Hoval Limited Northgate - Newark - Nottinghamshire NG24 1JN - UK Tel: (01636) 672711 - Fax: (01636) 673532 (International: +44 1636 673532) e-mail: [email protected] - Web: www.hoval.co.uk Page 1 of 1 By Appointment to Her Majesty the Queen Boiler Manufacturers & Engineers Hoval Ltd Newark Registered Number 592844 Solar Pre-commissioning Check List Site Address: Site Contact: Contact Number: K No: Plant room requirements 230v/110v 1phase electrical supply Cold feed tap available in plant room Drain available close to calorifier Yes No Access to roof required for Hoval Engineers Collector sensor must be fitted inside Solar Panel No valves should be fitted to solar panels Solar Panels should be covered to aid commissioning 2 core sensor cable to be wired from collector sensor to UVR Control Panel in plant room Pipework pressure tested to 5 bar Pipework and connections suitable for Solar temperatures (130°C) Expansion vessel piped to Solar pump station with isolating and drain valves fitted UVR Control Panel mounted adjacent to Calorifier Solar pump station and Anti-Legionella pump wired to UVR Control Panel 230v 1phase supply to UVR Control Panel Solar fluid left in plant room

Transcript of Solar Pre-commissioning Check List Site Contact

Page 1: Solar Pre-commissioning Check List Site Contact

Hoval Limited Northgate - Newark - Nottinghamshire NG24 1JN - UK Tel: (01636) 672711 - Fax: (01636) 673532 (International: +44 1636 673532) e-mail: [email protected] - Web: www.hoval.co.uk

Page 1 of 1

By Appointment to Her Majesty the Queen

Boiler Manufacturers & Engineers Hoval Ltd Newark

Registered Number 592844

Solar Pre-commissioning Check List Site Address: Site Contact: Contact Number: K No:

Plant room requirements

230v/110v 1phase electrical supply Cold feed tap available in plant room Drain available close to calorifier

Yes No Access to roof required for Hoval Engineers

Collector sensor must be fitted inside Solar Panel

No valves should be fitted to solar panels

Solar Panels should be covered to aid commissioning

2 core sensor cable to be wired from collector sensor to UVR Control Panel in plant room

Pipework pressure tested to 5 bar

Pipework and connections suitable for Solar temperatures (130°C)

Expansion vessel piped to Solar pump station with isolating and drain valves fitted

UVR Control Panel mounted adjacent to Calorifier

Solar pump station and Anti-Legionella pump wired to UVR Control Panel

230v 1phase supply to UVR Control Panel

Solar fluid left in plant room