Sprinkler Skipping

Page 3: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

Will “skipping” be a factor in the performance of the sprinkler (sprinkler in the fire area being cooled by

adjacent activated sprinklers preventing it

from operating)

The best wail for a system to fail is to “Skip” critical sprinklers from operating in the “Core” fire area.

Sprinkler Skipping

Page 4: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

4

“I just wish we could teach the first sprinkler to count to 10 before it

discharges water”

Core Fire Suppression

Steve Meyer - 1996

Page 5: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

5

Skipping Occurs When:

1. The higher the clearance is between what's burning and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers.

2. Strong fire plume velocities carry water and cooling back up to the surrounding sprinklers.

3. Water droplet size and velocity fails to penetrate the fire plume and gets carried back up to the surrounding sprinklers.

4. Obstructions to sprinkler discharge may cause #2 and #3

Page 6: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume
Page 7: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

FM Global

Page 8: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

Pan Fire Tests

Fire Source: 2.1m x 2.1m pan

Page 9: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

9

High Ceiling Tests

Fuel Arrangement: FMRC Class 2 commodity Fuel Height: 2.26 mClearance to ceiling: 15.4 m Arrangement of fuel package: 8 by 8, solid pile, 2 tiersDensity: 12 mm/minSprinklers: K115, RTI 140 (m-s)1/2 Standard Response, UprightSpacing: 3.0 m x 3.0 m

Page 10: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

10

Side View of Fuel Array

Class II Group A Plastics

Page 11: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

11

Plan View of Fuel Array – Test 1

Page 12: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

12

Plan View of Sprinkler Operation – Test 1

Page 13: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

13

FMRC Cartoned Unexpanded Group A Plastics

16‐oz Polystyrene Plastic Jars in compartmented cardboard cartons 

Page 14: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

14

Plan View of Fuel Array – Test 3 & 4

Page 15: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

15

Description of Full Scale Fire Test 3

Fuel Arrangement: FMRC Group A PlasticsFuel Height: 1.73 mClearance to ceiling: 15.9 mArrangement: 2 by 8, solid pile, 1 tierDensity: 12 mm/minSprinklers: K115, RTI 140 (m-s)1/2 Standard Response element, UprightSpacing: 3.0 m x 3.0 m

Page 16: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

16

Plan View of Sprinkler Operation – Test 3

Page 17: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

17

Results Test 3

Number of Sprinklers Operated: 26 !Skipping of Sprinklers: extremeTest terminated at 9 minutes before it yielded conclusive results

Key Take Away: Test failed

Page 18: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

18

Description of Full Scale Fire Test 5intended to provide a reference point for future work

Fuel Arrangement: FMRC Group A Plastics identical to test4Fuel Height: 1.73 m Clearance to ceiling: 16.6 m Clearance to deflector: 16.4 m Arrangement: 2 by 8, solid pile, 1 tierDensity: 18 mm/minSprinklers: K= 360 (EC-25), RTI 28 (m-s)1/2 Fast Response element, UprightSpacing: 6.1 m x 6.1 m

Page 19: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

19

EC-25 (Extended Coverage Extra Hazard Sprinkler)

Control Mode (Density/Area)Extended CoverageK-factor – 360 LPM/bar1/2

RTI: 28 (m-s)1/2 – Fast Response elementTemperature Ratings 74°C or 101°CPosition: UprightFinish: Natural BrassPipe Thread Connection: 1” NPT or ISO 7-R1

Page 20: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

20

Plan View of Sprinkler Operation – Test 5

Page 21: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

21

Results Test 5

Number of Sprinklers Operated: 1Ceiling temperature: Within acceptable levelsFire damage: Fire well confined to ignition arrayNo Skipping of sprinklers since only one operated

Key Take Away: Favorable results, fire losing intensity at 2 min. 10s. , one head operating, fire well confined but additional test needed to verify protection scheme

Page 22: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

20 FT HIGH PLATFORM

40 ft

10 ft

TEST NO.

OBSTRUCTION

1 4" BAR JOIST (8 IN. DOWN)

2 1-1/2" BRIDGING (8 IN. DOWN)

Obstructions

Page 23: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

PROTECTION SYSTEM K-14 ESFR SPRINKLER

CEILING SPRINKLERS ONLYPENDENT INSTALLATION10 FT X 10 FT SPACING14 IN. DEFLECTOR CLEARANCE75 PSI SYSTEM PRESSURENOMINAL RTI 50 165 oFK=140.70 IN. ORIFICE

Page 24: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

• TOTAL NUMBER OF SPRINKLERS• EIGHT (8) DURING TEST (Max)• BENCHMARK  ‐ ONE

• FIRE DAMAGE • IGNITION ARRAY ONLY

• CEILING STEEL TEMPERATURE • LESS THAN 1000 OF

Baseline

Page 25: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

PLAN VIEW

4'

Sprinkler

Bar Joist

N

Bar Joist

PROTECTION SYSTEM K-14 ESFR SPRINKLER

Page 26: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

TEST 1

BAR JOIST OBSTRUCTION (4” CHORD)RACK STORAGE - GROUP A CARTONED

UNEXPANDED PLASTICSCENARIO

30 FT STORAGE - IGNITION BELOW ONE 40 FT BUILDING

75 PSI - K14 ESFR

Page 27: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume
Page 28: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

RESULTS - TEST 1

29 SPRINKLER OPERATIONS

PEAK TEMPERATURES 1550 oF CEILING GAS 344 oF CEILING STEEL

Page 29: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

NO. TIME (M:SEC)1 0:392 - 12 1:30 - 2:0013 - 22 2:01 - 2:3023 - 26 2:31 - 3:0027 - 28 3:01 - 3:3029 3:40

SPRINKLER ACTUATION SEQUENCE ‐ TEST 1

Page 30: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

X

(27)1:41

(6)1:51

(12)1:57

(1)0:39

(25)2:42

(26)2:52

(29)3:40

(19)1:53

(28)3:38

IGNITION ZONE SPRINKLER ACTUATIONS ‐ TEST 1

Page 31: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

TEST 2

BRIDGING OBSTRUCTION (1.5” W)RACK STORAGE - GROUP A CARTONED

UNEXPANDED PLASTICSCENARIO

30 FT STORAGE - IGNITION BELOW ONE 40 FT BUILDING

75 PSI - K14 ESFR

Page 32: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

RESULTS - TEST 2

27 SPRINKLER OPERATIONS

PEAK TEMPERATURES 1162 oF CEILING GAS 227 oF CEILING STEEL

Page 33: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

SPRINKLER ACTUATION SEQUENCE - TEST 2

NO. TIME (M:SEC)1 0:422 1:30 - 2:003 - 21 2:01 - 2:3022 2:31 - 3:00 (2:42)23 - 26 3:01 - 3:3027 3:55

Page 34: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

X

(20)2:24

(25)3:28

(26)3:28

(1)0:42

(9)2:12

(23)3:07

(27)3:55

(22)2:42 (DNO)

IGNITION ZONE SPRINKLER ACTUATIONS ‐ TEST 2

Page 35: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

TEST RESULTS

NO.SPRINKLERS

FIREDAMAGE

MAX. STEELTEMP.

TEST 1 (JOIST)

29 +IGNITIONARRAY

344 OF

TEST 2(BRIDGING)

27 +IGNITIONARRAY

227 OF

Page 36: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

22 M

PH(45 KP

H)

Droplets Ability to Penetrate the Fire Plume

Page 37: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

Small Drops are Carried Back to Ceiling - May Skip or Prevent Adjacent Sprinklers from Opening

22 M

PH(45 KP

H)

Page 38: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

38

Page 39: Sprinkler Skipping - Society of Fire Protection Engineers · and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers. 2. Strong fire plume

CONCLUSIONS

• The higher the clearance is between what's burning and the sprinkler prevents droplets from reaching the hazard and cools the surrounding sprinklers.

• Strong fire plume velocities carry water and cooling back up to the surrounding sprinklers.

• Water droplet size and velocity fails to penetrate the fire plume and gets carried back up to the surrounding sprinklers.

• Obstructions to sprinkler discharge may cause #2 and #3