Switching Transients on a Southern Company 500 / 230 kV Auto- transformer: Examples from Project to Present Date IEEE Transformers Committee Meeting Minneapolis, MN 10/15/2007 Larry Coffeen NEETRAC High Voltage Laboratory Presentation courtesy of The Southern Company Contributions from JMX Services, Inc

Transcript of Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at...

Page 1: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Switching Transients on a Southern Company 500 / 230 kV Auto-

transformer: Examples from Project to Present Date

IEEE Transformers Committee MeetingMinneapolis, MN

10/15/2007

Larry CoffeenNEETRAC High Voltage Laboratory

Presentation courtesy of The Southern Company

Contributions from JMX Services, Inc

Page 2: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Switching transients at 500 / 230 kV auto-transformer

• Laboratory withstand & calibration tests on a field installed laboratory grade voltage divider

• Transients due to de-energizing 950 ft. of 500 kV bus with motorized disconnect switch

• On-line transfer function of 500 / 230 kV auto using same disconnect switch transient

• Show comparison of on-line transfer function to baseline off-line transfer function

• Show transients for switching 500 / 230 auto trans out of service and switching auto back in service

• Show frequency content of a low level area lightning strike typically used for on-line FRA calculation

Page 3: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Wideband Voltage Divider Near 230 kV X1 Bushing

Page 4: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

500 / 230 kV, Phase 3

Laboratory FRA Trailer

Page 5: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field
Page 6: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Laboratory Tests Performed

• ac 60 Hz ratio 40 kV - 300 kV (75,007:1)• Partial Discharge @ 300 kV (2 PC)• Withstand of 3+ & 3-, 1 MV lightning

impulses (72,973:1 compared to laboratory 2.1 MV impulse divider)

• Time domain comparisons 45 kV - 200 kV impulse with laboratory reference voltage divider (76,015:1)

Page 7: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Time Domain Calibration Check of BPA Voltage Divider

0

5

10

15

20

25

30

35

40

45

50

-5 5 15 25 35 45 55 65 75 85 95

Time(microseconds) @ 10MS/sec.

App

lied

Volta

ge(k

V)

HV Reference Divider BPA Divider

Page 8: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Time Domain Calibration Check of BPA Voltage Divider[zoom in on front & peak of impulse]

0

5

10

15

20

25

30

35

40

45

50

-1 0 1 2 3 4 5 6 7 8 9 10

Time(microseconds) @ 10 MS/sec.

App

lied

Volta

ge(k

V)

HV Reference Divider BPA Divider

Page 9: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

H1 Bushing Tap, HP Filtered

X1 Bushing Tap, HP Filtered

X1 Wideband Divider, HP Filtered

Phase 1 Neutral, HP Filtered

FFT of Divider Waveform

De-energize 500 kV Bus Section

Page 10: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of H1 Bush Tap Waveform

De-energize 500 kV bus section

H1 Bush Tap, HP Filtered

Page 11: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of H3 Bush Tap Waveform

H3 Bush Tap, HP Filtered

De-energize 500 kV bus section

X3 Bush Tap, HP Filtered

Phase 3 Neutral, HP Filtered

Divider not on Phase 3, noise shown

Page 12: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

On-line FRA of H3-H0X0 using 500 kV switching transient from previous slide

Page 13: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Off-line FRA test of all three H Windings.

Shows similar frequency peaks to online results from disconnect switch transient (previous slide)

Page 14: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Off-line test, Low Frequency Range

On-line has prominent peak here. On-line energy is much greater at this resonant frequency (about 175 kHz)

Page 15: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

H1 Bush Tap HP Filtered

X1 Bush Tap HP Filtered

Noise Interference

FFT of X1 Bush Tap

Phase 1 Neutral Bush HP Filtered

De-energize 230 kV Bus Section

Page 16: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of X2 Bush Tap

De-energize 230 kV bus section

X2 Bush Tap, HP Filtered

Divider not on X2, noise shown

Phase 2 Neutral Bush, HP Filtered

Page 17: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of Phase 3 Neutral Waveform

De-energize 230 kV bus section

H3 Waveform Clipped

X3 Waveform Clipped

Phase 3 Neutral Bush, HP Filtered

Divider not on X3, noise shown

Page 18: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

H1 Bush Tap, HP Filtered

X1 Bush Tap, HP Filtered

X1 full bandwidth on divider

Phase 1 Neutral, HP filtered

FFT of X1 Bush Tap Waveform

Pick up load on re-energize

Page 19: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of X2 Bush Tap Waveform

Pick up load on re-energize

X2 Bushing Tap, HP Filtered

Divider not on X2, noise shown

Phase 2 Neutral, HP Filtered

Page 20: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

H1 Bushing Tap, off scale

X1 Bushing Tap, off scale

WB divider X1 w/ HP filter

Phase 1 Neutral, HP filtered

FFT of WB divider waveform

Area Lightning Strike, Phase 1

Page 21: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of X2 Bush Tap Waveform

Area Lightning Strike, Phase 2

X2 Bush Tap, HP Filtered

Phase 2 Neutral Bush, HP Filtered

H2 Bush Tap, Clipped

Divider not on X2, noise shown

Page 22: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

FFT of H3 Bush Tap Waveform

Area Lightning Strike, Phase 3

H3 Bush Tap, HP Filtered

X3 Bush Tap, HP Filtered

Phase 3 Neutral Bush, HP Filtered

Divider not on X3, noise shown

Page 23: Switching Transients on a Southern Company 500 / 230 kV ... · PDF fileSwitching transients at 500 / 230 kV auto-transformer • Laboratory withstand & calibration tests on a field

Switching Transient Observations on 500 / 230 kV Auto-transformer Project to Date

• 500 / 230 kV systems can have transients present with frequency content into the MHz region.

• These transients can be generated by local switching and / or lightning.

• High frequencies can pass through a 500 / 230 kV auto with significant energy content to excite resonant frequencies in the windings.

• The TRV capacitors on the 230 kV low side breaker at the test site reduced significant transients at the transformer bushings for the normal dropping of load.

• We need to increase our dynamic range of transient recording input for the most severe transients.