    STRUCTURAL FIREPRECAUTIONS PART 1

  • 7/27/2019 Structual Fire Precaution Part 1

    2/28

    Scope of Presentation

    Objectives of Structural Fire Precautions

    Needs for Compartmentation

    Clarification of Clauses Conclusion

  • 7/27/2019 Structual Fire Precaution Part 1

    3/28

    Objectives of Structural Fire

    Precautions

    (a) To prevent the spread of fire between adjoiningbuildings by adequate separation;

    (b) To prevent the untimely collapse of building, includingwalls and floors of each unit in the event of a fire.

    (c) To prevent spread of fire from one unit to anotherwithin the building envelope by compartmentalisingeach unit with walls, floors and doors having therequisite fire resistance rating.

  • 7/27/2019 Structual Fire Precaution Part 1

    4/28

    Compartmentation

    Limits the size of the fire.

    Goal of compartmentation is confining a fire

    and minimizing risk of loss of occupants by

    segregating a space to control the spread the

    fire.

    Most common failure of compartmentation?

    Leaving a door open.

  • 7/27/2019 Structual Fire Precaution Part 1

    5/28

    Compartmentation

    Response

    Structure

    Protection

    Smoke

    Management

    Escape

    http://www.archiform3d.com/portfolios-architectural-renderings-video-website/breezes-3d-rendering-virtual-reality-gallery.htm
  • 7/27/2019 Structual Fire Precaution Part 1

    6/28

    Compartmentation

    Compartmentation by:-Area/Cubical Extent (Clause 3.2.1)

    - Height (Clause 3.2.4)

    -Residential II (Clause 3.2.5(a))

    -Purpose Group (Clause 3.2.5(b))

    -Basement Clause 3.2.5(c))

    -Others (FCC, kitchen etc)

    TABLE 3.2A SIZE LIMITATION OF BUILDING AND COMPARTMENT

    (1)

    Compartments

    (2)

    Maximum

    Floor Area

    (3)

    Maximum

    Cubical Extent

    Compartment below ground level. No

    compartment to comprise more than one storey.

    2000m 7500m

    Compartments between average ground level and

    a height of 24m. No compartment to comprise

    more than 3 storeys.

    4000m 15000m

    Compartments above a height of 24m from

    average ground level. No compartment to

    comprise more than one storey.

    2000m 7500m

    Note: Except Purpose Group I

  • 7/27/2019 Structual Fire Precaution Part 1

    7/28

    Compartmentation

    Compartmentation by:-Area/Cubical Extent (Clause 3.2.1)

    - Height (Clause 3.2.4)-Residential II (Clause 3.2.5(a))

    -Purpose Group (Clause 3.2.5(b))

    -Basement Clause 3.2.5(c))

    -Others (FCC, kitchen etc)

  • 7/27/2019 Structual Fire Precaution Part 1

    8/28

    Compartmentation

    Compartmentation by:-Area/Cubical Extent (Clause 3.2.1)

    - Height (Clause 3.2.4)-Residential II (Clause 3.2.5(a))

    -Purpose Group (Clause 3.2.5(b))

    -Basement Clause 3.2.5(c))

    -Others (FCC, kitchen etc)

  • 7/27/2019 Structual Fire Precaution Part 1

    9/28

    9

    Clause 3.2.3 Where however, the Relevant Authority is satisfied thatadditional floor area and cubical extent are necessary for any such building or

    compartment or part thereof, as aforesaid, he may consent to such additional

    floor area and cubical extent, provided :

    (a) Such building or compartment thereof is fitted throughout with an

    automatic sprinkler system which complies with the requirements in Chapter

    6,

    (b) There is proper accessibility of site to fire fighting appliances, in

    compliance with the requirements in Chapter 4,

    (c) All other measures have been or will be taken and maintained for lessening

    so far as is reasonably practicable, any danger from fire.

    Such consent shall continue in force only while such building or compartment

    is used for the purposes in respect of which such consent was given.

  • 7/27/2019 Structual Fire Precaution Part 1

    10/28

    10

    To avoid providing fire compartmentation in building to comply

    with the cubical extent and floor area control under Table 3.2A,

    automatic sprinkler system would be proposed as an

    alternative. Where automatic sprinkler system is to be provided

    to a building, compliance with Table 3.2A on max. 3 storeys per

    compartment is still required, unless atrium design is proposed

    subject to obtaining SCDF (FSSD)s prior approval beforesubmission of building plan.

    Source : Handbook 2002 Volume 5

  • 7/27/2019 Structual Fire Precaution Part 1

    11/28

    Mixed Development Mixed Development

    Compartment of 3 storeys /atrium design (with sprinkler protection)

    Acceptable

  • 7/27/2019 Structual Fire Precaution Part 1

    12/28

    Mixed Development Mixed Development

    Compartment more with more than single storeys (with sprinkler

    protection)

    Not Acceptable

  • 7/27/2019 Structual Fire Precaution Part 1

    13/28

    13

    3.2.2 (b) Where two buildings are connected byexternal open-sidedcovered way or covered link-bridge, the buildings areconsidered as separate buildings, if the following conditionsare complied with:(i) Within the covered way or link-bridge there is no

    commercial activities or other usage that would pose afire risk;(ii) The width of the covered way or covered link-bridgeshall not exceed 5m measured from eave to eave.

    Building A Building BGround

    Level

    Linkage

    Building

    A

    Building

    BLinkage

    Section View Plan View

  • 7/27/2019 Structual Fire Precaution Part 1

    14/28

    14

    3.2.2 (b) Where two buildings are connected byexternal open-sidedcovered way or covered link-bridge, the buildings areconsidered as separate buildings, if the following conditionsare complied with:(i) Within the covered way or link-bridge there is no

    commercial activities or other usage that would pose afire risk;(ii) The width of the covered way or covered link-bridgeshall not exceed 5m measured from eave to eave.

    Building A Building BGround

    Level

    Linkage

    Building

    A

    Building

    BLinkage

    Section View Plan View

    Air-Well Size should

    be Minimum 93 sqmand 6m Apart

  • 7/27/2019 Structual Fire Precaution Part 1

    15/28

    15

    Building A Building BGround

    Level

    Linkage

    Building

    A

    Building

    BLinkage

    Section View Plan View

    Minimum Air-Well

    Size should be based

    on

    Table 1.2.29

    (min. 10 by 10m)

    Staircase

    ventilation thru

    air-well

    3.2.2 (b) Where two buildings are connected byexternal open-sidedcovered way or covered link-bridge, the buildings areconsidered as separate buildings, if the following conditionsare complied with:

    (i) Within the covered way or link-bridge there is nocommercial activities or other usage that would pose afire risk;(ii) The width of the covered way or covered link-bridgeshall not exceed 5m measured from eave to eave.

  • 7/27/2019 Structual Fire Precaution Part 1

    16/28

    FIRE SEPARATION OF

    PRUPOSE GROUPS

    Clause 3.2.5 (b)

    Table 1.2 B Designation of Purpose Group

    1

    Mixed Development

    Note:

    Currently the Fire Code Review

    Committee is reviewing the usage

    in commercial Development

  • 7/27/2019 Structual Fire Precaution Part 1

    17/28

    FIRE SEPARATION OF

    PRUPOSE GROUPS

    Clause 3.2.5 (b)

    Rooms or spaces for ancillary usage

    located within a building or

    compartment of Purpose Group III,

    IV, V, Vi, VII and VIII as stipulated

    under cl.1.2.2(B).

    Table 1.2 B Designation of Purpose Group

    1

    2

    Mixed Development

    Refer to 1.2.2(B) (a) The ancillary

    office, sick room/first aid room,

    reception lobby/area, waiting area,

    staff lounge/staff recreation room,

    staff rest room/pantry, staff

    changing/locker room, etc.

  • 7/27/2019 Structual Fire Precaution Part 1

    18/28

    FIRE SEPARATION OF

    PRUPOSE GROUPS

    Clause 3.2.5 (b)

    Ancillary offices located within a

    building or compartment of

    Purpose Group III, V, VI, VII and

    VIII.

    Rooms or spaces for ancillary usage

    located within a building or

    compartment of Purpose Group III,

    IV, V, Vi, VII and VIII as stipulated

    under cl.1.2.2(B).

    Table 1.2 B Designation of Purpose Group

    1

    2

    3

    Mixed Development

    FIRE SEPARATION OF

  • 7/27/2019 Structual Fire Precaution Part 1

    19/28

    FIRE SEPARATION OF

    PRUPOSE GROUPS

    Clause 3.2.5 (b)

    Ancillary offices located within a

    building or compartment of

    Purpose Group III, V, VI, VII and

    VIII.

    Rooms or spaces for ancillary usage

    located within a building or

    compartment of Purpose Group III,

    IV, V, Vi, VII and VIII as stipulated

    under cl.1.2.2(B).

    Table 1.2 B Designation of Purpose Group

    For building types not included in theabove tables, occupancy load

    calculation shall be based on the

    figures established for buildings within

    the same purpose group, or as

    otherwise determined by

    the Relevant Authority.

    1

    2

    3

    4

    Mixed Development

  • 7/27/2019 Structual Fire Precaution Part 1

    20/28

    Under Clause 3.2.5 (d), can you

    install multi tiers car parksystem in basement car park?

  • 7/27/2019 Structual Fire Precaution Part 1

    21/28

    Clause 3.2.5 (d) - In any compartment below pavement level, nocompartment shall comprise more than one storey, except in the case of

    purpose groups IV, V and VII as permitted under sub-clause (c) (ii) and in

    the case of basement used solely for car parking. No part of a basement

    storey shall be used for the bulk storage of highly inflammable liquids or

    substances of an explosive nature.

    Answer is NOTo comply with Clause 1.1.7

    Fully Automated Mechanised Car Park (FAMCP)

  • 7/27/2019 Structual Fire Precaution Part 1

    22/28

    Clause 3.2.5 (f) Kitchen SeparationNotwithstanding all the above, the compartment where

    open flame cooking activities is carried out shall not

    comprise more than one storey.

    Kitchen

  • 7/27/2019 Structual Fire Precaution Part 1

    23/28

    Clause 3.2.5 (f) Kitchen SeparationNotwithstanding all the above, the compartment

    where open flame cooking activities is carried out

    shall not comprise more than one storey.

    Kitchen

    Fire Alarm Activation

    Smoke curtain

  • 7/27/2019 Structual Fire Precaution Part 1

    24/28

    Clause 3.2.5(j) (iii) Kitchen shall be enclosed with minimum 1-hour fire

    rated compartment wall, including -hour fire rated door. Kitchen can

    be located within each floor, but shall not be within the dormitory

    bedroom.Dormitory

    No Fire Door Needed

    External Corridor corridor

    to comply with cl.2.9.3 and cl.2.9.4

    Dormitory

  • 7/27/2019 Structual Fire Precaution Part 1

    25/28

    3.2.5 (o) Areas of Special Hazard(ii) Rooms housing transformer containing flammable liquid and

    generator rooms shall be located against

    an external wall.

    Transformer room-Transformers that is dry type no need to face external wall

    -Oil cooled type are to be located against an external wall above ground level to

    allow for external ventilation and explosion relief.

    external wall

    Transformer

  • 7/27/2019 Structual Fire Precaution Part 1

    26/28

    3.2.5 (o) Areas of Special Hazard(ii) Rooms housing transformer containing flammable liquid and generator

    rooms shall be located against an external wall.

    Transformer roomOpening of the external walls can be based on at least 10% of the floor

    area for natural ventilation of the transformer room

    external wall

    Transformer

  • 7/27/2019 Structual Fire Precaution Part 1

    27/28

    Transformer

    Transformer can be

    located in basement but

    ventilation openings to

    directly open to sky

  • 7/27/2019 Structual Fire Precaution Part 1

    28/28

    Conclusion

    Compartmentation is essential part of

    Structural Fire Precautions

    Part 2 - To prevent the spread of fire between

    adjoining buildings by adequate separation