SITOP select
Automation and Drives
SITOP selectElectronic Diagnosis Module
Fault diagnosis – rapid and reliable
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 2
SITOP select
Automation and Drives
Blow the whistle on plant downtimes
Keep the overview of your 24V load feeders.
Show the red card to downtimes caused by faults
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 3
SITOP select
Automation and Drives
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
The situation today
= ~
Drop in 24 V !
Load 2Load 1 Load 4Load 3
–
+
4A 6A 10A 10A
Circuit diagram of the power distribution for selective protection
24 V
Power supply, e.g. SITOP power
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 4
SITOP select
Automation and Drives
Reasons for selective triggering failure when fault occurs Long load lines Creeping short circuits Line circuit breakers dimensioned too large
Consequences Plant standstill due to drop in 24 V power Trouble-shooting much more difficult Long standstill times
Reason for undesired triggering during operation Excessive current peaks during startup
Consequence Malfunction, machine/plant switches off
The situation today
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 5
SITOP select
Automation and Drives
The solution
Fault paths are powered down reliably even under very poor operational conditions.
Retension of the 24 V power for all other paths Plant down time is reduced or even avoided. Fast trouble-shooting and fault localization
Loads with high startup current peaks power up with current limitation.
Malfunction-free device startup
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 6
SITOP select
Automation and Drives
The solution
Selectivity and fast error diagnosis of 24 V feeder circuits
Four feeder circuits (outputs) per module Each output can be set between 2 and 10 A using
potentiometer. Multi-color LED for each output for rapid fault localization Potential-free common signal contact for fault diagnosis Several modules can be connected to a single power supply. Simple and rapid installation using standard mounting rail Additional line protection and gradual equipment
commissioning with exchangeable FK2 blade-type fuse
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 7
SITOP select
Automation and Drives
Circuit diagram
=~ 24 V
Load 2 Load 4
Potential-freesignalling contact
SITOP selectReset
Power supply, e.g. SITOP power+
–
Control Logics
Load 1 Load 3
Diagnosis module with 4 outputs for current distribution
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 8
SITOP select
Automation and Drives
Switching characteristic
5.0 sec
0.10 sec
0.0 sec
0.1 sec
1.0 sec
10.0 sec
100.0 sec
0% 50% 100% 150%
I / Irated
t
Irated can be adjusted from 2 to 10 A per output circuit. Characteristics per currentrequirements depend on the output circuit.
From 0 A to the set value ( I/ Irated=100%) without switching off From set value up to 130% switch off after approx. 5 sec Above 130% of set value current limiting to 130% for 50 to
100 msec, next switch off Over the set value with simultaneous
collapse of the supply voltage below 20V immediate switch off
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 9
SITOP select
Automation and Drives
Device features
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data Two-color LED
Potentiometer Input terminals
Output terminals
Labeling field
Blade-type FK2 fuse
Common signalling contact
Reset
SITOP select fault diagnosis - rapid and reliable A&D SE PS 23.04.2002 10
SITOP select
Automation and Drives
Ordering data, technical specifications
Order Number 6EP1961-2BA00Input
•Rated voltage Vin rated DC 24 V
•Voltage range 22 to 30 V•Input current 40 A max. Output•Number of output channels 4 per module•Rated voltage Vout rated Vin -0.5 V•Rated current Iout up to +60 °C 10 A per channel•Setting range 2 to 10 A per channelEfficiency at V out rated ,I out rated Approx. 97%Protection and monitoring•Wire protection One blade-type FK2 15 A fuse per channel
Externally accessible•Operation indication Green for switched output (two-color LED per channel) Red for output switched off due to overload/short-circuit•Signalling contact Common signalling contact (N/O contact)Class of protection Class III (IEC 536; VDE 0106 T1)Degree of protection IP 20 (EN 60 529; VDE 0470 T1)CE certification YesTÜV type approval YesUL/cUL (CSA) approval UL 508, File 197259Electromagnetic compatibility EMC•Emitted interference EN 50081-1, EN 55022 class B•Noise immunity EN 50082-2Ambient temperature range 0 to +60 °C with natural air circulationDimensions (width x height x depth) 72 x 90 x approx. 90 mmWeight Approx. 0.4 kg
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data