RW West Consultants - az773218.vo.msecnd.net · RW West Consultants 7711 NE 199th St, Kenmore, WA...

49
RW West Consultants Property Inspection Report Cover Page 7711 NE 199th St, Kenmore, WA 98028 Inspection prepared for: FAIRA/ Chris Ellis Real Estate Agent: - Date of Inspection: 5/26/2017 Time: 9:00 AM Age of Home: 2012 Size: 2480 Weather: Sunny 60 degrees Order ID: 2045 Front door faces North for orientation purposes only. Inspector: Dee Robert Inman Wa. St. Home Inspector License #1459, FAA UAS Pilot License #3976466 Email: [email protected] www.rwwestinspections.com

Transcript of RW West Consultants - az773218.vo.msecnd.net · RW West Consultants 7711 NE 199th St, Kenmore, WA...

RW West ConsultantsProperty Inspection Report

Cover Page

7711 NE 199th St, Kenmore, WA 98028Inspection prepared for: FAIRA/ Chris Ellis

Real Estate Agent: -

Date of Inspection: 5/26/2017 Time: 9:00 AM Age of Home: 2012 Size: 2480

Weather: Sunny 60 degreesOrder ID: 2045

Front door faces North for orientation purposes only.

Inspector: Dee Robert InmanWa. St. Home Inspector License #1459, FAA UAS Pilot License #3976466

Email: [email protected]

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 1 of 48

Inspection Details We appreciate the opportunity to conduct this inspection for you! Please carefully read your entireInspection Report. Call us after you have reviewed your report, so we can go over any questionsyou may have. Remember, when the inspection is completed and the report is delivered, we are stillavailable to you for any questions you may have, throughout the entire closing process.Properties being inspected do not "Pass" or "Fail.” - The following report is based on an inspectionof the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFCI outlets may not be installed; thisreport will focus on safety and function, not current code. This report identifies specific non-code,non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repairany critical concerns and defects. Note that this report is a snapshot in time. We recommendthat you or your representative carry out a final walk-through inspection immediately beforeclosing to check the condition of the property, using this report as a guide. Red Notes Denote serious, safety or items that require further investigationBlue notes denote minor or maintenance itemGreen note denote locations and shutoff valves

1. AttendanceIn Attendance: Seller present

2. Home TypeHome Type: Two Story

3. OccupancyOccupancy:• Occupied - Furnished• The utilities were on at the time of inspection.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 2 of 48

General Exterior Note 1. Exterior NoteObservations:• North Elevation• South Elevation• East Elevation• West Elevation

||2||North Elevation ||2||West Elevation

||2||South Elevation ||2||East Elevation

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 3 of 48

Exterior Areas 1. Siding ConditionSiding appeared in good condition overall. • Cement fiberboard siding. • Cement fiber board sidingshake • Cultured stone siding • Plywood battenObservations:• Voids in the caulking around some of the windows/doors and corner areas, recommendrecaulking..primarily south side.• Loose siding at south side. Recommend securing.

Voids in caulk south side Loose siding at south side

Flashings are in place at butt ends2. GuttersGutters and downspouts appeared in good condition overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 4 of 48

Gutters appear to be clean3. Driveway and Walkway ConditionConcrete sidewalks and driveways appeared in good condition overall.

4. SoffitSoffits and eaves appeared in good condition overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 5 of 48

Corbel flashings are in place5. Door/WindowExterior doors appeared in operable condition, at time of inspection. • Threshold and jambsappeared in good condition overall. • Window frames and sills appeared in good condition overall.

Head flashings are in place6. GradingGrading appeared in good condition overall. • Collection drains present to help control runoff.Observations:• Foliage is touching the siding, recommend clearance is achieved as this is a conducive conditionfor wood destroying organisms and pests

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 6 of 48

Foliage touching siding Collection drain west side

North yard West yard

South yard East yard

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 7 of 48

7. ElectricalExterior outlets operate. • Exterior outlets are GFCI protected. • Exterior lights attached to thehouse operate overall.

8. Cable FeedsMaterials: Primary Service is Underground Service Lateral

9. Gas ConditionMeter located at west side. Main Gas shutoff is located to the lower left of the meter.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 8 of 48

Main Gas Shutoff10. Exterior Faucet ConditionExterior faucets were in operable condition overall.

11. Pressure70 psi

70 psi12. Gate ConditionMaterials: WoodObservations:• Fences are NOT INCLUDED as part of a home inspection.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 9 of 48

13. Retaining WallConcrete block retaining wall. • Retaining Walls appeared in good condition overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 10 of 48

Roof 1. Roof ConditionArchitectural Composition shingle. • Roof surface is appeared in good condition overall. •Inspected from Drone.Type Average life span 30 years for this type surface with proper maintenance and care.Observations:• Moss on roof. This can lead to the premature failure of the roof and subsequent leaks.Recommend treating moss with a moss retarding chemical. Pressure washing is not recommendedas it can damage surface and lessen life span.• Ridge cap damage at lower roof above entry.• Safety anchor weather boot loose. Recommend replacement to prevent water intrusion andcorrosion.

Safety anchor weather boot loose

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 11 of 48

Damaged ridge cap2. FlashingFlashing appeared in good condition overall.

Kick out flashings are in place3. ChimneyGas B vent appeared in good condition overall, B vent height was adequate overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 12 of 48

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 13 of 48

Attic 1 1. AtticAttic access is located in bedroom closet

2. FramingVisible framing appeared in good condition overall, no visible indications of decay or waterpenetration presently.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 14 of 48

3. VentilationVentilation appeared adequate overall. • Under eave soffit inlet vents noted. • Roof surface ventspresent.

Roof Surface Vent Eave Vents

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 15 of 48

4. Fan/DuctBathroom fans appeared to exhaust to the exterior overall.

5. Insulation ConditionBlown in fiberglass insulation noted.Depth: Insulation averages about 16-18 inches in depth, estimated R value 49.

6. RodentNo visible indications of Rodent Activity.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 16 of 48

General Interior Note 1. General NotesMaterials: Windows in the home are Double panel insulated glass windows. Any deficiencies arenoted in each room section for accessible windows • Doors in the home are considered operationalunless otherwise noted in each room sectionObservations:• Carpet Wrinkled, recommend restretching. Throughout upstairs

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 17 of 48

Entryway 1. ConditionsCeiling and walls are in good condition overall. Light fixture operates. Entry door operates andlocks overall. • Wood flooring is in good condition overall. • Heat register operates overall. •Accessible outlets operate.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 18 of 48

Dining Room 1. LocationLocation Adjacent to family room

2. Dining RoomWalls and ceilings appear in good condition overall. Flooring is wood. Heat register present.Accessible outlets operate. • Light fixture operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 19 of 48

Kitchen 1. Kitchen RoomWalls and ceilings appear in good condition overall. Flooring is wood. Heat register present.Accessible outlets operate. Light fixture operates. Sink and faucets are in operable conditionoverall. Cabinet doors and drawers are in operable condition overall.

2. Counter ConditionGranite counter tops are in good condition.Observations:• Voids in the counter at the back splash, recommend resealing.

Voids at backsplash3. CabinetCabinet doors and drawers are in operable condition overall.Observations:• Cabinet door hinges are loose, minor adjustment would remedy this condition.

4. DisposalDisposal operates overall.

5. DishwasherDishwasher was in operable condition.

6. MicrowaveObservations:• Built-in microwave ovens are tested using normal operating controls. Unit was tested andappeared to be serviceable at time of inspection. Leak and/or efficiency testing is beyond the scopeof this inspection. If concerned, client should seek further review by qualified technician prior toclosing.

7. Stove/OvenStove/oven were in operable condition overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 20 of 48

Oven is operational8. RefrigeratorRefrigerator was in operable condition.

Refrigerator temperature. Recommend lowering Freezer temp9. SinksSink was in operable condition overall.

10. ElectricalOutlets are GFCI protected at the counters.

11. Vent ConditionVent fan appears to exhaust to the exterior, part of microwave.

12. HeatingHeat register operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 21 of 48

Family Room 1. LocationLocation Southwest

2. Family RoomWalls and ceilings appear in good condition overall. Flooring is wood. Heat register present.Accessible outlets operate. • Light fixture operates. • Ceiling fan operates.

3. FireplaceFireplace is a gas unit. • Fireplace appeared in operable condition.Observations:• Gas Shutoff is located inside access panel under glass.• Pilot Controls are located inside access panel under glass.• Battery backup noted. Store batteries only during power outage to prevent carriage corrosion.

Electronic pilot controls

Gas shutoff Battery backup

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 22 of 48

1st Floor Bathroom 1. LocationMaterials: 1st Floor

2. RoomCeiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.

3. ElectricalGFI outlets within 6 feet of the sink.

4. CountersGranite counter tops are in good condition.

5. CabinetsCabinet doors and drawers are in operable condition overall.

6. SinksSink was in operable condition overall.

7. Exhaust FansVent fan operates overall.

8. FloorsTile Flooring is in good condition overall.

9. ShowerShower is in good condition overall. • Shower door is in operable condition overall.

10. ToiletToilet was in operable condition overall.

11. HeatingHeat register operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 23 of 48

Laundry 1. LocationUpstairs

2. ConditionCeiling and walls are in good condition overall. Accessible outlets operate. • Light fixture operates.

3. Exhaust FansVent fan operates overall.

4. DryerDryer appeared to exhaust to the exterior. • Dryer is electric Unit • 220 volt electrical service forelectric dryer.

5. Floor ConditionLinoleum Flooring is in good condition overall.

6. SinkSink is in operable condition overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 24 of 48

7. WasherMaterials: Washer appeared to be in operable condition. • Washer faucets were in operablecondition, no visible leakage.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 25 of 48

Stairs Leading to 2nd Floor 1. StairSteps appeared uniform. • Handrail appeared secure.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 26 of 48

Upstairs Hallway 1. ConditionsCeiling and walls are in good condition overall. Light fixture operates. • Carpet floor covering is ingood condition.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 27 of 48

Master Bedroom 1. LocationLocation North

2. BedroomWalls and ceilings appear in good condition overall. Flooring is carpet in good condition. Heatregister present. Accessible outlets operate.

3. HeatingHeat register operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 28 of 48

Master Bathroom 1. LocationMaterials: Bedroom

2. RoomCeiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.

3. ElectricalGFI outlets within 6 feet of the water sources.

4. CountersGranite counter tops are in good condition.

5. CabinetsCabinet doors and drawers are in operable condition overall.

6. SinksSinks are in operable condition overall.

7. Exhaust FansVent fan operates overall.

8. FloorsTile Flooring is in good condition overall.Observations:• Swelling and delaminated baseboard. Recommend replacement

Swelling and delaminated baseboard Grout staining in front of shower

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 29 of 48

Hall Bathroom1 1. LocationMaterials: Upstairs

2. RoomCeiling and walls are in good condition overall. Accessible outlets operate. Light fixture operates.

3. CountersFormica counter tops are in good condition overall.

4. TubObservations:• Faucet is difficult to operate. Faucet needs to be forced to the off position to turn water off.Recommend further investigation and corrections by licensed plumber.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 30 of 48

Bedroom 1 1. LocationLocation 1st Left

2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.

3. HeatingHeat register operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 31 of 48

Bedroom 2 1. LocationLocation 1st Right

2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.

3. HeatingHeat register operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 32 of 48

Bedroom 3 1. LocationLocation 2nd Left

2. Bedroom RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.

3. HeatingHeat register operates.

4. Doors

Strike plate loose at door

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 33 of 48

Bonus Room 1. LocationLocation Southwest upstairs

2. Bonus RoomWalls and ceilings appear in good condition overall. Flooring is carpet. Heat register present.Accessible outlets operate. • Light fixture operates.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 34 of 48

Garage 1. ConditionWalls and ceilings appeared in good condition overall. Accessible outlets operate. Light fixturesoperate overall. Flooring is concrete, visible portions in good condition overall. • Outlets are GFIprotected at walls.

Sheet rock damage at front north wall of garage2. Floor ConditionMaterials: Flooring is concrete, appeared in good condition overall.

3. DoorsEntry door is in operable condition overall.Observations:• Garage door leading to interior did not self close. Recommend adjustment or installing self closinghinge for fire protection and to prevent carbon monoxide from entering the living area.

4. Garage DoorsDouble garage door was in operable condition, was on auto opener. • Photo cell safety returnsoperate overall. • Tension safety returns operate overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 35 of 48

Heat/AC 1. Heating TypeGas forced air furnace. There was good air flow at the heat registers and cold air returns overall.

2. Heater Location The furnace is located in the atticFurnace is Bryant Brand. • 3 years of age approximately, average life span is 18 to 22 years.

3. Heating conditionObservations:• Service does not appear to have been performed within the last year, recommend serviced bylicensed HVAC contractor.• There was no visible disconnect/kill switch, recommend conditions are investigated further andcorrected as required by licensed HVAC contractor

All heat registers tested and have heat

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 36 of 48

4. Venting

5. FiltersLocation: Located inside a filter grill in the hall ceiling.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 37 of 48

Plumbing/Water Heater1 1. PlumbingWater lines were PEX plastic. • Drain and waste lines were plastic.

2. Water Heater ConditionHeater Type: Gas Water heater. • 40 gallonsLocation: The heater is located in the garage.Observations:• Water heater temperature is in excess of 120 degrees, recommend adjustment to preventaccidental scalding.

Water temp at kitchen sink

3. AgeApproximately 3 years of age, average life span is 10 to 12 years.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 38 of 48

4. ConditionSeismic straps are in place. • Expansion tank is in place.

5. TPRV ConditionTemperature Pressure Relief Valve (TPR Valve) present.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 39 of 48

Electrical 1 1. LocationMaterials: Located in the Garage

2. Electrical200 AMP service, 4/0 Aluminum service entrance wires.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 40 of 48

3. GroundingElectrical service is grounded and bonded.

4. Wiring TypeBreaker system present. Wiring sizes conform to breaker sizes overall. Smaller branch circuit wiringis copper.

5. Arc Fault CircuitsArc Fault Circuits in the panel for bedroom lights and outlets.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 41 of 48

Foundation/Crawlspaces 1. LocationEntryway closet.

2. FoundationContinuous concrete foundation visible portion appeared in good condition overall.

3. DrainageCrawlspace area was dry, there were no visible indications of standing water presently

4. FramingVisible framing appeared in good condition overall.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 42 of 48

5. VentilationVentilation appeared adequate.

6. Insulation ConditionUnfinished fiberglass batts noted.Depth: Insulation averages approximately 10 inches in depth, estimated R value 30.

7. Vapor BarrierVapor Barrier was in place.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 43 of 48

8. RodentNo visible indications of Rodent Activity.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 44 of 48

Shutoffs 1. Shutoff LocationsObservations:• Water Heater gas shutoff is located to the left of the water heater.• Water heater water line shutoff is located above the water heater.• Furnace gas shutoff is located to the left of the furnace.• Gas fireplace gas shutoff is located inside access panel under glass.• Main water shutoff is located on the south wall of the garage.

||2||Water Heater gas shutoff is located to the leftof the water heater.

||2||Water heater water line shutoff is locatedabove the water heater.

||2||Main water shutoff is located on the south wallof the garage.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 45 of 48

||2||Furnace gas shutoff is located to the left of the furnace.

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 46 of 48

Equipment 1. Appliances/EquipmentObservations:• Stove• Refrigerator• Dishwasher• Microwave• Disposal• Water Heater• Furnace• Washer• Dryer

||2||Disposal ||2||Dishwasher

||2||Refrigerator ||2||Microwave

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 47 of 48

||2||Stove ||2||Washer

||2||Dryer ||2||Water Heater

||2||Furnace

RW West Consultants 7711 NE 199th St, Kenmore, WA

Page 48 of 48

Report SummaryReport Summary

The summary below consists of potentially significant findings. These findings can be a safetyhazard, a deficiency requiring a major expense to correct or items I would like to draw extra attentionto. The summary is not a complete listing of all the findings in the report, and reflects the opinion ofthe inspector. Please review all pages of the report as the summary alone does not explain all of theissues. All repairs should be done by a licensed & bonded tradesman or qualified professional. Irecommend obtaining a copy of all receipts, warranties and permits for the work done.Hall Bathroom1Page 29 Item: 4 Tub • Faucet is difficult to operate. Faucet needs to be forced to

the off position to turn water off. Recommend furtherinvestigation and corrections by licensed plumber.

GaragePage 34 Item: 3 Doors • Garage door leading to interior did not self close.

Recommend adjustment or installing self closing hinge for fireprotection and to prevent carbon monoxide from entering theliving area.

Heat/ACPage 35 Item: 3 Heating condition • There was no visible disconnect/kill switch, recommend

conditions are investigated further and corrected as requiredby licensed HVAC contractor

Plumbing/Water Heater1Page 37 Item: 2 Water Heater

Condition• Water heater temperature is in excess of 120 degrees,recommend adjustment to prevent accidental scalding.