R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components Omar Abdelaziz, and Som Shrestha January 16 th , 2014 New York City

Transcript of R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz...

Page 1: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and ComponentsOmar Abdelaziz, and Som Shrestha

January 16th, 2014New York City

Page 2: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

2 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Overview

• System Drop-In Testing• Indoor Heat Exchanger Evaluation• Compressor Testing

Page 3: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

3 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

System Drop-In Testing

Page 4: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

4 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

System Description

• 5-TR heat pump unit– Outdoor unit: fixed capacity compressor, single speed fan– Single zone air handler: single

speed blower, draw-through configuration

• R410A baseline: GWP = 2100†

• R32/R152a (95% R32 -5%R152a): GWP ~ 687

† UNEP 2010

Page 5: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

5 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Heat Exchanger

• A-Coil – 8 circuits– OD = 3/8” (9.53 mm)– Tube thickness = 0.012”

(0.305 mm)

• Air flows from bottom to top• R410A TXV, set at ~ 5ºF

(3ºC) superheat

Page 6: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

6 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

System Setup

Page 7: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

7 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Results – System performance

0

10

20

30

40

50

60

70

80

A B C H1 H2 H3

Air-S

ide H

eat C

apac

ity (k

Btu/

W·h

)

R410A R32/R152a

02468

1012141618

A B C H1 H2 H3

EER

(Btu

/W·h

)

R410A R32/R152a

Page 8: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

8 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Additional System Performance Indicators

050

100150200250300350400450

A B C H1 H2 H3

Disc

harg

e Pre

ssur

e (ps

i)

R410A R32/R152a

0

1000

2000

3000

4000

5000

6000

A B C H1 H2 H3

Tota

l Pow

er C

onsu

mpt

ion

(W)

R410A R32/R152a

Page 9: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

9 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Compressor Discharge Temperature

100

120

140

160

180

200

220

A B C H1 H2 H3

Com

pres

sor D

ischa

rge T

empe

ratu

re, °

F

R410A R32/R152a

Page 10: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

10 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Indoor HX Evaluation

1.51.61.71.81.9

22.12.22.32.42.5

100 125 150 175 200 225

Over

all U

A, kW

/m2

Mass Flux, kg/m2.s

Evaporating Mode

R410AR32/R152a

Page 11: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

11 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Indoor HX Evaluation

0.50.55

0.60.65

0.70.75

0.80.85

0.90.95

50 75 100 125 150

Over

all U

A, kW

/m2

Mass Flux, kg/m2.s

Condensing Mode

R410AR32/R152a

Page 12: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

12 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Conclusions

• R32/R152a (95.22/4.78 by mass) was tested as a drop-in replacement to R410A

• R32/R152a has higher volumetric capacity and lower pressure drop through heat exchanger

• R32/R152a exhibited higher or similar system capacity for all test conditions

• In the evaporating mode, R32/R152a had comparable overall heat transfer characteristics to R410A even at much lower mass flux

• In the condensing mode, R32/R152a showed lower overall UA (5 to 21% lower) than R410A

Page 13: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

13 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Compressor Calorimeter Testing

Page 14: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

14 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Tested Refrigerants

Refrigerant ComponentsMass Fraction, % GWP100(†)

R-410a R-32/R-125 50/50 2100R-32 R-32 100 716DR-5 R-32/R-1234yf 72.5/27.5 520*L-41a R-32/R-1234yf/R-1234ze(E) 73/15/12 524*R-32/R-134a R-32/R-134a 94.07/5.93 755*† GWP100 based on UNEP, 2010* Calculated based on the GWP values of pure refrigerants and their mass fraction in the blend

Page 15: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

15 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Results

Page 16: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

16 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Results

Page 17: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

17 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Results

Page 18: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

18 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Results – R32/R134a

Test ConditionEER Capacity Discharge

TemperatureEvap 45°F/ Cond 130°F -2.20% -0.80% +37°REvap 50°F/ Cond 100°F -4.30% -2.8 +22°ROver the range -5.2% to -1.4% -4.9% to +0.3% +16 to +50°R

Deviation from R-410A performanceDeviation from R-410A performance

Page 19: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

19 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Conclusions

• R-32 resulted in capacity gain at the cost of slight efficiency loss and higher compressor discharge temperature

• DR-5 resulted in moderate capacity loss, less than 5% penalty in EER with increased discharge temperature within 20°R

• L-41a resulted in the most capacity degradation; however it behaved exceptionally well at high saturation discharge temperature (>130°F)

• At all test conditions, the EER with R-32/134a was lower than that with R-410A (by 1.4 to 5.2%). At higher discharge dew point temperatures, the ratio generally increased as the suction dew point temperature increased

Page 20: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

20 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Acknowledgements

• The authors would like to acknowledge funding from DOE-BTP and thank Mr. Antonio Bouza for his support

• The authors would like to thank Dr. Isaac Mahderekal, Mr. Vishaldeep Sharma, Randy Linkous and Brian Goins (ORNL), Kyle Karber (Post Graduate Research Associate), and Evelyn Tio for their technical support

Page 21: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

21 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Bibliography

• Open Source Life Cycle Climate Performance Design Tool: http://lccp.umd.edu/ornllccp/• Evelyn Tio, Randy Linkous, Neal Durfee, Omar Abdelaziz, 2012. “System Drop-in Test of R-32/R-152a

(95/5) in a 5-ton Air Source Heat Pump”, TEST REPORT #3, Air-Conditioning, Heating, and Refrigeration Institute Low-GWP Alternative Refrigerants Evaluation Program http://www.ahrinet.org/App_Content/ahri/files/RESEARCH/AREP_Final_Reports/AHRI%20Low-GWP%20AREP-Rpt-003.pdf

• UNEP 2010. “2010 Report of the refrigeration, air conditioning and heat pumps technical options committee; Chapter 2, Refrigerants.” United Nations Environment Programme (UNEP) Ozone Secretariat, Nairobi, Kenya, http://ozone.unep.org/teap/Reports/RTOC/RTOC-Assessment-report-2010.pdf

• Som Shrestha, Isaac Mahderekal, Vishaldeep Sharma, Omar Abdelaziz, 2013. “Compressor Calorimeter Test of R-410A Alternatives R-32, DR-5, and L-41a”, TEST REPORT #11, Air-Conditioning, Heating, and Refrigeration Institute Low-GWP Alternative Refrigerants Evaluation Program http://www.ahrinet.org/App_Content/ahri/files/RESEARCH/AREP_Final_Reports/AHRI%20Low-GWP%20AREP-Rpt-011.pdf

Page 22: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

22 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Questions?

Omar [email protected]

Page 23: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Appendix

Page 24: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

24 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Heat Pump Drop-In Test Instrumentation

• Airflow: Self-averaging Pitot, ±2% of reading• Refrigerant mass flow rate (liquid line): Coriolis flow and

density, bi-direction calibration, ±0.5% of reading• Refrigerant pressure measurement: ±0.08% Full scale of BSL

with ±1% span shift • Indoor airside temperature and relative humidity

measurements: ±0.15°C and ±1.5% RH • Refrigerant side temperature measurements: in-stream T-type

thermocouple ±1°F

Page 25: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

25 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Heat Pump Drop-In Test Instrumentation

• Outdoor airside measurement: T-type thermocouple grid ±1°F• Power measurement:

– Compressor: 0-20 kW ±0.5% F.S.– Outdoor Fan: 0-1 kW ±0.5% F.S.– Indoor Blower: 0-500 W ±0.5% F.S.

• Uncertainty propagation for the R410A Cooling Test A based on air side performance is‡:– Q=62933 [Btu/hr] ±881 (±1.4%)– EER=14.12 [Btu/hr-W] ±0.201 (±1.42%)

‡ Based on averaging 82 data points

Page 26: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

26 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Compressor Calorimeter Test Setup

• Test condition:– 70°F to 140°F SDT in 10°F

increments – 10°F to 55°F SST in 5°F

increments

Page 27: R-410A Alternative Lower GWP Refrigerants Drop in Testing: …€¦ · Omar Abdelaziz abdelazizoa@ornl.gov. 23 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and

27 R-410A Alternative Lower GWP Refrigerants Drop in Testing: System and Components

Compressor Calorimeter Instrumentation

The measured cooling capacity and EER were within 2.7% and 1.0%, respectively, of the manufacturer’s data.Intermediate tests confirmed repeatability of cooling capacity within 1.5% and EER within 2% at standard test conditions. Properties of refrigerants were calculated using REFPROP version 9.0 (Lemmon et al., 2010). Interaction parameters and “mixture” files provided by the refrigerant manufacturers were used in REFPROP to calculate properties of the alternative refrigerants (except for R-32 and R-32 + R-134a mixture) tested.

Instrument Measured AccuracyRTDs Temperature ± 0.4°FMass Flow Sensor Refrigerant mass flow rate ±0.10%

Power and Energy Meter Compressor and evaporator power ±0.5%

Pressure Transmitter Refrigerant pressure, high pressure side 0.25% F.S. [750 psia]

Pressure Transmitter Refrigerant pressure, low pressure side 0.25% F.S. [200 psia]