TECHNICAL & SERVICE MANUAL
Indoor unit[Model names] [Service Ref.]
PLFY-P32VAM-E PLFY-P32VAM-E.UKPLFY-P40VAM-E PLFY-P40VAM-E.UKPLFY-P50VAM-E PLFY-P50VAM-E.UKPLFY-P63VAM-E PLFY-P63VAM-E.UKPLFY-P80VAM-E PLFY-P80VAM-E.UKPLFY-P100VAM-E PLFY-P100VAM-E.UKPLFY-P125VAM-E PLFY-P125VAM-E.UK
No. OC313REVISED EDITION-A
INDOOR UNIT
Ceiling CassettesSeries PLFY
CONTENTS
1. SAFETY PRECAUTION··························22. PART NAMES AND FUNCTIONS ··········63. SPECIFICATIONS···································84. 4-WAY AIR FLOW SYSTEM·················115. OUTLINES AND DIMENSIONS············146. WIRING DIAGRAM·······························157. REFRIGERANT SYSTEM DIAGRAM ·····168. TROUBLE SHOOTING·························179. DISASSEMBLY PROCEDURE·············24
10. PARTS LIST··········································2711. OPTIONAL PARTS················Back cover
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
R407C R22R410A
Revision:• “ 10. PARTS LIST ” has been modified.
•Please void OC313
OC313-A--1.qxp 04.9.3 11:20 AM Page 1
-
2
1 SAFETY PRECAUTION
[1] Cautions for service·After recovering the all refrigerant in the unit, proceed to working.·Do not release refrigerant in the air.·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Cautions for units utilizing refrigerant R407C
CAUTIONS RELATED TO NEW REFRIGERANT
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
Use ESTR , ETHER or HAB as the lubricant to coat flares and flange connection parts.If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.
Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact witha flame, poisonous gases will be released.
Revision:1. “ 10. PARTS LIST ” has been modified on page 30 and 31.
Service Ref.Page
30
31
IncorrectRevise point
10. PART LISTFUNCTIONAL PARTSNo.7 POWER BOARD
10. PART LISTFUNCTIONAL PARTSNo.1 DRAIN PAN
S70 E00 529
S70 E20 313
S70 E01 529
S70 E02 313
Correct
2810. PART LISTFUNCTIONAL PARTSNo.10 MOTOR CAP
— S70 E50 129PLFY-P32VAM-E.UKPLFY-P40VAM-E.UKPLFY-P50VAM-E.UKPLFY-P63VAM-E.UK
PLFY-P100VAM-E.UKPLFY-P125VAM-E.UK
2. The description “The part name of symbol “I.B” is “SPCB” ” is added on both pages of wiring diagram and part list.
OC313-A--1.qxp 04.9.3 11:20 AM Page 2
-
3
[3] Service toolsUse the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R134a or R407C.
5 Adapter for reverse flow check. ·Attach on vacuum pump.
6 Refrigerant charge base.
7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
[2] Refrigerant recharging(1) Refrigerant recharging process
1Direct charging from the cylinder.·R407C cylinder are available on the market has a syphon pipe.·Leave the syphon pipe cylinder standing and recharge it.(By liquid refrigerant)
(2) Recharge in refrigerant leakage case·After recovering the all refrigerant in the unit, proceed to working.·Do not release the refrigerant in the air.·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Gravimeter
Unit
OC313-A--1.qxp 04.9.3 11:20 AM Page 3
-
4
Cautions for units utilizing refrigerant R410A
Store the piping to be used during installationindoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
Charge refrigerant from liquid phase of gascylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige-rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that cancause deterioration of refrigerant oil or malfunction of com-pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera-nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptorSize adjustment gauge
Gauge manifold
Torque wrenchGas leak detectorCharge hose
Tools for R410A
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com-pressor.
If large amount of mineral oil enter, that can cause deterio-ration of refrigerant oil etc.
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact witha flame, poisonous gases will be released.
OC313-A--1.qxp 04.9.3 11:20 AM Page 4
-
5
[1] Cautions for service(1) Perform service after collecting the refrigerant left in unit completely.(2) Do not release refrigerant in the air.(3) After completing service, charge the cycle with specified amount of refrigerant.(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant chargeWhen charging directly from cylinder· Check that cylinder for R410A on the market is syphon type.· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Gravimeter
Unit
[3] Service toolsUse the below service tools as exclusive tools for R410A refrigerant.
No. Specifications
1 Gauge manifold ·Only for R410A
·Use the existing fitting specifications. (UNF1/2)
·Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check ·Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder ·Only for R410A Top of cylinder (Pink)
Cylinder with syphon
8 Refrigerant recovery equipment
OC313-A--1.qxp 04.9.3 11:20 AM Page 5
-
6
2 PART NAMES AND FUNCTIONS
● Indoor Unit
Auto Air Swing VaneDisperses airflow up anddown and adjusts the angleof airflow direction.
Grille
FilterRemove dust and pollutantsfrom return air
Horizontal Air OutletSets airflow horizontal automaticallyduring cooling or dehumidifying.
Air IntakeReturns air from room.
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODEFILTER
TEST RUNFUNCTION
˚C1Hr.
NOT AVAILABLESTAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SETPress this button to switch between cool, dry, automatic and heat modes.
OPERATION SWITCH button
This sets the room temperature. Thetemperature setting can be performedin 1: units Setting range Cooler 19: to 30: Heater 17: to 28:
TEMP. ADJUSTMENT button
This switches between continuousoperation and the timer operation.
TIMER button
This switches between the operationand stop modes each time it is pressed.The lamp on this button lights duringoperation.
ON/OFF button
Only press this button to perform aninspection check or test operation.Do not use it for normal operation.
CHECK-TEST RUN button
This switch the horizontal fan motionON and OFF.
(Not available for this model.)
LOUVER button
This adjusts the vertical angle of theventilation.
AIR DIRECTION button
This resets the filter service indicationdisplay
FILTER button
This sets the current time, start time and stop time.
TIME SETTING button
This sets the ventilation fan speed.
AIR SPEED button
● Remote controllerOnce the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
● Operation buttonsNote : This figure is PAR-20MAA. Refer to each remote controller manual for the details.
OC313-A--1.qxp 04.9.3 11:20 AM Page 6
-
7
Caution● Only the Power display lights when the unit is stopped and power supplied to the unit.● When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.● “NOT AVAILABLE” is displayed when the Air speed button is pressed. This indicates that this room unit is not equipped with
the fan direction adjustment function and the louver function.● When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max.
2minutes). Please wait until this “H0” indication disappear then start the operation.
CENTRALLYCONTROLLED display
This indicates when the unit is con-trolled by optional features such ascentral control type remote controller.
TIMER display
This indicates when the continuousoperation and time operation modesare set.It also display the time for the timeroperation at the same time as whenit is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
The [STANDBY] symbol is only dis-played from the time the heatingoperation starts until the heated airbegins to blow.
DEFROST display
This indicates when the defrost operation is performed.
CHECK display
This indicates when a malfunctionhas occurred in the unit which shouldbe checked.
CLOCK display
The current time , start time and stoptime can be displayed in ten secondintervals by pressing the time switchbutton. The start time or stop time isalways displayed during the timeroperation.
● Display
In this display example on the bot-tom left, a condition where all dis-play lamps light is shown for expla-nation purposes although this differsfrom actual operation.
Operation lamp
This lamp lights during operation,goes off when the unit stops andflashes when a malfunction occurs.
POWER display
This lamp lights when electricity issupplied to the unit.
SET TEMPERATURE display
This displays the selected settingtemperature.
AIR DIRECTION display
This displays the air direction.
ROOM TEMPERATURE display
The temperature of the suction air is displayed during operation. Thedisplay range is 8°C to 39°C. Thedisplay flashes 8°C when the actualtemperature is less than 8°C andflashes 39°C when the actual tem-perature is greater than 39°C.
display
This display lights in the check mode or when a test operation isperformed.
CHECK MODE
TEST RUN
This lamp lights when the filter needto be cleaned.
AIR SPEED display
The selected fan speed is displayed.
FILTER display
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODEFILTER
TEST RUNFUNCTION
˚C1Hr.
NOT AVAILABLESTAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
OC313-A--1.qxp 04.9.3 11:20 AM Page 7
-
3-1. Specifications
8
3 SPECIFICATIONS
Item
kW
kW
kW
kW
A
A
—
mm
mm
mm
—
—
k/min
Pa
kW
—
—
[mm(in.)
[mm(in.)
[mm
dB
kg
Cooling capacity
Power
Heat exchanger
Insulator
Air filter
Fan ✕ No
Air flow W3
Pipedimensions
Unit drain pipe size
Noise level W3
Product weight
Exterior(munsell symbol)
Fan motoroutput
Externalstatic pressure
Liquidside
Gasside
Heating capacity
Fan
Dimensions
Height
Width
Depth
Elec
tric
char
acte
ristic
InputCooling
Heating
Cooling
HeatingCurrent
PLFY-P40VAM-E.UK PLFY-P50VAM-E.UKPLFY-P32VAM-E.UK PLFY-P63VAM-E.UK
3.6
4.0
0.12
0.12
0.59
0.59
14-13-12-11
31-29-28-27
0.14
0.14
0.68
0.68
Unit : Galvanized sheets with gray heat insulation Grills : ABS resin Munsell
258
840
840
Cross fin
Turbo fan ✕ 1
16-14-13-12
0
0.070
Polyethylene sheet
PP honey comb fabric
O.D.32 (PVC pipe VP-25 connectable)
32-30-28-27
7.1
8.0
0.16
0.16
0.78
0.78
[15.88(5/8")
[9.52(3/8")
33-31-29-28
Single phase 220-230-240V 50HzSingle phase 220V 60HzV·Hz
[12.7(1/2") / [15.88(5/8")(Compatible)[6.35(1/4")/[9.52(3/8")(Compatible)
4.5
5.0
5.6
6.3
18-16-15-14
[12.7(1/2")
[6.35(1/4")
2422
Note 1. Rating conditions(JIS B 8616)Cooling : Indoor : D.B. 27°C W.B. 19.0°C
outdoor : D.B. 35°CHeating : Indoor : D.B. 20°C
outdoor : D.B. 7°C W.B. 6°CNote 2. The number indicated in < > is just for the grille.
W 3. Air flow and the noise level are indicated as High-Medium1-Medium2-Low.
OC313-A--1.qxp 04.9.3 11:20 AM Page 8
-
9
Note 1. Rating conditions(JIS B 8616)Cooling : Indoor : D.B. 27°C W.B. 19.0°C
outdoor : D.B. 35°CHeating : Indoor : D.B. 20°C
outdoor : D.B. 7°C W.B. 6°CNote 2. The number indicated in < > is just for the grille.
W 3. Air flow and the noise level are indicated as High-Medium1-Medium2-Low.
Item
kW
kW
kW
kW
A
A
—
mm
mm
mm
—
—
k/min
Pa
kW
—
—
[mm(in.)
[mm(in.)
[mm
dB
kg
Cooling capacity
Power
Heat exchanger
Insulator
Air filter
Fan ✕ No
Air flow W3
Pipedimensions
Unit drain pipe size
Noise level W3
Product weight
Exterior(munsell symbol)
Fan motoroutput
Externalstatic pressure
Liquidside
Gasside
Heating capacity
Fan
Dimensions
Height
Width
Depth
Elec
tric
char
acte
ristic
InputCooling
Heating
Cooling
HeatingCurrent
PLFY-P80VAM-E.UK PLFY-P100VAM-E.UK PLFY-P125VAM-E.UK
9.0
10.0
0.18
0.18
0.86
0.86
258
22-20-18-16
0.070
15.88(5/8")
37-35-32-30
24
11.2
12.5
0.30
0.30
1.43
1.43
Unit : Galvanized sheets with gray heat insulation Grills : ABS resin Munsell
840
840
Cross fin
Turbo fan ✕ 1
27-25-22-19
0
Polyethylene sheet
PP honey comb fabric
9.52(3/8")
O.D.32 (PVC pipe VP-25 connectable)
41-39-36-33
14.0
16.0
0.34
0.34
1.64
1.64
298
0.120
29-27-24-21
43-41-38-35
Single phase 220-230-240V 50HzSingle phase 220V 60HzV·Hz
32
[15.88(5/8") / [19.05(3/4")(Compatible)
OC313-A--1.qxp 04.9.3 11:20 AM Page 9
-
10
3-2. Electrical parts specifications
Parts name
ModelSymbol
TH21
TH22
TH23
FUSE
MF
C
MV
DP
DS
LEV
H2
TB2
TB5
TB15
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
250V 6.3A
240V 21.8W
(L, N, ;) Rated to 330V 30A W
(M1, M2, S) Rated to 250V 20A W
(1, 2) Rated to 250V 10A W
Liquid pipe thermistor
Gas pipe thermistor
Fan motor capacitor
Vane motor
Drain-up mechanism
Drain sensor
Linear expansion valve
PLFY-P40VAM-E.UKPLFY-P32VAM-E.UK PLFY-P50VAM-E.UK PLFY-P63VAM-E.UK
Room temperaturethermistor
Fuse(Indoor controller board)
Fan motor(with inner-thermostat)
Inner-thermostat
Electric heater(Condensation proof)
Power supply terminalblock
Transmission terminalblock
MA remote controller terminal block
6-pole OUTPUT 70WD17B6P70MS
MSBPC20M04DC12V 300"/phase
PLD-12230ME-1INPUT 12/10.8W 24R/Hr
Thermistor resistance 0:/6k", 10:/3.9k", 20:/2.6k", 25:/2.2k", 30:/1.8k", 40:/1.3k"
DC12V Stepping motor drive port dimension 5.2" (0~2000pulse)EDM-40YGME
OFF 130: i 5:ON 90: i 20:
3.0+ ✕ 440V
W Note : Refer to WIRING DIAGRAM for the supplied voltage.
OC313-A--1.qxp 04.9.3 11:20 AM Page 10
-
11
Parts name
ModelSymbol
TH21
TH22
TH23
FUSE
MF
C
MV
DP
DS
LEV
H2
TB2
TB5
TB15
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
250V 6.3A
240V 21.8W
(L, N, ;) Rated to 330V 30A W
(M1, M2, S) Rated to 250V 20A W
(1, 2) Rated to 250V 10A W
Liquid pipe thermistor
Gas pipe thermistor
Fan motor capacitor
Vane motor
Drain-up mechanism
Drain sensor
Linear expansion valve
PLFY-P100VAM-E.UKPLFY-P80VAM-E.UK PLFY-P125VAM-E.UK
Room temperaturethermistor
Fuse(Indoor controller board)
Fan motor(with inner-thermostat)
Inner-thermostat
Electric heater(Condensation proof)
Power supply terminalblock
Transmission terminalblock
MA remote controller terminal block
6-pole OUTPUT 70WD17B6P70MS
6-pole OUTPUT 120WD176P120MS
MSBPC20M04DC12V 300"/phase
PLD-12230ME-1INPUT 12/10.8W 24R/Hr
Thermistor resistance 0:/6k", 10:/3.9k", 20:/2.6k", 25:/2.2k", 30:/1.8k", 40:/1.3k"
DC12V Stepping motor drive port dimension 5.2" (0~2000pulse)EDM-80YGME
OFF 130: i 5:ON 90: i 20:
3.5+ ✕ 440V 7.0+ ✕ 440V
W Note : Refer to WIRING DIAGRAM for the supplied voltage.
4 4-WAY AIR FLOW SYSTEM
4-1. Placement of the air outlets• For this grille, the blowout direction comes in 11 patterns.
Also, by setting the dip switches (SWA and SWB) on the circuit board to the appropriate settings, you can adjust the air flowand speed. Select the settings from Table according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
Blo
wou
t dire
ctio
npa
ttern
4-direction 3-direction 2-direction Note1.For 3 and 2-directional,please use the air outletshutter plate (option).
Pattern 1 Factory setting Pattern 4 One air outletfully closed
Pattern 6 Two air outletfully closed
OC313-A--1.qxp 04.9.3 11:20 AM Page 11
-
12
4-2. Fresh air intake (Installation of site)• At the time of installation, use the duct holes (cutout) located at the positions shown in following diagram, as and when required.
Note : Be sure to add135mm to the dimensions in the diagram that are marked with a “w” if installing a multi function casement(Option)
A.B
SW5240V220V
SWA
321
SWB234 1
234
(RE
D)
AD
DR
ES
SC
N43
(RE
D)
AD
DR
ES
SC
N82
1
Standard2.7m3.0m3.3m
2
High ceiling 13.0m3.3m3.5m
3
High ceiling 23.5m3.5m
—
12345678
CONNECTIONNo.
SW14
0SWC
SW1
87654321OFFON
109
00
SW11SW12
1ST.DIGIT2ND.DIGIT3RD.DIGIT
4 direction3 direction2 direction
SWASWB
PLFY-P32·P40·P50·P63·P80VAM-E
PLFY-P100·P125VAM-E
4
3
2
1
Standard3.2m3.6m4.0m
2
High ceiling 13.6m4.0m4.2m
3
High ceiling 24.2m4.2m
—
4 direction3 direction2 direction
SWASWB4
3
2
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set the up switches (SWA, SWB) on the circuit board to the appropriate setting.• Correspondence of ceiling heights to numbers of air outlets.
Fresh air intake hole
Fresh air intake hole diagram
3 - {2.8Burring hole
{125Burring hole pitch
{100(Cut out hole)
Refrigerant pipe Drain pipe Ceiling surface
120_
120_
w15
8
CN51
Multiple remotecontroller adapterPAC-SA88HA-E
Indoor controller board
Distance between indoorcontroller board and relaymust be within 10m.
Be sure to secure insulationmaterial by tape and such
5 Green
Yellow
OrangeConnector (5P)
Package sideMultiple remotecontroller adapterPAC-SA88HA-E
Be sure to secure insulationmaterial by tape and such
Installation at site
CN51on indoor controllerboard Red
Brown
1
~
CN51
MB
4-3. Interlocking operation method withduct fan (Booster fan)
• Whenever the indoor unit is operating, the duct fun alsooperates.(1)Connect the optional multiple remote controller
adapter(PAC-SA88HA-E)to the connector CN51 on the indoor controller board.
(2)Drive the relay after connecting the 12V DC relaybetween the Yellow and Orange connector lines.
MB: Electromagnetic switch power relay for duct fan.X: Auxiliary relay (For DC 12V, coil rating : 1.0W or below)
OC313-A--1.qxp 04.9.3 11:20 AM Page 12
-
13
Static pressure [Pa]
Air flow [m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
01 2 3 4 5 6
Static pressure [Pa]
Air flow [m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
0
1 2 3 4 5 6
Static pressure [Pa]
Air flow [m3/min]
50
-50
-100
-150
-200
0 1 2 3 4 5 6
Static pressure [Pa]
Air flow[m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
01 2 3 4 5 6 7 8 9
Static pressure [Pa]
Air flow[m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
0
1 2 3 4 5 6 7 8 9
Static pressure [Pa]
Air flow [m3/min]
50
-50
-100
-150
-200
0 1 2 3 4 5 6 7 8 9
ll PLFY-P32 · P40 · P50 · P63 · P80VAM-EMultifunction casement + Standard filter
22 PLFY-P100 · P125VAM-E
Multifunction casement + High efficiency filter
Taking air into the unit
Multifunction casement + Standard filter Multifunction casement + High efficiency filter
Taking air into the unit
4-4. Fresh air intake amount & static pressure characteristics
Q
0
BA C
1 Curve in thegraphs.
Duct characteristicsat site
Q
AE
C2
Q
Qa
AD
3
Q…Planned amount of fresh air intake
A…Static pressure loss of fresh airintake duct system with air flowamount Q
B…Forced static pressure at air condi-tioner inlet with air flow amount Q
C…Static pressure of booster fan withair flow amount Q
D…Static pressure loss increaseamount of fresh air intake dust sys-tem for air flow amount Q
E…Static pressure of indoor unit with airflow amount Q
Qa…Estimated amount of fresh airintake with out D
How to read curves
OC313-A--1.qxp 04.9.3 11:20 AM Page 13
-
14
5 OUTLINES AND DIMENSIONS
PLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
Unit : mm
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Drain pipeVP-25connection(O.D.{32)
Branch duct hole(Cut out hole)
Ceiling surface
Sus
pens
ion
bolt
pitc
h
Cei
ling
hole
Branchduct ho
Suspension bolt pitch
Ceiling hole
Air
outle
t hol
e
Air
inta
ke h
ole
411
Air intake holeAir intake grille
Power line entrySuspension bolt lower edge
Suspension boltM10 or W3/8
Control wire entry
Feeding hole(Drain pump)
577
374286
840
197 159
60
17+
5 0 30
190
159
605
159
192
170
140
50~
70
98 89
840
860~
910
20~
4520
~45
20~4520~45
Fresh air intake
Branch duct hole
860~910
810
159
1610
5
AB
77 51
M
M
M
1
2
M
950
5177
950
577
411
Terminal block{175
{150
14 - {2.8Burring hole
Models 1 Liquid Pipe 2 Gas Pipe
PLFY-P32VAM-E.UK
PLFY-P40VAM-E.UK
PLFY-P50VAM-E.UK
PLFY-P63VAM-E.UK
PLFY-P80VAM-E.UK
PLFY-P100VAM-E.UK
PLFY-P125VAM-E.UK
241
281
A
258
298
B
350
90
70_
100 100 90
100
130
155
167
[6.35
[9.52
[12.7
[15.88
[15.88/[19.05(Compatible)
[12.7 / [15.88(Compatible)
[6.35 / [9.52(Compatible)
High efficiency filter & Multi function 17
+5 0
135
Detail drawing of fresh air intake
3 - {2.8Burring hole
{125Burring hole pitch
{100(Cut out hole)
Ceiling surface
Liquid pipe
Gas pipe
120_
120_
w15
8
NOTES :1. When servicing, electrical parts box may be disassembled.
Make the wires loose enough when connecting heater power supply wire, remote controller wire, and indoor/outdoor unit connecting wire.
2. Detaching corner panel makes it possible to adjust the height of body with the grille attached.
3. Caution for attaching optional Muliti function casement and optional High efficiency filter : 1) Space behind the ceiling shall be high enough as specified
in the table below.
2) Add extra 135mm to the dimensions of w in the figure.3) Mount both High efficiency filter and Multi function casement together.
4. When connecting branch duct, be sure to insulate the heat.(Otherwise, it causes dew to from or drop.)
P32-P80P100-P125
400440
OC313-A--1.qxp 04.9.3 11:20 AM Page 14
-
15
WIRING DIAGRAM6
PLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
DAMPERCN27
MA-REMOTE CONTROLLERTB15
DRAIN WATER LIFTING-UP MACH.
SYMBOL NAMESYMBOL NAME
VARISTORZNR
A.B
LEV LINEAR EXPANSION VALVE
CIRCUIT BOARD
SW11
SW12
SW14
SWB
SW1
SW5
SWITCH
SWC
VOLTAGE SELECTION
FUNCTION SETTING
ADDRESS SETTING 1ST DIGIT
ADDRESS SETTING 2ND DIGIT
CONNECTION NO.
CEILING HEIGHT SELECTOR
DISCHARGE OUTLET NUMBER
SELECTOR
OPTION SELECTOR
NAMESYMBOL
TRANSMISSION
POWER SUPPLY
BLOCK
TERMINAL
TB5
TB2
DEW PREVENTION HEATER
VANE MOTORFAN MOTOR(WITH INNER THERMO.)
CAPACITOR(FAN MOTOR)
H2
MV
C
MF
DRAIN SENSORDS
DP DRAIN PUMP
FAN MOTORX4
FUSEFAN PHASE CONTROLF.C
FUSE(6.3A/250V)
INDOOR CONTROLLER BOARD
MODEL SELECTION
FUNCTION SETTING
CAPACITY CODE
REMOTE INDICATION
HA TERMINAL-A
CENTRALLY CONTROL
REMOTE SWITCH
SWITCH
SW4
SW3
SW2
CN52
CN51
CN41
CN32
HUMIDIFIERCONNECTORCN25I.B
TH21
PIPE TEMP.DETECTION/GAS
PIPE TEMP.DETECTION/LIQUID
ROOM TEMP.DETECTIONTHERMISTOR
(0:/15k",25:/5.4k")
(0:/15k",25:/5.4k")
(0:/15k",25:/5.4k")
TH23
TH22
AUX.RELAYX1
INDOOR POWER BOARDP.B
LED2 POWER SUPPLY(I.B)POWER SUPPLY(I.B)LED1
[LEGEND]
SWA
2.In case of using MA-Remote controller, please connect to TB15.(Remote controller wire is non-polar.)3.In case of using M-NET, please connect to TB5.(Transmission line is non-polar.)
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.NOTES:
4.Symbol[S] of TB5 is the shield wire connection.5.Symbols used in wiring diagram above are, :terminal block, :connecter.6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to the table below.7.Please set the switch SW5 according to the power supply voltage. Set SW5 to 240V side when the power supply is 230 and 240 volts. When the power supply is 220 volts, set SW5 to 220V side.
LED2
LED1
Mark
Power supply forMA-Remote controller
Main power supply Main power supply(Indoor unit:220-240V)power on ➔ lamp is lit
Meaning
Power supply for MA-Remote controlleron ➔ lamp is lit
Function
LED on indoor controller board for service
A.B
9 101 2 3 4 5 6 7 8
ONOFF
CN
43A
DD
RE
SS
(RE
D)
(RE
D)
CN
82A
DD
RE
SS
240V220V
No.CONNECTION
3RD.DIGIT 2ND.DIGIT 1ST.DIGIT
3
8
SW14SWC
SW11SW12
SW1
SW5 SWA SWB
21
234
1234567
1234
0 0 0
O
OFFON
OFFON
OFFON
OFFON
OFFON
OFFON
ONOFF
OFFON
OFFON
10987654321
10987654321
SW3
P125VAM654321
P100VAM654321
P80VAM654321
P63VAM654321
P50VAM
P40VAM
P32VAM
SW2
123456
654321
654321
TH21TH23 TH22
BLK
BLK
BLK
BLK
BLK
BLK
DSLEV
WH
T
RE
DY
LW
OR
NB
RN
BLU
123456
M1M2
TB5
(SHIELD)
12
TB15
S } BC CONTROLLERTO OUTDOOR UNIT
REMOTE CONTROLLERDC24-30V
BLUBLU
ORNORN }TO MA-REMOTE CONTROLLERDC8.7-13V
TB2
C
TB5
TB15
(For Control box)Position of TB2,TB5,TB15,C.
GRILLE
MV MV MV MV
5 5 5 55
H2
YLW
YLW
1 2 3 6 7 4 8 9 5 10
MF
C
RE
D
WH
T
BLKI.B
1 2 3
1 2 3
RE
D
BLU
POWERCND(RED)
FUSE
ZNR
1 3
BR
N
BR
N
DP
1 2
YLW
YLW
X1
D.U.M CNP(BLU)
X1
1 3
WH
T
BLKW
HT
BLK
P.B(DC13.1V)CN2S (WHT)
21
TRANSCNSK(RED)
321
(AC220-240V)
TB2L
N
220V 60Hz50Hz~/N 220-240V
POWER SUPPLY
(15A)BREAKER
FUSE(15A)
PULL BOX
INDOOR UNITTO NEXT
GRN/YLWBLU
RED
31
CN2M(BLU)M-NET
4 1
HA
(WHT)LIQUIDCN21
(RED)INTAKECN20
(BLK)GASCN29
(WHT)DRAINCN31
(WHT)LEVCN60
(WHT)REMOTESWITCHCN32
CN41(WHT)
(WHT)CENTRALLYCONTROLCN51
(GRN)REMOTEINDICATIONCN52(RED)
ADDRESSCN42
(RED)ADDRESSCN81
(GRN)VANECN6V
HUMIDIFIERCN25(WHT)
CN3A(BLU)REMOCON
(RED)DAMPERCN27
ONOFF
ONOFF
55
SW4
321 41
48 6
5 1SW3SW2
See fig:✻1
FAN(WHT)
FC
X4
X4
POWERCNDK(RED)
1 2CN2D(WHT) LED1
12
12
LED2
12122123
3 2 16 5 4
12345 109876123456
6 5 4 3 2 1 6 5 4 3 2 1 12348 75 1
13
2 1
1 3 5 1 3
w The part name of symbol “I.B” is “SPCB”.
w
OC313-A--1.qxp 04.9.3 11:20 AM Page 15
-
16
7 REFRIGERANT SYSTEM DIAGRAM
Strainer (#50mesh)
Strainer (#100mesh)
Strainer1 (#50mesh)Strainer2 (#100mesh)
Heat exchanger
Room temparature thermistor TH21
Gas pipe thermistor TH23
Liquid pipe thermistor TH22
Linear expansion valve
Gas pipe
Liquid pipe
Flare connection
Gas pipe
Liquid pipe
PLFY-P32, P40VAM-E
[12.7(1/2'')
[6.35(1/4'')
PLFY-P50VAM-E
[12.7(1/2'')/[15.88(5/8'')
[6.35(1/4'')/[9.52(3/8'')
PLFY-P63, P80VAM-E
[15.88(5/8'')
[9.52(3/8'')
PLFY-P100, P125VAM-E
[15.88(5/8'')/[19.05(5/8'')
[9.52(3/8'')
ItemCapacity
PLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
OC313-A--1.qxp 04.9.3 11:20 AM Page 16
-
17
TROUBLE SHOOTING8
8-1. How to check the partsPLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
Parts name Check points
Disconnect the connector then measure the resistance using a tester.(Surrounding temperature 10:~30:)
Disconnect the connector then measure the resistance valve using a tester.
Measure the resistance between the terminals using a tester.(Surrounding temperature 20:~30:)
Measure the resistance between the terminals using a tester.(Surrounding temperature 20:~30:)
Measure the resistance after 3 minutes have passed since the power supply was intercepted.(Surrounding temperature 0:~60:)
Vane motor
Linear expansionvalve
Drain pump
Drain sensor
Refer to the next page for the details.
Refer to the next page for the details.
Room temperaturethermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)
1
2
Yellow
Yellow
123
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
Abnormal
Open or short
Normal
150k" i10%
White-Red Yellow-Brown Orange-Red Blue-Brown
NormalConnector Abnormal
300" Open or short
Normal Abnormal
290" Open or short
OrangeRedWhite
Blue
Brown
Yellow
M
Orange
Red
White
Red — Yellow
Red — Blue
Red — Orange
Red — WhiteBlue Yellow
Measure the resistance between the terminals using a tester.Fan motor
11
22
33
Red
White
Black
Relay connector
Relay connector
Protector
P32, P40, P50, P63, P80
87.2"
104.1"
Abnormal
Open or short
P100, P125
28.7"
41.6"
Red-Black
White-Black
Motor terminalor
Relay connector
Normal
PLFY-P·VAM-E.UK
M
Refer to the next page for the details.
OC313-A--1.qxp 04.9.3 11:20 AM Page 17
-
18
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Res
ista
nce
(K"
)
4 [4
3
62
5
[3
2 [2
1 [1
[4
[3[2
[1
Controller board
Drive circuit
Relay connector
Connector(CN60)
DC12V
Brown
Red
Blue
Orange
Yellow
White
5
1
3
4
6
M
4
6
2
35
1
Blue
Brown
Yellow
OrangeRedWhite
Linear expansion valve
Room temperature thermistor(TH21)Liquid pipe temperature thermistor(TH22)Gas pipe temperature thermistor(TH23)
Thermistor R0=15k' ± 3%Fixed number of B=3480K ± 2%
Rt=15exp { 3480( ) }
0: 15k'10: 9.6k'20: 6.3k'25: 5.4k'30: 4.3k'40: 3.0k'
Thermistor R0=6.0k' ±5%Fixed number of B=3390K ±2%
Rt=6exp { 3390( ) }
0: 6.0k'10: 3.9k'20: 2.6k'25: 2.2k'30: 1.8k'40: 1.3k'60: 0.6k'
Thermistor for lower temperature
Linear expansion valve① Operation summary of the linear expansion valve.• Linear expansion valves open/close through the use of a stepping motor after receiving the pulse signal from the indoor
controller board.• Valve position can be changed in proportion to the number of pulse signals.
1273+t
1273
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color ofthe lead wire.
1273+t
1273
-20 0 20 40 60 80
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Res
ista
nce
(K"
)
Thermistor for drain sensor
OC313-A--1.qxp 04.9.3 11:20 AM Page 18
-
19
Output(Phase)
Output
{1
1
ON
{2 ON
{3 OFF
{4 OFF
2
OFF
ON
ON
OFF
3
OFF
OFF
ON
ON
4
ON
OFF
OFF
ON
➁ Linear expansion valve operation
➂ Trouble shooting
D
A
E
B
C
Open
Open
Extra tightening (200~800 pulse)
Pulse number
Outdoor unit R410A model : 1400 pulseOutdoor unit R22/R407C model : 2000 pulseOpening a valveall the way
Close
Close
Val
ve p
ositi
on (
capa
city
)
Closing a valve : 1 → 2 → 3 → 4 → 1Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.❈ 1. When linear expansion valve operation stops, all output phase
become OFF.2. At phase interruption or when phase does not shift in order,
motor does not rotate smoothly and motor will locks and vibrates.
❈ When the switch is turned on, 2200 pulse closing valve signalwill be send till it goes to point A in order to define the valve position.
When the valve moves smoothly, there is no noise or vibrationoccurring from the linear expansion valves : however, when thepulse number moves from E to A or when the valve is locked,more noise can be heard than in a normal situation.
❈ Noise can be detected by placing the ear against the screw driver handle while putting the screw driver tip to the linearexpansion valve.
654321
LED1k"
Symptom Check points
Operation circuit fail-ure of the microprocessor.
Disconnect the connector on the controller board, then con-nect LED for checking.
When power is turned on, pulse signals will output for 10 sec-onds. There must be some defects in the operation circuit ifthe LED does not light while the signals are output or keepslighting even after the signals stop.
Countermeasures
Exchange the indoor con-troller board at drive circuitfailure.
Linear expansionvalve mechanism islocked.
Valve doesn't closecompletely.
Wrong connection ofthe connector orcontact failure.
To check the linear expansion valve, operate the indoor unitin fan mode and at the same time operate other indoor unitsin cooling mode, then check the pipe temperature of the indoor unit by theoutdoor multi controller board operationmonitor. During fan operation, linearexpansion valve is closed completely and ifthere is any leaking, detecting temperatureof the thermistor will go lower. If the detect-ed temperature is much lower than the tem-perature indicated in the remote controller,
it means the valve is not closed all the way. It is not neces-sary to exchange the linear expansion valve, if the leakage issmall and not affecting normal operation.
Thermistor(Liquid pipe)
Linearexpansionvalve
Motor will idle and make a ticking noise when the motor isoperated while the linear expansion valve is locked. Thisticking sound is the sign of the abnormality.
Check the color of lead wire and missing terminal of the con-nector.
Exchange the linearexpansion vale.
Exchange the linearexpansion valve.
If large amount of thermis-tor is leaked, exchange thelinear expansion valve.
Disconnect the connectorat the controller board,then check the continuity.
Measure the resistance between each coil (white-red, yellow-brown, orange-red, blue-brown) using a tester. It is normal ifthe resistance is in the range of 150Ω ±10%.
Short or breakage ofthe motor coil of thelinear expansionvalve.
OC313-A--1.qxp 04.9.3 11:20 AM Page 19
-
20
Switch Function RemarksEffectivetiming
Under suspension
Under suspension
BeforepowersupplyON
BeforepowersupplyON
ONOFF
1 2 3 4 5 6 7 8 9 10
Address board
Operation by switch
ON OFF
Note :
w1 Fan operation at Heating mode.
w2 Heater thermostat ON is operating.
w3 SW 1-7=OFF, SW 1-8=ON → Setting air flow. SW 1-7=ON, SW 1-8=ON → Indoor fan stop.
Pole
Built-in remote controller
Provided
2,500hr
Effective
Always operated while the heat in ON w1
Low w3
Setting air flow w3
Effective
Effective
Filter clogging detection
Filter cleaning
Fresh air intake
Humidifier control
Air flow set in case ofHeat thermostat OFF
Auto restart function
Power ON/OFF by breaker
Indoor unit
Not provided
100hr
Not effective
Operated depends on the condition w2
Extra low w3
Depends on SW1-7
Not effective
Not effective
Cooling only
Available
Available
Available
Second setting
Horizontal angle
Effective
Not effective
9(5)degrees
15degrees
Heat pump / Cooling only
Louver / humidifier w6
Vane
Vane swing function
Vane horizontal angle
Vane cooling limit angle setting w4
Heat 4degrees up
Superheat setting temperature w5
Sub cool setting temperature
Heat pump
Not available
Not available
Not available
First setting
Down B, C
Not effective
Effective
6(2)degrees
10degrees
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
SW2Capacity
codesetting
1~6
1~5
SW3Function setting
Thermistor position
ONOFF
P32, P40 : SW3-9 = ONSW3-10 = OFF
P50~P125 : SW3-9 = OFFSW3-10 = OFF
1 2 3 4 5 6 7 8 9 10
Indoor controller board
Note : w4 At cooling mode, each angle can be used only 1 hour. w5 The numerical valve in the parentheses shows the case which the R22 outdoor unit is connected. w6 SW3-2 setting Only for PLFY-P·VAM, SW is used to change whether the humidifier functions or not. (Fixed the louver function less.)
Indoor controller board
Set while the unit is off.
Set while the unit is off.
Set for each capacity.
Indoor controller board
ONOFF
1 2 3 4 5
Capacity
P32 P63
P40 P80
P125
P50 P100
SW 2 Capacity SW 2 Capacity SW 2
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
ONOFF
1 2 3 4 5 6
SW1Function setting
SW4Model
Selection (Setting
for PLFY series)
Changing the opening of linear expansion valve when the thermostat is OFF
Switching remote controller display
Indicating if the thermostat is ON
Indicating fan operation ON/OFF
In case replacing the indoor controller board, make sure to set the switch to the factory-preset status, which is shown below.
8-2. FUNCTION OF DIP SWITCH
OC313-A--1.qxp 04.9.3 11:20 AM Page 20
-
21
0
5
9
4
8 37
2
6
1 0
5
9
4
8 37
2
6
1
0
5
9
4
8 37
2
6
1 0
5
9
4
8 37
2
6
1
0
8
F
7
E
6
D 5C
4
B
3
A
2
9
1
0
8
F
7
E
6
D 5C
4
B
3
A
2
9
1
220V 240V
Switch
SWACeilingheight
selector
SWBDischarge
outletnumberselector
SWCOptionselector
Rot
ary
switc
hR
otar
y sw
itch
SW14Connection
No.setting
SW5VoltageSelection
SW111st digitaddresssetting
SW122nd digitaddresssetting
Pole
(High ceiling2)
(High ceiling1)
(Standard)
3
2
1
(2 direction)
(3 direction)
(4 direction)
2
3
4
Option
Standard Option
Standard
1~3
3
2
2
Operation by switch
✽ Ceiling height can be changed depends on SWB setting.
Address setting should be done when M-NET Remote controller is being used.
When attach the optional high performance filter elements (multi function casement) tothe unit, be sure to attach it to the optionside in order to prevent the airflow reducing.
This is the switch to be used when the indoorunit is operated with R2 series outdoor unit as a set.
If the unit is used at the 230V or 240V area, set the voltage to 240V.If the unit is used at the 220V, set the voltage to 220V.
Remarks
Address board
Address board
Address board
Address can be set while the unit is stopped.
Address board
Address board
Address board
321
234
SW12
10
SW11
1SW12 SW11
SW14
SW14
220V 240V
SWB
PLFY-P32,P40,P50,P63,P80VAM-E
4 direction
3 direction
2 direction
4
3
2
2.7m
3.0m
3.3m
3.0m
3.3m
3.5m
3.5m
3.5m
—
SWA 1
StandardHigh
ceiling1High
ceiling2
2 3
SWB
PLFY-P100, P125VAM-E
4 direction
3 direction
2 direction
4
3
2
3.2m
3.6m
4.0m
3.6m
4.0m
4.2m
4.2m
4.2m
—
SWA 1
StandardHigh
ceiling1High
ceiling2
2 3
Effectivetiming
BeforepowersupplyON
Under operation or suspension
OC313-A--1.qxp 04.9.3 11:20 AM Page 21
-
22
8-3. TEST POINT DIAGRAM8-3-1. Indoor controller boardPLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
LED1Main power supply(Indoor unit : 220-240V)
CNDPower supply for indoor controller board Between 11 to 33 220-240V AC
CNPDrain pump output (DP)Between 11 to 33 220-240V AC
FUSE6.3A 250V
CNDKConnect to the indoor powerboard (CNSK)Between 11 to 33 220-240V AC
FANFan motor output (MF)
CN2DConnect to the indoor power board (CN2S)12.5-13.7V DC (Pin11 (+))
CN2MConnect to the terminal block (TB5)(M-NET transmission connecting wire)24-30V DC (non-polar)
CN3AConnect to the terminal block (TB15)(MA-Remote controller connecting wire)Between 11 to 33 8.7-13V DC (Pin11 (+))
CN29Pipe temperature thermistor/Gas (TH23)
CN21Pipe temperature thermistor/Liquid (TH22)
LED2Power supply for MA-Remote controller
CN32Connector (Remote switch)
SW4Model selection
CN60Linear expansion valve output (LEV)
CN31Drain sensor (DS)
SW3Function setting
CN51Centrally control
SW2Capacity setting
CN52Remote indication
CN6VVane motor output (MV)
CN20Room temperature thermistor (TH21)
CN25Connecter(Humidifier)
CN27Connector(Damper)
OC313-A--1.qxp 04.9.3 11:20 AM Page 22
-
23
8-3-2. Indoor power boardPLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
CNSKConnect to the indoor controller board (CNDK)Between 11 to 33 220-240V AC
CN2SConnect to the indoor power board (CN2D)Between 11 to 33 12.6-13.7V DC (Pin11 (+))
8-3-3. Circuit boardPLFY-P32VAM-E.UK PLFY-P80VAM-E.UKPLFY-P40VAM-E.UK PLFY-P100VAM-E.UKPLFY-P50VAM-E.UK PLFY-P125VAM-E.UKPLFY-P63VAM-E.UK
SW1Function setting
SW5Voltage selector
SWACeiling hightselector
SWBDischarge outletnumber selector
SW12address setting2nd digit
SW11address setting1st digit
SWCOption selector
OC313-A--1.qxp 04.9.3 11:20 AM Page 23
-
24
9 DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the air intake grille(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.(2) Remove the string hook from the panel to prevend the
grille from dropping.(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
4. Removing the electrical box(1) Remove the fan guard.(See photo 1)(2) Remove the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P).(3) Remove the room temperature thermistor with the holder.(4) Remove the bell mouth.(See photo 2)(5) Disconnect the relay connector in the electrical box.
Red (3P) for fan motor power supplyWhite (2P) for pipe temperature detection / liquid thermistorBlack (2P) for pipe temperature detection / gas thermistorBlue (2P) for drain pumpWhite (3P) for drain sensor
(6) Remove the 3 screws from the electrical box, loosenanother 2 screws to remove the box.
Indoor controller boardpower supply boardTerminal block (Power supply)Terminal block (Transmission)Terminal block (MA remote controller)CapacitorCircuit(address) board
PLFY-P80VAM-E.UK Be careful on removing heavy parts.
Photo 3
Figure 1
Photo 1
Air intake grille
Grille
2. Removing the fan guard(1) Open the air intake grille.(2) Remove the 3 screws of fan guard.
Nut
Air intake grille knob
3. Removing the room temperature thermistor(1)Remove the fan guard.(See photo 1)(2) Remove the screw(✕1) in the room temperature thermistor
holder to remove the holder and the room temperaturethermistor.
(3) Remove the 1 screw from the bell mouth, and unscrew theanother 2 screws (fixed to the oval hole which has differentdiameter) to remove the bell mouth.
(4) Hold the holder claw, and remove the room temperaturethermistor and holder.
(5) Disconnect the connector (red) in the indoor control board.
Bell mouth
Indoor controller board Connector
Terminalblock
Photo 2
Screws
Roomtemperaturethermistor
Air intake grille
Connector
Electricalbox
Powersupplyboard
Turbo fan
Screws
Fan guard
Air intake grille
Circuit(address)board
Capacitor
OC313-A--1.qxp 04.9.3 11:20 AM Page 24
-
25
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
6. Removing the pipe temperature detection / liquid thermistorand the pipe temperature detection / gas thermistor(1) Remove the fan guard.(See photo 1)(2) Remove the bell mouth.(See photo 2)(3) Remove the electrical box.(See photo 3)(4) Remove the turbo fan.(5) Remove the screw of the service panel.(6) Remove the service panel.(7) Remove the pipe temperature detection / liquid thermistor
and the pipe temperature detection / gas thermistor whichare inserted into the holder installed to the thin copper pipe.
(8) Disconnect the each 2-pin white(liquid) and black(gas)connector.
7. Removing the panel(1) Remove the air intake grille.(See figure 1)Corner panel (See figure 2)(1) Remove the screw of the corner.(2) Slide the corner panel to the direction of the arrow 3, and
remove the corner panel.Panel (See photo 6)(1) Disconnect the connector that connects with the unit.(2) Remove the 2 screws from the panel and loose another 2
screws, which fixed to the oval hole, have different diameter.(3) Rotate the panel a little to remove the panel. (Slide the
panel so that the screw comes to a large diameter of theoval hole, which has two different diameters.)
Photo 7
Photo 6
Photo 5
5. Removing the fan motor(1) Remove the fan guard.(See photo 1)(2) Remove the bell mouth.(See photo 2)(3) Remove the electrical box.(See photo 3)(4) Remove the turbo fan nut, washer and radiation cap(P100, P125).(5) Pull out the turbo fan.(6) Disconnect the connector of the fan motor lead wire.(7) Remove the 4 nuts of the fan motor.
Photo 4 Fan motor
Nut Connector
Service entrance
8. Removing the drain pan(1) Remove the panel. (See photo 6)(2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan.(3) Remove the corner cover. (2 screws)(4) Remove the bell mouth. (See photo 2)(5) Remove the electrical box. (See photo 3)(6) Remove the lead wire holder. (1 screw)(7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.Be careful not to crack or damage the pan.
Figure 2
Cornerpanel
ScrewCornerpanel Panel
PanelScrew
Connector Screw
Screw Screw
ScrewScrew
Drain pan
Drain plug(Larger one) Corner cover
Leadwireholder
Pipe temperaturedetection / liquidthermistor
Pipe temperaturedetection / gasthermistor
Nut
OC313-A--1.qxp 04.9.3 11:20 AM Page 25
-
26
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
10. Removing the heat exchanger(1) Remove the panel. (See photo 6)(2) Remove the fan guard. (See photo 1)(3) Remove the bell mouth. (See photo 2)(4) Remove the electrical box. (See photo 3)(5) Remove the drain pan. (See photo 7)(6) Remove the turbo fan. (See photo 4)(7) Remove the 3 screws of the piping cover, and pull out
piping cover.(8) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover.(9) Remove the screw of the coil support.
(10) Remove the 2 screws of the coil.(11) Pull out the heat exchanger.
9. Removing the drain pump and drain sensor(1) Remove the panel. (See photo 6)(2) Remove the fan guard. (See photo 1)(3) Remove the bell mouth. (See photo 2)(4) Remove the electrical box. (See photo 3)(5) Remove the drain pan. (See photo 7)(6) Cut the drain hose band with scissors and pull out the
drain hose from the drain pump.(7) Loosen the screw A (2 screws) and remove the screw
B (1 screw). Slide the drain pump in the direction of thearrow C and remove it.
(8) Remove the drain sensor with its holder from the drainpump.
Photo 8
ScrewA
Screw B
Drain sensor
Drain pumpDrain hose
Fixing band
Photo 9
Photo 10
Heat exchanger
Coilsupport
Coil screwsCoil support
Coilsupport
Screw
Outer wall cover Piping coverScrews ofpiping cover
C ➞
OC313-A--1.qxp 04.9.3 11:20 AM Page 26
-
27
PARTS LIST10
1
2
3
4
5
6
7
8
9
10
11
12
1
4
1
3
1
1
4
8
4
4
1
1PAR-20MAA
MV
AIR OUTLET GRILLE
AUTO VANE
CORNER PANEL
CORNER PANEL
L.L FILTER
GRILLE ASSY
VANE MOTOR
VANE BUSH
GEAR (VANE)
GEAR (MOTOR)
SCREW ASSY
REMOTE CONTROLLER
No. Part No. Part Name Specification
Q'ty/setPrice
Unit Amount
Remarks(Drawing No.)
WiringDiagramSymbol
Recom-mended
Q'ty
PLFY-
P80, P100, P125P32, P40, P50, P63
VAM-E.UKS70 E10 003
S70 E00 002
S70 E01 638
S70 E00 638
S70 E00 500
S70 E00 691
S70 E00 223
S70 E00 063
S70 E00 040
S70 E01 040
S70 E01 673
S70 030 713
Including H2
1
2
3
4
5
6
7
8
9
10
12
Part number that is circled is not shown in the figure.
PANEL PARTSPLFY-P32VAM-E.UKPLFY-P40VAM-E.UKPLFY-P50VAM-E.UKPLFY-P63VAM-E.UKPLFY-P80VAM-E.UKPLFY-P100VAM-E.UKPLFY-P125VAM-E.UK
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODEFILTER
TEST RUN
FUNCTION
˚C1Hr.
NOT AVAILABLESTAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
OC313-A--1.qxp 04.9.3 11:20 AM Page 27
-
28
No. Parts No. Parts NameWiring
DiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
123456
7
89
10111213141516
BASE DWGLEGDRUM 1 ASSYLEGTURBO FANSPL WASHERHEAT EXCHANGERHEAT EXCHANGERHEAT EXCHANGERHEAT EXCHANGERLINEAR EXPANSION VALVETHERMISTOR (LIQUID)MOTOR CAPTHERMISTOR (GAS)
INNER COVER ASSYLEGFAN MOTORMOTOR MOUNTDRUM 2 ASSY
1211111
111111141
121111
1
111111141
121111
1
111111141
121111
1111111141
LEVTH22
TH23
MFD17B6P70MS
S70 003 687S70 E01 130S70 005 688S70 E00 130S70 E00 114S70 08K 097S70 E60 480S70 E61 480S70 E62 480S70 E63 480S70 E60 401S70 17J 202S70 E50 129S70 79N 202S70 E00 659S70 E02 130S70 E06 762S70 A41 105S70 006 688
PLFY- · VAM-E.UK
P32 P40 P50 P63
Q'ty / setSpecifi-cation
Remarks(Drawing
No.)
FUNCTIONAL PARTSPLFY-P32VAM-E.UKPLFY-P40VAM-E.UKPLFY-P50VAM-E.UKPLFY-P63VAM-E.UK
4
7
6
5
2
1
15 14
13
2
12
9
10 THERMISTOR (GAS)
THERMISTOR (LIQUID)
SPL WASHER
8
3
16
11 MOTOR CAP
OC313-A--1.qxp 04.9.3 11:20 AM Page 28
-
29
No. Parts No. Parts Name
Q'ty / setWiring
DiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
12
3
4
5
6
7
8910
11
12
13
14
15
BASE DWGLEGDRUM 1 ASSYDRUM 1 ASSYLEGTURBO FANTURBO FANSPL WASHERHEAT EXCHANGERHEAT EXCHANGERLINEAR EXPANSION VALVETHERMISTOR (LIQUID)THERMISTOR (GAS)INNER COVER ASSYINNER COVER ASSYLEGFAN MOTORFAN MOTORMOTOR MOUNTDRUM 2 ASSYDRUM 2 ASSY
LEVTH22TH23
MFMF
D17B6P70MSD176P120MS
S70 003 687S70 E01 130S70 005 688S70 007 688S70 E00 130S70 E00 114S70 E01 114S70 08K 097S70 E64 480S70 E65 480S70 E70 401S70 17J 202S70 79N 202S70 E00 659S70 E02 659S70 E02 130S70 E06 762S70 E07 762S70 A41 105S70 006 688S70 008 688
121
11
11
1111
11
41
12
11
11
1111
11
14
1
12
11
11
1111
11
14
1
Specifi-cation
Remarks(Drawing
No.)PLFY- · VAM-E.UK
P80 P100 P120
4
7
6
5
2
1
14 13
12
2
11
9
FUNCTIONAL PARTS
PLFY-P80VAM-E.UKPLFY-P100VAM-E.UKPLFY-P125VAM-E.UK
10 THERMISTOR (GAS)
THERMISTOR (LIQUID)
SPL WASHER
8
3
15
OC313-A--1.qxp 04.9.3 11:20 AM Page 29
-
30
No. Parts No. Parts NameWiring
DiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
123456789101112131415161718192021
DRAIN PANDRAIN SOCKETDRAIN PUMPDRAIN SENSORDRAIN SENSOR HOLDERCONTROL BOXPOWER BOARDFUSEINDOOR CONTROLLER BOARDCONTROL COVER ASSYFAN GUARDTHERMISTOR (ROOM)ADDRESS CABLEADDRESS BOARDMA-REMOTE CONTROLLER TERMINAL BLOCKTRANSMISSION TERMINAL BLOCK POWER SUPPLY TERMINAL BLOCK FAN MOTOR CAPACITORCORNER COVERDRAIN PLUGDRAIN PLUG
111111111111111111111
DPDS
P.BFUSEI.B w
TH21
A.BTB15TB5TB2
C
6.3A 250V
2P(1, 2)(M1, M2, S)(L, N, E)3.0+ 440V
S70 E02 529S70 A41 523S70 E01 355S70 E00 266S70 31K 241S70 E00 503S70 E02 313S70 520 239S70 E35 310S70 003 503S70 E10 675S70 E00 202S70 E00 304S70 B02 294S70 512 716S70 B02 716S70 521 716S70 576 255S70 001 663S70 A48 524S70 A41 524
Q'ty / setSpecifi-cation
Remarks(Drawing
No.)PLFY- · VAM-E.UK
P32, P40, P50, P63
w The part name of symbol “I.B” is “SPCB”.
Part numbers that is circled is not shown in the figure.
11
12
18
16
15
19
CAPACITOR
TRANSMISSIONTERMINAL BLOCK
MA-REMOTECONTROLLERTERMINAL BLOCK
THERMISTOR (ROOM)
20
21
DRAIN PLUG
DRAIN PLUG
10
5
7
9
4
3
2
1
8
14
13
17 POWER SUPPLYTERMINAL BLOCK
FUSE
6
FUNCTIONAL PARTSPLFY-P32VAM-E.UK PLFY-P40VAM-E.UKPLFY-P50VAM-E.UK PLFY-P63VAM-E.UK
OC313-A--1.qxp 04.9.3 11:20 AM Page 30
-
31
No. Parts No. Parts NameWiring
DiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
1
234567891011121314151617
18
192021
DRAIN PANDRAIN PANDRAIN SOCKETDRAIN PUMPDRAIN SENSORDRAIN SENSOR HOLDERCONTROL BOXPOWER BOARDFUSEINDOOR CONTROLLER BOARDCONTROL COVER ASSYFAN GUARDTHERMISTOR (ROOM)ADDRESS CABLEADDRESS BOARDMA-REMOTE CONTROLLER TERMINAL BLOCKTRANSMISSIONTERMINAL BLOCK POWER SPPLY TERMINAL BLOCK FAN MOTOR CAPACITORFAN MOTOR CAPACITORCORNER COVERDRAIN PLUGDRAIN PLUG
1
11111111111111111
111
11111111111111111
1111
DPDS
P.BFUSEI.B w
TH21
A.BTB15TB5TB2
CC
6.3A 250V
2P(1, 2)(M1, M2, S)(L, N, E)3.5+ 440V7.0+ 440V
S70 E02 529S70 E01 529S70 A41 523S70 E01 355S70 E00 266S70 31K 241S70 E00 503S70 E02 313S70 520 239S70 E35 310S70 003 503S70 E10 675S70 E00 202S70 E00 304S70 B02 294S70 512 716S70 B02 716S70 521 716S70 17T 255S70 E02 255S70 001 663S70 A48 524S70 A41 524
Q'ty / setSpecifi-cation
Remarks(Drawing
No.)PLFY- · VAM-E.UKP80 P100, P125
w The part name of symbol “I.B” is “SPCB”.
Part numbers that is circled is not shown in the figure.
11
12
18
16
15
19
CAPACITOR
TRANSMISSIONTERMINAL BLOCK
MA-REMOTECONTROLLERTERMINAL BLOCK
THERMISTOR(ROOM)
20
21
DRAIN PLUG
DRAIN PLUG
10
5
7
9
4
3
2
1
8
14
13
17 POWER SUPPLYTERMINAL BLOCK
FUSE
6
FUNCTIONAL PARTSPLFY-P80VAM-E.UKPLFY-P100VAM-E.UKPLFY-P125VAM-E.UK
OC313-A--2.qxp 04.9.3 11:21 AM Page 31
-
cCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.Distributed in Sep. 2004. No. OC313 REVISED EDITION-A PDF 8Distributed in May 2004. No. OC313 PDF 8Made in Japan
New publication, effective Sep. 2004Specifications subject to change without notice
OPTIONAL PARTS11
11-1. Multi function casement
Part No. PAC-SG03TM-E
11-2. Air outlet shutter plate (20 sets)
Part No. PAC-SG06SP-E
11-3. High efficiency filter (PAC-SG03TM-E is required in using this optional part.)
Part No. PAC-SG01KF