T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019...

27
11 Brightwood St On October 1, 2019 Inspection Address Waterville Me Inspected By Terry Guimond 207 794 5321 P.O. Box 26 Howland Me 04448 [email protected] T.A.Guimond Home Inspections Client’s Name John Doe *** Residential Inspection Report *** 1 Cover Page

Transcript of T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019...

Page 1: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

11 Brightwood St

OnOctober 1, 2019

Inspection Address

Waterville Me

Inspected ByTerry Guimond

207 794 5321

P.O. Box 26 Howland Me 04448

[email protected]

T.A.Guimond Home Inspections

Client’s NameJohn Doe

*** Residential Inspection Report ***

1 Cover Page

Page 2: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Phone #:

Email Address:

Email Address:

Listing Agent

Name:

Terry Guimond

Buyer Agent

Name:

Phone #:

Estimated sq. ft.

1,700

Inspected by

Time of Inspection

11:00 AM

Single Family /Single Story

Weather Type:

Inspection Address

Weather Conditions

Client Information

Clear

50 Degrees

Structure Type

John Doe

Bangor Me 04401

207 941 0001

11 Brightwood St

Waterville Me

Street Address:

City, State, Zip:

General Information

T.A.Guimond Home Inspections

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Name:

Street Address:

City, State, Zip:

Phone #:

Email Address:

Temperature:

Construction Type

Vinyl Siding with wood frame construction

Number of Bedroom/Bath

2 Bedroom / 1,5Bath / 2 Car Garage

Estimated Year Built

2003

2 Client Infomation

Page 3: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

This report is the exclusive property of inspection company and the client whose name appears herewith, and its use by any

unauthorized persons is strictly prohibited. The observations and opinions expressed within this report are those of inspection

company and supersede any alleged verbal comments. We inspect all of the systems, components, and conditions described in

accordance with home inspector’s standards of practice. The report is not intended for third party dissemination. This report

shall not be forwarded to any other person, company, or legal entity without inspection company express written approval.

Inspection company copyrights this report, which is protected by copyright law.

Inspection / Report limitations

This inspection report is to inform you of current condition as observed at time of inspection. As a general rule cosmetic

deficiencies are considered normal wear and tear and are not within the scope of this inspection unless they constitute major

and visually observable defects as defined in the Inspection Agreement. However some items, which may be considered

cosmetic in nature, may have been noted to assist you in evaluating other issues covered in the Inspection Agreement.

It is ultimately your decision on what concerns you would like corrected. Keep in mind that if you do not get them corrected

now the defects will have to be corrected in the future at your expense. It is not possible to detect every concern during a

general visual inspection. Things are going to happen and this inspection in no way is a warranty or guarantee as to the

condition of the property. Make sure to complete a final walk through of the property before the close of escrow.

This inspection does not include testing for radon, mold, termites and other wood destroying organisms, pests and rodents or

other hazardous materials unless specifically requested.

We are always interested in advancing the quality of our service and our report. We welcome and value your input. We adhere

to a high standard of professionalism and treat everyone with the utmost courtesy and respect.

We are proud of our service and trust you will be happy with the quality of our inspection and report. Please contact us with

any concerns you may have regarding the report. We will be glad to discuss them with you.

3 Client Infomation

Page 4: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Report SummaryThis Report Summary will describe area(s) of concern that were observed at time of inspection by this inspector that may need

some type of repair, replacement, service or further review. Keep in mind that all homes need some type of repair, even if only

minor and generally older homes well need more repairs. All safety concerns mentioned within this report should be reviewed and

repaired prior to occupancy. While every effort is made to identify existing and potential problems at the time of the inspection, it

is not possible for a home inspector to foresee all problems that might arise in the future. This Report Summary is provided as a

courtesy and cannot be considered a substitute for reading the entire report.

Utility Systems and Components

Electrical Service Connection and Components: Inspected

• The house breaker box has one breaker that has 2 circuits hooked to it. A Tandem breaker should be installed here.

Also above the house breaker panel where the wires go to the attic should be sealed off better

Electrical: Interior / Bedroom Areas: Inspected

• Smoke and C/O Detectors should be updated

Electrical: Kitchen / Bathroom / Exterior Areas: Inspected

• The outside outlet on the house needs a GFCI installed and also on the outlet by the main garage panel. There also

is a outlet in the upstairs shop that needs a cover

Gas / Fuel Supply System: Safety Hazard

• The inadvertent movement of the gas service line can cause leaks to form at the connections on either end of the

line. For these simple reasons, the gas line needs to be buried at a safe and required depth, Propane gas lines running

along the top of the ground are illegal and unsafe. Also where the gas enters the house should have some protection

from being broken off. And the hole filled to keep water ,air and bugs out.

Grounds

Tree’s / Shrubbery: Inspected

• The trees on the right side of the garage needs the branches trimmed back

Structural Systems

Ceiling: Inspected

• The ceiling trim in the closets are missing

Walls (Exterior): Inspected

• The Fascia has holes from when the rain gutters were on the house, And where the house fascia meets the entry

should be calked, Also the Fascia on the right gable end looks like it has moved

Door(s) (Interior & Exterior) includes Garage Door: Inspected

• The furnace room door is rubbing on the floor when opened

Balcony / Decks / Porches: Inspected

• Needs pressure washing, (Slippery when wet)

Roof and AtticRoof Covering: Inspected

• The roof has several rust spots that need to be sanded, primed and painted with a color matching paint. The cap

needs the rusted screws replaced and the cap overlaps resealed and the vent pipe flashing resealed. And the green

trim on the gable ends need to be sealed at the top. Some pictures will be in the flashing section

Flashing: Inspected

• The vent pipe needs to be resealed, New screws in the cap (rusting), and Gable rake trim sealed at the top

Kitchen

Report Summary Page4

Page 5: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Kitchen Plumbing: Inspected

• The sink on the right has no visible trap

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein

Report Summary Page5

Page 6: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Color of selection below will indicate the level of concern for each area at time of inspection

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

General Observation

Inspected Satisfactory

Service Connection

Location: Main Panel - Inside of garage

Services connection: Public Utilities (Underground Service)

Service on during inspection:

200 Amp service

Yes Type of wiring:

Service size sub panel: In Furnace room

Our inspection of Electrical System and components in accordance with industry standards of practice includes identifying the

type and capacity of the service, evaluating panels, overload conductors, wires, panel grounds, the testing of a representative

number of switches and outlets that were visible and accessible, and the presence or absence of smoke detector(s)/carbon

monoxide detector(s). This report is to inform you of current condition as observed at time of inspection. We recommend that

all electrical repairs and or replacements be evaluated and corrected by a qualified electrical contractor.

Electrical Service Connection and Components

Electrical Observations

Copper

Service size main panel:

Electrical System

120 / 240 Volt (Nominal) Amp:

The house breaker box has one breaker that has 2 circuits hooked to it. A Tandem breaker should be installed here. Also above

the house breaker panel where the wires go to the attic should be sealed off better

Damaged / Repair Safety HazardInspected Not Inspected Not Present

Amp: 100 amp

house panel

6 Electrical and Plumbing Systems

Page 7: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Color of selection below will indicate the level of concern for each area at time of inspection

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Damaged / Repair Safety HazardInspected Not Inspected Not Present

Our inspection of the Plumbing Systems and components in accordance with industry standards of practice includes a visual

examination of the accessible and visible plumbing fixtures and components. The plumbing system and their components are

tested and observed using normal operating controls, testing functional flow and observance of any active leakage throughout

fixture(s) and faucet(s). All underground and hidden piping and components, including water supply lines, waste lines, fuel lines,

storage tanks & sprinkler systems are beyond the scope of this inspection. Leakage or corrosion in underground and hidden

piping cannot be detected by a visual inspection, and for this reason we recommend further evaluation by a qualified contractor

to confirm its actual condition. This report is to inform you of current condition as observed at time of inspection. We

recommend that all material defects noted below be fully evaluated and/or corrected by a qualified plumbing contractor prior

to the close of escrow or contingencies.

Electrical: Kitchen / Bathroom / Exterior Areas

Switches / Outlets / Fixtures

Electrical: Interior / Bedroom Areas

Inspected

Switches / Outlets / Fixtures / Smoke Detector(s) / CO Detector(s)

Satisfactory

Observation:

Inspected Satisfactory / Fair

Observation:

Plumbing Systems

Smoke and C/O Detectors should be updated

The outside outlet on the house needs a GFCI installed and also on the outlet by the main garage panel. There

also is a outlet in the upstairs shop that needs a cover

Outside by house entry shop ceiling

7 Electrical and Plumbing Systems

Page 8: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Color of selection below will indicate the level of concern for each area at time of inspection

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Damaged / Repair Safety HazardInspected Not Inspected Not Present

Sewage Supply System

Cleanouts located side of home

Further Comments

Service on during inspection: Yes

Services connection: Public Utilities (Underground Service)

Service on during inspection:

Public Utilities (Underground Service)

Type of supply lines: Copper piping

Static water pressure reading (psi): 55 - 65

Yes

Satisfactory

Gas / Fuel Supply System

Inspected Satisfactory

Service Connection

Location:

Further Comments

Type of drain pipes: ABS pipe

General Observation

General Observation

Safety Hazard

Yes

Location:

Further Comments

Qualified Professional Recommended

Service Connection

Location: Back wall of the house

Services connection: LP (Propane)

Service on during inspection:

General Observation

Inspected

Service Connection

The inadvertent movement of the gas service line can cause leaks to form at the connections on either end of the line. For these

simple reasons, the gas line needs to be buried at a safe and required depth, Propane gas lines running along the top of the

ground are illegal and unsafe. Also where the gas enters the house should have some protection from being broken off. And the

hole filled to keep water ,air and bugs out.

No concerns observed

Water Supply System

House

Services connection:

8 Electrical and Plumbing Systems

Page 9: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home Inspections

Color of selection below will indicate the level of concern for each area at time of inspection

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Damaged / Repair Safety HazardInspected Not Inspected Not Present

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein

No concerns observed

9 Electrical and Plumbing Systems

Page 10: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Further Comments:

ConcreteMaterial:

Material: Grass / Vegetation

Satisfactory

Further Comments: No concerns observed

Back yard

No concerns observed

Inspected

No concerns observed

General Observation

Satisfactory

Description

Material: Grass / Vegetation

Further Comments:

Description

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Grounds

Grass / Vegetation

Further Comments: No concerns observed

Satisfactory

Inspected Not Inspected Not Present Safety HazardDamaged / Repair

Front yard

T.A.Guimond Home Inspections

Color of selection below will indicate the level of concern for each area at time of inspection

Our inspection of the Grounds area(s) in accordance with industry standards of practice are inspected visually for positive grading

and drainage that are essential to the welfare of a property and does not attempt to determine the condition of any underground

piping, including municipal water, sewer service piping or septic systems. Also inspected are the trees and shrubbery that can

cause foundation and or roof damage when growing too closely to the structure. While driveways and sidewalks of a residence

may be dirt, gravel or paved with a hard, solid surface, such as concrete or asphalt. Some cracking in driveways and walkways can

be expected; however, they should not cause a tripping hazard, erosion or in any way negatively impact the house. This report is

to inform you of current condition as observed at time of inspection.

Satisfactory

Description

Description

Inspected

Inspected

Side yard(s)

General Observation

Driveway / Sidewalks

General Observation

Material:

Inspected

General Observation

Grounds10

Page 11: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Date Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Inspected Not Inspected Not Present Safety HazardDamaged / Repair

T.A.Guimond Home Inspections

Color of selection below will indicate the level of concern for each area at time of inspection

Fencing / Gate

General Observation

Description

Inspected

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein.

Grading / Slope

Satisfactory

Further Comments: The trees on the right side of the garage needs the branches trimmed back

Tree’s / Shrubbery

Further Comments: No concerns observed

General Observation

Description

Satisfactory / Fair

Description

Material: Plastic

General Observation

Inspected

Satisfactory

Further Comments: No concerns observed

Inspected

Grounds11

Page 12: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

General Observation

Inspected Satisfactory

Description

Material: Carpet, Tile

Further Comments: No concerns observed

Floors

Further Comments: No concerns observed

Structural Components / Foundation / Sub Areas

Type of Foundation(s) Slab Foundation with frost walls

Inspected Satisfactory

Description

FoundationGeneral Observation

Our inspection of the Structural Components / Foundation / Sub Areas in accordance with industry standards of practice, that

includes the visually accessible areas of carports, patio covers, awnings, decks, walls, flooring, ceilings, fascia, trim, soffits,

balconies, doors, windows, basement and stairways. We visually inspect the foundation and look for any evidence of structural

deficiencies, while foundation type and material of construction may defer such as concrete, masonry block, brick, stone and or

wood foundation, they can experience some degree of cracking due to stress, settlement, shrinkage and various temperature

change. We will not inspect any detached structures unless contracted to do so. This inspection does not include the geological

conditions of the property, such as soil expansion or soil compaction. This inspector is not required to enter any area or perform

any procedure that may damage the property or its components or be dangerous to or adversely affect the health of the home

inspector or other persons. This inspector will not enter crawlspaces or any areas where headroom clearance is less than 18

inches and the width of the access opening is less than 18 inches by 24 inches or where inspector reasonably determines

conditions or materials are hazardous to his health or safety. This report is to inform you of current condition as observed at time

of inspection.

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Structural Components / Foundation / Sub Areas12

Page 13: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Further Comments: The ceiling trim in the closets are missing

CeilingGeneral Observation

Inspected Satisfactory / Fair

Description

Material: Drywall

Structural Components / Foundation / Sub Areas13

Page 14: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Further Comments: The Fascia has holes from when the rain gutters were on the house, And where the house fascia meets the

entry should be calked, Also the Fascia on the right gable end looks like it has moved

Walls (Exterior)General Observation

Inspected Satisfactory / Fair

Description

Material:

Further Comments: No concerns observed

Walls (Interior)General Observation

Inspected Satisfactory

Description

Material: Drywall

Vinyl

Further Comments: No concerns observed

Window(s)General Observation

Inspected Satisfactory

Description

Material: Vinyl (dual pane)

Structural Components / Foundation / Sub Areas14

Page 15: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Further Comments: The furnace room door is rubbing on the floor when opened

Door(s) (Interior & Exterior) includes Garage DoorGeneral Observation

Inspected Satisfactory

Description

Type: Wood and metal, two car garage door (Metal)

No concerns observed

Basement / Sub AreasGeneral Observation

Not Present Satisfactory

Description

Material: Basement Foundation - Concrete

Further Comments:

Structural Components / Foundation / Sub Areas15

Page 16: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Needs pressure washing, (Slippery when wet)Further Comments:

Wood and plasticMaterial:

Description

Satisfactory / FairInspected

General Observation

Balcony / Decks / Porches

Wood structureMaterial:

No concerns observedFurther Comments:

Further Comments: No concerns observed

Basement - Drainage - Sumps and Pumps

conditions agreed upon therein.

Awning(s) / Patio cover(s) / Carport(s)

No concerns observedFurther Comments:

PlasticMaterial:

Description

SatisfactoryInspected

General Observation

Stairways-Handrails-Guardrails (Interior & Exterior)

Description

SatisfactoryLimited Inspection

General Observation

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

General Observation

Not Present Satisfactory

Description

Material: Concrete wall

Structural Components / Foundation / Sub Areas16

Page 17: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Further Comments: No concerns observed

Description

Material: Concrete, wood upstairs

General Observation

Inspected Satisfactory

Description

Material: Vinyl lap siding

FlooringGeneral Observation

Inspected Satisfactory

Walls (Interior and Exterior)

Further Comments: No concerns observed

Inspected Satisfactory

Description

Further Comments: No concerns observed

Electrical / Lighting / OutletsGeneral Observation

Our inspection of Detached Structure area(s) in accordance with industry standards of practice includes the visually accessible

areas of walls, floors, ceilings, cabinets and closets, and includes the testing of a representative number of windows and doors,

switches and outlets, also the plumbing system and their components if present are tested and observed, which includes testing

functional flow and leaks throughout fixture(s) and faucet(s). Inspect drain, waste and vent system and report on deficiencies.

However, we do not move furniture, lift carpets or rugs, empty closets or cabinets. This report is to inform you of current

condition as observed at time of inspection.

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Detached Structure

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Detached Structure17

Page 18: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Satisfactory

Plumbing

Not Present Satisfactory

Description

Door(s) / Garage door(s)General Observation

Inspected Satisfactory

Description

Material: Two car garage door (Metal)

Description

Further Comments: No concerns observed

Cabinet(s) and Countertop(s)General Observation

Inspected Satisfactory

Description

Material: Wood

Further Comments: No concerns observed

Description

Further Comments: No concerns observed

General Observation

Attic / RaftersGeneral Observation

Inspected

Window(s)General Observation

Inspected Satisfactory

Material: Vinyl (dual pane)

Further Comments: upstairs

Further Comments: No concerns observed

Type:

Detached Structure18

Page 19: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

RoofingGeneral Observation

Inspected Satisfactory

Description

Material: Standing seam, Painted steel

Further Comments: No concerns observed

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein.

Detached Structure19

Page 20: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Roof StructureGeneral Observation

Our inspection of the Roof and Attic area(s) in accordance with industry standards of practice includes a visual observation of the

roof covering, gutters, downspouts, vents, flashings, chimney, skylight and other roof penetrations within the limits of

accessibility. The inspector may walk the surface of a roof in order to inspect it and its components but may inspect it by other

means if the roof cannot be safely accessed, due to its height, weather conditions, or if the roofing material could be damaged by

foot traffic. The inspector is not required to, predict the service life expectancy or inspect underground downspout diverter pipes,

remove snow ice or debris, or inspect antennae, lighting arrestors or similar attachments. All roofing types require some type of

annual maintenance (some types more frequent than others). Failure to perform routine maintenance can result in leaks and

accelerate roof covering and flashings deterioration. An inspector cannot guarantee a roof is leak free, only observation during a

prolonged rainfall can determine this. This report is to inform you of current condition as observed at time of inspection. We do

not attempt to enter attics that have less than thirty-six inches of headroom, are restricted by ducts, or in which the insulation

obscures the joists and thereby makes mobility hazardous, in which case we would inspect them as best as we can from the

access point. In regard to evaluating the type and amount of insulation on the attic floor, we use only generic terms and

approximate measurements, and do not sample or test the material for specific identification. Also, we do not disturb or move

any portion of it, and it may well obscure water pipes, electrical conduits, junction boxes, exhaust fans, and other components.

Roof and Attic

Inspected Satisfactory

Description

Further Comments: No concerns observed

Roof and Attic 20

Page 21: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Roof Covering

Further Comments: The roof has several rust spots that need to be sanded, primed and painted with a color matching paint. The

cap needs the rusted screws replaced and the cap overlaps resealed and the vent pipe flashing resealed.

And the green trim on the gable ends need to be sealed at the top. Some pictures will be in the flashing

section

General Observation

Inspected Satisfactory / Fair

Description

Material: Painted green steel standing seam Viewed from: Walking on the roof

Further Comments: Medium pitch

Roof SlopeGeneral Observation

Inspected Satisfactory

Description

Further Comments: No concerns observed

Gutters and Down SpoutsGeneral Observation

Not Present Satisfactory

Description

Material:

Roof and Attic 21

Page 22: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Further Comments: The vent pipe needs to be resealed, New screws in the cap (rusting), and Gable rake trim sealed at the top

FlashingGeneral Observation

Inspected Satisfactory

Description

Material: Painted green steel

VentilationGeneral Observation

Inspected Satisfactory

Description

Further Comments: No concerns observed

ridge cap joints cap screws are all rusted

vent pipe flashing

3 different areas need to be sealed

on the gable peaks

Roof and Attic 22

Page 23: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

Description

SatisfactoryInspected

General Observation

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein.

Viewed From: By entering crawl space

Attic Vents

No concerns observedFurther Comments:

No concerns observedFurther Comments:

Gable vents and soffitType:

Description

Inspected

General Observation

Fiberglass battMaterials:

Attic Structure

No concerns observedFurther Comments:

Satisfactory

Description

SatisfactoryInspected

General Observation

Insulation

Roof and Attic 23

Page 24: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Material: Tile

Further Comments: No concerns observed

Floor Covering (Kitchen)General Observation

Inspected Satisfactory

Description

Color of selection below will indicate the level of concern for each area at time of inspection

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

KitchenOur inspection of the Kitchen area(s) in accordance with industry standards of practice includes the visually accessible areas of

walls, floors, ceilings, cabinets and closets, and includes the testing of a representative number of windows and interior doors,

switches and outlets, also the plumbing system and their components are tested and observed, which includes testing functional

flow and leaks throughout fixture(s) and faucet(s). Inspect drain, waste and vent system and report on deficiencies. We will not

attempt to move furniture, lift carpets or rugs, empty closets or cabinets. This report is to inform you of current condition as

observed at time of inspection.

Cabinet(s)

Countertop(s)

Inspected Satisfactory

Further Comments: No concerns observed

Satisfactory

Description

General Observation

Inspected

Material: Laminate countertop

General Observation

Description

Material: Wood Cabinets

Further Comments: No concerns observed

Kitchen24

Page 25: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Color of selection below will indicate the level of concern for each area at time of inspection

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

conditions agreed upon therein.

Further Comments: No concerns observed

Kitchen PlumbingGeneral Observation

Inspected Recommend Repair

Description

Closet(s) / PantyGeneral Observation

Inspected Satisfactory

Description

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

Material: Copper and PVC

Further Comments: The sink on the right has no visible trap

Material: Wood door(s)

Kitchen25

Page 26: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

Cooling System

No concerns observed

SatisfactoryNot Present

General Observation

Year Model:Furnace Name:

Cooling type:

Serial #:Model #:

Further Comments

Back yardLocation:

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein.

Bradford-White

Heat source type:

Safety Hazard

Location:

Color of selection below will indicate the level of concern for each area at time of inspection

Boiler room

Fuel type: LP Gas (Propane) Vent type: Forced ventilation

The components of most heating and air-conditioning systems have a design-life ranging from ten to twenty years, but can fail

prematurely with poor maintenance, which is why we apprise you of their age whenever possible. We test and evaluate them in

accordance with the standards of practice, which means that we do not dismantle and inspect the concealed portions of

evaporator and condensing coils, the heat exchanger, which is also known as the firebox, electronic air-cleaners, humidifiers,

ducts and in-line duct-motors or dampers. We perform a conscientious evaluation of both systems, but we are not specialists.

However, even the most modern heating systems can produce carbon monoxide, which in a sealed or poorly ventilated room

can result in sickness, debilitating injury, and even death. Therefore, in accordance with the terms of our contract, it is essential

that any recommendations that we make for service or a second opinion be scheduled before the close of escrow, because a

specialist could reveal additional defects or recommend further upgrades that could affect your evaluation of the property, and

our service does not include any form of warranty or guarantee.

Furnace Name:

Model #: Serial #:

Year Model:

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Heating and Cooling

Heating System

General Observation

Inspected Satisfactory

Further Comments

Radiant Heating System

Inspected

2003

Not Inspected Not Present Damaged / Repair

No concerns observed

Heating and Cooling26

Page 27: T.A.Guimond Home Inspections · T.A.Guimond Home Inspections Date Of Inspection: October 1, 2019 Inspection Address: 11 Brightwood St , Waterville Me This report is the exclusive

This Home Inspection Field Report is confidential and has been produced in accordance with our signed contract agreement and is subject to the terms and

conditions agreed upon therein.

Tank capacity: TanklessLP Gas (Propane)

Ventilation type: Plastic flue ventilation

Location: Boiler room

Further Comments

Type of system:

Functional Satisfactory

Color of selection below will indicate the level of concern for each area at time of inspection

Inspected Not Inspected Not Present Damaged / Repair Safety Hazard

2003Rinnai

Water Heating System

Brand: Year Model:

Model #: Serial #:

Gas demand water heater

Fuel type:

T.A.Guimond Home InspectionsDate Of Inspection: October 1, 2019

Inspection Address: 11 Brightwood St , Waterville Me

Water Heating System(s)There are a wide variety of residential water heaters systems that range in capacity from fifteen to one hundred gallons. They

can be expected to last at least as long as their warranty, or from five to eight years, but they will generally last longer. However,

few of them last longer than fifteen or twenty years and many eventually leak. So it is always a good idea to have them installed

over a drain pan plumbed to the exterior. Also, it is very important to flush them annually to remove loose sentiment that

includes the calcium chloride bi-products of many water softening systems. The water temperature should be set at a minimum

range of 110 degrees Fahrenheit to kill microbes and a maximum of 140 degrees to prevent scalding. Also, water heaters can be

dangerous if they are not seismically secured and equipped with either a pressure/temperature relief valve and discharge pipe

plumbed to the exterior, or a Watts 210 gas shut-off valve. Therefore, in accordance with the terms of our contract, it is essential

that any recommendations that we make for service or a second opinion be scheduled before the close of escrow, because a

specialist could reveal additional defects or recommend further upgrades that could affect your evaluation of the property, and

our service does not include any form of warranty or guarantee.

General Observation

No concerns observed

Water Heating System(s)27