RP/09/19
APPENDIX 4A
Place
xxxxxxxxxxxxxxxxxxxxxx Township Revenue
Nativity Scene
PROPOSED FEASTIVE LIGHTING
Rochdale town centre
ROCHDALE CHRISTMAS DECORATION
Festive Decorations Notes
Installation of features
a) All illuminated features are to be installed at a minimum height of 3.5mtrs
(unless notified otherwise by the Engineer) from ground level to the base of
the feature over pedestrian footways and pedestrian areas and 5.8mtrs for
cross-road features or where 0.5mtr set back from kerb cannot be achieved.
b) The features are to be supported by a minimum of two fixings. It is the
Contractors responsibility to ensure that the fixings are appropriate to
support the feature and that no damage is caused to the column or post.
Any damage caused (including protective finishes) must be rectified by
Contractor at his own cost and before the defect date as stated in the
Contract.
Period of Operation
a) Charles Endirect Festive Cut Out (Ref SP2L4/OLDHAM 2) Electronic time-switches
and Tofco Festive Cut Out (Ref Type 1 / Festive Cut Out) are installed in the
columns & Feeder Pillars. The Contractor shall include for the installation and
setting of all time switches. New time switches may require a 230v 50Hz supply for
approximately 48hrs to become fully charged.
b) Period of operation 16:00hrs to Midnight seven days a week (TBC by the engineer)
13. Electrical Supplies
a) Illuminated features mounted on lighting columns are supplied from a
secondary cut-out Charles Endirect / Tofco festive Cut out incorporating a DP
isolator, RCBO & time-clock by means of a 16/32amp 3pin Commando socket
outlet attached to the column shaft.
b) Across road Illuminated features attached to buildings are supplied from
dedicated feeder pillars via a DP isolator & time-clock.
c) Christmas Trees furnished with LED P Lights are supplied from dedicated feeder
pillars incorporating a DP isolator, RCBO, time-clock and transformer the outgoing
steel wire armoured cable is ducted to the base of the tree and terminated into a
tree socket. The Contractor must allow for electrical test and inspection of any
feeder pillar in accordance with BS7671 and all other relevant legislation and codes
of practice.
14. Connections and Wiring
a) All connections and wiring are to be carried out in accordance with BS 7671
Regulations for Electrical Installations, ILP Code of Practice for Electrical Safety in
Highway Electrical Operations and the County Surveyor's Society Code of Practice
for the installation, operation and removal of seasonal decorations. All connections
are to be sufficient to prevent the ingress of water.
Extract from, Part 2 Works Information & Specification.
Location of Christmas tree
For specific detail of equipment/features to be
mounted/furnished refer to part 2 Works Information &
Specification of the Contract.
Existing position of road lighting column having an
illuminated feature mounted as per notes.
Live tree furnished with all year round lights.
Wall mounted Spherical features
Existing feeder pillar location with incoming supply,
having 100mm diameter ducting to tree pit. (Electrical
apparatus as per note C).
Wall mounted Zig Zag features