ServoMaster User Manual 12911004

22
User Man u al ServoMaster Fire Alarm Panel 12 100 xx POWER  FAULT SYSTEM FAULT TEST ALARM SOUNDERS DELAYED DI SABLEMENTS OPERATOR ACCESS MENU ALARMS ALARM SILENCE ABC  DEF GHI JKL  MNO PQR STU  _VW  XYZ 7  8 9 4  5  6 1  2  3 0 ServoMaster FIRE NEXT ALARM SERVOTEKNIKK 17.06.2003 16:47  Normal oper ation 12 911 004 2003-06 Last revision: 26. Jun 2003

Transcript of ServoMaster User Manual 12911004

  • User Man ual

    ServoMasterFire Alarm Panel

    12 100 xx

    POWER FAULT

    SYSTEM FAULT

    TEST ALARM SOUNDERS DELAYED

    DISABLEMENTS OPERATOR ACCESS

    MENUALARMS

    ALARMSILENCE

    ABC DEF GHI

    JKL MNO PQR

    STU _VW XYZ

    7 8 9

    4 5 6

    1 2 3

    0

    ServoMaster

    FIRE

    NEXTALARM

    SERVOTEKNIKK

    17.06.2003 16:47

    Normal operation

    12 911 0042003-06 Last re vi sion: 26. Jun 2003

  • ServoMaster User Manual 12 911 004Page 2 2003-06

    Ta b l e o f C o n t e n t s1 Gen eral. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    1.1 About this man ual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31.2 Def i ni tions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    2 FUNC TIONAL DE SCRIP TION . . . . . . . . . . . . . . . . . . . . . . 42.1 ServoMaster Op er a tor Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42.1.1 Ac cess code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42.1.2 Dis play. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.1.3 Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.1.4 In di ca tor lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    3 Alarm Mes sages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.1 Pri or i ties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.2 Fire Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.2.1 In di ca tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.2.2 In case of FIRE ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83.3 Pre-alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.3.1 In di ca tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.3.2 In case of PRE-ALARM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.4 Tech ni cal alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.4.1 In di ca tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.4.2 In case of TECH NI CAL ALARM. . . . . . . . . . . . . . . . . . . . . . . . . . 103.5 Fault Warn ing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113.5.1 In di ca tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113.5.2 In case of FAULT WARN ING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113.5.3 Fault find ing ta ble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123.5.4 Re plac ing sen sors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123.6 Disablements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133.6.1 In di ca tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133.6.2 Ac tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133.7 Test Con di tion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133.7.1 In di ca tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133.7.2 Ac tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    4 MENU FUNC TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144.1 Func tion Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144.2 Main Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154.2.1 Disablements - Out lets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154.2.2 Disablements - Sen sors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164.2.3 View In for ma tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.2.4 Main te nance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184.2.5 Sys tem set tings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194.2.6 Ser vice Func tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204.2.7 Sys tem Con fig u ra tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    5 Con trol mod ule con nec tions. . . . . . . . . . . . . . . . . . . . . . 21

  • 1 GENERAL1.1 About this manual

    This user man ual is in tended as a guide for the user of the ServoMaster fire alarm panel.The man ual should also be used as a sup ple ment to other man u als de scrib ing installation,test ing, ser vice and main te nance.This man ual only de scribes panel func tions re lat ing to AC CESS LEVEL 2 as spec i fied byEN54-2 (i.e. reg u lar op er a tion by trained per son nel).

    1.2 DefinitionsSome words and phrases used in this manual are ex plained in the ta ble be low.

    Phrase Definition ReadAc cess Code A four digit code to be en tered on the op er a tor panel

    to pre vent un au tho rized use.2.1.1

    Con trolModule

    A mi cropro ces sor based unit for han dling in com ingalarm sig nals and out go ing ac tions.Sev eral con trol modules and op er a tor pan els can bein ter con nected on a ServoLan bus.

    5

    De tec tor Any type of el e ment ca pa ble of de tect ing fire, smoke,gas etc. or any change of sta tus that can be used asin put for a ServoMaster con trol mod ule.

    5

    Dis able ment A user ini ti ated func tion that will put sen sors or out letstem po rary out of ser vice.

    3.6

    Key A push-but ton on an operator panel ex e cut ing a pre -de ter mined func tion.

    2.1.3

    Loop A sig nal ca ble with a num ber of de tec tors start ing andend ing in a con trol mod ule (ad dress able loop) or ter -mi nated in an end-of-line re sis tor (col lec tive loop).

    5

    Menu A choice of ac tions listed on a op er a tor panel dis play.Out let A num ber of con nec tion points in a con trol mod ule

    used for man ag ing ac tions dur ing an alarm sit u a tionlike fault in di ca tion, sound ing alarm bells, clos ing firedoors and ini ti at ing other fire pre vent ing ac tions.

    4.2.1

    Op er a torPanel

    A unit with warn ing lights, func tional keys and in for ma -tion dis play.A op er a tor panel gives in for ma tion about alarms andsta tus of the ServoMaster sys tem. Cer tain tests and sys tem pa ram e ters can be set froman op er a tor panel.

    2.1

    Pri or ity Alarm type im por tance. An alarm with higher pri or ity will over rule an alarm ormes sage with lower pri or ity.There are 6 pri or ity lev els.

    3.1

    Sen sor All de tec tors and el e ments that can give a fire alarmsig nal such as smoke and fire de tec tors and man ualfire alarm call-points.All sen sors are given an unique five digit iden ti fi ca tionnum ber, the two first dig its rep re sents the sen sorszone and the tree last the sen sor num ber in the zone.

    5

    Sys tem The en tire ServoMaster in stal la tion including con trolmodules, op er a tor pan els, de tec tors and sub-sys tems.

    5

    Viewport Part of dis play re served for cer tain types of mes -sages.

    2.1.2

    Zone A user de fined area with up to 99 sen sors.Each zone is given an unique three digit num ber inthe range 001 - 654.

    12 911 004 ServoMaster User Manual2003-06 Page 3

  • 2 FUNCTIONAL DESCRIPTION2.1 ServoMaster Operator Panel

    The primary func tion of the op er a tor panel is to pro vide both vi sual and au di ble firealarms. To en sure that the sys tem is al ways in per fect work ing con di tion, the panel con tin -u ously mon i tors all in ter nal cir cuits and func tions as well as all ca bles and equip mentmounted ex ter nally. The op er a tor panel will give vi sual and au di ble alarm of all op er a -tional dis tur bances. The front panel of ServoMaster is equipped with an LCD dis play with back-light, a nu -meric key board, six keys for op er at ing the panel and 11 LEDs for sta tus in for ma tion.

    In nor mal op er a tion the dis play shows date and time and the text Nor mal op er a tion.

    2.1.1 Access codeThe operator panel keys can be protected against unauthorized use by an access code.When used in marine environment, the use of access code is normally skipped. The accesscode protection is permanently turned on or off by the installer in the SystemConfiguration menu.When first press ing a pro tected key, you will be prompted by the dis play to en ter the code:

    En ter the ac cess code and press OKDefault access code is 0110. The code should be changed by entering the System Settingsmenu. See section 4.2.5.When the 4-digit access code has been correctly entered, the action of the original key willbe carried out. (Does not apply for the Acknowledge Alarm button, se section 3.2).A green in di ca tor marked OP ER A TOR AC CESS will be lit when the ac cess code hasbeen cor rectly en tered. As long as this light stays on, all panel keys are un pro tected. Thelight will go off au to mat i cally one min ute af ter the en ter ing of the ac cess code. By press ing any key dur ing this in ter val, the time will au to mat i cally be ex tended (to one min ute fol -low ing the last key pres sure).Note that some key func tions are not pro tected by the ac cess code:

    The au di ble warn ing fol low ing the oc cur rence of a fault mes sage may be si lenced. During alarm conditions, it is possible to scroll between multiple alarms in the display.

    WARNING: To protect the panel against unauthorized use, do not leave the panel as long as theOPERATOR ACCESS indicator is lit.

    ServoMaster User Manual 12 911 004Page 4 2003-06

    POWER FAULT

    SYSTEM FAULT

    TEST ALARM SOUNDERS DELAYED

    DISABLEMENTS OPERATOR ACCESS

    MENUALARMS

    ALARMSILENCE

    ABC DEF GHI

    JKL MNO PQR

    STU _VW XYZ

    7 8 9

    4 5 6

    1 2 3

    0

    ServoMaster

    FIRE

    NEXTALARM

    SERVOTEKNIKK

    17.06.2003 16:47

    Normal operation

    Fire alarm indication

    Power-ON indication

    Status information lights

    LCD information and menudisplay

    Panel function key text

    Panel function keys

    Alpha-numeric keyboard

    Multiple alarms indication

    Permanent function keys

    OPERATOR ACCESS

  • Alarms, faults and menus are shown on a 40 char ac ters by 16 lines graph i cal LCD dis playwith ad just able back-light.The dis play is di vided in four viewports: The Header viewport shows the type of alarm or mes sage given in the In for ma tion

    viewports or the cat e gory of the cho sen menu. The font is larger to be better vis i ble.Date and time is shown in the up per right cor ner ex cept in Menu mode and Alarm sit u -a tion.

    The two In for m a tion viewports will dis play mes sages like alarm de tails, fault warn -ings, disablements, etc.The up per viewport will show the first message. If there are more alarms or messages,the lower viewport will show the last one. Scrolling through sev eral messages will beshown in the up per viewport.In Menu mode both viewports are used to dis play the menu choices.

    The But ton viewport is re served for panel func tion key text. The text will ap pearabove one or more of the three panel func tion keys to in di cate their func tion. The func -tion de pends upon the panels op er a tional mode.

    2.1.3 KeysThe ServoMaster is op er ated by six func tion keys and an al pha-nu meric key board. Thekey board has sev eral func tions. The nec es sary in struc tions are shown in the dis play for the var i ous menus.

    Panel functi on keysThese three keys lo cated be low the dis play will change their func tion ac cord ing to the op -er a tor panels func tional mode.The key func tions are shown on the lower part of the dis play just above the buttons.

    Menu Al arms

    Press the key in Nor mal Op er a tion to en ter the Menu mode. When the panel is in Alarm State, this key can be used to tog gle be tween the pres ent

    alarm mes sage and Menu dis play.

    Next alarmThe two LEDs di rectly above the key will be lit if there are more than one ac tive alarm inthe sys tem. Press the key to scroll through the dif fer ent alarms.

    The alarm messages will be shown in the up per in for ma tion viewport of the dis play.

    Alar m si lence

    Press the key to stop an au di ble alarm. This will si lence both the panel buzzer and all alarm sounders in the sys tem.

    Press the key once more to re start the au di ble alarm.

    2.1.4 Indicator lightsPower

    The green POWER LED is lit when the sys tem is pow ered from mains or bat tery.If the mains, bat tery or fuses should fail, there will be a fault in di ca tion on the dis play.

    There is no ac ces si ble mains ON/OFF switch.

    12 911 004 ServoMaster User Manual2003-06 Page 5

    I nf o

    MENUALARMS

    NEXTALARM

    ALARMSILENCE

    POWER

    But t on vi ewpor t

    Header v i ewpor t

    Upper i nf or mat i on v i ewpor t

    Lower i nf or mat i on v i ewpor t

  • Fire The two red LEDs close to the FIRE sign will flash at a 2 Hz rate in the event of a fire

    alarm. The buzzer will sound at the same rate dur ing a fire alarm. The buzzer can be si lenced by the Alarm Si lence but ton.

    Read more about fire alarm in sec tion 3.2.

    Fault

    The yel low FAULT LED is lit if there is a fault in the sys tem such as de tec tor faults,bat tery faults, bro ken fuses, com mu ni ca tion faults, etc.

    If there is a sys tem fault, the SYS TEM FAULT LED will be on as well. The buzzer will sound in ter mit tently at 1Hz. The buzzer can be si lenced by the Alarm Si lence but ton.

    Read more about faults in sec tion 3.5.

    Test

    The yel low TEST LED will be ON when the sys tem is in test mode.Read more about tests in sec tion 3.7.

    Dis able ments The yel low DIS ABLE MENT LED will be ON if one or more out lets or sen sors have been

    dis abled by the op er a tor.Read more about disablements in sec tion 3.6.

    Alarm sound ers de layed The ALARM SOUNDERS DE LAYED LED will be ON if there is a de lay be tween a

    sen sor has de tected a fire and the sound ers give and au di ble alert. The de lay time is set from the con fig u ra tion pro gram. The de lay can be turned on/off from the op er a tor panel. (See sec tion 4.2.5.)

    Op er a tor ac cess The OP ER A TOR AC CESS LED will be ON when the op er a tor has ac cess to per form

    ac tions on the op er a tor panel when the ac cess code has been cor rectly en tered. As long as this light stays on, all panel keys are un pro tected. The light will go off au to mat i cally one min ute af ter the en ter ing of the ac cess code. By pressing any key during this interval, the time will automatically be extended to

    one minute following the last key pressure. To change the ac cess code, see sec tion 4.2.5.

    Alarm transmission delayedThis function is not available if there are no indicators on the operator panel. The yellow ALARM TRANSMISSION DELAYED LED indicates that the

    transmission to the fire brigade will be delayed. The delay time is set from the configuration program. The de lay can be turned on/off from the op er a tor panel. (See sec tion 4.2.5.)

    This function can be used if there are often false alarms and it is desired to check andrectify the cause before the fire brigade is automatically called.Delayed alarm transmission is an optional function as per EN 54-2, and may not beavailable on certain models of the ServoMaster.

    Alarm transmission activeThis function is not available if there is no indicator on the operator panel. The red ALARM TRANSMISSION ACTIVE LED indicates that the alarm has been

    forwarded to a remote station, e.g. the fire brigade.Remote alarm transmission is an optional function as per EN 54-2, and may not beavailable on certain models of the ServoMaster.

    ServoMaster User Manual 12 911 004Page 6 2003-06

    ALARM SOUNDERS DELAYED

    OPERATOR ACCESS

    FAULT

    SYSTEM FAULT

    TEST

    DISABLEMENTS

    ALARM TRANSMISSION DELAYED

    ALARM TRANSMISSION ACTIVE

    FIRE

  • 3 ALARM MESSAGES3.1 Priorities

    There are six alarm types in the ServoMaster sys tem. These alarms are in di cated andtreated in dif fer ent ways by sound, light and dis play text. Some alarms may ini ti ate au to -matic ex ter nal ac tions.The alarm types have pri or i ties which means that an alarm with higher pri or ity will over -rule any alarm with a lower pri or ity on the ServoMaster panel.

    Alarm ServoMaster panel Ex ter nalType Priority Display Warn ing

    lightsBuzzercy cle

    Alarmbells

    Autoaction

    Fire alarm 1 Fire alarm FIRE 50/502 Hz

    Yes* Yes*

    Pre-alarm 2 Pre-alarm - 20/801 Hz

    No* No*

    Technicalalarm

    3 Techn.alarm

    - Program-able

    No* No*

    Test 4 Test alarm TEST** - No NoFaultwarning

    5 Fault FAULT 50/501 Hz

    No* No*

    Dis able 6 Dis abled Disable-ments

    - No No

    * De fault set ting. Ac tion is programable.** Only when the central is set in test mode.

    3.2 Fire AlarmFire alarm is a sit u a tion where a sen sor de tects smoke or flame, or when a man ual firealarm call-point is ac ti vated.

    3.2.1 Indications Fire alarm is in di cated on the op er a tor panel by two flash ing red LEDs in the field

    marked FIRE. The in ter nal buzzer as well as alarm bells and/or horns will sound. The up per part of the dis play will show the type and number of fire alarms and the

    num ber of zones where alarms are ini ti ated. The first and last fire alarm with de scrib ing text is shown in the mid area of the dis play

    (up per and lower in for ma tion viewport). Line 1 shows type of alarm, alarm num ber and time stamp. Line 2 shows cus tomer de fined zone text. Line 3 shows cus tomer de fined sen sor text. Line 4 shows zone num ber, sen sor num ber, type of alarm ing sen sor and phys i cal po -

    si tion of the sen sor. The phys i cal in for ma tion is presented as:panel num ber /mod ule num ber /loop num ber /sen sor num ber.

    Panel func tion key text Ac knowl edge is shown on the lower part of the dis play.If there are more than one alarm, the two other keys are marked: Pre vi ous alarm andScroll sen sors.If there are alarms from more than one zone, the key text will tog gle be tween Scrollsen sors and Scroll zones.

    12 911 004 ServoMaster User Manual2003-06 Page 7

    FIRE

    ALARMS: 3 ZONES: 2Fire alarm 1 27.11.2002 12:56:43Bridge deck, port sideCabin 13Zone 105 Sensor 7 (SSD530) A/2/1/5Fire alarm 3 27.11.2002 13:15:48Bridge deck, corridorArea B Zone 106 Sensor 1 (MCP545) A/2/1/16

    PreviousAlarm

    Acknow-ledge

    Scrollzone

  • 3.2.2 In case of FIRE ALARM

    F Read the dis play text.Scroll through all alarms if more than two are present.The scrolled alarm text is al ways shown in the up per in for ma tion viewport.The lower in for ma tion viewport shows the most re cent fire alarm, not in flu enced byscroll ing. Press NEXT ALARM to view the following alarm.

    The two LEDs are lit as long as there are more than one alarm.

    Press Pre vi ous alarm to scroll back wards through the alarms.

    By press ing Scroll Sen sors, the alarms are shown chro no log i cally, start ing with firstalarm and end ing with last alarm.

    If the alarms orig i nates from more than one zone, the right func tion but ton will have thetext: Scroll Zones. Press the but ton Scroll Zones to show the first alarm in all ac tual zones when the but -

    tons Next Alarm and Pre vi ous Alarm are used.

    F The rea son for the fire alarm must be de ter mined by ex am in ing the area. Per form ac tions ac cord ing to lo cal in struc tions.ServoMaster may au to mat i cally per form pre de ter mined ac tions like alert ing the safetyper son nel, clos ing fire doors, clos ing valves, man ag ing fans and ven ti la tors, etc.

    F Turn off sound ers by press ing the key ALARM SI LENCE only when thisalert is no longer needed. You will be prompted to en ter the ac cess code.The dis play re mains un changed. The alarm sound ers may be turned on again by press ing the key once more.

    F Press the MENU ALARMS key if there is need to en ter the MENU dur ing a fire alarm condition. There may be a need to view in for ma tion like e.g. pre-alarms or tech ni cal alarms that

    are over ruled by the fire alarm. Tog gle back to view the fire alarms by press ing the key once more.

    The dis play will au to mat i cally change back to the fire alarm dis play af ter a pre set time.

    F The fire alarms are re set one by one by press ing the key marked Ac knowl edge.Ac knowl edge will work on the alarm shown in the up per in for ma tion viewport only.An as ter isk (*) is shown in front of the first line to in di cate that the alarm has beenac knowl edged.

    When a fire alarm is ac knowl edged, it will re main in the dis play un til the de tec tor hasre turned to Nor mal op er a tion

    When all fire alarms are ac knowl edged and there are no more sen sors de tect ing anyfire con di tion, the Fire alarm text will dis ap pear from the dis play and the text: Nor malop er a tion is dis played.

    ServoMaster User Manual 12 911 004Page 8 2003-06

    NEXTALARM

    Previousalarm

    Scrollsensors

    Scrollzones

    ALARMSILENCE

    MENUALARMS

    Acknow-ledge

    * Fire alarm 1

  • 3.3 Pre-alarmPre-alarm is a sit u a tion where a sen sor with high sensitivity level de tects an ab nor mal con -di tion. This is NOT a fire alarm! Non of the spe cial fire alarm out puts will be ac ti vated.

    3.3.1 Indication The in ter nal buzzer will sound with short beeps at 1 Hz.

    The alarm bells and/or horns will not be ac ti vated. There is no spe cial LED on the op er a tor panel to in di cate Pre-alarm. The up per part of the dis play will show the type and num ber of alarms and the num ber

    of zones where alarms are ini ti ated. The dis play will show the same in for ma tion as for Fire alarm. See sec tion 3.2.1

    Line 1 will in di cate the alarm type as Pre-alarm. ServoMaster may au to mat i cally per form pre de ter mined ac tions like clos ing valves,

    man ag ing fans and ven ti la tors etc.

    F Ob serve that fire alarms have pri or ity over pre-alarms.If a fire alarm oc curs when the op er a tor panel in di cates a pre-alarm, the fire alarm willover rule all pre-alarms and the op er a tor panel will show fire alarms only.To view any pre-alarms dur ing a fire alarm con di tion, push the Menu< >Alarms key. Se lect: View in for ma tion\View alarms by level\View pre-alarms.

    3.3.2 In case of PRE-ALARM

    F Read the dis play text.Scroll through all pre-alarms if more than two are in di cated.The scrolled alarm text is al ways shown in the up per in for ma tion viewport.The lower in for ma tion viewport shows re cent pre-alarm. Not in flu enced by scroll ing. Press NEXT ALARM to view any further alarms.

    The two LEDs are lit as long as there are two or more alarms present.

    Press Pre vi ous alarm to scroll back wards.

    F The rea son for the pre-alarm must be de ter mined by ex am in ing the area. Per form ac tions ac cord ing to lo cal in struc tions.F Turn off the buzzer by press ing the key ALARM SI LENCE only when thisalert is no lon ger needed.

    You will be prompted to en ter the ac cess code.The dis play re mains un changed. The buzzer can be turned on again by press ing the key once more.

    F The pre-alarms are re set one by one by press ing the key marked Ac knowl edge.Ac knowl edge will work on the alarm shown in the up per in for ma tion viewport only.An as ter isk (*) is shown in front of the first line to in di cate that the alarm is de ac ti vated.

    When alarm con di tion on the ac knowl edged sen sor is re moved, the alarm text will dis ap -pear.

    When all pre-alarms are ac knowl edged and all sen sors with pre-alarm are back in Nor -mal op er a tion, the pre-alarm text will dis ap pear from the dis play and the text: Nor malop er a tion is dis played.

    12 911 004 ServoMaster User Manual2003-06 Page 9

    PRE-ALARMS: 1 ZONES: 1Pre-alarm 1 27.11.2002 12:56:43Bridge deck, port sideCabin 13Zone 5 Sensor 7 (SSD530) A/2/1/5

    Acknow-ledge

    MENUALARMS

    NEXTALARM

    Previousalarm

    ALARMSILENCE

    Acknow-ledge

    * Pre-alarm 1

  • 3.4 Technical alarmTech ni cal alarms are ac ti vated from con tact changes in a de vice. The sig nals are cus tomerde fined and ac tion out puts can be programed.

    3.4.1 Indication The in ter nal buzzer will sound with short beeps at a 1 Hz (programable).

    The alarm bells and/or horns will not be ac ti vated. There is no spe cial LED on the op er a tor panel to in di cate Tech ni cal alarm. The up per part of the dis play will show the type and num ber of alarms and the num ber

    of zones where alarms are ini ti ated. The dis play will show the same in for ma tion as for Fire alarm. See sec tion 3.2.1

    Line 1 will in di cate the alarm type as Techn. alarm. ServoMaster may au to mat i cally per form pre de ter mined ac tions like clos ing valves,

    dis con nect ing power etc.

    F Ob serve that fire alarms and pre-alarms have pri or ity over tech ni cal alarms.If an alarm with higher pri or ity oc curs when the op er a tor panel in di cates a techn. alarm,the pri or ity alarm will over rule all tech ni cal alarms and the op er a tor panel will show pri or -ity alarms only.To view possible tech ni cal alarms dur ing a pri or ity alarm con di tion, push the MenuAlarms key. Se lect: View in for ma tion \ View alarms by level \ View tech ni cal alarms

    3.4.2 In case of TECHNICAL ALARM

    F Read the dis play text.Scroll through all tech ni cal alarms if more than one is in di cated.The scrolled alarm text is al ways shown in the up per in for ma tion viewport.The lower in for ma tion viewport shows the most re cent alarm, not in flu enced by scroll ing. Press NEXT ALARM to view any further alarms.

    The two LEDs are lit as long as there are more than one alarm to view. Press Pre vi ous alarm to scroll back wards.

    F The rea son for the tech ni cal alarm is in di cated on the dis play.Verify by ex am in ing the alarm ing de vice. Per form cor rec tive ac tions ac cord ing to lo cal in struc tions.

    F Turn off the buzzer by press ing the key ALARM SI LENCE only when thisalert is no lon ger pres ent. You will be prompted to en ter the ac cess code (if valid).The dis play re mains un changed. The buzzer can be turned on again by press ing the key once more.

    F The alarms are reset one by one by pressing the key marked Acknowledge.Ac knowl edge will work on the alarm shown in the up per in for ma tion viewport only.An as ter isk (*) is shown in front of the first line to in di cate that the alarm is de ac ti vated.

    When the con di tion on the ac knowl edged de vice is re moved, the alarm text will dis ap pear. When all alarms are acknowledged and there are no more devices de tect ing any con di -

    tion, the alarm text will dis ap pear from the dis play and the text: Nor mal op er a tion isdis played.

    ServoMaster User Manual 12 911 004Page 10 2003-06

    MENUALARMS

    NEXTALARM

    Previousalarm

    ALARMSILENCE

    Acknow-ledge

    TECHNICAL ALARMS: 2 ZONES: 1Techn. alarm 1 27.11.2002 12:56:43Engine roomFan blockedZone 5 Sensor 7Techn. alarm 2 27.11.2002 13:15:48Engine roomDoor open Zone 5 Sensor 1

    PreviousAlarm

    Acknow-ledge

    * Techn. alarm 1

  • 3.5 Fault WarningFault warnings are ac ti vated if there is a hard ware or soft ware fault in the sys tem like de -tec tor faults, power faults, com mu ni ca tion faults etc.

    3.5.1 Indication Fault warn ing is in di cated on the op er a tor panel by the FAULT LED.

    If there is a fault in the soft ware con trolled sys tems, the SYS TEM FAULT LED willbe on as well.

    The in ter nal buzzer will sound with short beeps at a 1 Hz (programable).The alarm bells and/or horns will not be ac ti vated.

    The up per part of the dis play will show the num ber of faults. The dis play will show the same in for ma tion as for Fire alarm. See sec tion 3.2.1

    Line 1 will in di cate the alarm type as Fault.

    F Ob serve that fire- , pre- and tech ni cal alarms have pri or ity over fault warn -ings.If an alarm with higher pri or ity oc curs when the op er a tor panel in di cates a fault warn ing,the pri or ity alarm will over rule all fault warn ings and the op er a tor panel will show pri or ityalarms only.To view possible fault warn ings during a priority alarm condition, push the MenuAlarms key. Select: View information \ View alarms by level \ View faults.

    3.5.2 In case of FAULT WARNING

    F A SYS TEM FAULT is se ri ous since the con trol cir cuitry of the fire de tec -tion sys tem may have re duced func tion al ity. Con tact the man u fac turer or the lo cal rep re sen ta tive im me di ately for ser vice and

    re pair.

    F Read the dis play text. The text will in di cate the fault type and lo ca tion. Scroll through all fault warn ings if more than one is in di cated.

    The scrolled alarm text is al ways shown in the up per in for ma tion viewport. The lower in for ma tion viewport shows the most re cent alarm and is not in flu enced

    by scroll ing. Press NEXT ALARM to view any further alarm.

    The two LEDs are lit as long as there are more alarms to view.

    Press Pre vi ous alarm to scroll back wards.

    F The rea son for the fault warn ing must be de ter mined by con sult ing thefault-find ing ta ble in sec tion 3.5.3 and by ex am in ing the de vice. Per form cor rect ing ac tions ac cord ing to lo cal in struc tions.

    F Turn off the buzzer by press ing the key ALARM SI LENCE only when thisalert is no lon ger needed.The dis play re mains un changed. The buzzer can be turned on again by press ing the key once more.

    12 911 004 ServoMaster User Manual2003-06 Page 11

    FAULT

    SYSTEM FAULT

    FAULTS: 3Fault 1 27.05.2003 12:56:43Deck ACabin 231Zone 101 Sensor 1 (STD531) A/1/1/2Fault 3 27.05.2003 13:15:48Car deckStarboardZone 101 Sensor 4 (SSD531) A/1/1/3

    PreviousAlarm

    Acknow-ledge

    MENUALARMS

    NEXTALARM

    Previousalarm

    ALARMSILENCE

  • F The alarms are re set one by one by press ing the key marked Ac knowl edge. You will be prompted to en ter the ac cess code (if valid).Ac knowl edge will work on the alarm shown in the up per in for ma tion viewport only.An as ter isk (*) is shown in front of the first line to in di cate that the alarm has beenacknowledged. As soon as the fault on the ac knowl edged de vice is solved, the alarm text will dis ap -

    pear. When all alarms are ac knowl edged and there are no more fault con di tions, the alarm

    text will dis ap pear from the dis play and the text: Nor mal op er a tion is dis played.

    3.5.3 Fault finding table

    DIS PLAY TEXT POS SI BLE FAULTSSen sor fault A sensor's in ter nal sur veil lance sys tem re ports a fault

    like dust or dirt. A sen sor may have been re moved from the base. The central module re ceives no an swer from a sensor.

    Loop fault The loop wires are in ter rupted or bro ken.

    Alarm out letsfault

    The alarm out let wires may be bro ken or short cir cuited. An alarm out let fuse may be blown. Alarm out lets 1 and 2 are sep a rately mon i tored.

    Fire door out letfault

    The door mag net out let fuse may be bro ken.

    Gen eral in letcir cuit fault

    The loop wire for the Gen eral inlet push but ton may be in ter rupted or bro ken.

    Data comm. out lets fault

    The data communication out let wires may be bro ken or short cir cuited. The fuse may be blown.

    Ground fault One or more of the fol low ing ca bles may have a re sis tance less than 1 kW to ground: -Bat tery pole (BATT) + or -Loop ca bles (L1-4) A or B -Alarm bell out let (AB1-2) + or -Door hold out let (DH1-2) + or -Alarm in put (IP1-2)

    Bat tery fault There may be a fault in the backup bat tery or its con nect ing ca bles. Bat tery fuses may be blown. The bat tery volt age may be too low. Bat tery ca pac ity may be in suf fi cient.

    Power sup plyfault

    The power sup ply may be lost. The sup ply volt age may be too low. Fuses may have blown in the panel or the power sup ply.

    Please re fer to the in stal la tion man ual 12 911 003 for de tailed test and fault de scrip tion.

    3.5.4 Replacing sensorsA faulty sen sor on an addressable loop can be changed while the loop is ac tive. Re move the faulty sen sor from its base by turn ing the sen sor coun ter clock wise. Insert a new de tec tor within 40 sec. to avoid fault warn ing, "Miss ing de tec tor". Wait 3-5 sec. for the red detector in di ca tor light. The light will be on for 2-3 sec. while

    the sen sor is au to mat i cally con fig ured.The sensor is now con fig ured and rec og nized by the sys tem and put into ser vice.For mass replacement of sensors, contact the service responsible.See also "Verify replaced sensors" in section 4.2.4.

    ServoMaster User Manual 12 911 004Page 12 2003-06

    Acknow-ledge

    * Fault 1

  • 3.6 DisablementsDis able ment con di tion will oc cur if any de vice, out lets or part of the sys tem is dis abled.Dis able ment is a user ini ti ated func tion to put de vice(s) or out let(s) tem po rary out of ser -vice as de scribed in sec tions 4.2.1 and 4.2.2.

    3.6.1 Indications The DIS ABLE MENTS LED is con stant ON.

    The display text Normal operation is changed to System functions are disabled.The preceding lines will describe the disabled sensors and outlets.

    There will be no sound in di ca tions.

    3.6.2 Actions To re-en able dis abled out lets and sen sors, press the MENU< > ALARMS key. Se lect Dis able ments - Out lets from the main menu.

    Select the disabled outlet and press the key marked Enable.Repeat for all disabled outlets. See more details in section 4.2.1.

    Se lect Dis able ments - Sen sors from the main menu. Select Enable all Sensors or follow the details given in section 4.2.2. Con firm by pressing the MENU< > ALARMS key. Exit all menus and the dis play will show Nor mal op er a tion if there are no more

    disablements.

    3.7 Test ConditionThe sys tem is in test con di tion when ServoMaster is set to test mode for sys tem com mis -sion ing or ser vice.

    3.7.1 Indications The TEST LED is permanently ON. The display text Normal operation is changed to System is in test mode. There will be no sound in di ca tions.

    3.7.2 ActionsThe test is prob a bly per formed from an other lo ca tion. You should normally not in ter fere with the on go ing test pro ce dure.

    12 911 004 ServoMaster User Manual2003-06 Page 13

    DISABLEMENTS

    17.06.2003 16:47

    System functions are disabledDetectors are disabled

    MENUALARMS

    Enable

    TEST

    17-11-2002 16:47

    System is in test mode

  • 4 MENU FUNCTIONSIt is pos si ble to per form cer tain func tions, view sys tem in for ma tion and set some sys temoptions from the ServoMaster op er a tor panel. The menu for these ser vices are ac cessed byus ing the panel keys and the menu is shown on the dis play. The func tion is se lected from a main menu with sub menus as shown in the ta ble be low. You may be prompted to en ter the ac cess code to enter the menus.

    4.1 Function Menu

    ServoMaster User Manual 12 911 004Page 14 2003-06

    DISABLEMENTS- OUTLETS

    Alarm soundersDoor holdersFire brigadeFault outletControl outlet

    Disablements - ZonesDisablements - Sensors* List disabled sensorsEnable all sensors* Disable all with fault warn.* Disable all with techn. Alarm* Disable all with fire alarm

    View zoneView sensor

    Overview disablementsView all sensors disablements View disabled outlets* View event log* View system configuration

    View alarms by level

    Test LEDs and LCD display Test zoneReset loop **)Verify replaced sensors **)

    Change panel node numberView firmware versionsCancel operator accessOperator access setup

    Set display backlightSet display contrastSet LED intensitySet date and time* Change date and time formatChange access code* Delay alarm sounders* Printer settings

    Set contrast center positionDis. sounder act. by faultPanel resetOperator panel informationLoop commissioning* Alarm simulations

    DISABLEMENTS- SENSORS

    VIEW INFORMATION

    MAINTENANCE

    SYSTEMSETTINGS

    SERVICE FUNCTIONS

    SYSTEMCONFIGURATION

    View fire alarmsView pre-alarmsView technical alarmsView faultsView test alarms

    Simulate fire alarmSimulate technical alarmSimulate fault warning

    MAIN MENU SUB MENU

    For service personnel only

    * May not be implemented in this version.

    **) Contact service before use

  • 4.2 Main Menu Press the MENU< >ALARMS key to en ter the func tion menu. The menu may be password protected.

    The Operator Access LED is lit when operation is possible.

    Nav i gate using the Up and Down keys. Press En ter to se lect func tion. Se lect EXIT and press En ter to re turn to the main win dow

    or press the MENU< >ALARMS key twice.

    4.2.1 Disablements - OutletsSe lect this menu with the En ter key if you want to dis able out lets. The out put will not betriggered by any alarm when dis abled.All choices on the sub menu are marked EN ABLED as de fault. Press the Down key to se lect the de sired op tion. Press the Dis able key to dis able se lected op tion.

    This key text will change to En able when the op tion is dis abled.

    Alarm sounders All fire alarm sounders connected to the Alarm Bell outputs AB1 and AB2 will be

    disabled. The panel buzzer will not be disabled.

    Door holders Door magnets connected to the Door Hold outlet DH will not release and close fire

    doors.

    Con trol out lets All automatic actions like closing valves and starting ventilation fans connected to

    the Control Outlets CO1 and CO2 will be disabled.

    Fire brigade Fire bri gade call or other fire alert ac tions con nected to the FIRE out let will not take

    place.

    Fault out let Fault alert con nected to the FAULT out let will not be ini ti ated.

    Press the En ter key when fin ished. Exit the main menu.

    The yellow lamp DISABLEMENTS is ON and the display text during disablements is:

    System functions are disabledOutlets are disabled

    To re-en able dis abled func tions, go through the pro ce dure de scribed above but se lect thedis abled op tions and press the En able key.

    12 911 004 ServoMaster User Manual2003-06 Page 15

    MENUALARMS

    Select Function

    DownEnter Up

    EXITDisablements - SensorsView informationMaintenanceSystem settingsService functionsSystem configuration

    Disablements - Outlets

    Down Disable

    Disablements - Outlets

    DownBack Disable

    Alarm sounders ENABLEDDoor release ENABLEDControl outlets ENABLEDFire brigade ENABLEDFault outlets ENABLED

    DISABLEMENTS

    KADIR SARI

    KADIR SARI

    KADIR SARI

  • 4.2.2 Disablements - SensorsSe lect this menu with the En ter key if you want to dis able sen sors or zones dur ing ac tiv i -ties that de velop heat or smoke, test or ser vice that may cause un de sired ac tions. Press the Down or Up keys and se lect the de sired op tion with the En ter key.

    Dis able ments - ZonesNo smoke or heat de tec tors within the se lected zone will de tect fire when dis abled. Man -ual call points can not be dis abled and will re main in ser vice. En ter the zone number, 3 digits (zone 1 = 001).

    The dis play will show the sta tus for the se lected zone as EN ABLED. Press the Dis able key to dis able the se lected zone.

    If the zone is al ready dis abled the key is marked En able. En ter further zone num bers as de sired. Press the Back key to re turn to the Dis able ments menu.

    Dis able ments - Sen sorsSelected sensor will not report alarms. En ter the sen sor num ber (zone/sen sor, 3+2 dig its).

    The dis play will show the sta tus for the se lected sen sor as EN ABLED or DIS ABLED. Press the key marked Dis able or En able to change the se lected sen sors sta tus. En ter further sen sor num bers as de sired. Press the Back key to re turn to the Dis able ments menu.

    List dis abled sensors *) Show a list of all dis abled sen sors.

    Se lect op tion List all sen sors dis abled by op er a tor or List all sen sors dis abled bytimer. Con firm by En ter

    Press the Back key to re turn to the Dis able ments menu.

    En able all sen sors Press the En able key to put all dis abled sensors back in ser vice. Con firm by En ter.

    The dis play shows the text All sen sors en abled. Press the Back key to re turn to the Dis able ments menu .

    Dis able all with fault warn. *) Disable all sensors which are in a fault warning mode. See section 3.5.

    Press the Dis able key to dis able all sen sors gen er at ing a fault warn ing. Con firm by En ter.The dis play shows the text All sen sors with fault warn. dis abled.

    Press the Back key to re turn to the Dis able ments menu.

    Dis able all with techn. alarm *) Disable all sensors which are in a technical alarm mode. See section 3.4

    Press the Dis able key to dis able all sen sors gen er at ing a tech ni cal alarm. Con firm by En ter.The dis play shows the text All sen sors with techn. alarm dis abled.

    Press the Back key to re turn to the Dis able ments menu.

    Dis able all with fire alarm *) Disable all sensors which are in a fire alarm mode. See section 3.1

    Press the Dis able key to dis able all sen sors gen er at ing a fire alarm. Con firm by En ter.The dis play shows the text All sen sors with fire alarm dis abled.

    Press the Back key to re turn to the Dis able ments menu.

    *) The function may not be implemented in this version.

    ServoMaster User Manual 12 911 004Page 16 2003-06

    Disablements - Sensors

    Down

    BackDisablements - SensorsEnable all sensorsDisablements - Zones

    Enter Up

    Disablements - Sensors

    Clear ENABLE

    Enter sensor number: ---/--Status sensor 101/01: DISABLEDPanel A, LC 1, Loop 1, Dev. 1

    Back

  • 4.2.3 View InformationSe lect View in for ma tion with the En ter key if you want to check the sta tus of theServoMaster. This fea ture is use ful when you want to obtain in for ma tion about a sta tusother than the cur rent dis play, e.g. check out alarms with lower pri or ity.

    View zones Se lect View zones and con firm by En ter. En ter the zone num ber 3 digits (zone 1 = 001). The display will show the ENABLED/DISABLED status for the selected zone.

    The status cannot be changed from this window See section 4.2.2 to change. Press the Back key to return to the View Information menu.

    View sen sors Se lect View sen sors and con firm by En ter En ter the sen sor num ber (zone/sen sor, 3+2 dig its). The dis play will show sen sor sta tus:

    Enabled/disabled Cannot be changed from this window. See section 4.2.2. Panel Connected to panel A-F LC Loop Control 1-8 Loop Loop number Dev. Sensor number Alarm level NONE, Fire alarm, Pre-alarm, Techn. alarm, Test, Fault Dig. status for service only Info status for service only

    Press the Back key to re turn to the View in for ma tion menu.

    View alarms by level Select View alarms by level and confirm by Enter. The dis play shows a new menu with a list of alarm types:

    View fire alarms View pre-alarms View technical alarms View faults View test alarms

    Se lect the ac tual alarm type with the Up/Down keys and con firm by En ter. The display will show the same window as for Alarms. See sections 3.1 to 3.5.

    It is possible to acknowledge the alarm(s) from this window. If the alarm type is not pres ent, the dis play will show: There are no ... alarms. Press the Back key to re turn to the View in for ma tion menu.

    Over view disablements Se lect Over view disablements and con firm by En ter.

    The dis play will show a list with all dis able ment. Press the Back key to re turn to the View in for ma tion menu.

    View all sen sor disablements Se lect View all sen sor disablements and con firm by En ter.

    The display will show the first disablement. Press the Next key to view the next disablement, if any. Press the Back key to re turn to the View in for ma tion menu.

    12 911 004 ServoMaster User Manual2003-06 Page 17

    View information

    Down

    BackView sensorView alarms by levelOverview disablementsView all sensor disablementsView disabled outlets

    View zone

    Enter Up

    View Sensors

    Clear

    Select sensor: ---/--Status zone 1 /1: ENABLEDPanel A, LC 1, Loop 1, Dev. 1Alarm level: NONEDig. status: 00H, Info status 0

    Back

  • ServoMaster User Manual 12 911 004Page 18 2003-06

    Test zone

    Clear Stoptest

    Enter zone number: ---Status zone 101: ENABLEDAlarm level: NONETest mode: ACTIVE

    Back

    TEST

    DISABLEMENTS

  • Ver ify replaced sen sorsThis func tion may be used to con fig ure one or more re placed sen sors in a loop. Se also sec -tion 3.5.4 re gard ing sen sor re place ment.Please con tact ser vice for com plete pro ce dure. Se lect Ver ify re placed sen sors and con firm by En ter.

    The dis play will show the first unconfigured sen sor. Press Save to store the zone ad dress in the sen sor. Press Next to show the next unconfigured sen sor. Press the Back key to re turn to the Main te nance menu.

    4.2.5 System settingsA few op er a tor panel dis play set tings can be per formed from this menu. Se lect Sys tem set tings from the Main menu and con firm by En ter. Se lect the option by the Up or Down keys and con firm by Enter.

    Set dis play backlight Se lect Set dis play backlight and con firm by En ter.

    The dis play shows the ac tual back-light in ten sity in % on a graph i cal bar. Se lect new back-light intensity in steps of 10% by the Up/Down keys.

    The bar changes and the ac tual light is ap plied to the LCD dis play. Press OK to con firm the set ting and re turn to the Sys tem set tings menu.

    Se lect dis play con trast Se lect Set dis play contrast and con firm by En ter.

    The dis play shows the ac tual con trast value from -5 to +5 on a graph i cal bar. Se lect new con trast level in 10 steps using the Up/Down keys.

    The bar changes and the ac tual contrast is ap plied to the LCD dis play. Press OK to con firm the set ting and re turn to the Sys tem set tings menu.

    Set LED in ten sity Se lect Set LED in ten sity and con firm by En ter.

    The dis play shows the ac tual back-light in ten sity in % on a graph i cal bar. Se lect new LED in ten sity in steps of 10% by the Up/Down keys.

    The bar changes and the ac tual light is ap plied to the LEDs. Press OK to con firm the set ting and re turn to the Sys tem set tings menu.

    Set date and timeIn nor mal op er a tion, the dis play al ways shows date and time. In or der to change time and/or date, se lect Set date and time and con firm by En ter.

    The dis play shows the date and time. En ter the cor rect date and time by us ing the nu meric key board. Press Back to con firm and re turn to the Sys tem set tings menu.

    12 911 004 ServoMaster User Manual2003-06 Page 19

    Set display backlight

    DownOK Up

    Current display backlight setting: 80%

    0% | | | | 50% | | | | 100%

    System Settings

    DownSelect Up

    BackSet display contrastSet LED intensitySet date og time

    Set display backlightSet display backlight

    Set display contrast

    DownOK Up

    Current display contrast: 2

    -5 | | | | 0 | | | | +5

    Set date and time

    Set correct date and time_9.11.2002 08:29:04

    Clear CancelBack

    Set LED intensity

    DownOK Up

    Current LED intensity setting: 80%

    0% | | | | 50% | | | | 100%

  • Change date and time for mat *) The de fault date for mat is: dd-mm-yyyy - The de fault time for mat is: 24 hrs Se lect the date and time for mat from the al ter na tives and press En ter to con firm.

    Delay alarm sounders *)The de fault time de lay be fore the alarm sound ers are ac ti vated is set from the setupprogram. The delay can be disabled or enabled by selecting Delay alarm sounders . Se lect Dis able if the screen show En abled and visa versa. Press Back to re turn to the Sys tem set tings menu.

    Delay alarm transmission *)The in di ca tor lights "Alarm trans mis sion de layed" and "Alarm trans mis sion ac tive" arenot in cluded on some pan els. The func tion is there fore not avail able in those ver sions.The de fault time de lay be fore the Alarm transmission is ac ti vated is set from the setup pro -gram. The de lay can be dis abled or en abled by se lect ing Alarm transmission de lay. Se lect Dis able if the screen show En abled and visa versa. Press Back to re turn to the Sys tem set tings menu.

    Change ac cess codeWhether or not the menu should be ac cess level 2 code pro tected is set by the setup pro -gram. If the menu is pro tected, the de fault ac cess code is 0110. This code should bechanged be fore the sys tem is put into nor mal ser vice. Se lect Change ac cess code. En ter the New ac cess code, 4 dig its. Re peat the ac cess code when asked to and con firm by OK. Use the Clear key to de lete the last digit en try. Use the Can cel key to re turn to Sys tem set tings with out chang ing the ac cess code.

    NOTE: Keep the code at a safe place un avail able for per sons not con cerned. Only au tho rized per -son nel should know the code! If the code is for got ten or lost, con tact ser vice. Ac cess tothe menus is then only pos si ble through the ac cess level 3 ser vice code.

    Printer set tings *)

    4.2.6 Service FunctionsThis menu is pro tected by ac cess level 3 code and should be used by qual i fied ser vice per -son nel only. The sub menu con tains se lec tions rel e vant to the par tic u lar installation and is used dur ingin stal la tion, com mis sion ing and ser vice.

    4.2.7 System ConfigurationThis menu is pro tected by ac cess level 3 code and should be used by qual i fied ser vice per -son nel only. The sub menu con tains se lec tions rel e vant to the par tic u lar in stal la tion and is used dur ingin stal la tion, com mis sion ing and ser vice.

    *) This func tion may not be im ple mented in this ver sion.

    ServoMaster User Manual 12 911 004Page 20 2003-06

    ALARM SOUNDERS DELAYED

    Alarm sounders delay

    Back DISABLE

    Alarm sounders delay: ENABLED

    ALARM TRANSMISSION DELAYED

    ALARM TRANSMISSION ACTIVE

    Alarm transmission delay

    Back DISABLE

    Alarm transmission delay: ENABLED

    Change access code

    Enter new access code: - - - -

    Clear CancelOK

  • 5 CONTROL MODULE CONNECTIONS

    12 911 004 ServoMaster User Manual2003-06 Page 21

    0

    4

    8 26

    AC E

    .

    .

    .

    .

    .

    .

    .

    .

    FUSE

    S

    CH1

    1.0A

    T

    CH2

    1.0A

    T

    AB

    11.

    0AT

    AB

    21.

    0AT

    DH

    1.0A

    T

    BAT

    T.5.

    0AT

    PS 5.0A

    TCO

    1Co

    ntro

    lOu

    tlet

    0V BAT

    RTN

    CHG

    - + - +- + NO C NC NO C NCNO C NC B2 A2 B1 A1 B2 A2 B1 A1

    BAT

    TBa

    ttery

    PSPo

    w. S

    uppl

    yD

    HDo

    or H

    old

    AB

    1

    Alar

    m B

    ells

    AB

    2

    Alar

    m B

    ells

    FAUL

    T

    FIR

    E L2Ad

    dres

    sabl

    elo

    op L1Ad

    dres

    sabl

    elo

    op

    UPPE

    R R

    OW

    Local LAN

    PC in

    terfa

    ceFo

    r m

    ain

    ten

    ance

    u

    se o

    nly

    ! Powe

    r

    Powe

    r

    Powe

    r

    11

    22

    28 VD

    C

    24 V

    Mai

    ns

    10K

    33

    36

    6+_

    STD

    / SSD

    / UTD

    PFR

    / MPD

    / CLM

    / MSO

    PFR

    / MPD

    / CLM

    / MSO

    PFR

    / MPD

    / CLM

    / MSO

    STD

    / SSD

    / UTD

    MCP

    SEC

    MBF/

    MSB

    GPT-

    AG

    Blac

    k

    Red

    BA

    LB

    AL

    BA

    L

    0V +V -D +D

    0V +V -D +D

    0V +V -D +D

    0V +V -D +D

    0V +V -D +D

    0V +V -D +D

    OPE

    RAT

    OR

    PAN

    ELO

    PER

    ATO

    RPA

    NEL

    OPE

    RAT

    OR

    PAN

    EL

    10 w

    ire10

    w

    ire10

    w

    ire

    CO2

    Cont

    rol

    Outle

    t

    0V TSNS

    GN

    DBA

    L

    NO C NC B2 A2 B1 A1 B2 A2 B1 A10V +V -D +D 0V +V -D +D 0V IP2

    0V IP1

    Do

    n

    ot

    con

    nec

    t

    BA

    LBa

    ckup

    Line

    CH2

    Serv

    oLan

    CH1

    Serv

    oLan

    IP2

    Inpu

    tIP

    1In

    put

    LOW

    ER R

    OW

    Char

    ger

    vo

    ltage

    ad

    justm

    ent

    Do

    n

    ot r

    eadju

    st!

    Mo

    dule

    ad

    dres

    s se

    lect

    ion

    18k10k

    OPA

    OPA

    OPA

    L4Ad

    dres

    sabl

    elo

    op L3Ad

    dres

    sabl

    elo

    op

    -

    - ++

    SW1

    SW2

  • ZENITEL NORWAY [email protected]

    Table of Contents1 General 31.1 About this manual 31.2 Definitions 3

    2 FUNCTIONAL DESCRIPTION 42.1 ServoMaster Operator Panel 42.1.1 Access code 42.1.2 Display 52.1.3 Keys 52.1.4 Indicator lights 5

    3 Alarm Messages 73.1 Priorities 73.2 Fire Alarm 73.2.1 Indications 73.2.2 In case of FIRE ALARM 8

    3.3 Pre-alarm 93.3.1 Indication 93.3.2 In case of PRE-ALARM 9

    3.4 Technical alarm 103.4.1 Indication 103.4.2 In case of TECHNICAL ALARM 10

    3.5 Fault Warning 113.5.1 Indication 113.5.2 In case of FAULT WARNING 113.5.3 Fault finding table 123.5.4 Replacing sensors 12

    3.6 Disablements 133.6.1 Indications 133.6.2 Actions 13

    3.7 Test Condition 133.7.1 Indications 133.7.2 Actions 13

    4 MENU FUNCTIONS 144.1 Function Menu 144.2 Main Menu 154.2.1 Disablements - Outlets 154.2.2 Disablements - Sensors 164.2.3 View Information 174.2.4 Maintenance 184.2.5 System settings 194.2.6 Service Functions 204.2.7 System Configuration 20

    5 Control module connections 21