SB - HVACR

36
® SB

Transcript of SB - HVACR

Page 1: SB - HVACR

1

®

www.coldinnovation.it

®

SB

Page 2: SB - HVACR

Available versions . . . . . . . . . . . . . . . . . . . pag. 4

Structure of electro-galvanized and painted steel sheet . . . . . . . . . . . . . . . . . . pag. 5

Ecological refrigerant R410A . . . . . . . . . . pag. 5

Scroll compressors . . . . . . . . . . . . . . . . . . pag. 6

Condenser coils . . . . . . . . . . . . . . . . . . . . . pag. 6

Brazed plates evaporators . . . . . . . . . . . . pag. 7

Axial fans . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 7

Thermostatic expansion valves . . . . . . . . pag. 8

Electronic expansion valves . . . . . . . . . . . pag. 8

4-way reversing valve . . . . . . . . . . . . . . . . pag. 9

Electronic regulation . . . . . . . . . . . . . . . . . pag. 9

Hydronic circuit . . . . . . . . . . . . . . . . . . . . pag. 10

Operating range . . . . . . . . . . . . . . . . . . . . pag. 10

Versions and accessories . . . . . . . . . . . . .pag. 11

Technical sheets . . . . . . . . . . . . . . . . . . . pag. 12

Performances . . . . . . . . . . . . . . . . . . . . . pag. 20

Dimensional drawings . . . . . . . . . . . . . . . pag. 29

®

INDEX

Page 3: SB - HVACR

3

®

www.coldinnovation.it

Air cooled water chillers and heat pumps, axial fans, hermetic scroll compressors, brazed plate evaporators, refrigerant gas R410A, condensing unit.1 refrigerant circuit with 1 or 2 compressors.Units designed for commercial or indu-strial applications.

Only for outdoor installation.

Cooling capacity from 10 up to 130 kWHeating capacity from 11 up to 144 kW

SB

R410Arefrigerant

Page 4: SB - HVACR

4

®

www.coldinnovation.it

AvAilAble versions

� CHILLER: basic version with large operative range of outdoor air temperature (-15°C up to 43°C).

� HEAT PUMP: with large operative range of outdoor air temperature (-10°C up to 40°C in he-ating mode); used for hydronic circuits with 2 tubes, during winter produces hot water up to 50°C, and during summer produces cold water.

� SILENT: unit equipped with soundproof compressors and fan speed controller for limited noise levels. The unit can work during the night with reduced fan speed.

� CONDENSING UNITS: this units are supplied without evaporator, expansion valve and hydro-nic components; they are able to be connected with a remote direct expansion heat exchanger (example a cooling coil inside an air handling unit (AHU)).

� HEAT PUMP CONDENSING UNITS: this units are supplied without evaporator and hydronic components; they are able to be connected with a remote exchanger for direct and reversing cycle (example a cooling/heating coil inside an air handling unit (AHU))

� PARTIAL HEAT RECOVERY (desuperheater): an heat exchanger is inserted along the com-pressors discharge line before the condenser, it’s able to desuperheat the hot gas and pro-duces hot water up to 55°C. The amount of recovered energy is around the 30% of the cooling energy production.

� TOTAL HEAT RECOVERY: a water condenser is inserted on the discharge line of the compres-sors in parallel with the air condenser, when the recovery circuit is not satisfied, a changeover valve diverts the refrigerant hot gas in the water condenser, to transfer the total condensing energy on the hot water circuit.The amount of recovered energy is around the 135% of the cooling energy production.

� TWO FREECOOLING VERSIONS:

• STANDARD FREECOOLING: near the finned condenser there is a second finned heat exchanger with water inside (freecooling exchanger); if the external air temperature falls below than a con-veniently limit, a switch valve diverts the water flow through the freecooling exchanger (freecoo-ling and compressors work together); when outdoor air temperature falls under a second project limit, all compressors are completely stopped:

- The air flow by fans cools directly the water inside the freecooling exchanger and the EER of the unit increase up to 20-22 W/W.

- This solution needs to use water with antifreeze for the winter period for antifreeze protection.

• FREECOOLING WITH SEPARATED CIRCUIT: the freecooling circuit is separate from user circuit, so the antifreeze mixture charge can be limit to it; the chiller mode has more efficiency and the user plant is in global less expensive.

� CLIENT: units with special equipment or devices.

Page 5: SB - HVACR

5

®

www.coldinnovation.it

structure of electro-gAlvAnized And pAinted steel sheet

ecologicAl refrigerAnt r410A

This refrigerant R410A with zero ozone depletion potential (ODP=0) together with a very low value for the global warming effective potential, is the best choice for circuits with scroll compressors.

Thanks to its characteristics of heat transfer and its heat capacity in the gas phase, allows high yields of condensers having small diameter tube, and can re-duce the airflow needed for condensation.

Features

Air condensed water chiller with scroll

compressors.

R410A

Page 6: SB - HVACR

6

®

www.coldinnovation.it

scroll compressors one or two high-efficiency scroll compressor on each circuit for maximum energy efficiency at partial loads.

The choice of scroll compressor allows you to have low vibration and noise emissions.Reliability is high thanks to the reduced number of moving parts and to the high capa-city of the compressor to adapt to many different conditions.

Due to its construction, hermetic scroll compressors withstand at flooded start much better than the piston or screw compressors (in faulty conditions).

On unit with multiple compressors, when only one of them is started (this happen during many hours in a year) it can work with oversized of the heat exchangers and this produce a bigger efficiency du-ring working conditions partialized.

The example is as follows:If a circuit with two compressors has a value of EER= 2.70 W/W, when on the same circuit only one compressor opera-tes the EER value climbs to 3.74 W/W; the result of this technology is that the value of ESEER (seasonal average efficiency) increases much more than in chillers with only one compressor per circuit.

condenser coils with high-efficiency design, equipped by internally grooved copper tubes for maximize the heat exchange, with small diameter to minimize the refrigerant charge.

The special profile of the fins allows to obtain excellent performance of heat exchange with the air, together with the use of internally grooved tubes we have low values of the condensing tempera-ture and consequently high compres-sors performances.In the case of heat pumps, the fins have hydrophilic surface treatment in order to obtain high performance of water drain during defrosting of the battery.

Finned condenser

Scroll Compressor section

Page 7: SB - HVACR

7

®

www.coldinnovation.it

brAzed plAtes evAporAtors specifically designed for R410A, made in stainless steel.

In addition to a very high mechanical re-sistance, due to the use of stainless steel, they have high corrosion resistance.These evaporators work in perfect countercurrent, and allow to have very high evaporation temperature compared other kind of evaporator, for maximize EER performance.An integrated distributor guarantees a perfect equalization of the refrigerant gas flow inside each plate heat exchanger, for maximum performances. On heat pumps the evaporator commutates to condenser mode and produces hot water.

Brazed plate evaporator

AxiAl fAns

The chillers are normally supplied with fans equipped with AC motor, control-led by a fan speed controller (cut phase regulator) that allows the modulation of speed so as to manage the condensing pressure with the change of cooling load and outdoor air temperature.

Fans are available on request with a EC motor (Electronically Commutated Mo-tor) that enable high performance.At full load, an EC motor saves 20% energy compared to a conventional AC motor, and the difference increases up to 57% when the comparison is made at partialized con-ditions, with the air flow capacity equal to half of the maximum flow. The higher cost of the fans with EC motor is repaid by the energy saving after about 2 years of unit work. In addition to energy saving the low axial fans speed,facilitate limited noise le-vels when the unit works during the night.

Fan with EC motor

Fan with AC motor

Page 8: SB - HVACR

8

®

www.coldinnovation.it

thermostAtic expAnsion vAlves

Standard production is equipped by ther-mostatic expansion valves to ensure a re-turn of dry gas to the compressor.

electronic expAnsion vAlves on requestby request the unit can be equipped with electronic expansion valves.

These valves, via an electronic driver, a temperature sensor and a pressure transmit-ter, are able to provide a more precise value of superheating.

The graph below shows the effect of switching between the operation of a chiller with a TEV (thermostatic expansion valve) to an EEV (electronic expansion valve). The lowering of the average superheat value, the stability of the value itself and the ope-rating pressure are clearly evident.

Its use is highly recommended in the case of heat pumps, where in winter operation, it allows to have a very low superheating (this allow COP increasing) and the correct function of unit also with much lower outdoor air temperatures, up to 3 °C less com-pared to use of thermostatic valves.

Carel controllers andElectronic Expansion Valve

Page 9: SB - HVACR

9

®

www.coldinnovation.it

4-wAy reversing vAlve

Used for heat pump version converts the re-frigerant circuit configuration from chiller to heat pump. When switched on, the unit is converted to heat pump (the chiller evapo-rator works at condenser mode and produ-ces hot water - winter). When switched off the refrigerant circuit is converted to chiller mode (summer) or defrosting (winter).

electronic regulAtion by A microprocessor cArd for the management and control of all functional parameters

The controls normally used are parame-tric products of Carel.For all the unit the used control is mC2-SE.

On request or for special units, it is pos-sible use controllers belonging to family Carel pCO or from other manufacturers. In any case, the functions controlled are:

a. regulation on inlet water temperature, with the alternative possibility of adju-sting the output water temperature;

b. management of cooling capacity (or he-ating) with turning ON or OFF the com-pressors, depending on the request of the hydronic circuit; the control is such that the number of operating hours per year of each compressor, is the same for everyone;

c. prevent high pressure - this function allows you to turn off one of the com-pressors on the same circuit when the condensing pressure rises too much;

d. reverse cycle for hot gas defrost;e. fan speed regulation (for units that are

equipped - able to handle the conden-sing pressure as a function of load and air ambient temperature) allows to use the chiller also in very low ambient temperatures;

f. management of evaporating pressure in heat pump mode - this feature al-lows the modulation of the fans when the outdoor air temperature is above 5-6 ° C to reduce noise emissions to a minimum level;

g. antifreeze heaters - a set of heaters

protect the parts of circuits containing water when their temperature ( cau-sed from low outdoor air temperature) drops below the safety threshold;

h. low noise mode – this feature as stan-dard on SILENT version, allows you to change the fan speed adjustment in the night hours, with limited noise emission;

i. evaporator pump control; �backup evaporator pump; �rotation pumps (active only in the presence of double pump); �energy save mode (pump switched on only when needed) - this feature allows a considerable energy saving, trough turning ON the pump for only as long it is necessary - this function is useful when you have constant wa-ter flow on chiller side and variable water flow on the system side, by in-serting a manifold by-pass between them: the maximum benefit is obtai-ned when a buffer tank is installed;

j. water flow switch;k. variable set point of water tempera-

ture depending on outdoor air tempe-rature (sliding set temperature) or by

4 ways reversing valve

μC2SE

Page 10: SB - HVACR

10

®

www.coldinnovation.it

hydronic circuit

The unit is normally equipped with Vic-taulic flexible couplings complete with clamps and solder terminals.On request the unit can be completed with the provision of pump, safety valve, water fil-ter, buffer tank and backup pump. Excluded some units, it is possible to choose betwe-en low pressure pump, and high pressure pump with standard performance.

For special requirements is possible to install special pumps, but in this case the buffer tank is not available.The circuits are protected against free-zing by heaters, down to outdoor air tem-perature of -15°C.On heat pumps the expansion vessel is not supplied. On freecooling with separate circuit the backup pump is not available.

external contact;l. start compressors by external con-

tacts (only condensing units);m. communication with supervisory

systems;

n. anti freeze alarm;o. high – low pressure alarmsp. compressors alarmq. water flow alarmr. pump alarm

operAting rAnge thank to the use of fan speed controller the operating range is very wide.

operating ranges forcooling and heating

modes

Page 11: SB - HVACR

11

®

www.coldinnovation.it

operating ranges forcooling and heating modes

versions And Accessories on demAnd

� N ..........Basic � H ..........Heat pump � C ..........Condensing unit � CH ........Heat pump condensing unit � R ..........Partial recovery (desuperhea-

ter) (1) � R1 .........Total recovery (1) � F ..........Freecooling (1) � FS ........Freecooling with separated

circuit(1) � CLIENT Special features on specific

customer needs � EEV ......Electronic expansion valve/s � P1 .........Hydronic Kit with pump, safety

valve, water filter � P2 ........Hydronic Kit with double pump,

safety valve, water filter (1) � P3 ..........Hydronic Kit with high pressure

pump, safety valve, water filter (1) � P4 ........Hydronic Kit with double high

pressure pump, safety valve, water filter (1)

� P1S ....... P1 + Buffer tank, electric heater and expansion vessel (2)

� P2S .......P2 + Buffer tank, electric heater and expansion vessel (1) (2) (4)

� P3S ......P3 + Buffer tank, electric hea-ter and expansion vessel (1) (2)

� P4S .......P4 + Buffer tank, electric heater and expansion vessel (1) (2) (4)

� RS485 ..Serial board RS 485 � RS232 ..Serial board RS 232 for modem � LON .....Serial board LON FTT10 STD � WEB .....Board for local LAN or internet � CK ........Clock board � RIF .......Power factor corrector (3) � ST ........Low starting current device (3) � AV ........Anti-vibration mountings � AV1 .......Anti-vibration mountings high

performances � PR .......Remote control panel � MRV .....Fan speed controller � KK ........Low outdoor air temperature

start device � SOV ......2 way shut-off valve for safety

valves � EF ........Fan with EC motor(3)

(1) Not available on SB-10; 15; 21; 28

(2) For SB-..-H (heat pumps) the expan-sion vessel is not supplied

(3) Not available on SB-10; 15; 21; 28; 36; 41

(4) Not available when selected option FS

Page 12: SB - HVACR

12

®

www.coldinnovation.it

Size 10 15 21 28 36 41 48 52 57 65 74 89 105 116 129

Cooling capacity (kW) 10,18 14,43 21,18 27,76 36,67 41,21 47,15 53,02 58,31 66,25 75,20 92,51 106,36 118,13 131,47

Power input (kW) 3,14 4,54 6,95 9,24 11,73 13,61 16,93 19,24 22,56 25,00 29,28 32,18 38,71 45,36 50,35

Maximum power input at limit conditions (kW) 3,55 5,28 7,92 10,74 13,46 15,75 19,11 21,90 26,11 29,05 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 45,00 45,00 44,50 44,50 44,00 42,00 42,50 40,50 44,00 43,00 41,20 41,50

Water flow (m3/h) 1,75 2,48 3,64 4,78 6,31 7,09 8,11 9,12 10,03 11,39 12,93 15,91 18,29 20,32 22,61

Pressure loss of hydronic circuit (kPa) 17,61 22,24 28,98 33,99 40,91 49,41 46,16 58,43 40,74 50,86 46,86 57,03 56,73 42,65 50,62

EER (kW/kW) 3,24 3,18 3,05 3,01 3,13 3,03 2,78 2,76 2,58 2,65 2,57 2,87 2,75 2,60 2,61

ESEER (kW/kW) 4,30 4,27 4,21 4,18 4,25 4,19 4,04 4,02 3,89 3,95 3,88 4,10 4,02 3,91 3,92

Sound pressure at 10m (dB(A)) 39,20 39,20 41,53 41,73 40,77 44,13 47,33 47,38 47,36 47,33 49,14 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 8,87 13,57 18,04 22,91 26,58 33,06 37,58 44,06 48,82 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 16,57 21,15 26,15 33,84 38,84 47,17 52,17 59,17 66,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 63,60 85,60 105,20 149,20 161,60 183,60 164,60 169,60 185,60 192,60 219,60 258,20 271,20 316,20 329,20

Buffer tank capacity (lt) 25,00 25,00 25,00 25,00 180,00 180,00 180,00 180,00 180,00 180,00 180,00 330,00 330,00 330,00 330,00

Maximum operating pressure PS (bar) 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00

Power input of low pressure pump (kW) 0,09 0,11 0,16 0,20 0,59 0,65 0,74 0,84 0,92 1,02 1,13 1,31 1,43 1,94 2,07

Amperage of low pressure pump (A) 0,55 0,71 1,00 1,24 1,21 1,35 1,52 1,74 1,89 2,11 2,33 2,70 2,94 4,01 4,27

Available pressure with low prevalence hydronic kit (kPa) 92,39 77,76 66,02 56,01 93,37 83,40 84,51 98,03 113,62 100,09 99,86 80,38 72,22 128,31 109,93

Power input of high pressure pump (A) - - - - 0,72 0,80 0,91 1,10 1,21 1,35 1,51 2,05 2,12 2,26 2,51

Amperage of high pressure pump (A) - - - - 1,49 1,66 1,88 2,28 2,49 2,79 3,12 4,23 4,37 4,66 5,19

Available pressure with high prevalence hydronic kit (kPa) - - - - 173,12 163,22 164,46 200,08 215,74 202,35 202,31 180,38 172,22 218,31 199,93

FREE COOLING

Cooling capacity (kW) - - - - 33,74 37,91 43,38 48,78 53,65 60,95 69,18 85,11 97,85 108,68 120,95

Power input (kW) - - - - 1,24 1,29 1,76 1,76 1,76 1,67 1,67 2,49 3,29 3,29 3,16

Water flow (m3/h) - - - - 6,31 7,09 8,11 9,12 10,03 11,39 12,93 15,91 18,29 20,32 22,61

Pressure loss of hydronic circuit at chiller mode (kPa) - - - - 55,23 66,71 62,31 78,87 55,00 68,66 63,26 77,00 76,59 57,58 68,34

Pressure loss of hydronic circuit at freecooling mode (kPa) - - - - 88,37 106,74 99,70 126,20 88,00 109,86 101,22 123,19 122,54 92,13 109,35

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 90,00 93,70 136,57 177,77 232,54 260,06 295,63 330,26 361,12 406,64 456,95 551,15 623,53 683,00 748,05

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 180,00 187,40 273,13 355,54 465,08 520,13 591,26 660,53 722,24 813,28 913,89 1102,31 1247,06 1366,00 1496,10

technicAl sheets sb-n

Page 13: SB - HVACR

13

®

www.coldinnovation.it

Size 10 15 21 28 36 41 48 52 57 65 74 89 105 116 129

Cooling capacity (kW) 10,18 14,43 21,18 27,76 36,67 41,21 47,15 53,02 58,31 66,25 75,20 92,51 106,36 118,13 131,47

Power input (kW) 3,14 4,54 6,95 9,24 11,73 13,61 16,93 19,24 22,56 25,00 29,28 32,18 38,71 45,36 50,35

Maximum power input at limit conditions (kW) 3,55 5,28 7,92 10,74 13,46 15,75 19,11 21,90 26,11 29,05 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 45,00 45,00 44,50 44,50 44,00 42,00 42,50 40,50 44,00 43,00 41,20 41,50

Water flow (m3/h) 1,75 2,48 3,64 4,78 6,31 7,09 8,11 9,12 10,03 11,39 12,93 15,91 18,29 20,32 22,61

Pressure loss of hydronic circuit (kPa) 17,61 22,24 28,98 33,99 40,91 49,41 46,16 58,43 40,74 50,86 46,86 57,03 56,73 42,65 50,62

EER (kW/kW) 3,24 3,18 3,05 3,01 3,13 3,03 2,78 2,76 2,58 2,65 2,57 2,87 2,75 2,60 2,61

ESEER (kW/kW) 4,30 4,27 4,21 4,18 4,25 4,19 4,04 4,02 3,89 3,95 3,88 4,10 4,02 3,91 3,92

Sound pressure at 10m (dB(A)) 39,20 39,20 41,53 41,73 40,77 44,13 47,33 47,38 47,36 47,33 49,14 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 8,87 13,57 18,04 22,91 26,58 33,06 37,58 44,06 48,82 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 16,57 21,15 26,15 33,84 38,84 47,17 52,17 59,17 66,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 63,60 85,60 105,20 149,20 161,60 183,60 164,60 169,60 185,60 192,60 219,60 258,20 271,20 316,20 329,20

Buffer tank capacity (lt) 25,00 25,00 25,00 25,00 180,00 180,00 180,00 180,00 180,00 180,00 180,00 330,00 330,00 330,00 330,00

Maximum operating pressure PS (bar) 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00

Power input of low pressure pump (kW) 0,09 0,11 0,16 0,20 0,59 0,65 0,74 0,84 0,92 1,02 1,13 1,31 1,43 1,94 2,07

Amperage of low pressure pump (A) 0,55 0,71 1,00 1,24 1,21 1,35 1,52 1,74 1,89 2,11 2,33 2,70 2,94 4,01 4,27

Available pressure with low prevalence hydronic kit (kPa) 92,39 77,76 66,02 56,01 93,37 83,40 84,51 98,03 113,62 100,09 99,86 80,38 72,22 128,31 109,93

Power input of high pressure pump (A) - - - - 0,72 0,80 0,91 1,10 1,21 1,35 1,51 2,05 2,12 2,26 2,51

Amperage of high pressure pump (A) - - - - 1,49 1,66 1,88 2,28 2,49 2,79 3,12 4,23 4,37 4,66 5,19

Available pressure with high prevalence hydronic kit (kPa) - - - - 173,12 163,22 164,46 200,08 215,74 202,35 202,31 180,38 172,22 218,31 199,93

FREE COOLING

Cooling capacity (kW) - - - - 33,74 37,91 43,38 48,78 53,65 60,95 69,18 85,11 97,85 108,68 120,95

Power input (kW) - - - - 1,24 1,29 1,76 1,76 1,76 1,67 1,67 2,49 3,29 3,29 3,16

Water flow (m3/h) - - - - 6,31 7,09 8,11 9,12 10,03 11,39 12,93 15,91 18,29 20,32 22,61

Pressure loss of hydronic circuit at chiller mode (kPa) - - - - 55,23 66,71 62,31 78,87 55,00 68,66 63,26 77,00 76,59 57,58 68,34

Pressure loss of hydronic circuit at freecooling mode (kPa) - - - - 88,37 106,74 99,70 126,20 88,00 109,86 101,22 123,19 122,54 92,13 109,35

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 90,00 93,70 136,57 177,77 232,54 260,06 295,63 330,26 361,12 406,64 456,95 551,15 623,53 683,00 748,05

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 180,00 187,40 273,13 355,54 465,08 520,13 591,26 660,53 722,24 813,28 913,89 1102,31 1247,06 1366,00 1496,10

bAsic version

Technical specificaTions aT following condiTions cooling: waTer (in/ouT) 12/7°c; ouTdoor air 35°c; evaporaTing 5°c for condensing uniT

heaTing for heaTpump chiller: waTer (in/ouT) 40/45°c; ouTdoor air 7°c b.s./ur 87%;condensing 50°c for heaTpump condensing uniT

free cooling: waTer (in/ouT) 15/10°c, ouTdoor air 2°c; power supply: 400v - 3 - 50hz

sound pressure on free field reflecTing surface (direcTiviTy facT. 2) according To iso 3744

Page 14: SB - HVACR

14

®

www.coldinnovation.it

Size 10 15 21 28 36 41 48 52 57 65 74 89 105 116 129

Cooling capacity (kW) 9,92 14,05 20,63 27,05 35,72 40,15 45,93 51,65 56,81 64,53 73,25 90,12 103,61 115,08 128,07

Power input (kW) 3,14 4,54 6,95 9,24 11,73 13,61 16,93 19,24 22,56 25,00 29,28 32,18 38,71 45,36 50,35

Maximum power input at limit conditions (kW) 3,55 5,28 7,92 10,74 13,46 15,75 19,11 21,90 26,11 29,05 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 44,00 45,00 43,50 43,50 43,00 41,00 41,50 39,50 43,00 42,00 40,20 40,50

Water flow (m3/h) 1,71 2,42 3,55 4,65 6,14 6,91 7,90 8,88 9,77 11,10 12,60 15,50 17,82 19,79 22,03

Pressure loss of hydronic circuit (kPa) 37,58 36,38 62,29 57,45 67,10 69,48 40,18 49,92 51,62 66,31 46,75 61,81 68,40 74,10 65,63

EER (kW/kW) 3,16 3,09 2,97 2,93 3,05 2,95 2,71 2,68 2,52 2,58 2,50 2,80 2,68 2,54 2,54

ESEER (kW/kW) 4,26 4,23 4,16 4,14 4,20 4,15 3,99 3,97 3,84 3,89 3,83 4,05 3,97 3,86 3,86

HEAT PUMP

Heating capacity (kW) 11,2 15,9 23,3 30,6 40,4 45,4 51,9 58,4 64,2 72,9 82,8 101,8 117,1 130,0 144,7

Power input (heating mode) (kW) 3,4 4,9 7,1 9,6 12,7 14,4 16,5 18,8 21,0 24,8 29,3 33,5 38,2 43,4 50,1

Water flow (heating mode) (m3/h) 1,9 2,7 4,0 5,3 6,9 7,8 8,9 10,0 11,0 12,5 14,2 17,5 20,1 22,4 24,9

Pressure loss of hydronic circuit (kPa) 46 44 75 70 81 84 49 60 63 80 57 75 83 90 80

Minimum operating outdoor air temperature in heating mode (°C) -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0

COP (kW/kW) 3,33 3,22 3,30 3,20 3,18 3,14 3,15 3,11 3,05 2,94 2,83 3,04 3,06 3,00 2,89

Sound pressure at 10m (dB(A)) 39,20 39,20 41,53 41,73 40,77 44,13 47,33 47,38 47,36 47,33 49,14 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 8,87 13,57 18,04 22,91 26,58 33,06 37,58 44,06 48,82 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 16,57 21,15 26,15 33,84 38,84 47,17 52,17 59,17 66,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 3,60 3,60 105,20 149,20 161,60 183,60 164,60 169,60 185,60 192,60 219,60 258,20 271,20 316,20 329,20

Buffer tank capacity (lt) 25,00 25,00 25,00 25,00 180,00 180,00 180,00 180,00 180,00 180,00 180,00 330,00 330,00 330,00 330,00

Maximum operating pressure PS (bar) 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00

Power input of low pressure pump (kW) 0,09 0,11 0,16 0,20 0,59 0,65 0,74 0,84 0,92 1,02 1,13 1,31 1,40 1,56 1,73

Amperage of low pressure pump (A) 0,55 0,71 1,00 1,24 1,21 1,35 1,52 1,74 1,89 2,11 2,33 2,70 2,90 3,22 3,58

Available pressure with low prevalence hydronic kit (kPa) 92,39 77,76 66,02 56,01 93,37 83,40 84,51 98,03 113,62 100,09 99,86 80,38 102,30 110,78 111,06

Power input of high pressure pump (A) - - - - 0,72 0,80 0,91 1,10 1,21 1,35 1,51 0,72 2,23 2,47 2,75

Amperage of high pressure pump (A) - - - - 1,49 1,66 1,88 2,28 2,49 2,79 3,12 1,48 4,60 5,11 5,68

Available pressure with high prevalence hydronic kit (kPa) - - - - 173,12 163,22 164,46 200,08 215,74 202,35 202,31 180,38 202,30 210,78 211,06

FREE COOLING

Cooling capacity (kW) 9,12 12,93 18,98 24,88 32,86 36,94 42,26 47,52 52,26 59,37 67,39 82,91 95,32 105,87 117,83

Power input (kW) 0,49 0,49 0,93 0,93 1,24 1,29 1,76 1,76 1,76 1,67 1,67 2,49 3,29 3,29 3,16

Water flow (m3/h) 1,71 2,42 3,55 4,65 6,14 6,91 7,90 8,88 9,77 11,10 12,60 15,50 17,82 19,79 22,03

Pressure loss of hydronic circuit at chiller mode (kPa) 50,73 49,11 84,10 77,56 90,59 93,80 54,25 67,40 69,69 89,51 63,11 83,44 92,35 100,03 88,60

Pressure loss of hydronic circuit at freecooling mode (kPa) 81,17 78,57 134,55 124,09 144,94 150,08 86,79 107,83 111,50 143,22 100,98 133,50 147,75 160,05 141,77

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 97,20 101,19 147,49 191,99 251,14 280,87 319,28 356,69 390,01 439,17 493,50 595,25 673,41 737,64 807,90

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 194,40 202,39 294,99 383,98 502,29 561,74 638,56 713,37 780,02 878,34 987,01 1190,49 1346,83 1475,28 1615,79

technicAl sheets sb-h

Page 15: SB - HVACR

15

®

www.coldinnovation.it

Size 10 15 21 28 36 41 48 52 57 65 74 89 105 116 129

Cooling capacity (kW) 9,92 14,05 20,63 27,05 35,72 40,15 45,93 51,65 56,81 64,53 73,25 90,12 103,61 115,08 128,07

Power input (kW) 3,14 4,54 6,95 9,24 11,73 13,61 16,93 19,24 22,56 25,00 29,28 32,18 38,71 45,36 50,35

Maximum power input at limit conditions (kW) 3,55 5,28 7,92 10,74 13,46 15,75 19,11 21,90 26,11 29,05 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 44,00 45,00 43,50 43,50 43,00 41,00 41,50 39,50 43,00 42,00 40,20 40,50

Water flow (m3/h) 1,71 2,42 3,55 4,65 6,14 6,91 7,90 8,88 9,77 11,10 12,60 15,50 17,82 19,79 22,03

Pressure loss of hydronic circuit (kPa) 37,58 36,38 62,29 57,45 67,10 69,48 40,18 49,92 51,62 66,31 46,75 61,81 68,40 74,10 65,63

EER (kW/kW) 3,16 3,09 2,97 2,93 3,05 2,95 2,71 2,68 2,52 2,58 2,50 2,80 2,68 2,54 2,54

ESEER (kW/kW) 4,26 4,23 4,16 4,14 4,20 4,15 3,99 3,97 3,84 3,89 3,83 4,05 3,97 3,86 3,86

HEAT PUMP

Heating capacity (kW) 11,2 15,9 23,3 30,6 40,4 45,4 51,9 58,4 64,2 72,9 82,8 101,8 117,1 130,0 144,7

Power input (heating mode) (kW) 3,4 4,9 7,1 9,6 12,7 14,4 16,5 18,8 21,0 24,8 29,3 33,5 38,2 43,4 50,1

Water flow (heating mode) (m3/h) 1,9 2,7 4,0 5,3 6,9 7,8 8,9 10,0 11,0 12,5 14,2 17,5 20,1 22,4 24,9

Pressure loss of hydronic circuit (kPa) 46 44 75 70 81 84 49 60 63 80 57 75 83 90 80

Minimum operating outdoor air temperature in heating mode (°C) -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0

COP (kW/kW) 3,33 3,22 3,30 3,20 3,18 3,14 3,15 3,11 3,05 2,94 2,83 3,04 3,06 3,00 2,89

Sound pressure at 10m (dB(A)) 39,20 39,20 41,53 41,73 40,77 44,13 47,33 47,38 47,36 47,33 49,14 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 8,87 13,57 18,04 22,91 26,58 33,06 37,58 44,06 48,82 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 16,57 21,15 26,15 33,84 38,84 47,17 52,17 59,17 66,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 3,60 3,60 105,20 149,20 161,60 183,60 164,60 169,60 185,60 192,60 219,60 258,20 271,20 316,20 329,20

Buffer tank capacity (lt) 25,00 25,00 25,00 25,00 180,00 180,00 180,00 180,00 180,00 180,00 180,00 330,00 330,00 330,00 330,00

Maximum operating pressure PS (bar) 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00 6,00

Power input of low pressure pump (kW) 0,09 0,11 0,16 0,20 0,59 0,65 0,74 0,84 0,92 1,02 1,13 1,31 1,40 1,56 1,73

Amperage of low pressure pump (A) 0,55 0,71 1,00 1,24 1,21 1,35 1,52 1,74 1,89 2,11 2,33 2,70 2,90 3,22 3,58

Available pressure with low prevalence hydronic kit (kPa) 92,39 77,76 66,02 56,01 93,37 83,40 84,51 98,03 113,62 100,09 99,86 80,38 102,30 110,78 111,06

Power input of high pressure pump (A) - - - - 0,72 0,80 0,91 1,10 1,21 1,35 1,51 0,72 2,23 2,47 2,75

Amperage of high pressure pump (A) - - - - 1,49 1,66 1,88 2,28 2,49 2,79 3,12 1,48 4,60 5,11 5,68

Available pressure with high prevalence hydronic kit (kPa) - - - - 173,12 163,22 164,46 200,08 215,74 202,35 202,31 180,38 202,30 210,78 211,06

FREE COOLING

Cooling capacity (kW) 9,12 12,93 18,98 24,88 32,86 36,94 42,26 47,52 52,26 59,37 67,39 82,91 95,32 105,87 117,83

Power input (kW) 0,49 0,49 0,93 0,93 1,24 1,29 1,76 1,76 1,76 1,67 1,67 2,49 3,29 3,29 3,16

Water flow (m3/h) 1,71 2,42 3,55 4,65 6,14 6,91 7,90 8,88 9,77 11,10 12,60 15,50 17,82 19,79 22,03

Pressure loss of hydronic circuit at chiller mode (kPa) 50,73 49,11 84,10 77,56 90,59 93,80 54,25 67,40 69,69 89,51 63,11 83,44 92,35 100,03 88,60

Pressure loss of hydronic circuit at freecooling mode (kPa) 81,17 78,57 134,55 124,09 144,94 150,08 86,79 107,83 111,50 143,22 100,98 133,50 147,75 160,05 141,77

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 97,20 101,19 147,49 191,99 251,14 280,87 319,28 356,69 390,01 439,17 493,50 595,25 673,41 737,64 807,90

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 194,40 202,39 294,99 383,98 502,29 561,74 638,56 713,37 780,02 878,34 987,01 1190,49 1346,83 1475,28 1615,79

heAt pump

Technical specificaTions aT following condiTions cooling: waTer (in/ouT) 12/7°c; ouTdoor air 35°c; evaporaTing 5°c for condensing uniT

heaTing for heaTpump chiller: waTer (in/ouT) 40/45°c; ouTdoor air 7°c b.s./ur 87%;condensing 50°c for heaTpump condensing uniT

free cooling: waTer (in/ouT) 15/10°c, ouTdoor air 2°c; power supply: 400v - 3 - 50hz

sound pressure on free field reflecTing surface (direcTiviTy facT. 2) according To iso 3744

Page 16: SB - HVACR

16

®

www.coldinnovation.it

Size 10 13 15 18 21 25 28 32 36 41 45 48 52 57 65 74 83 89 105 116 129

Cooling capacity (kW) 10,18 12,73 14,43 17,41 21,18 24,47 27,76 32,67 36,67 41,21 45,40 47,74 54,08 59,77 68,07 76,14 82,50 94,82 107,69 119,02 133,77

Power input (kW) 3,11 3,79 4,47 5,59 6,81 7,92 9,08 11,02 11,53 13,37 15,04 16,60 18,84 22,21 24,57 28,85 26,49 31,65 38,17 44,84 49,72

Maximum power input at limit conditions (kW) 3,55 4,41 5,28 6,41 7,92 9,33 10,74 12,71 13,46 15,75 17,01 19,11 21,90 26,11 29,05 34,40 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 45,00 45,00 45,00 45,00 44,00 45,00 44,50 45,00 44,00 43,20 41,00 41,40 40,00 44,50 43,00 42,50 40,90 40,80

EER (kW/kW) 3,28 3,36 3,23 3,11 3,11 3,09 3,06 2,96 3,18 3,08 3,02 2,88 2,87 2,69 2,77 2,64 3,11 3,00 2,82 2,65 2,69

ESEER (kW/kW) 4,32 4,35 4,30 4,24 4,24 4,23 4,21 4,16 4,27 4,22 4,19 4,10 4,10 3,98 4,03 3,94 4,24 4,18 4,07 3,95 3,98

Sound pressure at 10m (dB(A)) 39,20 39,20 39,20 40,37 41,53 41,73 41,73 41,73 40,77 44,13 47,33 47,33 47,38 47,36 47,33 49,14 48,07 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 5500,00 5500,00 10500,00 10500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 7,50 8,87 10,56 13,57 15,80 18,04 20,92 22,91 26,58 43,64 33,06 37,58 44,06 48,82 57,18 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 15,57 16,57 19,72 21,15 23,65 26,15 30,33 33,84 38,84 38,84 47,17 52,17 59,17 66,17 76,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 63,60 74,60 85,60 101,18 105,20 127,20 149,20 171,92 161,60 183,60 101,60 164,60 169,60 185,60 192,60 219,60 223,20 258,20 271,20 316,20 329,20

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 85,50 87,26 89,01 93,46 129,74 136,23 168,88 177,32 220,91 247,06 280,85 280,85 313,75 343,06 386,31 434,10 523,60 523,60 592,36 648,85 710,65

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 171,00 174,51 178,03 186,93 259,48 272,45 337,76 354,65 441,83 494,12 561,70 561,70 627,50 686,13 772,62 868,20 1047,19 1047,19 1184,71 1297,70 1421,30

technicAl sheets sb-c

Page 17: SB - HVACR

17

®

www.coldinnovation.it

Size 10 13 15 18 21 25 28 32 36 41 45 48 52 57 65 74 83 89 105 116 129

Cooling capacity (kW) 10,18 12,73 14,43 17,41 21,18 24,47 27,76 32,67 36,67 41,21 45,40 47,74 54,08 59,77 68,07 76,14 82,50 94,82 107,69 119,02 133,77

Power input (kW) 3,11 3,79 4,47 5,59 6,81 7,92 9,08 11,02 11,53 13,37 15,04 16,60 18,84 22,21 24,57 28,85 26,49 31,65 38,17 44,84 49,72

Maximum power input at limit conditions (kW) 3,55 4,41 5,28 6,41 7,92 9,33 10,74 12,71 13,46 15,75 17,01 19,11 21,90 26,11 29,05 34,40 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 45,00 45,00 45,00 45,00 44,00 45,00 44,50 45,00 44,00 43,20 41,00 41,40 40,00 44,50 43,00 42,50 40,90 40,80

EER (kW/kW) 3,28 3,36 3,23 3,11 3,11 3,09 3,06 2,96 3,18 3,08 3,02 2,88 2,87 2,69 2,77 2,64 3,11 3,00 2,82 2,65 2,69

ESEER (kW/kW) 4,32 4,35 4,30 4,24 4,24 4,23 4,21 4,16 4,27 4,22 4,19 4,10 4,10 3,98 4,03 3,94 4,24 4,18 4,07 3,95 3,98

Sound pressure at 10m (dB(A)) 39,20 39,20 39,20 40,37 41,53 41,73 41,73 41,73 40,77 44,13 47,33 47,33 47,38 47,36 47,33 49,14 48,07 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 5500,00 5500,00 10500,00 10500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 7,50 8,87 10,56 13,57 15,80 18,04 20,92 22,91 26,58 43,64 33,06 37,58 44,06 48,82 57,18 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 15,57 16,57 19,72 21,15 23,65 26,15 30,33 33,84 38,84 38,84 47,17 52,17 59,17 66,17 76,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 63,60 74,60 85,60 101,18 105,20 127,20 149,20 171,92 161,60 183,60 101,60 164,60 169,60 185,60 192,60 219,60 223,20 258,20 271,20 316,20 329,20

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 85,50 87,26 89,01 93,46 129,74 136,23 168,88 177,32 220,91 247,06 280,85 280,85 313,75 343,06 386,31 434,10 523,60 523,60 592,36 648,85 710,65

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 171,00 174,51 178,03 186,93 259,48 272,45 337,76 354,65 441,83 494,12 561,70 561,70 627,50 686,13 772,62 868,20 1047,19 1047,19 1184,71 1297,70 1421,30

condensing unit

Technical specificaTions aT following condiTions cooling: waTer (in/ouT) 12/7°c; ouTdoor air 35°c; evaporaTing 5°c for condensing uniT

heaTing for heaTpump chiller: waTer (in/ouT) 40/45°c; ouTdoor air 7°c b.s./ur 87%;condensing 50°c for heaTpump condensing uniT

free cooling: waTer (in/ouT) 15/10°c, ouTdoor air 2°c; power supply: 400v - 3 - 50hz

sound pressure on free field reflecTing surface (direcTiviTy facT. 2) according To iso 3744

Page 18: SB - HVACR

18

®

www.coldinnovation.it

Size 10 13 15 18 21 25 28 32 36 41 45 48 52 57 65 74 83 89 105 116 129

Cooling capacity (kW) 9,78 12,23 13,85 16,72 20,34 23,50 26,66 31,37 35,21 39,58 43,60 45,85 51,93 57,40 65,37 73,11 79,22 91,06 103,41 114,29 128,46

Power input (kW) 3,11 3,79 4,47 5,59 6,81 7,92 9,08 11,02 11,53 13,37 15,04 16,60 18,84 22,21 24,57 28,85 26,49 31,65 38,17 44,84 49,72

Maximum power input at limit conditions (kW) 3,55 4,41 5,28 6,41 7,92 9,33 10,74 12,71 13,46 15,75 17,01 19,11 21,90 26,11 29,05 34,40 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 44,50 45,00 44,75 44,00 43,00 45,00 43,50 44,00 43,00 42,20 40,00 40,40 39,00 43,50 42,00 41,50 39,90 39,80

EER (kW/kW) 3,15 3,23 3,10 2,99 2,99 2,97 2,94 2,85 3,05 2,96 2,90 2,76 2,76 2,58 2,66 2,53 2,99 2,88 2,71 2,55 2,58

ESEER (kW/kW) 4,26 4,30 4,23 4,17 4,17 4,16 4,14 4,08 4,21 4,16 4,12 4,03 4,02 3,89 3,95 3,85 4,17 4,10 3,99 3,87 3,89

HEAT PUMP

Heating capacity (kW) 11,05 13,82 15,66 18,90 22,98 26,56 30,13 35,45 39,79 44,72 49,26 51,81 58,68 64,86 73,86 82,62 89,52 102,90 116,86 129,15 145,16

Power input (heating mode) (kW) 3,07 3,98 4,61 5,82 6,48 7,67 8,91 10,90 11,72 13,43 14,19 15,10 17,55 19,95 23,86 27,83 27,08 32,38 35,44 40,34 47,54

Minimum operating outdoor -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00

COP (kW/kW) 3,60 3,48 3,39 3,25 3,55 3,46 3,38 3,25 3,39 3,33 3,47 3,43 3,34 3,25 3,10 2,97 3,31 3,18 3,30 3,20 3,05

Sound pressure at 10m (dB(A)) 39,20 39,20 39,20 40,37 41,53 41,73 41,73 41,73 40,77 44,13 47,33 47,33 47,38 47,36 47,33 49,14 48,07 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 5500,00 5500,00 10500,00 10500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 7,50 8,87 10,56 13,57 15,80 18,04 20,92 22,91 26,58 43,64 33,06 37,58 44,06 48,82 57,18 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 15,57 16,57 19,72 21,15 23,65 26,15 30,33 33,84 38,84 38,84 47,17 52,17 59,17 66,17 76,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 63,60 74,60 85,60 101,18 105,20 127,20 149,20 171,92 161,60 183,60 101,60 164,60 169,60 185,60 192,60 219,60 223,20 258,20 271,20 316,20 329,20

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 85,50 87,26 89,01 93,46 129,74 136,23 168,88 177,32 220,91 247,06 280,85 280,85 313,75 343,06 386,31 434,10 523,60 523,60 592,36 648,85 710,65

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 171,00 174,51 178,03 186,93 259,48 272,45 337,76 354,65 441,83 494,12 561,70 561,70 627,50 686,13 772,62 868,20 1047,19 1047,19 1184,71 1297,70 1421,30

technicAl sheets sb-ch

Page 19: SB - HVACR

19

®

www.coldinnovation.it

Size 10 13 15 18 21 25 28 32 36 41 45 48 52 57 65 74 83 89 105 116 129

Cooling capacity (kW) 9,78 12,23 13,85 16,72 20,34 23,50 26,66 31,37 35,21 39,58 43,60 45,85 51,93 57,40 65,37 73,11 79,22 91,06 103,41 114,29 128,46

Power input (kW) 3,11 3,79 4,47 5,59 6,81 7,92 9,08 11,02 11,53 13,37 15,04 16,60 18,84 22,21 24,57 28,85 26,49 31,65 38,17 44,84 49,72

Maximum power input at limit conditions (kW) 3,55 4,41 5,28 6,41 7,92 9,33 10,74 12,71 13,46 15,75 17,01 19,11 21,90 26,11 29,05 34,40 34,40 37,63 44,42 52,75 58,83

Maximum outdoor air temperature (°C) 45,00 45,00 45,00 44,50 45,00 44,75 44,00 43,00 45,00 43,50 44,00 43,00 42,20 40,00 40,40 39,00 43,50 42,00 41,50 39,90 39,80

EER (kW/kW) 3,15 3,23 3,10 2,99 2,99 2,97 2,94 2,85 3,05 2,96 2,90 2,76 2,76 2,58 2,66 2,53 2,99 2,88 2,71 2,55 2,58

ESEER (kW/kW) 4,26 4,30 4,23 4,17 4,17 4,16 4,14 4,08 4,21 4,16 4,12 4,03 4,02 3,89 3,95 3,85 4,17 4,10 3,99 3,87 3,89

HEAT PUMP

Heating capacity (kW) 11,05 13,82 15,66 18,90 22,98 26,56 30,13 35,45 39,79 44,72 49,26 51,81 58,68 64,86 73,86 82,62 89,52 102,90 116,86 129,15 145,16

Power input (heating mode) (kW) 3,07 3,98 4,61 5,82 6,48 7,67 8,91 10,90 11,72 13,43 14,19 15,10 17,55 19,95 23,86 27,83 27,08 32,38 35,44 40,34 47,54

Minimum operating outdoor -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00 -10,00

COP (kW/kW) 3,60 3,48 3,39 3,25 3,55 3,46 3,38 3,25 3,39 3,33 3,47 3,43 3,34 3,25 3,10 2,97 3,31 3,18 3,30 3,20 3,05

Sound pressure at 10m (dB(A)) 39,20 39,20 39,20 40,37 41,53 41,73 41,73 41,73 40,77 44,13 47,33 47,33 47,38 47,36 47,33 49,14 48,07 48,07 51,96 51,87 51,78

Total air flow (m3/h) 5500,00 5500,00 5500,00 5500,00 10500,00 10500,00 10500,00 10500,00 14000,00 14500,00 19750,00 19750,00 19750,00 19750,00 18750,00 18750,00 28000,00 28000,00 37000,00 37000,00 35500,00

Number of compressors (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00 2,00

Number of circuits (n.) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Rated current at nominal conditions (A) 6,13 7,50 8,87 10,56 13,57 15,80 18,04 20,92 22,91 26,58 43,64 33,06 37,58 44,06 48,82 57,18 57,18 62,84 75,59 88,58 98,32

Maximum current at full load (A) 14,57 15,57 16,57 19,72 21,15 23,65 26,15 30,33 33,84 38,84 38,84 47,17 52,17 59,17 66,17 76,17 76,17 89,68 105,35 118,35 131,35

Maximum starting current (A) 63,60 74,60 85,60 101,18 105,20 127,20 149,20 171,92 161,60 183,60 101,60 164,60 169,60 185,60 192,60 219,60 223,20 258,20 271,20 316,20 329,20

Number of antivibrating supports 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00 4,00

Load capacity required to single antivibrating support (daN) 85,50 87,26 89,01 93,46 129,74 136,23 168,88 177,32 220,91 247,06 280,85 280,85 313,75 343,06 386,31 434,10 523,60 523,60 592,36 648,85 710,65

Total weight with no water and excluded any hydronic kit and buffer tank (kg) 171,00 174,51 178,03 186,93 259,48 272,45 337,76 354,65 441,83 494,12 561,70 561,70 627,50 686,13 772,62 868,20 1047,19 1047,19 1184,71 1297,70 1421,30

heAt pump - condensing unit

Technical specificaTions aT following condiTions cooling: waTer (in/ouT) 12/7°c; ouTdoor air 35°c; evaporaTing 5°c for condensing uniT

heaTing for heaTpump chiller: waTer (in/ouT) 40/45°c; ouTdoor air 7°c b.s./ur 87%;condensing 50°c for heaTpump condensing uniT

free cooling: waTer (in/ouT) 15/10°c, ouTdoor air 2°c; power supply: 400v - 3 - 50hz

sound pressure on free field reflecTing surface (direcTiviTy facT. 2) according To iso 3744

Page 20: SB - HVACR

20

®

www.coldinnovation.it

SB-N

Outlet water temperature (°C)

5 6 7 8 10 15 20

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

32

10 10,1 2,8 10,4 2,6 10,7 2,8 11,0 2,8 11,7 2,8 13,3 2,9 13,6 2,9

15 14,3 4,1 14,7 4,1 15,2 4,1 15,6 4,2 16,5 4,2 18,8 4,3 19,3 4,3

21 20,9 6,2 21,6 6,2 22,3 6,2 22,9 6,2 24,3 6,3 27,6 6,4 28,3 6,5

28 27,4 8,4 28,3 8,4 29,2 8,4 30,1 8,5 31,8 8,5 36,2 8,7 37,1 8,8

36 36,2 10,5 37,4 10,5 38,5 9,9 39,7 10,6 42,0 10,7 47,8 10,9 48,9 11,0

41 40,7 12,3 42,0 12,3 43,3 11,6 44,6 12,4 47,2 12,5 53,7 12,7 55,0 12,8

48 46,6 14,9 48,1 14,9 49,6 14,1 51,0 15,0 54,0 15,1 61,5 15,4 62,9 15,6

52 52,4 17,1 54,1 17,1 55,7 16,2 57,4 17,2 60,7 17,4 69,1 17,7 70,8 17,9

57 57,6 20,3 59,4 20,4 61,3 19,3 63,1 20,5 66,8 20,7 76,0 21,1 77,8 21,3

65 65,4 22,6 67,5 22,7 69,6 21,5 71,7 22,9 75,9 23,0 86,3 23,4 88,4 23,7

74 74,3 26,8 76,7 26,9 79,0 25,4 81,4 27,1 86,1 27,3 98,0 27,7 100,4 28,0

89 91,4 29,3 94,3 29,4 97,2 27,8 100,1 29,6 106,0 29,8 120,6 30,4 123,5 30,7

105 105,1 34,6 108,4 34,7 111,8 32,8 115,1 35,0 121,8 35,2 138,6 35,8 142,0 36,2

116 116,7 41,1 120,4 41,2 124,2 39,0 127,9 39,3 135,3 39,9 154,0 41,4 157,7 42,3

129 129,9 45,8 134,0 46,0 138,2 43,5 142,3 43,8 150,6 44,5 171,3 46,2 175,5 47,2

Out

door

air

tem

pera

ture

(°C

)

35

10 9,6 2,9 9,9 2,9 10,2 2,9 10,5 2,9 11,1 3,0 12,6 3,0 12,9 3,0

15 13,6 4,3 14,0 4,3 14,4 4,4 14,9 4,4 15,7 4,4 17,9 4,5 18,3 4,5

21 19,9 6,5 20,5 6,5 21,2 6,5 21,8 6,6 23,1 6,6 26,3 6,7 26,9 6,8

28 26,1 8,8 26,9 8,8 27,8 8,9 28,6 8,9 30,3 9,0 34,4 9,1 35,3 9,2

36 34,5 11,0 35,6 11,1 36,7 11,1 37,8 11,2 40,0 11,2 45,5 11,4 46,6 11,6

41 38,7 12,9 40,0 13,0 41,2 13,0 42,4 13,1 44,9 13,2 51,1 13,4 52,3 13,5

48 44,3 15,7 45,7 15,7 47,2 15,8 48,6 15,9 51,4 16,0 58,5 16,2 59,9 16,4

52 49,8 18,0 51,4 18,0 53,0 18,1 54,6 18,2 57,8 18,3 65,7 18,6 67,3 18,8

57 54,8 21,4 56,6 21,5 58,3 21,6 60,1 21,7 63,6 21,8 72,3 22,2 74,1 22,4

65 62,3 23,8 64,3 23,9 66,2 24,0 68,2 24,1 72,2 24,3 82,1 24,7 84,1 25,0

74 70,7 28,2 72,9 28,3 75,2 28,4 77,5 28,5 82,0 28,7 93,2 29,2 95,5 29,6

89 87,0 30,9 89,7 31,0 92,5 31,1 95,3 31,2 100,8 31,4 114,7 32,0 117,5 32,3

105 100,0 36,4 103,2 36,6 106,4 36,7 109,5 37,0 115,9 37,6 131,9 39,0 135,1 39,9

116 111,0 43,3 114,6 43,4 118,1 43,6 121,7 43,9 128,8 44,6 146,5 46,3 150,0 47,3

129 123,6 48,3 127,5 48,4 131,5 48,6 135,4 49,0 143,3 49,7 163,0 51,6 167,0 52,8

cc = cooling capaciTy ; pi = power inpuT;correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

cooling main value;

performAnces

Page 21: SB - HVACR

21

®

www.coldinnovation.it

performAnces

SB-N

Outlet water temperature (°C)

5 6 7 8 10 15 20

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

38

10 9,1 3,2 9,4 3,2 9,7 3,1 10,0 3,1 10,5 3,1 12,0 3,2

15 12,9 4,8 13,3 4,6 13,7 4,6 14,1 4,6 14,9 4,6 17,0 4,7

21 18,9 7,2 19,5 6,9 20,1 6,9 20,7 6,9 21,9 7,0 24,9 7,1

28 24,8 9,7 25,6 9,3 26,3 9,3 27,1 9,4 28,7 9,4 32,7 9,6

36 32,7 12,2 33,8 11,6 34,8 12,4 35,8 11,7 37,9 11,8 43,2 12,0

41 36,8 14,2 37,9 13,6 39,1 14,5 40,3 13,7 42,6 13,8 48,5 14,1

48 42,1 17,3 43,4 16,5 44,7 17,5 46,1 16,7 48,8 16,8 55,5 17,1

52 47,3 19,8 48,8 18,9 50,3 20,1 51,8 19,1 54,8 19,2 62,4 19,6

57 52,0 23,6 53,7 22,6 55,3 24,0 57,0 22,8 60,3 22,9 68,6 23,3

65 59,1 26,3 61,0 25,1 62,9 26,7 64,8 25,3 68,5 25,5 78,0 26,0

74 67,1 31,1 69,2 29,8 71,4 31,6 73,5 30,0 77,8 30,2 88,5 30,7

89 82,5 34,0 85,2 32,6 87,8 34,5 90,4 32,8 95,7 33,0 108,9 33,6

105 94,9 40,1 97,9 38,4 100,9 40,8 104,0 41,1 110,0 41,7 125,2 43,3

116 105,4 47,7 108,7 45,6 112,1 48,4 115,5 48,8 122,2 49,5 139,0 51,4

129 117,3 53,2 121,0 50,9 124,8 54,0 128,5 54,4 136,0 55,2 154,7 57,4

Out

door

air

tem

pera

ture

(°C

)

40

10 8,8 3,4 9,0 3,5 9,3 3,2 9,6 3,2 10,2 3,2

15 12,4 5,1 12,8 4,7 13,2 4,7 13,6 4,7 14,4 4,8

21 18,2 7,7 18,8 7,1 19,4 7,1 20,0 7,1 21,1 7,2

28 23,9 10,4 24,6 9,6 25,4 9,6 26,2 9,7 27,7 9,7

36 31,5 13,0 32,5 12,0 33,6 13,2 34,6 12,1 36,6 12,2

41 35,4 15,2 36,6 14,1 37,7 15,5 38,8 14,2 41,1 14,3

48 40,6 18,5 41,9 17,1 43,1 18,7 44,4 17,2 47,0 17,3

52 45,6 21,2 47,1 19,5 48,5 21,5 50,0 19,7 52,9 19,8

57 50,2 25,2 51,8 23,3 53,4 25,6 55,0 23,5 58,2 23,6

65 57,0 28,1 58,8 25,9 60,6 28,5 62,4 26,1 66,1 26,3

74 64,7 33,2 66,7 30,7 68,8 33,7 70,9 30,9 75,0 31,1

89 79,6 36,3 82,1 33,6 84,6 36,9 87,2 37,2 92,3 34,1

105 91,5 42,9 94,4 39,7 97,3 43,6 100,2 43,9 106,1 44,6

116 101,6 50,9 104,8 47,1 108,1 51,7 111,3 52,1 117,8 52,9

129 113,1 56,8 116,7 52,5 120,3 57,7 123,9 58,1 131,1 59,0

cc = cooling capaciTy ; pi = power inpuT;correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

cooling main value;

Page 22: SB - HVACR

22

®

www.coldinnovation.it

SB-Cevaporating temperature (°C)

0 2 3,5 5 6,5 8 10

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi (kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

32

10 9,1 2,9 9,7 2,7 10,2 2,9 10,7 2,9 11,2 3,0 11,7 3,0 12,3 3,0

13 11,4 3,5 12,2 3,6 12,8 3,6 13,4 3,6 14,0 3,6 14,6 3,6 15,4 3,7

15 12,9 4,2 13,8 4,2 14,5 4,2 15,2 4,2 15,8 4,3 16,5 4,3 17,4 4,3

18 15,6 5,2 16,7 5,2 17,5 5,3 18,3 5,3 19,1 5,3 19,9 5,4 21,0 5,4

21 18,9 6,3 20,3 6,4 21,3 6,4 22,3 6,5 23,3 6,5 24,3 6,5 25,6 6,6

25 21,9 7,4 23,4 7,4 24,6 7,5 25,7 7,5 26,9 7,6 28,0 7,6 29,6 7,7

28 24,8 8,5 26,6 8,5 27,9 8,6 29,2 8,6 30,5 8,7 31,8 8,7 33,6 8,8

32 29,2 10,3 31,2 10,3 32,8 10,4 34,3 10,5 35,9 10,5 37,4 10,6 39,5 10,6

36 32,8 10,7 35,1 10,8 36,8 10,2 38,5 10,9 40,3 11,0 42,0 11,1 44,3 11,1

41 36,8 12,5 39,4 12,5 41,4 11,8 43,3 12,7 45,3 12,8 47,2 12,8 49,8 12,9

45 40,6 14,0 43,4 14,1 45,6 13,3 47,7 14,3 49,9 14,3 52,0 14,4 54,9 14,5

48 42,7 15,5 45,7 15,6 47,9 14,7 50,2 15,7 52,4 15,8 54,7 15,9 57,7 16,0

52 48,3 17,5 51,7 17,7 54,3 16,7 56,8 17,9 59,4 18,0 62,0 18,1 65,4 18,2

57 53,4 20,7 57,2 20,8 60,0 19,6 62,8 21,1 65,6 21,2 68,5 21,3 72,2 21,5

65 60,8 22,9 65,1 23,1 68,3 21,7 71,5 23,3 74,8 23,4 78,0 23,6 82,3 23,7

74 68,0 26,9 72,8 27,1 76,4 25,5 80,0 27,4 83,6 27,5 87,2 27,7 92,0 27,9

83 73,7 24,7 78,9 24,9 82,8 23,4 86,7 25,1 90,6 25,3 94,5 25,4 99,7 25,6

89 84,7 29,5 90,7 29,7 95,2 28,0 99,7 30,0 104,1 30,2 108,6 30,4 114,6 30,6

105 96,2 35,6 103,0 35,8 108,1 33,7 113,2 34,1 118,3 34,5 123,4 36,6 130,2 36,9

116 106,3 41,8 113,8 42,1 119,5 39,6 125,1 40,1 130,7 40,6 136,3 41,0 143,9 41,7

129 119,5 46,3 127,9 46,7 134,3 43,9 140,6 44,5 146,9 45,0 153,2 45,5 161,7 46,2

Out

door

air

tem

pera

ture

(°C

)

35

10 8,7 3,1 9,3 3,0 9,7 3,1 10,2 3,1 10,6 3,1 11,1 3,1 11,7 3,2

13 10,8 3,7 11,6 3,7 12,2 3,8 12,7 3,8 13,3 3,8 13,9 3,8 14,6 3,9

15 12,3 4,4 13,1 4,4 13,8 4,4 14,4 4,5 15,1 4,5 15,7 4,5 16,6 4,5

18 14,8 5,5 15,8 5,5 16,6 5,6 17,4 5,6 18,2 5,6 19,0 5,7 20,0 5,7

21 18,0 6,7 19,3 6,7 20,2 6,8 21,2 6,8 22,1 6,8 23,1 6,9 24,4 6,9

25 20,8 7,8 22,3 7,8 23,4 7,9 24,5 7,9 25,6 8,0 26,7 8,0 28,1 8,1

28 23,6 8,9 25,3 9,0 26,5 9,0 27,8 9,1 29,0 9,1 30,3 9,2 31,9 9,2

32 27,8 10,8 29,7 10,9 31,2 11,0 32,7 11,0 34,1 11,1 35,6 11,1 37,6 11,2

36 31,2 11,3 33,4 11,4 35,0 11,4 36,7 11,5 38,3 11,6 40,0 11,7 42,2 11,7

41 35,0 13,1 37,5 13,2 39,4 13,2 41,2 13,4 43,1 13,4 44,9 13,5 47,4 13,6

45 38,6 14,8 41,3 14,9 43,4 14,9 45,4 15,0 47,4 15,1 49,5 15,2 52,2 15,3

48 40,6 16,3 43,4 16,4 45,6 16,4 47,7 16,6 49,9 16,7 52,0 16,8 54,9 16,9

52 46,0 18,5 49,2 18,6 51,6 18,6 54,1 18,8 56,5 18,9 58,9 19,0 62,2 19,2

57 50,8 21,8 54,4 22,0 57,1 22,0 59,8 22,2 62,5 22,3 65,1 22,4 68,7 22,6

65 57,9 24,1 61,9 24,3 65,0 24,3 68,1 24,6 71,1 24,7 74,2 24,8 78,3 25,0

74 64,7 28,3 69,3 28,5 72,7 28,5 76,1 28,9 79,6 29,0 83,0 29,2 87,6 29,4

83 70,1 26,0 75,1 26,2 78,8 26,2 82,5 26,5 86,2 26,6 89,9 26,8 94,9 27,0

89 80,6 31,1 86,3 31,3 90,6 31,3 94,8 31,6 99,1 31,8 103,4 32,0 109,0 32,2

105 91,5 37,5 98,0 37,8 102,8 37,7 107,7 38,2 112,5 38,6 117,4 39,1 123,8 39,6

116 101,2 44,0 108,3 44,4 113,7 44,3 119,0 44,8 124,4 45,4 129,7 45,9 136,9 46,6

129 113,7 48,8 121,7 49,2 127,8 49,1 133,8 49,7 139,8 50,3 145,8 50,9 153,8 51,6

cc = cooling capaciTy ; pi = power inpuT;correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

cooling main value;

Page 23: SB - HVACR

23

®

www.coldinnovation.it

cc = cooling capaciTy ; pi = power inpuT;correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

cooling main value;

SB-Cevaporating temperature (°C)

0 2 3,5 5 6,5 8 10

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi (kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

40

10 7,9 3,5 8,5 3,6 8,9 3,4 9,3 3,4 9,7 3,4 10,2 3,4

13 9,9 4,3 10,6 4,1 11,1 4,1 11,7 4,1 12,2 4,1 12,7 4,1

15 11,2 5,1 12,0 4,8 12,6 4,8 13,2 4,8 13,8 4,9 14,4 4,9

18 13,5 6,4 14,5 6,0 15,2 6,0 15,9 6,1 16,7 6,1 17,4 6,1

21 16,5 7,8 17,6 7,3 18,5 7,3 19,4 7,4 20,3 7,4 21,1 7,5

25 19,0 9,0 20,4 8,5 21,4 8,5 22,4 8,6 23,4 8,6 24,4 8,7

28 21,6 10,4 23,1 9,7 24,3 9,8 25,4 9,8 26,5 9,9 27,7 9,9

32 25,4 12,6 27,2 11,8 28,5 11,9 29,9 11,9 31,2 12,0 32,6 12,1

36 28,5 13,2 30,5 12,4 32,0 13,5 33,6 12,5 35,1 12,6 36,6 12,6

41 32,1 15,3 34,3 14,3 36,0 15,7 37,7 14,5 39,4 14,6 41,1 14,7

45 35,3 17,2 37,8 16,1 39,7 17,6 41,5 16,3 43,4 16,4 45,3 16,5

48 37,1 18,9 39,8 17,8 41,7 19,5 43,7 18,0 45,7 18,1 47,6 18,2

52 42,1 21,5 45,0 20,2 47,3 22,1 49,5 20,4 51,7 20,5 53,9 20,6

57 46,5 25,4 49,8 23,8 52,2 26,1 54,7 24,1 57,2 24,2 59,6 24,3

65 52,9 28,0 56,7 26,3 59,5 28,8 62,3 26,6 65,1 26,8 67,9 26,9

74 59,2 32,9 63,4 30,9 66,5 33,8 69,7 31,3 72,8 31,4 75,9 31,6

83 64,2 30,2 68,7 28,4 72,1 31,1 75,5 28,7 78,9 28,9 82,3 29,0

89 73,7 36,1 79,0 33,9 82,9 37,1 86,8 37,6 90,7 34,5 94,6 38,4

105 83,8 43,6 89,7 40,9 94,1 44,8 98,5 45,3 103,0 45,8 107,4 46,3

116 92,6 51,2 99,1 48,1 104,0 52,6 108,9 53,2 113,8 53,8 118,7 54,5

129 104,0 56,8 111,4 53,3 116,9 58,3 122,4 59,0 127,9 59,7 133,4 60,4

Page 24: SB - HVACR

24

®

www.coldinnovation.it

SB-HOutlet water temperature (°C) Outlet water temperature (°C)

5 7 10 40 45 50

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Tae winter (°C)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

32

10 9,8 2,8 10,4 2,6 11,4 2,8

Out

door

air

tem

pera

ture

(°C

)

-8

6,7 2,7

15 13,9 4,1 14,8 4,1 16,1 4,2 9,5 4,0

21 20,4 6,2 21,7 6,2 23,6 6,3 13,9 5,7

28 26,7 8,4 28,4 8,4 31,0 8,5 18,2 7,7

36 35,3 10,5 37,5 10,6 40,9 10,2 24,1 10,2

41 39,7 12,3 42,2 12,4 46,0 11,9 27,0 11,6

48 45,4 14,9 48,3 15,0 52,6 14,5 30,9 13,2

52 51,0 17,1 54,3 17,2 59,2 16,6 34,8 15,1

57 56,1 20,3 59,7 20,5 65,1 19,7 38,3 16,9

65 63,8 22,6 67,8 22,8 73,9 22,0 43,5 19,9

74 72,4 26,8 77,0 27,0 83,9 26,0 49,4 23,5

89 89,0 29,3 94,7 29,5 103,2 28,5 60,7 26,9

105 102,4 34,6 108,9 34,8 118,7 33,6 69,8 30,7

116 113,7 41,1 121,0 41,4 131,8 39,9 77,5 34,8

129 126,5 45,8 134,6 46,1 146,7 44,5 86,3 40,2

Out

door

air

tem

pera

ture

(°C

)

35

10 9,3 2,9 9,9 2,9 10,8 3,0

Out

door

air

tem

pera

ture

(°C

)

-5

7,0 2,7 6,9 3,2 6,8 3,6

15 13,2 4,3 14,1 4,4 15,3 4,4 10,0 4,0 9,8 4,6 9,6 5,3

21 19,4 6,5 20,6 6,5 22,5 6,6 14,6 5,7 14,4 6,6 14,1 7,6

28 25,4 8,8 27,0 8,9 29,5 9,0 19,2 7,7 18,8 9,0 18,5 10,3

36 33,6 11,0 35,7 11,1 38,9 11,4 25,4 10,2 24,9 11,9 24,4 13,7

41 37,7 12,9 40,1 13,0 43,8 13,3 28,5 11,6 28,0 13,6 27,4 15,5

48 43,2 15,7 45,9 15,8 50,1 16,2 32,6 13,2 32,0 15,5 31,4 17,7

52 48,5 18,0 51,6 18,1 56,3 18,5 36,7 15,1 36,0 17,6 35,3 20,2

57 53,4 21,4 56,8 21,6 61,9 22,1 40,3 16,9 39,6 19,8 38,8 22,6

65 60,7 23,8 64,5 24,0 70,3 24,6 45,8 19,9 44,9 23,3 44,1 26,7

74 68,9 28,2 73,3 28,4 79,8 29,1 52,0 23,5 51,0 27,5 50,0 31,5

89 84,7 30,9 90,1 31,1 98,2 31,8 64,0 26,9 62,8 31,5 61,5 36,0

105 97,4 36,4 103,6 36,7 112,9 37,6 73,5 30,7 72,1 35,9 70,7 41,1

116 108,2 43,3 115,1 43,6 125,4 44,6 81,7 34,8 80,1 40,7 78,6 46,7

129 120,4 48,3 128,1 48,6 139,6 49,7 90,9 40,2 89,2 47,0 87,4 53,8

cc = cooling capaciTy ; pi = power inpuT; hc= heaTing capaciTy

correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

cooling main value; heaTing main value

Page 25: SB - HVACR

25

®

www.coldinnovation.it

cc = cooling capaciTy ; pi = power inpuT; hc= heaTing capaciTy

correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

cooling main value; heaTing main value

SB-HOutlet water temperature (°C) Outlet water temperature (°C)

5 7 10 40 45 50

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Tae winter (°C)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

38

10 8,8 3,2 9,4 3,3 10,3 3,1

Out

door

air

tem

pera

ture

(°C

)

0

7,6 2,7 7,5 3,2 7,3 3,6

15 12,5 4,8 13,3 4,6 14,5 4,6 10,8 4,0 10,6 4,6 10,4 5,3

21 18,4 7,2 19,6 6,9 21,3 7,0 15,9 5,7 15,6 6,6 15,3 7,6

28 24,1 9,7 25,7 9,3 28,0 9,4 20,8 7,7 20,4 9,0 20,0 10,3

36 31,9 12,2 33,9 11,7 37,0 12,6 27,5 10,2 27,0 11,9 26,5 13,7

41 35,8 14,2 38,1 13,7 41,5 14,8 30,9 11,6 30,3 13,6 29,7 15,5

48 41,0 17,3 43,6 16,6 47,5 17,9 35,4 13,2 34,7 15,5 34,0 17,7

52 46,1 19,8 49,0 19,0 53,4 20,6 39,8 15,1 39,0 17,6 38,3 20,2

57 50,7 23,6 53,9 22,7 58,8 24,5 43,7 16,9 42,9 19,8 42,1 22,6

65 57,6 26,3 61,2 25,2 66,8 27,3 49,7 19,9 48,7 23,3 47,8 26,7

74 65,3 31,1 69,5 29,9 75,8 32,3 56,4 23,5 55,3 27,5 54,3 31,5

89 80,4 34,0 85,5 32,7 93,2 35,3 69,4 26,9 68,1 31,5 66,8 36,0

105 92,4 40,1 98,3 38,6 107,2 41,7 79,8 30,7 78,3 35,9 76,7 41,1

116 102,7 47,7 109,2 45,8 119,0 49,5 88,6 34,8 86,9 40,7 85,2 46,7

129 114,2 53,2 121,5 51,1 132,5 55,2 98,6 40,2 96,7 47,0 94,9 53,8

Out

door

air

tem

pera

ture

(°C

)

40

10 8,5 3,4 9,1 3,5 9,9 3,2

Out

door

air

tem

pera

ture

(°C

)

7

11,4 2,9 11,2 3,4 11,0 3,9

15 12,1 5,1 12,9 4,7 14,0 4,8 16,2 4,2 15,9 4,9 15,6 5,7

21 17,7 7,7 18,9 7,1 20,6 7,2 23,8 6,0 23,3 7,1 22,9 8,1

28 23,3 10,4 24,7 9,6 27,0 9,7 31,2 8,2 30,6 9,6 30,0 10,9

36 30,7 13,0 32,7 12,1 35,6 13,5 41,1 10,9 40,4 12,7 39,6 14,5

41 34,5 15,2 36,7 14,1 40,0 15,8 46,2 12,3 45,4 14,4 44,5 16,5

48 39,5 18,5 42,0 17,1 45,8 19,2 52,9 14,1 51,9 16,5 50,9 18,9

52 44,4 21,2 47,3 19,6 51,5 22,0 59,5 16,0 58,4 18,8 57,2 21,5

57 48,9 25,2 52,0 23,4 56,7 26,2 65,4 18,0 64,2 21,0 62,9 24,1

65 55,5 28,1 59,0 26,0 64,4 29,2 74,3 21,2 72,9 24,8 71,5 28,4

74 63,0 33,2 67,0 30,8 73,1 34,5 84,4 25,0 82,8 29,3 81,2 33,5

89 77,5 36,3 82,5 33,7 89,9 37,8 103,8 28,7 101,8 33,5 99,9 38,4

105 89,1 42,9 94,8 39,8 103,3 44,6 119,4 32,7 117,1 38,2 114,8 43,7

116 99,0 50,9 105,3 47,3 114,8 52,9 132,6 37,1 130,0 43,4 127,5 49,7

129 110,2 56,8 117,2 52,7 127,7 59,0 147,5 42,8 144,7 50,1 141,9 57,3

Page 26: SB - HVACR

26

®

www.coldinnovation.it

SB-CHevaporating temperature (°C) condensing temperature (°C)

3 5 7 45 50 55

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Tae winter (°C)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

32

10 9,7 2,9 10,3 2,8 11,2 3,0

Out

door

air

tem

pera

ture

(°C

)

-8

6,6 2,5

13 18,3 3,6 19,5 3,6 21,3 3,6 9,4 3,2

15 13,7 4,2 14,6 4,2 15,9 4,3 9,3 3,7

18 25,1 5,3 26,7 5,3 29,1 5,4 12,9 15,2

21 20,1 6,4 21,4 6,5 23,3 6,5 13,7 5,2

25 35,2 7,5 37,5 7,5 40,9 7,6 18,1 6,2

28 26,3 8,5 28,0 8,6 30,5 8,7 18,0 7,2

32 47,0 10,4 50,0 10,5 54,5 10,6 24,2 8,8

36 34,8 10,9 37,0 10,9 40,3 10,6 23,7 9,4

41 39,1 12,6 41,6 12,7 45,3 12,2 26,7 10,8

45 65,4 14,2 69,5 14,3 75,8 13,8 33,6 11,4

48 45,3 15,6 48,2 15,7 52,5 15,2 30,9 12,1

52 51,3 17,7 54,6 17,9 59,5 17,2 35,0 14,1

57 56,7 20,9 60,3 21,1 65,8 20,3 38,7 16,0

65 64,6 23,1 68,7 23,3 74,9 22,5 44,0 19,2

74 72,2 27,2 76,8 27,4 83,8 26,4 49,3 22,3

83 118,8 25,0 126,4 25,1 137,7 24,2 61,0 21,7

89 90,0 29,8 95,7 30,0 104,3 29,0 61,3 26,0

105 102,2 36,0 108,7 36,2 118,5 34,9 69,7 28,5

116 112,9 42,2 120,1 42,5 130,9 41,0 77,0 32,4

129 126,9 46,8 135,0 47,2 147,2 45,5 86,5 38,2

Out

door

air

tem

pera

ture

(°C

)

35

10 9,2 3,1 9,8 3,1 10,7 3,1

Out

door

air

tem

pera

ture

(°C

)

0

7,5 2,5 7,4 2,9 7,2 3,3

13 18,3 3,8 19,5 3,8 21,3 3,8 9,4 3,2 9,2 3,7 9,1 4,3

15 13,0 4,4 13,9 4,5 15,1 4,5 10,7 3,7 10,5 4,3 10,3 5,0

18 25,1 5,6 26,7 5,6 29,1 5,7 12,9 15,2 12,6 17,7 12,4 20,3

21 19,1 6,8 20,3 6,8 22,2 6,9 15,7 5,2 15,4 6,1 15,1 7,0

25 35,2 7,9 37,5 7,9 40,9 8,0 18,1 6,2 17,8 7,2 17,4 8,2

28 25,1 9,0 26,7 9,1 29,1 9,2 20,5 7,2 20,1 8,4 19,7 9,6

32 47,0 10,9 50,0 11,0 54,5 11,1 24,2 8,8 23,7 10,2 23,2 11,7

36 33,1 11,4 35,2 11,5 38,4 11,8 27,1 9,4 26,6 11,0 26,1 12,6

41 37,2 13,3 39,6 13,4 43,1 13,7 30,5 10,8 29,9 12,6 29,3 14,4

45 65,4 14,9 69,5 15,0 75,8 15,4 33,6 11,4 32,9 13,3 32,3 15,3

48 43,1 16,5 45,8 16,6 50,0 17,0 35,3 12,1 34,6 14,2 34,0 16,2

52 48,8 18,7 51,9 18,8 56,6 19,3 40,0 14,1 39,2 16,5 38,5 18,9

57 54,0 22,0 57,4 22,2 62,6 22,7 44,2 16,0 43,4 18,7 42,5 21,4

65 61,4 24,4 65,4 24,6 71,2 25,1 50,3 19,2 49,4 22,4 48,4 25,7

74 68,7 28,6 73,1 28,9 79,7 29,5 56,3 22,3 55,2 26,1 54,2 29,9

83 118,8 26,3 126,4 26,5 137,7 27,1 61,0 21,7 59,8 25,4 58,7 29,1

89 85,6 31,4 91,1 31,6 99,3 32,4 70,1 26,0 68,8 30,4 67,4 34,8

105 97,2 37,9 103,4 38,2 112,7 39,1 79,6 28,5 78,1 33,3 76,6 38,1

116 107,4 44,5 114,3 44,8 124,6 45,9 88,0 32,4 86,3 37,9 84,7 43,4

129 120,8 49,4 128,5 49,7 140,0 50,9 98,9 38,2 97,0 44,6 95,2 51,1

cc = cooling capaciTy ; pi = power inpuT; hc= heaTing capaciTy

correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

heaTing main value

Page 27: SB - HVACR

27

®

www.coldinnovation.it

SB-CHevaporating temperature (°C) condensing temperature (°C)

3 5 7 45 50 55

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Cc(kW)

Pi(kW)

Tae winter (°C)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Hc(kW)

Pi(kW)

Out

door

air

tem

pera

ture

(°C

)

40

10 8,4 3,6 8,9 3,7 9,8 3,4

Out

door

air

tem

pera

ture

(°C

)7

11,3 2,6 11,0 3,1 10,8 3,5

13 18,3 4,1 19,5 4,1 21,3 4,1 9,4 3,2 9,2 3,7 9,1 4,3

15 11,9 5,2 12,7 4,8 13,8 4,9 16,0 3,9 15,7 4,6 15,4 5,3

18 25,1 6,0 26,7 6,1 29,1 6,1 12,9 15,2 12,6 17,7 12,4 20,3

21 17,5 8,0 18,6 7,4 20,3 7,5 23,4 5,5 23,0 6,5 22,5 7,4

25 35,2 8,5 37,5 8,6 40,9 8,7 18,1 6,2 17,8 7,2 17,4 8,2

28 22,9 10,6 24,4 9,8 26,6 9,9 30,7 7,6 30,1 8,9 29,5 10,2

32 47,0 11,9 50,0 11,9 54,5 12,1 24,2 8,8 23,7 10,2 23,2 11,7

36 30,3 13,5 32,2 12,5 35,1 14,0 40,6 10,0 39,8 11,7 39,0 13,4

41 34,0 15,6 36,2 14,5 39,5 16,2 45,6 11,5 44,7 13,4 43,9 15,4

45 65,4 16,2 69,5 16,3 75,8 18,3 33,6 11,4 32,9 13,3 32,3 15,3

48 39,4 19,4 42,0 18,0 45,7 20,2 52,8 12,9 51,8 15,1 50,8 17,3

52 44,7 22,0 47,5 20,4 51,8 22,9 59,8 15,0 58,7 17,5 57,5 20,1

57 49,4 26,0 52,5 24,1 57,2 27,0 66,1 17,1 64,9 19,9 63,6 22,8

65 56,2 28,7 59,8 26,6 65,2 29,8 75,3 20,4 73,9 23,9 72,4 27,3

74 62,9 33,7 66,9 31,3 72,9 35,0 84,2 23,8 82,6 27,8 81,0 31,9

83 118,8 28,5 126,4 28,7 137,7 32,2 61,0 21,7 59,8 25,4 58,7 29,1

89 78,3 37,0 83,3 34,3 90,8 38,4 104,9 27,7 102,9 32,4 100,9 37,1

105 88,9 44,6 94,6 41,4 103,1 46,3 119,1 30,3 116,9 35,4 114,6 40,6

116 98,3 52,4 104,6 48,6 114,0 54,5 131,7 34,5 129,2 40,3 126,6 46,2

129 110,5 58,1 117,5 53,9 128,1 60,4 148,0 40,6 145,2 47,5 142,3 54,4

cc = cooling capaciTy ; pi = power inpuT; hc= heaTing capaciTy

correcTion facTors for freecooling version: cooling capaciTy:0,97 power inpuT:1,02correcTion facTors for eThylen glicol percenTage and for difference TemperaTure of waTer aT inleT-ouTleT, see aT end of chapTer

heaTing main value

Page 28: SB - HVACR

28

®

www.coldinnovation.it

correction fActors for ethylene glycol content

Weight percentage of glycol % 0 10 20 30 40 50

Freezing point (°C) 0 -3,6 -8,8 -15,7 -24,86 -37,13

Minimum outlet water temperature allowed (°C) 5,5 1,9 -3,3 -10,2 -19,4 -31,6

Cooling capacity correction factor (dT=5°C) 1,000 0,993 0,985 0,978 0,970 0,963

correction fActors for differentiAl wAter temperAture in-out

Differential water temperature (Inlet - Outlet) °C 3 4 5 6 7 8 9 10

Cooling capacity correction factor 0,970 0,985 1,000 1,008 1,016 1,024 1,032 1,040

The Technical daTa in This documenT are noT binding. rigel impianTi s.r.l. keeps righTs To make any Technical modificaTions aT any Time wiThouT noTice due To iTs improvemenT process.

Page 29: SB - HVACR

29

®

www.coldinnovation.it

DIMeNsIONaL DraWINGsunit sb sizes 10, 10-c, 13-c, 15, 15-c, 18-c

Page 30: SB - HVACR

30

®

www.coldinnovation.it

unit sb sizes 21, 21-c, 25-c, 28, 28-c, 32-c

Page 31: SB - HVACR

31

®

www.coldinnovation.it

unit sb sizes 36, 36-c, 41, 41-c

Page 32: SB - HVACR

32

®

www.coldinnovation.it

unit sb sizes 45-c, 48, 48-c, 52, 52-c, 57, 57-c, 65, 65-c, 74, 74-c

Page 33: SB - HVACR

33

®

www.coldinnovation.it

unit sb sizes 83-c, 89, 89-c, 105, 105-c, 116, 116-c, 129, 129-c

Page 34: SB - HVACR

NOtes

............................................................................................................

............................................................................................................

............................................................................................................

...........................................................................................................

...........................................................................................................

............................................................................................................

............................................................................................................

...........................................................................................................

............................................................................................................

............................................................................................................

...........................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

...........................................................................................................

...........................................................................................................

............................................................................................................

...........................................................................................................

............................................................................................................

...........................................................................................................

...........................................................................................................

......... ..................................................................................................

............................................................................................................

............................................................................................................

...........................................................................................................

...........................................................................................................

............................................................................................................

...........................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

............................................................................................................

...........................................................................................................

Page 35: SB - HVACR

®

Cold InnovationZona Industriale Padule - 06020, Gubbio (PG) - Italy

Tel. +39 075 929 11 13 Fax +39 075 929 92 [email protected]

www.coldinnovation.it

Page 36: SB - HVACR

www.coldinnovation.it

®

VEN

ERU

CCI 0

113