TEST REPORT
REPORT NO : 2018MA0771 PAGE : 1 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QASInternational Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means orforms (including but not limited to advertising purposes) without written approval from the Managing Director, SIRIM QAS InternationalSdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.
THIS TEST REPORT IS ISSUED IN SECURED PDF SOFTCOPY
Applicant : ITHAD ENGINEERING SDN BHDNo.37, Jalan Taming 7,Taman Taming Jaya, Balakong,43300 Seri kembangan,Selangor, Malaysia.
Manufacturer : ITHAD ENGINEERING SDN BHDNo.37, Jalan Taming 7,Taman Taming Jaya, Balakong,43300 Seri kembangan,Selangor, Malaysia.
Product : 19" DATA CENTRE SERVER RACKReference Standard / Method of Test
: MANUFACTURER'S SPECIFICATION- Load Test
Description of sample / Description of Test Specimen
: Brand: PrimestarModel: 42U Server RackOverall Dimension: 600(W)X1000(D)X2000(H) - mmSample Quantity: 1 unit
Date Received of Complete Application
: 04 September 2018
Job No. : J20181390652Description of Test Results / Overall Test Result
: The test result of the submitted test sample is described on page 3&4 of this test report.
Issued Date : 27 September 2018
Approved Signatories;
...................................................... (MOHD HAFIZOL BIN SHAARI)
Testing Executive
...................................................... (MOHD FAIZAR BIN MUSTAFA)
Head Mechanical & Automotive Section
Testing Services Department
REPORT NO. : 2018MA0771 PAGE: 2 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms (including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.
TEST INFORMATION
19” DATA CENTRE SERVER RACK
Test Item : Load Test
Test Description : 1. Safe working load (SWL): 1500 kg 2. Safety factor (SF): 1 3. Total load: 1500 kg 4. Load for each tray: 150kg/tray 5. Test duration: 24 hours 6. Record the dimension between tray:
i. Before test ii. Immediately after full test load is applied (0 hours) iii. At 3 hours after load applied iv. At end of the full test load period (24 hours) v. At 1 hour after relaxation period (after load remove from
tray)
Test Requirement : Record the deflection at each period of test and make the visual observation on each tray and any relative part of racking systems
Figure 1: 19” Data Centre Server Rack
REPORT NO. : 2018MA0771 PAGE: 3 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms (including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.
TEST RESULT
19” DATA CENTRE SERVER RACK
Orientation
Dimension (mm) Deflection
(Before and after load) Before 0 hours 3 hours 24 hours
After
Relaxation mm %
L1-1
L1-2
L1-3
L1-4
196
155
196
152
195
154
195
151
195
154
195
151
194
153
194
150
196
155
195
151
2
2
2
2
1.02
1.29
1.02
1.32
L2-1
L2-2
L2-3
L2-4
147
147
148
148
146
146
147
147
146
146
147
147
146
145
146
146
147
147
147
148
1
2
2
2
0.68
1.36
1.35
1.35
L3-1
L3-2
L3-3
L3-4
147
147
147
148
146
146
146
147
146
146
146
147
145
145
145
146
147
147
147
147
2
2
2
2
1.36
1.36
1.36
1.35
L4-1
L4-2
L4-3
L4-4
148
146
147
147
147
145
146
146
147
145
146
146
146
144
145
145
148
146
147
147
2
2
2
2
1.35
1.37
1.36
1.36
L5-1
L5-2
L5-3
L5-4
147
147
149
148
146
146
148
147
146
146
148
147
145
145
147
145
147
146
148
148
2
2
2
3
1.36
1.36
1.34
2.03
L6-1
L6-2
L6-3
L6-4
192
192
192
192
191
191
191
191
191
191
191
191
190
190
191
190
191
192
192
192
2
2
1
2
1.04
1.04
0.52
1.04
L7-1
L7-2
L7-3
L7-4
148
147
147
147
147
146
145
146
147
146
145
146
146
145
144
145
148
147
147
147
2
2
3
2
1.35
1.36
2.04
1.36
L8-1
L8-2
L8-3
L8-4
147
147
148
147
146
146
147
146
146
146
147
146
145
145
146
145
147
147
148
147
2
2
2
2
1.36
1.36
1.35
1.36
L9-1
L9-2
L9-3
L9-4
148
147
149
148
147
146
148
147
147
146
148
147
146
146
147
147
148
147
149
148
2
1
2
1
1.35
0.68
1.34
0.68
L10-1
L10-2
L10-3
L10-4
147
147
149
147
146
146
148
146
146
146
148
146
145
145
147
145
147
147
148
137
2
2
2
2
1.36
1.36
1.34
1.36
REPORT NO. : 2018MA0771 PAGE: 4 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms (including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.
TEST RESULT
19” DATA CENTRE SERVER RACK
Maximum Deflection (%) 2.04 L7-3
Minimum Deflection (%) 0.52 L6-3
Average Deflection (%) 1.28 -
Note: Please refer Appendix I for drawing orientation of dimension measurement and appendix II for test
pictures.
Overall Observation
Upon the completion of the load test, the product (19” Data Centre Server Rack) was found in
satisfactory condition. No physical damage was observed on racking systems part assembly such as
tray, frame and mounting during or after the loading test. All critical dimensions and parts were remained
intact after test was performed.
REPORT NO. : 2018MA0771 PAGE: 5 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms (including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.
APPENDIX I
DRAWING ORIENTATION OF DIMENSION MEASUREMENT
Figure 2: Drawing orientation of dimension measurement
1
2 3 4
L10
L9
L8
L7
L6
L5
L4
L3
L2
L1
REPORT NO. : 2018MA0771 PAGE: 6 OF 6
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms (including but not limited to advertising purposes) without written approval from Managing Director, SIRIM QAS International Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.
APPENDIX II
PICTURES OF THE LOAD TEST SETUP
Figure 3-5: Load Test setup