PV Array Commissioning and Troubleshooting with the...
Transcript of PV Array Commissioning and Troubleshooting with the...
PV Array Commissioning and Troubleshooting
with the
Solmetric PV Analyzer
Paul Hernday
Senior Applications Engineer
cell 707-217-3094
April 11, 2013
Review of I-V Curves
I-V and P-V Curves Expect this shape for un-shaded, healthy modules & strings
Cu
rre
nt
Voltage
Isc
Voc
I-V curve
Vmp
Imp
Po
we
r
P-V curve
Pmax
*P-V curve is calculated from the measured I-V curve
Max power point
I-V Curve Deviations Each represents a reduction of generating power
Any reduction of the knee of the curve
means reduced output power.
Cu
rre
nt
(A)
Voltage (V)
Isc
Voc
Increased
slope
Reduced
slope
Mismatch losses
(incl. shading)
Normal I-V curve
Reduced
current
Reduced
voltage
Conventional measurements do not reveal many of these effects
How I-V Curve Tracing Works (in concept)
Current
(I) Voltage
(V)
Cu
rre
nt
Voltage
(I)
(V)
(I, V)
Adjust the
load
resistor
1
3 Plot the
point
Read I & V
2
• A curve tracer instrument
does all of this automatically
• The load may be resistive,
capacitive, or electronic
Solmetric PV Analyzer
• 600V, 20A (1000V version coming)
• Measured vs predicted (5 dots)
• PC-based (control, display, storage)
• Wireless interface for convenience and workplace safety
Solmetric PVA-600 PV Analyzer
Irradiance sensor (in plane of array)
Temperature sensor (module backside)
Built-in PV models
Module make & model Tilt
Azimuth Irradiance
Module temperature Latitude
Longitude Date & time
5 dots predict curve shape
All wireless
How it works
PV Module or string
How the Solmetric PV Analyzer Works
Controller
&
Wireless
‘I’ sense
‘V’ sense Capacitor (1 of 3)
PV Test
Leads
NEMA 4X FG Enclosure
• The PV Analyzer uses a capacitor as the load.
• Current and voltage change smoothly, at controlled rate, across the voltage range,
ideal for accurately testing high efficiency modules.
Bleed
resistor Switch
Solmetric PV Analyzer Users I-V curve tracing is embedded in the PV community
EPC organizations
System Integrators
Consulting Engineers
Training Organizations Technical colleges
IBEW
Training Centers
O&M Companies
Electrical contractors
I
V
Module Manufacturers
Inverter Manufacturers
PV Analyzer Benefits
•One measurement per string (& one hookup at combiner box)
•Allows testing array performance before inverter is online
• Instant performance check via built-in PV models
•Automated data analysis and reporting
•Faster troubleshooting
Greater productivity
Greater insight
• I-V curve is the most complete performance measurement possible,
capturing Isc, Voc, Imp, Vmp, Pmax, plus the entire I-V curve
• Independent Pmax measurement for each string
•Helps us think like a PV array”
Setup & Measurement - Commercial Systems
Setup and Measurement Example: Measuring strings at a combiner box
Hardware setup (do once at each combiner box):
1. Move the sensors (if necessary to stay in wireless range)
2. Open the DC disconnect of the combiner box
3. Lift the string fuses
4. Clip PV Analyzer test leads to the buss bars
1. Insert a string fuse
2. Press “Measure”
3. View and save results
4. Lift the fuse
Electrical measurement (repeat for each string):
10-15 seconds, typically
Example Measurement Setup
Courtesy of Chevron Energy Solutions © 2011
Wireless Sensor Kit Irradiance & temperature sensors
Irradiance
transmitter
Receiver (USB)
Temperature
transmitter
K-type
thermocouple
Omega Part #
5SRTC-GG-K-
30-72
.
SolSensor™ Wireless PV Reference Sensor
• Integrated construction
• Silicon irradiance sensor with
temperature compensation and
software
• Compatible with external irradiance
sensors via auxiliary port
• Two thermocouples
• Tilt sensor
• Clamps to module frame in plane of
array
• 100m wireless range
• Tripod mounting option
• Rechargeable
Measurement Process 860kW 7-inverter system
Courtesy of Portland Habilitation Center
and Dynalectric Oregon
1. Open the DC disconnect
for the sub-array that you
want to test.
Measurement Process
Courtesy of Portland Habilitation Center
and Dynalectric Oregon
2. Locate the
combiner box
Measurement Process Combiner box wiring
Courtesy of Portland Habilitation Center
and Dynalectric Oregon
3. With a clamp-meter,
verify that the load has
been disconnected.
4. Then lift all of the
fuses.
Measurement Process Insert a single fuse to test the corresponding string
Courtesy of Portland Habilitation Center
and Dynalectric Oregon
5. Clip the PV Analyzer
to the buss bars.
6. Push down a fuse and
make an I-V curve
measurement. Lift
fuse again.
7. View and save results.
8. Repeat for the other
strings.
Setup & Measurement – Residential Systems
SolSensor™ Setup
• Clamp SolSensor to a module frame
• Tape thermocouple tip to backside
• Press the ‘ON’ button (glows red)
Accessing PV Source Circuits for performance measurements
DC Combiner
Box
2
Inverter
J-Box
2 5
DC Disco
DC Disco
AC
AC Inverter
DC Disco
DC Disco
4
3
4
Small Residential System
Larger Residential System
• Access = Isolating the source circuit + Connecting to it
• Choose the safest, most convenient point
• Sometimes you’ll need two access points for one string
1
1
5
3
Warning: Shut down inverter and open DC disconnect before accessing PV source circuits.
Accessing PV Circuits at an integrated DC disconnect
1. Open the AC and DC disconnects
2. Lift the string fuses
3. Connect the PV Analyzer test leads to
the grounded conductor terminal strip
and to the ungrounded conductor fuse
clip (supply side), observing correct
polarity.
• Use the Solmetric armored, high-current test leads. Attach the supplied alligator clips or high-current
probes like the Fluke model FTP.
• Usually can’t alligator clip to a terminal block because of the insulating plastic cover. Install a short,
insulated, temporary wire pigtail in the terminal block, to clip to.
Unbroken Conductor Runs
• The most common example is a
negative-grounded system with the
negative conductors passing unbroken
through a DC disconnect switch.
• Grounded conductors passing through
the enclosure ‘unbroken’
• Can isolate the PV source circuits by
opening the switch, and connect to
them at the top (supply side) of the
switch.
• Connect to the grounded conductors
by attaching a pigtail to their terminal
block at the inverter.
Live Demo of PV Analyzer Software
Irradiance Issues
Low Irradiance
Problem: Max power performance at
low irradiance is not a good
predictor of performance at
high irradiance.
Solution:
Negotiate for new date.
If that’s not possible, test
for function, and re-test
later for performance.
Unstable Irradiance
Problem: Unstable irradiance
introduces error in
irradiance and temperature
measurements, making
data analysis less
accurate.
Solution:
Trigger tests at moments
when irradiance is high
Use real-time, wireless
sensors rather than manual
sensors & data entry.
Effect of Time Delay Between I-V and irradiance measurements
PV performance measurements can be less accurate
under conditions of unstable irradiance, even if the
irradiance is nominally high. Here is why.
There is typically some small time delay between the
I-V curve and irradiance measurements. As shown in
this graph, if the irradiance changes during this time
delay, the measured irradiance value will not be
representative of the condition under which the I-V
curve was measured. In other words, under unstable
irradiance conditions, a time delay between the two
measurements translates into irradiance
measurement error.
The longer the time delay, the more vulnerable the
performance measurement is to this source of
irradiance error.
This error is minimized when using real-time, wireless
irradiance sensing with very short time intervals
between irradiance measurements.
At the other extreme, the error is maximized when
you measure and enter irradiance values manually,
because of the time these steps require.
10s 10s 10s 10s 10s
980
960
940
920
900
10-second intervals
Irra
dia
nce
(W
/m2)
30
Data Analysis
Displays Generated by the I-V Data Analysis Tool
1950
2000
2050
2100
7
6
5
4
3
2
1
0
Fre
qu
en
cy
Pmax (Watts)
7
6
5
4
3
2
1
0
Cu
rren
t (A
mp
s)
0 100 200 300 400 500
Voltage (Volts)
7
6
5
4
3
2
1
0
Cu
rren
t (A
mp
s)
0 100 200 300 400 500
Voltage (Volts)
String I-V ‘combo’ graph
(one per combiner)
String table
(one row per string)
Distribution graph
(for each parameter)
Tour of the Data Analysis Tool
Measurement Examples
0
1
2
3
4
5
6
7
8
0 50 100 150 200 250 300 350 400
Voltage - V
Cu
rren
t -
A
String 4B14
String 4B15
High Series Resistance
Neighboring
strings Faulty module
J-box failure Example of a series resistance problem
Probably failure mode:
Heat cycling bond degradation resistive heating
Backside view Backside view, closeup
Frontside view
Hot Spots
String of Field-aged, Early TF Modules Degraded fill factor, lower output power
Array-as-sensor mode for viewing relative changes in curve shape
Dropped Cell String from shorted bypass diode
• Shorted bypass diode, or
• Mismatch causing diode to turn on
when current starts flowing
Bypass Diodes
Bypass Diodes
• PV modules designed for grid-tie systems have
extra components – semiconductor “bypass
diodes” – designed to protect shaded, badly
soiled, or cracked cells from electrical and
thermal damage. Bypass diodes also allow non-
shaded modules to keep producing, by shunting
current around groups of shaded cells.
• In most module designs, the bypass diodes are
mounted in the junction box on the module
backside. In many cases, the junction box can
be opened to test and replace the bypass
diodes.
• Each bypass diode protects a different group of
cells within the module. For example, in a 72-cell
crystalline silicon module there may be three
bypass diodes, each protecting a group of 24
cells, usually laid out as two adjacent columns
as viewed in portrait mode.
Bypass Diodes
• This sketch shows current flow in a typical 72-
cell PV module with 3 bypass diodes (shown
at top).
• If none of the cells is seriously shaded or
otherwise impaired in its ability to generate
current, the current flows as shown by the
green path. The bypass diodes do not
conduct current.
• In the next slide, we shade a cell and the
bypass diode protecting that cell group turns
on, routing current around the partially
shaded group.
Bypass Diodes
• In this sketch, a cell at lower right has been
shaded. Assuming this module is loaded, the
bypass diode protecting that group of cells
turns on, routing current around that group,
protecting the shaded cell.
• Another benefit of bypass diodes is that by
eliminating the shade-induced restriction to
current flow, they preserve the production of
the non-shaded modules and cell groups.
Shading
I-V Curve of a Partially Shaded String
• Multiple ‘knees’ multiple power peaks
• Peaks evolve as conditions change
• Inverter tries to find and track the highest peak
Cu
rre
nt
Voltage
Isc
Voc
Po
we
r
Bypass diode
turning on
Depth of step is
proportional to shading
factor on most shaded cell
Partially shaded residential array Measure the single string mounted along lower edge of roof
I-V Curve of the partially shaded string Single string mounted along lower edge of roof
Approximately 40% reduction in string’s output power
Shade 2 cells in the same cell-string Single module with 72 cells and 3 bypass diodes
Shading one
cell string
drops 1/3 of
PV module
voltage and
power
Shade 2 cells in adjacent cell-strings Single module with 72 cells and 3 bypass diodes
The same
amount of
shade,
oriented
differently,
drops 2/3 of
PV module
voltage and
power.
Tapered Shading
Tapered shading From adjacent row, parapet wall, railing, etc
• This effect produces an I-V
curve deviation similar to
that of shunt loss
• The tapered sliver of shade
causes a slight current
mismatch across cell
groups and modules
• In tilt-up system, the
impact of this shade is felt
only early and late in the
day, at low sun angles
• In general, inter-row
shading losses are greater
if rows are ‘crowded’ to
increase peak capacity
Cu
rre
nt
Voltage
Isc
Voc
rows not
parallel
Effect of
tapered
shade
Shade ‘taper’ across a cell-string Single module with 72 cells and 3 bypass diodes
Non-Uniform Soiling
Random Non-uniform Soiling (seagull example)
• Effect is similar to random
partial shading
• Shows up as steps or
notches in the I-V curve
Lower Edge Soiling (“dirt dam”) Common in arrays with tilt less than 10 degrees
Dirty
Clean
50% of the
power loss 50% of the
power loss
Snow
Snow on Array (light cover)
Snow on Array (heavier cover)
Troubleshooting Using Selective Shading
Max power point
I-V Curve Deviations Each represents a reduction of generating power
Any reduction of the knee of the curve
means reduced output power.
Cu
rre
nt
(A)
Voltage (V)
Isc
Voc
Increased
slope
Reduced
slope
Mismatch losses
(incl. shading)
Normal I-V curve
Reduced
current
Reduced
voltage
Conventional measurements do not reveal many of these effects
Selective Shading Technique
Photo courtesy of Harmony Farm Supply
and Dave Bell (shown)
Key to the technique: Blocking the light turns on the bypass diode, shorting out the cell group.
String with one bad module
Cu
rre
nt
Voltage
Isc
Voc
This is the string
with no shade,
showing a step.
Shading any good
module produces
this red curve, still
showing the step
Troubleshooting using selective shading to identify a bad module
The method can also be used to identify
a bad cell string in a single module
Shading the bad
module produces this
blue curve, with no
step.
PV Array Commissioning and Troubleshooting
with the
Solmetric PV Analyzer
Paul Hernday
Senior Applications Engineer
cell 707-217-3094
April 11, 2013