL-225B3

    Frame Size [A]TypeNumber of PolesOutside view

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.

    !5 : Specify rated frequency, 50 or 60Hz.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

    Utilization Category RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.] DIMENSIONS (mm)

    abcd/e

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    A15 40 7520 50 10030 60

    690

    8518018050/38 @585/64 @5180/135180/135180/135180/13585180180

    40408

    110230133162/4.7

    '

    (AX) (AL)

    (TYD)

    A700800 !4

    !5690

    8518018050/38 @585/64 @5180/135180/135180/135180/13585180180

    40408

    240400133199/6327

    '

    (AX) (AL)

    (TYD)

    A450500600

    690

    8518018050/38 @585/64 @5180/135180/135180/135180/13585180180

    40408

    240400133199/6327

    '

    (AX) (AL)

    (TYD)

    A125 200 300150 225 350175 250 400

    690

    8518018050/38 @585/64 @5180/135180/135180/135180/13585180180

    40408

    210300133202/5617.7

    ' (BAR)

    (AX) (AL)

    (TYD)

    A125 200150 225175

    690

    8518018050/38 @585/64 @5180/135180/135180/135180/13585180180

    40408

    140260133183/469.3

    ' (BAR)

    (AX) (AL)

    (TYD)

    z Moulded Case Circuit BreakersCurrent-limiting Breakers, TL Series (180kA)2

    d e

    b

    ca

  • 20

    3200TT-32003

    4000TO-40003

    3200TO-32003

    Frame Size [A]TypeNumber of PolesOutside view

    NOTES: ' : Standard. This configuration is used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : DC rating available on request.

    !3 : Special specificacion.!5 : Specify rated frequency, 50 or 60Hz.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.

    A4000

    !5690

    658513045/3465/4985/6485/64100/75130/986585130

    40408

    390560235315120

    '

    (AX) (AL)

    (TYD)

    B250028003200

    !5690

    658513045/4265/4985/6485/64100/75130/98658513042

    842 (0.3sec)

    390560235315120

    '

    (with Adi. STD)

    (AX) (AL)

    !6

    (TYD)

    A250028003200

    !5690

    658513045/3465/4985/6485/64100/75130/986585130

    40408

    390560235315120

    '

    (AX) (AL)

    !6

    (TYD)

    Utilization Category RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

    460V220V

    IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.] DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

    STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.F

    z Moulded Case Circuit BreakersTO/TT Series2

    d

    b

    ca

  • 21

    Frame Size [A]TypeNumber of PolesOutside viewNRC=Nominal Rated CurrentASR=Adjustable Setting Range

    NOTES: ' : Standard. This configuration is used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.

    o : For AC UVT, a UVT controller is mounted externally.!0 : One is supplied with every five breakers. Please Specify if more are required.!2 : Line side interpole barriers are supplied as standard.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Values at 1000V AC.

    15 5020 6030 7540 1001100

    6.510

    1051651251433.2

    '

    (AX)(AL)

    !2 (TYD)

    NRC ASRmin. max.

    250 125 250400 200 4001100

    12.5

    1402601031314.8

    ' (BAR)

    (PTA only)

    (AX)(AL) o

    NRC ASRmin. max.

    630 315 630

    1100

    12.518 @4

    2102731031459.6

    '

    (AX)(AL) o

    NRC ASRmin. max.

    800 400 800

    1100

    12.518 @4

    2102731031459.7

    '

    (AX)(AL) o

    NRC ASRmin. max.

    1000 500 10001250 630 12501100

    20

    21037012017122.0

    '

    (AX)(AL) o !0

    RATED CURRENT (IN) [A]Calibrated at 40C

    Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]cos =0.3 1100V

    900V DIMENSIONS (mm)

    abcd

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) STANDARD FEATURESon off colour indicationTrip button PROTECTIVE FUNCTIONSElectronic type

    Adjustable LTD, STD & INSTAdjustable GFT or Adjustable PTA (option)Trip indicators (option)

    Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips

    ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2 LTF

    @3 LTSDoor flange D.FIP20 protection (plug-in type) IP20

    TemBreakz Moulded Case Circuit BreakersMining Series2

    d

    b

    ca

    100TL-100EM3

    400XV400NE3

    630XV630PE3

    800XV800PE3

    1250XV1250NE3

  • 22

    TemBreakz Moulded Case Circuit BreakersNon-automatic Trip Breakers2

    Frame size (A)TypeNumber of polesOutside view

    RATINGRated current (In) [A] at 45CRated insulation voltage (Ui) [V AC]Rated operational voltage [V] AC 50/60Hz

    DCRated short circuit making capacity [kA peak]Rated short time current (Icw) [kA rms] DIMENSIONS (mm)

    abcd

    Outline dimensions same as forWeight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

    Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

    For distribution boardDraw-out (DO) STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX,AXEmounted Alarm switch AL,ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear connect/ plug-in type TCRInterpole barrier TBAAccessory lead terminal LTF

    LTSDoor flange D.F

    Max. Switching Current [A] ACDC

    Endurance with current(No. of operating cycles) without current

    e : Comes with conductor pressing terminal.o : The UVT controller is installed externally, when provided with AC UVT.

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.

    d

    b

    ca

    100XS100NNB2 3 4

    1006906902502.51.8 (1sec)

    60 90 1201556886XS100NB0.78 1.1 1.4

    '

    (AXE)(ALE)

    60025060004000

    30XS30NNB2 3

    306606602502.51.8 (1sec)

    50 751306887XS30NB0.48 0.74

    ' e

    (AXE)(ALE)

    1807560004000

    50XS50NNB2 3

    506606602502.51.8 (1sec)

    50 751306887XS50NB0.48 0.74

    ' e

    (AXE)(ALE)

    30012560004000

    100XE100NN2 3

    1006606602502.51.8 (1sec)

    50 751306887XE100NS0.48 0.74

    '

    (AXE)(ALE)

    60025060004000

    225XE225NNC3

    2256906902505.53 (1sec)

    1051606083XE225NC1.4

    ' (BAR)

    (AXE)(ALE)

    135056040004000

    225XS225NN3 4

    22569069025064 (1sec)

    105 14016586107XS225NS1.85 2.4

    ' (BAR)

    (AXE)(ALE)

    135056040004000

    400XS400NN3 4

    40069069025095 (1sec)

    140 185260103131XS400NS4.7 6.1

    ' (BAR)

    (AX)(AL)

    2400100010005000

  • 23

    TemBreakz Moulded Case Circuit BreakersNon-automatic Trip Breakers2

    Frame size (A)TypeNumber of polesOutside view

    RATINGRated current (In) [A] at 45CRated insulation voltage (Ui) [V AC]Rated operational voltage [V] AC 50/60Hz

    DCRated short circuit making capacity [kA peak]Rated short time current (Icw) [kA rms] 1sec DIMENSIONS (mm)

    abcd

    Outline dimensions same as forWeight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

    Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

    For distribution boardDraw-out (DO) STANDARD FEATURESon off colour indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX,AXEmounted Alarm switch AL,ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear connect/ plug-in type TCRInterpole barrier TBAAccessory lead terminal LTF

    LTSDoor flange D.F

    Max. Switching Current [A] ACDC

    Endurance with current(No. of operating cycles) without current

    d

    b

    ca

    600XS600NN3 4

    600690690250159.6 (0.3sec)

    210 280273103145XS600NS9.0 11.5

    '

    (AX)(AL)

    3600150010005000

    800XS800NN3 4

    800690690250159.6 (0.3sec)

    210 280273103145XS800NS9.4 12.2

    '

    (AX)(AL)

    480020005003500

    1000XS1000NN3 4

    10006906902503215 (0.3sec)

    210 280370120171XS1000NE20.4 26.4

    '

    (AX)(AL)

    600025005002500

    1200XS1200NN3 4

    12006906902503215 (0.3sec)

    210 280370120171XS1200NE20.4 26.4

    '

    (AX)(AL)

    720030005002000

    1600XS1600NN3 4

    16006906902504520 (0.3sec)

    210 280370140191XS1600NE24.9 32.9

    '

    (AX)(AL)

    960040005002000

    2000XS2000NN3 4

    20006906902509035 (0.3sec)

    320 429450185245XS2000NE51.8 64.8

    '

    (AX)(AL)

    !2

    1200050005002000

    2500XS2500NN3 4

    25006906902509035 (0.3sec)

    320 429450185245XS2500NE60 75.7

    '

    (AX)(AL)

    !2

    1500062505002000

    o : The UVT controller is installed externally, when provided with AC UVT.!2 : Handle is supplied as standard.

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.

    These are the switches without automatic trip units, and the switching capacity is 6 times the rated current.Remote tripping is possible when equipped with shunt trip or undervoltage trip.Auxiliary switch or alarm switch can also be fitted. For the details on the specifications please contactTERASAKI.

  • 24

    15/30}620/45}935/75}1550/100}20100/200}40250500

    6 12.852.5 23.355 170

    110230133162

    4.7

    '

    (AX)(AL)

    (TYD)

    100TL-100SC3

    225TL-225SB3

    400TL-400S3

    600TL-600S3

    800TL-800S3

    900TL-1000S3

    125/300}30200/400}40225/600}60225/750}75

    250500

    6 12.852.5 23.370 450

    140260133183469.3

    '

    (AX)(AL)

    (TYD)

    250/500}50300/600}60400/800}80400/1100}110400/1500}150250500

    6 12.852.5 23.3140 430

    2103001332025617.7

    '

    (AX)(AL)

    (TYD)

    600/1100}110600/1500}150600/1900}190600/2300}230

    250500

    6 12.852.5 23.3140 330

    2404001331996327

    '

    (AX)(AL)

    (TYD)

    800/1100}110800/1500}150800/1900}190800/2300}230

    250500

    6 12.852.5 23.3220 400

    2404001331996327

    '

    (AX)(AL)

    (TYD)

    900/1900}190900/2300}230

    250500

    6 12.852.5 23.3220 400

    2404001331996327

    '

    (AX)(AL)

    (TYD)

    RATINGSRated current [A] at 40C / magnetic trip current [A]

    DC rated voltage [V] 2 poles in series3 poles in series

    Examples of I2t let-through at faultinterruption (500V DC)Prospective SC fault [kA]Time-constant [ms]I2t103 A2 s DIMENSIONS (mm)

    abcde

    Weight (kg) ' marked standard type CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

    Attached flat barSolderless terminal (PWC)

    Rear connect (RC) Bolt studFlat bar stud

    Plug-in (PM) For switchboardFor distribution board

    Draw-out (DO) PROTECTIVE FUNCTIONSFixed magnetic trip (INST trip only) ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip UVT

    Externally Motor operator MOTmounted External operating handle OHE

    OHJOHH

    Extension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle lock HLInterpole barrier TBAAccessory lead terminal @2 LTF

    @3 LTSDoor flange D.F

    Frame Size [A]TypeNumber of polesOutside view

    NOTES: ' : Standard, this configuration used unless otherwise specified. : Optional standard, specify when ordering. : yes or available. : no or not available.

    @2 : Draw out leads horizontally.@3 : Draw out leads vertically.

    d e

    b

    ca

    z Moulded Case Circuit BreakersThyristor Protection Breakers2

  • 25

    10 30 (6) (32)15 40 (16) (63)20 50 (25)q460

    2.5 2.5 2.52.5 2.5 2.5 5 w 5 w 5 w 5 5 5 5 6(3) 6(3) 6(3)6(3) 6(3) 6(3) 6(3)6(3) 6(5) 6(5) r 10(5) 10(5) 10(5) 10(5) 10(5) 1 5

    25 50 75 100956077 79160 340 500 660

    '

    '

    10 30 (25)15 40 (32)20 50 (63)q460

    2.5 2.5 2.5 2.5 5 w 5 5 5 6(3)

    6(3) 6(3)6(3) 6(5) 6(5) 10(5)r 10(5) 10(5)10(5) 10(5) 10(5) 5

    25 50 7574.56077 79130 280 410

    '

    10 3015 4020 50

    250

    5555

    5074.56079280

    '

    60 (80)75100q460

    5 5 55 5 5 5 5 55 5 5 5 5 6 6 66 6 6 66 10 10 1010 10 10 10 10 10 1 5

    25 50 75 100956077 80210 420 630 840

    '

    '

    60 (80)75100q460

    6 66 6 66 10 1010 10 1010 10 101 5

    25 50 7577.56077 80210 420 490

    '

    50TB-5S1 2 3 4

    50TB-5P1 2 3

    50TB-5D2

    100TB-10S1 2 3 4

    100TB-10P1 2 3

    RATED CURRENT (In) [A]at 40C (45C for marine applications)

    Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 460V

    265V220V110/220V110V

    BS 3871 part1 e 440V254/440V380V,415V220/380V,240/415V220V,240V120/240V120V

    DC RATED BREAKING CAPACITY [kA] 125V DIMENSIONS (mm)

    abcd

    Weight (g) CONNECTIONSFront-connect (FC)Plug-in (line end)Front-connect (load end)Plug-in MOUNTINGS (optional)ClipClip-in chassisDouble mounting baseSingle mounting base PROTECTIVE FUNCTIONSThermal and fixed magnetic trips ACCESSORIES (option) CODEShunt trip SHTHandle holder HHHandle lock HLHandle capFlash plateProtection coverInterpole barrier TBA

    Frame Size [A]TypeNumber of polesOutside view

    Accessories for TB series

    NOTES: ' : Standard. : yes or available. : no or not available.

    q : Rated current shown in ( ) available on request. (except JIS and marine standard).w : 2.5kA for 10A rating.e : Rated breaking capacities shown in ( ) are applied to 6A and 10A ratings.r : Apply its breaking capacity at 120V. AC if necessary.

    shunt trip protective cover handle holder handle lock(for single poletype use only)

    handle cap flash plate

    type: TKB-50SGH (red) type: TKB-50SG (red)type: TAA-5CR (red)

    TAA-5CY (yellow)TAA-5CG (green)

    d

    b

    ca

    Miniature Circuit BreakersTB Series for Distribution Board Use2

  • 26

    TemBreakz Moulded Case Circuit BreakersAdjustable Thermal Trip2

    RATED CURRENT (In) [A]at 45C

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V400V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' Marked standard type CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

    Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

    For distribution boardDraw-out (DO) PROTECTIVE FUNCTIONSAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips STANDARD FEATURESon off color indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.FIP20 protection Plug-in type IP20

    125 125 160 250 250 400 400 630XS125CJ XS125NJ XS160NJ XS250NJ XS250PJ XS400CJ XS400NJ XS630CJ*3 4 *3 4 *3 4 *3 4 *3 4 *3 4 *3 4 *3 4

    d

    b

    ca

    Frame Size [A]TypeNumber of PolesOutside viewNOTE: *2 pole breaker is 3 pole breaker with centre pole

    omitted.

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : D C rating available on request.o : The UVT controller is installed externally when provided with AC UVT.@2 : Draw out leads horizontally@3 : Draw out leads vertically@5 : The application on IT systems on this voltage is not available.

    Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj.range Rated Adj.range Rated Adj.range Rated Adj.range Rated Adj.rangeCurr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. 20 12.5 20 20 12.5 20 160 100 160 160 100 160 160 100 160 250 160 250 250 160 250 400 250 400 32 20 32 32 20 32 250 160 250 250 160 250 400 250 400 400 250 400 630 400 630 50 32 50 50 32 50 63 40 63 63 40 63100 63 100 100 63 100125 80 125 125 80 1258 8 8 8 8 8 8 8690 690 690 690 690 690 690 690

    5/2.5 @5 8/4 @5 8/4 @5 8/4 @5 16/8 @5 18/9 @5 16/8 @57.5/3.8 @5 12/6 @5 22/11 @5 22/11 @5 22/11 @5 22/11 @5 30/15 @5 25/13 @510/5 22/11 25/13 25/13 25/13 30/15 42/21 30/1514/7 25/13 25/13 25/13 35/18 35/18 50/25 35/1818/9 30/15 35/18 35/18 35/18 35/18 50/25 45/2318/9 30/15 35/18 35/18 35/18 35/18 50/25 45/2325/13 50/25 50/25 50/25 50/25 50/25 85/43 50/25 12 22 22 22 22 30 2510 22 25 25 25 30 42 3525 50 50 50 50 50 85 50

    10 15 40 40 40 40 40 4015 20 40 40 40 40 40 40

    A A A A A A A A

    90 120 90 120 105 140 105 140 105 140 140 185 140 185 210 280155 155 165 165 165 260 260 27386 86 86 86 103 103 103 103104 104 107 107 124 131 131 1451.3 1.58 1.3 1.58 1.85 2.4 1.85 2.4 2.1 2.6 4.7 6.1 4.7 6.1 9.0 11.5

    ' ' ' ' ' ' ' (BAR) (BAR) (BAR) (BAR) (BAR) '

    (AXE) (AXE) (AXE) (AXE) (AXE) (AX) (AX) (AX)(ALE) (ALE) (ALE) (ALE) (ALE) (AL) (AL) (AL)

  • 27

    TemBreakz Moulded Case Circuit BreakersAdjustable Thermal Trip2

    630 800 125 160 250XS630NJ XS800NJ XH125NJ XH160NJ XH250NJ*3 4 *3 4 *3 4 *3 4 *3 4

    Frame Size [A]TypeNumber of PolesOutside viewNOTE: *2 pole breaker is 3 pole breaker with centre pole

    omitted.

    RATED CURRENT (In) [A]at 45C

    Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC] AC RATED BREAKING CAPACITY [kA sym. rms.]IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

    440V415V400V380V240V

    NEMA AB-1 600V480V240V

    Without Inst. 240-690V DC RATED BREAKING CAPACITY [kA] q 250V

    125VRated short time current (lcw) [kA. rms.]Utilization Category DIMENSIONS (mm)

    abcd

    Weight (kg) ' Marked standard type CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

    Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

    For distribution boardDraw-out (DO) PROTECTIVE FUNCTIONSAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips STANDARD FEATURESon off color indicationTrip button ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

    Shunt trip SHTUndervoltage trip o UVT

    Externally Motor operator MOTmounted External Panel mount. type OHE

    operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

    @3LTSDoor flange D.FIP20 protection Plug-in type IP20

    d

    b

    ca

    Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj. rangeCurr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max.400 250 400 800 500 800 20 12.5 20 160 100 160 160 100 160630 400 630 32 20 32 250 160 250

    50 32 50 63 40 63100 63 100125 80 125

    8 8 8 8 8690 690 690 690 690

    20/10 @5 20/10 @5 8/4 @5 15/7.5 @5 15/7.5 @535/18 @5 35/18 @5 25/13 @5 25/13 @5 25/13 @550/25 50/25 42/21 42/21 42/2150/25 50/25 50/25 50/25 50/2565/33 65/33 50/25 50/25 50/2565/33 65/33 50/25 50/25 50/2585/43 85/43 85/43 85/43 85/4330 30 25 25 2550 50 42 42 4285 85 85 85 85

    40 40 40 40 4040 40 40 40 40

    A A A A A

    210 280 210 280 90 120 105 140 105 140273 273 155 165 165103 103 86 103 103145 145 104 124 1249.0 11.5 9.4 12.2 1.3 1.58 2.1 2.6 2.1 2.6

    ' ' '' ' (BAR) (BAR)

    (AX) (AX) (AXE) (AXE) (AXE)(AL) (AL) (ALE) (ALE) (ALE)

    NOTES: ' : Standard. This configuration used unless otherwise specified. : Optional standard. Specify when ordering. : yes or available. : no or not available.q : D C rating available on request.o : The UVT controller is installed externally when provided with AC UVT.@2 : Draw out leads horizontally@3 : Draw out leads vertically@5 : The application on IT systems on this voltage is not available.

  • 28

    Approvals and Applicable Breaking Capacities to Marine Standards.Breaker Rated Poles Ratedtype current[A] voltage[V]XS30NB 3,5,10,15,20,30 2,3 500

    250125

    XE50NB 3,5,10,15,20,30,40,50 2,3 500250125

    XS50CB 10,15,20,30,40,50 2,3 500250125

    XS50NB 10,15,20,30,40,50 2,3 500250125

    XH50NS 15,20,30,40,50 3 500FOR JAPANESE MARKET 250XS60NS 60 2,3 500FOR JAPANESE MARKET 250

    125XE100NS 10,15,20,30,40, 2,3 500

    50,60,75,100 250125

    XS100NB 15,20,30,40,50, 2,3 50060,75,100 250

    XH100NS 15,20,30,40,50, 3 50060,75,100 250

    XE225NS!7 125,150,175,200,225 3 500FOR JAPANESE MARKET 250XS225NS 125,150,175,200, 3 500

    225 250XH225NS 125,150,175,200, 3 500

    225 250XH225NE 125~225 3 500

    125,150,175,200, 250225 500

    FOR JAPANESE MARKET 250XS400CS 125,150,175,200,225 3 500

    250,300,350,400 250XS400NS 125,150,175,200,225 3 500

    250,300,350,400 250XS400NE 125~225,200~400 3 500

    125,150,175,200, 250225,250,300,350, 500400 250

    XS600CS 300,400,500,600 3 500250

    XS600NS 300,400,500,600 3 500250

    XS600NE 300~600 3 500300,350,400,500, 250600 500

    250XS800CS 700,800 3 500

    250XS800NS 700,800 3 500

    250XS800NE 400~800 3 500

    400,450,500,600, 250700,800 500

    250

    AC Rated breaking capacity [kA sym. rms.]/Rated making capacity [kA peak]NK LR AB GL BV2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.642/96.785/19810/18.525/53.242/95.610/18.525/53.242/95.622/50.150/11542/96.785/19815/31.325/53.225/56.250/11542/96.785/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w

    5 5 5

    5 5 5

    7.5 7.5 7.5

    7.5 7.5 7.5 7.5 7.515

    40 40.6 40 40

    7.5 7.85 7.5 7.515

    7.5 7.85 7.5 7.515

    15 15 15 15 15

    40 40.6 40 40

    10 10.1 10 10

    40 40.6 40 40

    40 40.6 40 40

    40

    DC Ratedbreaking capacity [kA]NK LR AB GL BV

    2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.643.7/96.888.8/20410.25/18.125.6/53.243.3/96.910/17.2!125/60.5!242/97.9!422/50.150/11543.7/96.888.8/20415.4/31.425.6/53.226.0/56.651.0/11643.7/96.888.8/20451.9/121q88.8/204q5.09/9.4w5.09/9.4w33.1/72.651.0/11653.5/12588.8/20451.9/121q88.8/204q5.09/9.4w5.09/9.4w33.1/72.651.0/11653.5/12588.8/20453.5/125q88.8/204q10.2/19.3w10.2/19.3w33.1/72.651.0/11653.5/12588.8/20453.5/125q88.8/204q10.2/19.3w10.2/19.3w

    2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.642/96.785/19810/18.525/53.242/95.610/18.525/53.242/95.622/50.150/11542/96.785/19815/31.325/53.225/56.250/11542/96.785/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w

    10/18.5!125/52.5!242/95.6!942/88.2!185/187!210/18.5!125/52.5!242/95.6!910/18.5!125/52.5!242/95.6!925/52.5!150/105!242/88.2!185/187!215/30!125/52.5!225/52.5!150/105!242/88.2!185/187!242/88.2!1q85/187!2q

    30/63!150/105!242/88.2!185/187!242/88.2!1q85/187!2q

    30/63!150/105!250/105!185/187!250/105!1q85/187!2q

    30/63!150/105!250/105!185/187!250/105!1q85/187!2q

    10/17!125/52.5!242/88.2!9

    10/17e25/52.5!3

    25/52.5!150/105!242/88.2!185/187!2

    25/52.5!150/105!242/88.2!185/187!2

    42/88.2!185/187!2

    50/105!185/187!2

    NOTES: q : with INSTw : without INSTe : at 450V AC!1 : The value is Icu at 450V AC. Contact Terasaki for Ics value.!2 : The value is Icu at 240V AC. Contact Terasaki for Ics value.!3 : at 240V AC!4 : at 120V AC!5 : Being or will be applied!7 : Plug-in type only. For the mounting and the other details refer to XS225NS.!9 : The value is Icu at 120V AC. Contact Terasaki for Ics value.

    TemBreakz Moulded Case Circuit BreakersMarine Approval2

  • 29

    NOTES: q : with INSTw : without INSTe : at 450V ACr : at 220V ACt : 50/116kA at 660V ACy : 50/115kA at 690V ACu : 2.5/4.1kA for 10A ratingi : at 110V AC

    o : at 225V AC!0 : at 250V DC!1 : The value is Icu at 450V AC. Contact Terasaki for Ics value.!3 : at 240V AC!5 : Being or will be applied!6 : The value is Icu!8 : Contact Terasaki for Ics value.!9 : 2.5/3.57kA for 10A rating.

    Approvals and Applicable Breaking Capacities to Marine Standards.Breaker Rated Poles Ratedtype current[A] voltage[V]XH800PS 700,800 3 460XS1200NE 200~400,400~800, 3 500

    600~1200 250200,225,250,300,350,400,450 500500,600,700,800,1000,1200 250

    XS1600NE 800~1600 3 500800,900,1000, 5001200,1400,1600

    XS2000NE 1200~2000 3 5001200,1400,1600 5001800,2000

    XM30NB 0.7,1.4,2,2.6,4,5, 3 5008,10,12,16,25,32 250

    XM50CB 0.7,1.4,2,2.6,4,5,8,10, 3 50012,16,25,32,40,45 250

    TB-5D 10,15,20,30,40 2 25050 125

    TB-5S 10,15,20,30,40 2 25050 125

    TB-5P 10,15,20,30,40 2 25050 125

    TL-100F 15,20,30,40,50 3 46060,75,100

    TL-225F 125,150,175,200, 3 460225

    TL-400E 250,300,350,400 3 460TL-600NE 300~600 3 690

    300,350,400, 460500,600 240

    TL-800NE 400~800 3 690400,450,500, 460600,700,800 240

    TL-1000NE 500~1000 3 690500,600,700, 460800,900,1000 240

    TL-1200NE 600~1200 3 690600,700,800, 4601000,1200 240

    TL-100C 15,20,30,40,50, 3 50060,75,100

    TL-225B 125,150,175,200, 3 500225 250

    TL-400 125,150,175,200,225, 3 500250,300,350,400 250

    TL-600 450,500,600 3 500250

    TL-800 700,800 3 500250

    AC Rated breaking capacity [kA sym. rms.]/Rated making capacity [kA peak]NK LR AB GL BV85/19350/117q85/198q15/31.3w15/31.3w85/196q20/46w

    85/195q42/99w

    2.5/3.85/8.72.5/3.85/8.75/8.0u42/99.35/8.0u42/99.35/8.0u42/99.3120/280

    120/280

    120/280

    125/295

    125/295

    125/295

    125/295

    180/396

    180/396

    180/396

    180/396

    180/396

    5 5 5

    5 5

    5 5 5

    40 40

    40 40

    40 40

    40 40

    DC Ratedbreaking capacity [kA]NK LR AB GL BV

    85/19353.5/125q88.8/204q15.4/31.4w15.4/31.4w87.1/194.9q21.5/51.5w

    87.1/194.9q43.0/102.9w

    2.5/3.85/8.72.5/3.85/8.75/8.0u43.5/101.65/8.0u43.5/101.65/8.0u43.5/101.6120/280

    120/280

    120/280

    125/295

    125/295

    45/93.8!8125/295!1150/345!845/93.8!8125/295!1150/345!8180/419y!1

    180/419y!1

    180/419y!1

    180/419y!1

    180/419y!1

    85/19350/117q85/198q15/31.3w15/31.3w85/196q20/46w

    85/195q42/99w

    2.5/3.85/8.72.5/3.85/8.75/8.0u42/99.3

    5/8.0u42/99.3120/280

    120/280

    120/280

    125/295

    125/295

    125/295

    125/295

    180/396

    180/396

    180/396

    180/396

    180/396

    85/187!165/143q!1100/220q!2

    85/187q!1

    85/187q!1

    5/7.98r!942/102i5/7.98r!942/102i5/7.98r!942/102i120/288!1

    120/288!1

    120/288!145/92!8125/298!1150/347!845/92!8125/298!1150/347!845/92!8125/298!1150/347!845/92!8125/298!1150/347!8180/419!1

    180/419!1

    180/419!1

    180/419!1

    180/419!1

    65/143q!1

    5/8.0uo7.5/13.7i

    5/8.0uo7.5/13.7i120/280!6

    120/280!6

    120/280!845/94.5!8125/275!1150/330!845/94.5!8125/275!1150/330!845/94.5!8125/275!1150/330!845/94.5!8125/275!1150/330!8180/415!8

    180/415!8

    180/415!8

    180/415!8

    180/415!8

  • 30

    1002.0

    1185A850mm245mm1185A850mm245mm992A600mm238mm

    TZS-100

    681.1

    650A325mm229mm650A325mm229mm556A250mm226mm

    TZS-68

    400.7

    298A100mm217mm298A100mm217mm257A80mm215.5mm

    TZS-40

    240.3

    139A30mm210.5mm139A30mm210.5mm115A22mm29.5mm

    TZS-24

    150.2

    61A8mm26mm61A8mm26mm49A5.5mm25mm

    TZS-15

    120 qw24096-132192-26430100300 e5001000below 0.040.30.5 er1260/78/1000.22

    '

    t1C yLED (Red)electrical u1VA

    TZS-AD

    TypePhase and 33W, 12Wwires 34WOutside view

    RATINGSRated control voltage [V AC]

    50/60HzApplicable range 120V AC

    240V ACRated sensitivity current [mA]

    Rated operating time (sec)

    Dimensions [mm] (surface mount) W/H/DWeight [kg] (surface moun