Air Treatment Division PRODUCT GUIDE GEA Close Control Aerial values always on the level

Transcript of PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C...

Page 1: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Air Treatment Division

PRODUCT GUIDE

GEA Close ControlAerial values always on the level

Page 2: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0
Page 3: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide Contents

PR-2006-0294-GB Subject to modifications 01/2007 1

Unit Ranges

MS Range – “X” and “C” Versions .......................................................................... 2 T Range – “X”, “A”, “W” and “C” Versions............................................................... 4 E Range – “A”, “W” and “F” Versions.................................................................... 10 E Range – “X” and “C” Versions ........................................................................... 12 E Range – Combicool Versions ............................................................................ 14 TW Range – Weatherproof Versions ................................................................... 16 EP Range – External Packaged Versions ........................................................... 18 IP Range – Internal Packaged Versions .............................................................. 20 HS Range – High Static Versions ......................................................................... 24 Zone Unit Range ZU and ZD Versions ........................................................... 26 LECU – Local Environmental Control Unit ........................................................... 28 CA Range – Water Chillers ................................................................................... 29 C Range – Air Cooled Condensing Units.............................................................. 30 DCRA Range – Air Cooled Condensers ............................................................... 31 DDRA Range – Drycoolers ................................................................................... 32 C3-05 Controls ..................................................................................................... 33

Display Details ............................................................................................. 33 Hardware Structure ...................................................................................... 34 Inputs and Outputs........................................................................................ 35

Due to our policy of continuous development and improvement, the specifications and data herein are subject to change without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this Product Guide, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. GEA makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use.

Page 4: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

MS RANGE Product Guide

2 PR-2006-0294-GB Subject to modifications 01/2007

U7 U11

°

° °

800

° °

°

°

800

1400 300 2000 360

Main Features Airflow: Upflow, front grille air return with front air discharge via an adjustable grille Construction: Steel chassis with removable front and side panels. Thermally and acoustically

insulated with 20mm thick class ”O” insulation. Designed and built in accordance with BS EN ISO 9001.

Coils: Made from 3/8” copper tubes with aluminium fins at 14 or 16 per inch and fitted with stainless steel condensate tray.

Fans: Forward curved double inlet fans and an integral 3-speed direct-drive motor. Filters: 25mm thick disposable pleated filters to EU4 (G4) standard. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with steel fins and safety cut out. LPHW heating also

available. Controls: Denco C3-05 controls as standard. Ancillaries: A wide range of matching optional extras is available.

Page 5: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide MS RANGE

PR-2006-0294-GB Subject to modifications 01/2007 3

All Versions U 7 U 11

Air Volume m³/s m³/hr Number of Fans -

0.35 1260

2

0.8 2880

3

Heating Steps - Capacity kW

1 2.5

2 5.0

Humidifier Capacity kg/hr Power kW Feed Size mm Drain Size mm

3.0 2.3 15 22

3.0 2.3 15 22

Filters Number Off - Length mm Width mm Depth mm

1 840 280 25

2 720 310 25

Weight kg 85 120

“X” Versions U 7 U 11

Total NETT Duty kW Sensible Duty kW

6.37 5.23

9.86 9.61

Condensing Unit Type - Number Off -

CS28 1

CS40 1

Suction Line Connection ins Liquid Line Connection ins

5/8 3/8

3/4 1/2

Maximum Full Load Current Amps 15.9 18.5

“C” Versions U 7 U 11

Total GROSS Duty kW Sensible Duty kW

5.44 5.03

13.39 12.12

CW Flow Rate l/s Unit Pressure Drop kPa

0.26 124.0

0.64 95.5

Chilled Water In Size mm Chilled Water Out Size mm

15 15

22 22

Maximum Full Load Current Amps 15.1 16.1 Cooling performances are based on: - Air on at 24°C, 45%RH. - 32°C ambient temperature. - Standard matching Condensing Units (alternative combinations available, please enquire for details). - 1.5K suction line loss. - Chilled water in 7°C, temperature rise 5K. Maximum Full Load Current based on worst condition on any single phase when operating automatically and could be: - Fan + Cooling + Humidifying. - Fans + Heating + Humidifying. - Fans + Cooling + Reheating (Dehum).

Page 6: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

T RANGE Product Guide Models 3 – 21

4 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW U/D3-5

U/D3-12 END VIEW U/D8-21

U/D17-21

1940

1940

385 665 685 1250

Main Features Airflow: Upflow and Downflow models, with various return and discharge configurations. Construction: Rigid Aluzink frame with Class ‘O’ insulated hinged panels. Serviceable exclusively

from the front. Designed and built in accordance with BS EN ISO 9001. Coils: The coils are made up of 3/8” Copper tubes, DX coils are inner grooved, with

aluminium fins and fitted with stainless steel condensate trays. Coils are inclined for maximum face area, minimum pressure drop and noise reduction. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C”version units.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Each fitted with back-seating isolating valves with an oil level sight glass on larger models and High and Low pressure switches.

Ambicool: Provides free or partially free cooling by exploiting low ambient conditions. Typically reduces running time and energy costs by 70% in northern Europe. (F version)

Condensers: Water Cooled, compact pressed stainless steel plate heat exchanger, provides high velocity and low pressure drop.

Fans: Models 3 - 5 have one backward-curved, direct drive centrifugal fan, with a single inlet and integral single speed motor. Models 8 – 21 have one or two double width forward curved fans with double inlets and an integral three-speed direct drive motor, with lowest speed for dehumidification.

Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with Stainless Steel fins and safety cut-out. LPHW also

available. Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries: A wide range of matching optional extras is available.

Page 7: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide T RANGE Models 3 – 21

PR-2006-0294-GB Subject to modifications 01/2007 5

All Versions 3 4 5 8 10 12 17 19 21

Airflow m³/s m³/hr Number of Fans -

0.30 1080

1

0.35 1260

1

0.42 1510

1

0.70 2520

1

0.80 2880

1

1.00 3600

1

1.40 5040

2

1.60 5760

2

1.80 6480

2

Heating Capacity kW 3.0 6.0 12.0

Filters (Std EU4) No. Size: L x W x D mm

1 455 x 455 x 50

2 442 x 505 x 50

2 885 x 505 x 50

“X” Versions 3 4 5 8 10 12 17 19 21

Total NETT Duty kW Sensible Duty kW

4.63 4.08

4.75 4.42

5.61 5.12

9.49 8.65

11.58 10.01

13.41 11.56

17.57 16.68

19.43 18.44

22.98 20.98

Suction Connection ins Liquid Connection ins

3/4 3/8

3/4 3/8

3/4 3/8

7/8 1/2

7/8 1/2

1-1/8 1/2

1-1/8 5/8

1-1/8 5/8

1-1/8 5/8

Condensing Unit - CT18 CT18 CT22 CS40 CM48 CM61 CP72 CP81 CL90

Full Load Current Amps 19.2 19.2 19.2 21.0 22.1 24.2 28.6 28.6 30.5

Weight kg 135 210 345

“A” Versions 3 4 5 8 10 12 17 19 21

Total NETT Duty kW Sensible Duty kW

- - 5.66 5.14

8.76 8.30

12.10 10.24

14.16 11.84

16.18 15.61

18.32 17.59

20.78 19.77

Discharge Connection ins Liquid Connection ins

- - 1/2 3/8

3/4 1/2

3/4 1/2

3/4 1/2

7/8 5/8

7/8 5/8

7/8 5/8

Scroll Compressor ZR - - 22 34 48 61 61 72 81

Std Condenser ‡ DCRA - - 08-6 13-6 21-6 21-6 26-6 26-6 32-6

Full Load Current Amps - - 20.2 19.9 20.9 23.0 32.7 34.0 36.1

Weight kg - - 165 255 445

“W” Versions 3 4 5 8 10 12 17 19 21

Total NETT Duty kW Sensible Duty kW

- - 5.73 5.17

8.74 8.28

11.73 10.08

13.90 11.76

15.71 15.25

18.01 17.35

20.30 19.33

Cooling Water Connections mm

- - 22

28

28

28

35

35

35

Scroll Compressor ZR - - 22 34 48 61 61 72 81

Std W/C Condenser B - - 8/20 8/30 8/30 8/30 10/30 10/30 10/30

Full Load Current Amps 19.2 19.9 20.9 23.0 31.7 33.0 35.1

Weight kg - - 175 270 460

“F” Versions 3 4 5 8 10 12 17 19 21

Total NETT Duty kW Sensible Duty kW

- - - 7.84 7.63

10.66 9.63

12.61 11.14

14.13 14.03

16.28 16.02

18.14 17.74

Cooling Water Conn’s mm - - - 28 28 28 35 35 35

Scroll Compressor ZR - - - 34 48 61 61 72 81

Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30

Full Load Current Amps 19.9 20.9 23.0 31.7 33.0 35.1

Weight kg - - - 305 505

“C” Versions 3 4 5 8 10 12 17 19 21

Total GROSS Duty kW Sensible Duty kW

- - 5.82 5.36

- - 13.87 12.53

- - -

Chilled Water Conn’s mm - - 22 - - 28 - - -

Chilled Water Flow l/s Pressure Loss kPa

- - 0.3 50

- - 0.7 58

- - -

Full Load Current Amps - - 19.2 - - 19.9 - - -

Weight kg - - 140 - - 215 - - -

All Cooling performances are based on Downflow Units with standard airflow at 24°C, 45%RH, standard EU4 (G4) filtration, 50 Pa minimum external static pressure, standard Condensers / Condensing Units and the following: - “X” Versions – 1.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “A” Versions – 0.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “W” Versions – 0.5K suction line loss, Refrigerant R407C, condensing water in at 30°C and rise 8K. - “F” Version – Coolant: 25% ethylene glycol solution, temperature in at 40°C, temperature rise 6K, Refrigerant R407C, suction line loss 0.5K. - “C” Versions – Chilled Water at 7°C and rise 5K. Humidifier details for ALL Units: Capacity – 3 kg/hr, Power – 2.3 kW, Feed Connection Size – 15mm, Drain Size – 22mm. ‡ Quiet / Residential Condensers are available as an alternative to the standard versions stated, please enquire for details. Full Load Current is worst case phase current for components that can be selected to operate at any one time by the automatic control system, each component operating at “maximum load conditions”.

Page 8: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

T RANGE Product Guide Models 23 – 42

6 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW

U/D23-42 U/D23-28 U/D32-42

1940

685 1250 1840

Main Features Airflow: Upflow and Downflow models, with various return and discharge configurations. Construction: Rigid Aluzink frame with Class ‘O’ insulated hinged panels. Serviceable exclusively

from the front. Designed and built in accordance with BS EN ISO 9001. Coils: The coils are made up of 3/8” Copper tubes, DX coils are inner grooved, with

aluminium fins and fitted with stainless steel condensate trays. Coils are inclined for maximum face area, minimum pressure drop and noise reduction. One and two circuit coils are available. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C” version units.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Each fitted with back-seating isolating valves with an oil level sight glass on larger models and High and Low pressure switches.

Ambicool: Provides free or partially free cooling by exploiting low ambient conditions. Typically reduces running time and energy costs by 70% in northern Europe. (F version)

VRF: Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increased compressor life and greater cooling control.

Condensers: Water Cooled, compact pressed stainless steel plate heat exchanger, provides high velocity and low pressure drop.

Fans: Models 23 – 42 have two or three double width forward curved fans with double inlets and an integral three-speed direct drive motor, with lowest speed for dehumidification.

Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with Stainless Steel fins and safety cut-out. LPHW also

available. Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries: A wide range of matching optional extras is available.

Page 9: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide T RANGE Models 23 – 42

PR-2006-0294-GB Subject to modifications 01/2007 7

All Versions 23 28 32 37 42 Airflow m³/s

m³/hr

Number of Fans -

2.00

7200

2

2.17

7810

2

2.50

9000

3

2.90

10440

3

3.30

11880

3

Heating Capacity kW 12.0

Filters (Std EU4) No. Size: L x W x D mm

2 885 x 505 x 50

3 885 x 540 x 50

23† 28† 32† 37† 42 “X” Versions 1 circuit 1 cct VRF 1 circuit 1 cct VRF 1 circuit 1 cct VRF 1 circuit 1 cct VRF 1 circuit 1 cct VRF

Total NETT Duty kW Sensible Duty kW

26.38 23.18

24.45 22.38

29.23 24.95

28.32 24.57

31.22 29.52

33.79 30.62

36.13 33.37

37.12 33.78

41.33 37.03

- -

Suction Connection ins Liquid Connection ins

1-1/8 5/8

1-3/8 5/8

1-3/8 3/4

1-3/8 3/4

1-3/8 3/4

- -

Condensing Unit 1 No. CL11 CLV48 CL12 CLV61 CL12 CLV72 CL16 CLV81 CL19 -

Full Load Current Amps 33.1 35.5 35.5 40.5 44.6 -

Weight kg 660 810

23 28 32 37 42 “A” Versions 1 cct VRF 2 circuit 1 cct VRF 2 circuit 1 cct VRF 2 circuit 1 cct VRF 2 circuit 1 cct VRF 2 circuit

Total NETT Duty kW Sensible Duty kW

23.83 22.12

24.80 22.53

27.32 24.15

28.73 24.74

31.64 29.72

31.58 29.69

35.76 33.21

35.67 33.18

39.35 36.21

40.17 36.55

Discharge Connection ins Liquid Connection ins

1-1/8 5/8

3/4 1/2

1-1/8 5/8

3/4 1/2

1-1/8 3/4

3/4 1/2

1-1/8 3/4

7/8 5/8

1-1/8 3/4

7/8 5/8

Scroll Compressor † ZR 48 (2 No) 61 (2 No) 61 (2 No) 72 (2 No) 81 (2 No)

Std Condenser ‡ DCRA 32-6 (1No) 21-6 (2No) 32-6 (1No) 21-6 (2No) 50-6 (1No) 21-6 (2No) 50-6 (1No) 26-6 (2No) 50-6 (1No) 26-6 (2No)

Full Load Current Amps 37.8 42.0 47.6 50.2 54.4

Weight kg 860 1010

“W” Versions 23 28 32 37 42 Total NETT Duty kW Sensible Duty kW

23.55 22.01

27.66 24.29

30.10 28.65

34.43 32.57

38.34 35.79

Cooling Water Conn’s mm 35 35 42 42 42

Scroll Compressor † ZR 48 (2 No) 61 (2 No) 61 (2 No) 72 (2 No) 81 (2 No)

Std W/C Condenser B 10 / 30 10 / 30 10 / 40 10 / 40 10 / 40

Full Load Current Amps 36.8 41.0 42.0 44.6 48.8

Weight kg 460 535

“F” Versions (at m³/s) 23 (1.95) 28 (2.12) 32 (2.40) 37 (2.80) 42 (3.23) Total NETT Duty kW Sensible Duty kW

21.21 20.30

24.97 23.00

27.04 26.14

31.16 29.91

34.38 32.94

Cooling Water Conn’s mm 35 35 42 42 42

Scroll Compressor † ZR 48 (2 No) 61 (2 No) 61 (2 No) 72 (2 No) 81 (2 No)

Std W/C Condenser B 10 / 30 10 / 30 10 / 40 10 / 40 10 / 40

Full Load Current Amps 36.8 41.0 42.0 44.6 48.8

Weight kg 505 590

“C” Versions 23 28 32 37 42 Total GROSS Duty kW Sensible Duty kW

- 28.65 26.38

- - 45.36 41.26

Chilled Water Conn’s mm - 35 - - 42

Chilled Water Flow l/s Pressure Loss kPa

- 1.4 65

- - 2.2 80

Full Load Current Amps - 28.6 - - 29.6

Weight kg - 355 - - 430

All Cooling performances are based on Downflow Units with standard airflow at 24°C, 45%RH, standard EU4 (G4) filtration, 50 Pa minimum external static pressure, standard Condensers / Condensing Units and the following: - “X” Versions – 1.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “A” Versions – 0.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “W” Versions – 0.5K suction line loss, Refrigerant R407C, condensing water in at 30°C and rise 8K. - “F” Version – Coolant: 25% ethylene glycol solution, temperature in at 40°C, temperature rise 6K, Refrigerant R407C, suction line loss 0.5K. - “C” Versions – Chilled Water at 7°C and rise 5K. Humidifier details for ALL Units: Capacity – 3 kg/hr, Power – 2.3 kW, Feed Connection Size – 15mm, Drain Size – 22mm. † 1 Circuit VRF “A” type and all “W” type Models are VRF as standard. “X” Version also available as 2 circuit. ‡ Quiet / Residential Condensers are available as an alternative to the standard versions stated, please enquire for details. Full Load Current is worst case phase current for components that can be selected to operate at any one time by the automatic control system, each component operating at “maximum load conditions”. “X” loads based on 2 circuit, “A” based on 2 circuit VRF.

Page 10: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

T-RANGE Product Guide Models 48 – 83

8 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW

U/D48-83 U/D48-53 U/D63-83

1940

985 1250 1840

Main Features Airflow: Upflow and Downflow models, with top, bottom or three-side return and discharge

configurations. Construction: Rigid Aluzink frame with Class ‘O’ insulated hinged panels. Serviceable exclusively

from the front. Designed and built in accordance with BS EN ISO 9001. Coils: The coils are made up of 3/8” Copper tubes, DX coils are inner grooved, with

aluminium fins and fitted with stainless steel condensate trays. Coils are inclined for maximum face area, minimum pressure drop and noise reduction. Two and four circuit coils are available. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C”version units.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Each fitted with back-seating isolating valves with an oil level sight glass on larger models and High and Low pressure switches.

VRF: Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increased compressor life and greater cooling control.

Condensers: Water Cooled, compact pressed stainless steel plate heat exchanger, provides high velocity and low pressure drop.

Fans: Models 48 – 83 have four or six double width forward curved fans with double inlets and an integral three-speed direct drive motor.

Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with Stainless Steel fins and safety cut-out. Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries: A wide range of matching optional extras is available.

Page 11: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide T-RANGE Models 48 – 83

PR-2006-0294-GB Subject to modifications 01/2007 9

All Versions 48 53 63 73 83

Airflow m³/s

m³/hr

Number of Fans -

3.70

13320

4

4.01

14436

4

4.40

15840

6

5.35

19260

6

6.10

21960

6

Heating Capacity kW 12.0

Filters (Std EU4) No. Size: L x W x D mm

4 885 x 505 x 50

6 885 x 540 x 50

48 53 63 73 83 “X” Versions

2 circuit 2 circuit VRF

2 circuit 2 circuit VRF

2 circuit 2 circuit VRF

2 circuit 2 circuit VRF

2 circuit 2 circuitVRF

Total NETT Duty kW Sensible Duty kW

52.36 45.00

48.59 43.42

57.95 48.46

56.14 47.70

61.65 55.65

71.85 57.75

71.85 64.57

73.71 65.36

82.07 71.81

- -

Suction Connection ins Liquid Connection ins

1-1/8 5/8

1-3/8 5/8

1-3/8 3/4

1-3/8 3/4

1-3/8 3/4

- -

Condensing Unit 2 No. CL11 CLV48 CL12 CLV61 CL12 CLV72 CL16 CLV81 CL19 -

Full Load Current Amps 55.0 59.8 60.8 68.8 77.0 -

Weight kg 660 810

48 53 63 73 83 “A” Versions

2 circuit VRF

4 circuit 2 circuit VRF

4 circuit 2 circuit VRF

4 circuit 2 circuit VRF

4 circuit 2 circuit VRF

4 circuit

Total NETT Duty kW Sensible Duty kW

47.38 44.92

49.28 43.71

54.22 46.89

56.94 48.03

62.38 55.96

60.64 55.22

71.10 64.26

70.94 64.19

78.15 70.17

77.95 70.09

Discharge Connection ins Liquid Connection ins

1-1/8 5/8

3/4 1/2

1-1/8 5/8

3/4 1/2

1-1/8 3/4

3/4 1/2

1-1/8 3/4

7/8 5/8

1-1/8 3/4

7/8 5/8

Scroll Compressor † ZR 48 (4 No) 61 (4 No) 61 (4 No) 72 (4 No) 81 (4 No)

Std Condenser ‡ DCRA 32-6 (2No) 21-6 (4No) 32-6 (2No) 21-6 (4No) 50-6 (2No) 21-6 (4No) 50-6 (2No) 26-6 (4No) 50-6 (2No) 26-6 (4No)

Full Load Current Amps 48.3 56.7 60.0 66.2 74.6

Weight kg 860 1010

“W” Versions 48 53 63 73 83

Total NETT Duty kW Sensible Duty kW

46.80 42.68

54.81 47.14

59.34 54.68

68.37 63.12

76.08 69.31

Cooling Water Connections mm

2 x 35 2 x 35 2 x 42 2 x 42 2 x 42

Scroll Compressor † ZR 48 (4No) 61 (4No) 61 (4No) 72 (4No) 81 (4No)

Std W/C Condenser B 10 / 30 (2No) 10 / 30 (2No) 10 / 40 (2No) 10 / 40 (2No) 10 / 40 (2No)

Full Load Current Amps 45.0 53.4 54.4 58.6 67.0

Weight kg 890 1040

“C” Versions 48 53 63 73 83

Total GROSS Duty kW Sensible Duty kW

- 53.65 49.79

- - 85.26 77.94

Chilled Water Connections mm

-

54 -

-

54

Chilled Water Flow l/s Pressure Loss kPa

- 2.7 56

- - 4.4 72

Full Load Current Amps - 33.6 - - 34.6

Weight kg - 680 - - 830

All Cooling performances are based on Downflow Units with standard airflow at 24°C, 45%RH, standard EU4 (G4) filtration, 50 Pa minimum external static pressure, standard Condensers / Condensing Units and the following: - “X” Versions – 1.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “A” Versions – 0.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “W” Versions – 0.5K suction line loss, Refrigerant R407C, condensing water in at 30°C and rise 8K. - “C” Versions – Chilled Water at 7°C and rise 5K. Humidifier details for ALL Units: Capacity – 8 kg/hr, Power – 6 kW, Feed Connection Size – 15mm, Drain Size – 22mm. † 2 Circuit “A” type and all “W” type Models are VRF as standard. ‡ Quiet / Residential Condensers are available as an alternative to the standard versions stated, please enquire for details. Full Load Current is worst case phase current for components that can be selected to operate at any one time by the automatic control system, each component operating at “maximum load conditions”. “X” loads based on 2 circuit, “A” based on 2 circuit VRF.

Page 12: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

E RANGE Product Guide UPFLOW AND DOWNFLOW A, W AND F VERSIONS

10 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW U/D 24/34 U/D 44/54 U/D 64/74

1940

830

1915

2500

3090

U/D 84/94

1940

(U/D

84)

1965

(U/D

94)

3680 (U/D84)

3980 (U/D94)

Main Features Airflow Upflow and Downflow models, with various return and discharge configurations. Construction Rigid Aluzink frame with Class ‘O’ insulated panels. Serviceable exclusively from the front, due

to swing-out electrical box. Designed and built in accordance with ISO 9001. Coils Both DX and Freecool coils are made up of 3/8” copper tube, DX coils are inner grooved, with

aluminium fins at 12 fpi. Arranged in a ‘V’ formation for downflow and an ‘A’ formation for upflow, and fitted with stainless steel condensate-trays.An Electronic Expansion Valve option is available.

Compressors Fully hermetic scroll compressors, installed with AV mounts on a robust frame in the right hand service section, out of the air-stream. Each fitted with back-seating isolating valves with an oil level sight glass on larger models. High and low pressure switches are provided.

Ambicool Provides free or partially free cooling by exploiting low ambient conditions. Typically reduces running time and energy costs by 70% in northern Europe. (F version)

VRF Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increased compressor life and greater cooling control.

Condensers Water Cooled, compact pressed stainless steel plate heat exchanger, provides high velocity and low pressure drop.

Fans Low speed, double-inlet, double-width, forward curved fans. Individual EFF1 motors with adjustable belt drive. Quiet "sealed for life" ball or roller bearings and anti-vibration rubber gasket.

Filters Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier Electrode boiler type with proportional control. Heaters Electric elements with stainless steel fins as standard, two or three stage heating control.

LPHW also available. Controls Denco C3-05 controls as standard. Powerful microprocessor controller with graphical liquid

crystal display. Full range of communications interfaces available. Ancillaries A wide range of matching optional extras is available.

Controller and Isolator positions for Models 44 to 94 A,W & F

Denotes Controller and Isolator position on Downflow units

Denotes Controller and Isolator position on Upflow units

Page 13: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide E RANGE UPFLOW AND DOWNFLOW A, W AND F VERSIONS

PR-2006-0294-GB Subject to modifications 01/2007 11

ALL Versions 24 34 44 54 64 74 84 94

Airflow m³/s 2.2 2.6 3.4 4.3 5.6 6.2 6.7 7.5

Standard Scroll ZR Compressors No.

48K 2

81K 2

81K 2

12M 2

12M 2

81K 4

81K 4

12M 4

Heating Steps - Heating Capacity kW

2 12.0

2 12.0

2 12.0

2 12.0

3 18.0

3 18.0

3 18.0

3 18.0

Humidifier Capacity kg/hr Humidifier Power kW

8 6.0

8 6.0

15 11.3

15 11.3

15 11.3

15 11.3

15 11.3

15 11.3

Number of Filters - 2 2 3 3 4 4 5 5

“A” Version 24 34 44 54 64 74 84 94

Total NETT Duty kW Sensible Duty kW

26.8 25.6

37.3 31.7

40.8 39.1

57.9 50.2

61.6 59.0

79.0 69.5

82.7 77.3

109.2 90.7

Standard A/C DCRA Condensers ‡ No.

21-6 2

21-6 2

21-6 2

32-6 2

32-6 2

50-6 2

50-6 2

50-6 2

Discharge Connection ins Liquid Connection ins

3/4 1/2

7/8 1/2

7/8 5/8

1-1/8 5/8

1-1/8 3/4

1-1/8 3/4

1-1/8 3/4

1-1/8 3/4

Full Load Current Amps 36.4 47.4 61.1 73.7 80.1 96.2 96.2 121.4

Nominal Weight kg 520 535 770 795 1045 1090 1220 1230

“W” Version 24 34 44 54 64 74 84 94

Total NETT Duty kW Sensible Duty kW

26.3 25.2

38.6 32.2

42.8 40.6

59.7 50.9

65.5 62.1

78.7 69.3

82.7 77.3

115.5 93.4

Standard W/C B- Condensers No.

10/30 2

10/40 2

10/40 2

35/20 2

35/30 2

35/30 2

35/30 2

35/40 2

Condenser Water In/Out Connections mm

28 28 28 42 54 54 54 54

Full Load Current Amps 34.1 45.1 58.8 71.4 77.8 90.6 90.6 115.8

Nominal Weight kg 535 550 860 890 1075 1130 1280 1305

“F” Version (at m³/s) 24 34 44 54 (4.20) 64 74 (6.00) 84 94 (7.30)

Total NETT Duty kW Sensible Duty kW

24.0 23.3

35.3 30.5

39.1 37.7

54.8 48.1

59.9 57.5

71.7 65.2

75.3 72.0

106.7 88.9

Standard W/C B- Condensers No.

10/30 2

10/40 2

10/40 2

35/20 2

35/30 2

35/30 2

35/30 2

35/40 2

Coolant In/Out Connections mm

35 35 42 42 54 54 54 54

Full Load Current Amps 34.1 45.1 58.8 71.4 77.8 90.6 90.6 115.8

Nominal Weight kg 720 740 1165 1200 1480 1525 1705 1760

All Duties are NETT, based on Downflow Units with standard airflow at 24°C, 45%RH, standard filtration (EU4 – G4), 50 Pa external static pressure and the following: - “A” Version – 32°C Ambient Temperature, Refrigerant R407C, suction line loss 0.5K. - “W” Version – Condenser Water at 30°C, temperature rise 8K, Refrigerant R407C, suction line loss 0.5K. - “F” Version – Coolant: 25% ethylene glycol solution, temperature in at 40°C, temperature rise 8K, Refrigerant R407C, suction

line loss 0.5K. ‡ Quiet / Residential Condensers are available as an alternative to the standard versions stated, please enquire for details. Humidifier details (all units): Feed – 15mm, Drain – 22mm. Filter Sizes (all units): 640 mm x 525 mm x 100 mm. VRF option available on all versions. Full Load Current is worst case phase current for components that can be selected to operate at any one time by the automatic control system, each component operating at “maximum load conditions”.

Page 14: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

E RANGE Product Guide UPFLOW AND DOWNFLOW X AND C VERSIONS

12 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW U/D 24/34 U/D 44/54 U/D 64/74

1940

830 1275 1865 2450

U/D 84/94

3040

Main Features Airflow Upflow and Downflow models, with various return and discharge configurations. Construction Rigid Aluzink frame with Class ‘O’ insulated panels. Serviceable exclusively from the

front, due to swing-out electrical box. Designed and built in accordance with I SO 9001.

Coils Both DX and Freecool coils are made up of 3/8” of copper tube, DX coils are inner grooved, with aluminium fins at 12 fpi. Arranged in a ‘V’ formation for downflow and an ‘A’ formation for upflow, and fitted with stainless steel condensate-trays. A three port modulating valve is fitted to the “C”version units.

Fans Low speed, double-inlet, double-width, forward curved fans. Individual EFF1 motors with adjustable belt drive. Quiet "sealed for life" ball or roller bearings and anti-vibration rubber gasket.

Filters Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier Electrode boiler type with proportional control. Heaters Electric elements with aluminium fins as standard, two or three stage heating control.

LPHW also available. Controls Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries A wide range of matching optional extras is available.

Page 15: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide E RANGE UPFLOW AND DOWNFLOW X AND C VERSIONS

PR-2006-0294-GB Subject to modifications 01/2007 13

ALL Versions 24 34 44 54 64 74 84 94

Airflow m³/s 2.2 2.6 3.4 4.3 5.6 6.2 6.7 7.5

Heating Steps - Heating Capacity kW

2 12.0

2 12.0

2 12.0

2 12.0

3 18.0

3 18.0

3 18.0

3 18.0

Humidifier Capacity kg/hr Humidifier Power kW

8 6.0

8 6.0

15 11.3

15 11.3

15 11.3

15 11.3

15 11.3

15 11.3

Number of Filters - 2 2 3 3 4 4 5 5

“X” Versions 24 34 44 54 64 74 84 94

Airflow m³/s 2.2 2.6 3.4 4.3 5.6 6.2 6.7 7.5

Total NETT Duty kW Sensible Duty kW

29.3 27.0

34.4 30.5

47.8 42.9

59.9 51.0

64.0 61.0

73.0 67.0

85.7 78.6

92.7 83.8

Standard Cond Unit No.

CM61 2

CP72 2

CL90 2

CL12 2

CL12 2

CL16 2

CP90 4

CL90 4

Suction Connection ins Liquid Connection ins

7/8 1/2

1-1/8 1/2

1-1/8 5/8

1-3/8 5/8

1-3/8 3/4

1-3/8 3/4

1-3/8 3/4

1-5/8 3/4

Full Load Current Amps 41.7 47.3 67.6 73.2 79.6 91.0 103.6 109.2

Nominal Weight kg 345 345 485 485 735 735 795 795

All Duties are NETT, based on Downflow Units with standard airflow at 24°C, 45%RH, standard filtration (EU4 – G4), 50 Pa external static pressure, 32°C ambient temperature, Refrigerant R407C, suction line loss 1.5K.

“C” Versions 24 34 44 54 64 74 84 94

Airflow m³/s - 2.6 - 4.3 - 6.2 - 7.5

Total GROSS Duty kW Sensible Duty kW

- -

36.9 33.2

- -

62.1 54.8

- -

87.4 77.0

- -

108.0 95.1

Chilled Water In/Out Connections mm

- -

35

- -

42

- -

54

- -

54

Chilled Water Flow l/s Number of Valves - Pressure Loss kPa

- - -

1.8 1

80

- - -

3.0 1

85

- - -

4.2 1

84

- - -

5.1 1 94

Full Load Current Amps - 37.1 - 50.8 - 65.9 - 65.9

Nominal Weight kg - 345 - 485 - 735 - 795

All Duties are GROSS, based on Downflow Units with standard airflow at 24°C, 45%RH, standard filtration (EU4 – G4), 50 Pa external static pressure and the following; - Chilled water in 7°C and temperature rise of 5K. Humidifier details (all units): Feed – 15mm, Drain – 22mm. Filter Sizes (all units): 640 mm x 525 mm x 100 mm. VRF option available up to model 94 on all versions. Full Load Current is worst case phase current for components that can be selected to operate at any one time by the automatic control system, each component operating at “maximum load conditions”.

Page 16: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

E RANGE Product Guide UPFLOW AND DOWNFLOW DX / CW COMBICOOL MODELS

14 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW U/D 34 U/D 54 U/D 74

1940

800

1915

2500

3090

U/D 94

1965

3980

Main Features Airflow Upflow and Downflow models, with various return and discharge configurations. Construction Rigid Aluzink frame with Class ‘O’ insulated panels. Serviceable exclusively from the

front, due to swing-out electrical box. Designed and built in accordance with ISO 9001.

Coils Both DX and Chilled Water coils are made up of 3/8” copper tube, DX coils are inner grooved, with aluminium fins at 12 fpi. Arranged in a ‘V’ formation for downflow and an ‘A’ formation for upflow, and fitted with stainless steel condensate-trays. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C”version units.

Compressors Fully hermetic scroll compressors, installed with AV mounts on a robust frame in the right hand service section, out of the air-stream. Each fitted with back-seating isolating valves with an oil level sight glass on larger models. High and low pressure switches are provided, and a LP alarm delay kit standard on A versions.

VRF Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increased compressor life and greater cooling control.

Fans Low speed, double-inlet, double-width, forward curved fans. Individual EFF1 motors with adjustable belt drive. Quiet "sealed for life" ball or roller bearings and anti-vibration rubber gasket.

Filters Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier Electrode boiler type with proportional control. Heaters Electric elements with stainless steel fins as standard, two or three stage heating

control. LPHW also available. Controls Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries A wide range of matching optional extras is available.

Controller and Isolator positions for Models 54,74 & 94

Denotes Controller and Isolator position on Downflow units

Denotes Controller and Isolator position on Upflow units

Page 17: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide E RANGE UPFLOW AND DOWNFLOW DX / CW COMBICOOL MODELS

PR-2006-0294-GB Subject to modifications 01/2007 15

ALL Versions 24 34 44 54 64 74 84 94

Airflow m³/s 2.2 2.6 3.4 4.2 5.6 6.0 6.7 7.3

Heating Steps - Heating Capacity kW

2 12.0

2 12.0

2 12.0

2 12.0

3 18.0

3 18.0

3 18.0

3 18.0

Humidifier Capacity kg/hr Humidifier Power kW

8 6.0

8 6.0

15 11.3

15 11.3

15 11.3

15 11.3

15 11.3

15 11.3

Number of Filters - 2 2 3 3 4 4 5 5

“DX” Versions 24 34 44 54 64 74 84 94

Total NETT Duty kW Sensible Duty kW

29.1 26.8

34.1 30.2

47.6 42.7

59.5 50.3

63.5 60.4

72.4 65.9

85.1 77.9

91.9 82.5

Standard Cond Unit No.

CM61 2

CP72 2

CL90 2

CL12 2

CL12 2

CL16 2

CP90 4

CL90 4

Suction Connection ins Liquid Connection ins

7/8 1/2

1-1/8 1/2

1-1/8 5/8

1-3/8 5/8

1-3/8 3/4

1-3/8 3/4

1-3/8 3/4

1-5/8 3/4

Full Load Current Amps 40.7 43.7 67.0 77.0 83.4 91.4 101.4 107.0

“DA” Version 24 34 44 54 64 74 84 94

Total NETT Duty kW Sensible Duty kW

26.6 25.4

37.0 31.4

40.5 38.8

57.5 49.4

61.0 58.5

78.4 68.3

82.0 76.6

108.4 89.4

Standard Scroll ZR Compressors No.

48K 2

81K 2

81K 2

12M 2

12M 2

81K 4

81K 4

12M 4

Standard A/C DCRA Condensers ‡ No.

21-6 2

21-6 2

21-6 2

32-6 2

32-6 2

50-6 2

50-6 2

50-6 2

Discharge Connection ins Liquid Connection ins

3/4 1/2

7/8 1/2

7/8 5/8

1-1/8 5/8

1-1/8 3/4

1-1/8 3/4

1-1/8 3/4

1-1/8 3/4

Full Load Current Amps 37.1 47.4 61.1 73.7 80.1 96.2 96.2 121.0

“DW” Version 24 34 44 54 64 74 84 94

Total NETT Duty kW Sensible Duty kW

26.1 25.0

38.3 32.0

42.6 40.4

59.2 50.2

65.0 61.5

78.1 68.2

82.0 76.6

114.5 92.08

Standard Scroll ZR Compressors No.

48K 2

81K 2

81K 2

12M 2

12M 2

81K 4

81K 4

12M 4

Standard W/C B- Condensers No.

10/30 2

10/40 2

10/40 2

35/20 2

35/30 2

35/30 2

35/30 2

35/40 2

Condenser Water In/Out Connections mm

28

28

28

42

54

54

54

54

Full Load Current Amps 34.1 45.1 58.8 71.4 77.8 90.6 90.6 115.8

“DC” Versions 24 34 44 54 64 74 84 94

Total GROSS Duty kW Sensible Duty kW

- -

36.9 33.2

- -

60.9 53.9

- -

85.1 75.3

- -

105.7 93.3

Chilled Water In/Out Connections mm

- -

35

- -

42

- -

54

- -

54

Chilled Water Flow l/s Number of Valves - Pressure Loss kPa

- - -

1.8 1

80

- - -

3.0 1

85

- - -

4.2 1 84

- - -

5.1 1

94

All Duties are NETT, based on Downflow Units with standard airflow at 24°C, 45%RH, standard filtration (EU4 – G4), 50 Pa external static pressure and the following: - “DX” Version – 32°C Ambient Temperature, Refrigerant R407C, suction line loss 1.5K. - “DA” Version – 32°C Ambient Temperature, Refrigerant R407C, suction line loss 0.5K. - “DW” Version – Condenser Water at 30°C, temperature rise 8K, Refrigerant R407C, suction line loss 0.5K. - “DC” Version – Duty is GROSS, chilled water at 7°C, temperature rise 5K. ‡ Quiet / Residential Condensers are available as an alternative to the standard versions stated, please enquire for details. VRF option available on all versions. Full Load Amps is worst case phase current for components that can be selected to operate at any one time by the automatic control system.

Page 18: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

TW RANGE Product Guide

16 PR-2006-0294-GB Subject to modifications 01/2007

Main Features Airflow: Upflow and Downflow models, with various return and discharge configurations. Construction: Rigid “Aluzink” frame with class ”O” insulated heavy duty, weatherproof, lift-off panels.

Serviced exclusively from the front. Designed and built in accordance with BS EN ISO 9001.

Coils: The coils are made up of 3/8” copper tubes, DX coils are inner grooved, with aluminium fins and fitted with stainless steel condensate trays. Coils are inclined for maximum face area, minimum pressure drop and noise reduction. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C” version units.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Each fitted with back-seating isolating valves with an oil level sight glass on larger models and high and low pressure switches.

VRF: Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increase in compressor life and greater cooling control. This is standard for models 23 – 42.

Condensers: Water Cooled versions use compact brazed pressed stainless steel heat exchangers providing high velocity and low pressure drop.

Fans: Models 3 – 5 have one backward-curved, direct-drive centrifugal fan, with a single inlet and integral single speed motor. Models 8 – 42 have one, two or three double width forward curved fans with double inlets and an integral 3-speed direct-drive motor, with the lowest speed for dehumidification.

Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with stainless steel fins and safety cut out. LPHW heating

also available. Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries: A wide range of matching optional extras is available.

3 No.Denco Air Cooled Condensers

3 No.Denco TW Range Units

Typical Installation

Page 19: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide TW RANGE

PR-2006-0294-GB Subject to modifications 01/2007 17

All Versions 3 4 5 8 10 12 17 19 21 23 28 32 37 42

Airflow m³/s m³/hr Number of Fans -

0.30 1080

1

0.35 1260

1

0.42 1510

1

0.70 2520

1

0.80 2880

1

1.00 3600

1

1.40 5040

2

1.60 5760

2

1.80 6480

2

2.00 7200

2

2.17 7810

2

2.50 9000

3

2.90 10440

3

3.3011880

3

Heating Capacity kW 3.0 6.0 12.0 12.0

Filters (Std EU4) No. Size: L x W x D mm

1 455 x 455 x 50

1 885 x 505 x 50

2 885 x 505 x 50

3 885 x 540 x 50

“X” Versions 3 4 5 8 10 12 17 19 21 23 28 32 37 42

Total NETT Duty kW Sensible Duty kW

4.57 4.05

4.69 4.39

5.54 5.09

9.36 8.59

11.43 9.95

13.24 11.49

17.33 16.49

19.17 18.24

22.15 20.64

25.84 23.00

28.65 24.70

30.62 29.05

35.59 33.14

40.8936.85

Suction Connection ins Liquid Connection ins

3/4 3/8

3/4 3/8

3/4 3/8

7/8 1/2

7/8 1/2

1-1/8 1/2

1-1/8 5/8

1-1/8 5/8

1-1/8 5/8

1-1/8 5/8

1-3/8 5/8

1-3/8 3/4

1-3/8 3/4

1-3/83/4

Condensing Unit - CT18 CT18 CT22 CS40 CM48 CM61 CP72 CP81 CL90 CL11 CL12 CL12 CL16 CL19

Full Load Current Amps 17.4 19.2

17.4 19.2

17.4 19.2

19.1 21.0

20.1 22.1

21.9 24.2

25.8 28.6

25.8 28.6

27.6 30.5

29.7 33.1

31.8 35.5

31.8 35.5

35.6 40.5

39.244.6

Weight kg 135 210 345 445

“A” Versions 3 4 5 8 10 12 17 19 21 23 28 32 37 42

Total NETT Duty kW Sensible Duty kW

- - 5.66 5.14

8.76 8.30

12.10 10.24

14.16 11.84

16.18 15.61

18.32 17.59

20.78 19.77

23.83 22.12

27.32 24.15

31.64 29.72

35.76 33.21

39.3536.21

Discharge Connection ins Liquid Connection ins

- - 1/2 3/8

3/4 1/2

3/4 1/2

3/4 1/2

7/8 5/8

7/8 5/8

7/8 5/8

7/8 5/8

1-1/8 5/8

1-1/8 3/4

1-1/8 3/4

1-1/83/4

Scroll Compressor ZR - - 22 34 48 61 61 72 81 48† 61† 61† 72† 81†

Std Condenser ‡ DCRA - - 08-6 13-6 21-6 21-6 26-6 26-6 32-6 32-6 32-6 50-6 50-6 50-6

Full Load Current Amps - - 20.2 19.9 20.9 23.0 32.7 34.0 36.1 37.8 42.0 47.6 50.2 54.4

Weight kg - - 165 255 445 520

“W” Versions 3 4 5 8 10 12 17 19 21 23 28 32 37 42

Total NETT Duty kW Sensible Duty kW

- - 5.73 5.17

8.74 8.28

11.73 10.08

13.90 11.76

15.71 15.25

18.01 17.35

20.30 19.33

23.55 22.01

27.66 24.29

30.10 28.65

34.43 32.57

38.3435.79

Cooling Water Connections mm

- - 22

28

28

28

35

35

35

35

35

42

42

42

Scroll Compressor ZR - - 22 34 48 61 61 72 81 48† 61† 61† 72† 81†

Std W/C Condenser B - - 8/20 8/30 8/30 8/30 10/30 10/30 10/30 10/30 10/30 10/40 10/40 10/40

Full Load Current Amps 19.2 19.9 20.9 23.0 31.7 33.0 35.1 36.8 41.0 42.0 44.6 48.8

Weight kg - - 175 270 460 535

“C” Versions 3 4 5 8 10 12 17 19 21 23 28 32 37 42

Total GROSS Duty kW Sensible Duty kW

- - 5.82 5.36

- - 13.87 12.53

- - - - 28.65 26.38

- - 45.3641.26

Chilled Water Connections mm

-

-

22

-

-

28

-

-

-

-

35

-

-

42

Chilled Water Flow l/s Pressure Loss kPa

- - 0.3 50

- - 0.7 58

- - - - 1.4 65

- - 2.280

Full Load Current Amps - - 19.2 - - 19.9 - - - - 28.6 - - 29.6

Weight kg - - 140 - - 215 - - - - 355 - - 430

All Cooling performances are based on Downflow Units with standard airflow at 24°C, 45%RH, standard EU4 (G4) filtration, 50 Pa minimum external static pressure, standard Condensers / Condensing Units and the following: - “X” Versions – 1.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “A” Versions – 0.5K suction line loss, Refrigerant R407C, 32°C ambient temperature. - “W” Versions – 0.5K suction line loss, Refrigerant R407C, condensing water in at 30°C and rise 8K. - “C” Versions – Chilled Water at 7°C and rise 5K. Humidifier details for ALL Units: Capacity – 3 kg/hr, Power – 2.3 kW, Feed Connection Size – 15mm, Drain Size – 22mm. “X”, “A” and “W” Versions use Scroll type compressors. † Models 23 – 42 “A” and “W” are VRF as standard. ‡ Quiet / Residential Condensers are available as an alternative to the standard versions stated, please enquire for details. Full Load Current is worst case phase current for components that can be selected to operate at any one time by the automatic control system, each component operating at “maximum load conditions”.

Page 20: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

EP RANGE Product Guide

18 PR-2006-0294-GB Subject to modifications 01/2007

Models: EP3 and EP6 Models: EP9 and EP12

Conditioned Air Out

Conditioned Air Out

Fresh Air In

Conditioned Air In

1880

Fresh Air In

Conditioned Air In

1880

Condenser Air Out

Condenser Air Out

830 530 1260 530

Models: EP15 and EP18

Conditioned Air Out

Fresh Air In

Conditioned Air In

2040

Condenser Air Out

1760 530

Main Features Airflow: Upflow models, with return and discharge outlets for through wall operation. Construction: Steel cabinet with graphite (RAL 7024) finish. Insulated removable panels with class

“O” foam. Serviced exclusively from the outside of the unit. Designed and built in accordance with BS EN ISO 9001.

Coils: The DX coils are made up of 3/8” inner grooved copper tubes with aluminium fins and fitted with stainless steel condensate trays. Coils are inclined for maximum face area, minimum pressure drop and noise reduction.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Freecooling: Direct low ambient fresh air free cooling is provided via a modulating damper section. Fans: Models have one, two or three backward-curved, direct-drive centrifugal fans, with a

single inlet and integral single speed motor. Special DC fans are available to run from backup power supplies.

Filters: Disposable pleated filters to EU3 (G3) as standard for conditioned air. Fly screen for fresh air inlet is also fitted.

Heaters: Electric heating elements with stainless steel fins and safety cut out. Controls: Electronic microprocessor controls giving digital temperature read out, set-point

change facility, high and low temperature alarms and indication of on-off status. All parameters are factory set.

Ancillaries: A wide range of matching optional extras is available.

Please Note:

The EP - ‘Externally Packaged’ range is specifically designed for full outdoor installation and none of the system components are located indoors.

As an alternative, a range of RP – ‘Room Packaged’ units designed for full indoor installation is also available. In this configuration none of the system components are located outdoors.

Details of the RP range are available on request.

Page 21: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide EP RANGE

PR-2006-0294-GB Subject to modifications 01/2007 19

3 6 9 12 15 18

Nominal Airflow m³/s m³/hr No. of Evaporator Fans - No. of Condenser Fans -

0.3 1080

1 1

0.4 1440

1 1

0.6 2160

2 2

0.8 2880

2 2

1.0 3600

3 3

1.2 4320

3 3

Total Duty kW Sensible Duty kW

5.1 3.9

7.3 6.1

10.5 9.2

13.8 12.2

15.8 15.2

21.2 18.7

Heating Steps - Heating Capacity kW

1 1.5

1 1.5

2 3.0

2 3.0

2 3.0

2 3.0

Filters (Std – G3) - Length mm Width mm Depth mm

1 750 220 20

1 750 220 20

1 1075 220 20

1 1075 220 20

1 1575 220 20

1 1575 220 20

Scroll Compressor ZR Number fitted -

22K 1

28K 1

48K 1

61K 1

72K 1

81K 1

Full Load Current Amps 7.5 7.5 9.1 11.2 13.4 15.5

Weight kg 180 180 270 270 360 360

Cooling performances are based on: - Standard airflow and filtration (G3) - Minimum of 50 Pa external static - Air on at 24°C, 45%RH - Ambient temperature 32°C Full Load Current depends on worst condition on any single phase when operating automatically and could be: - Fans + Cooling - Fans + Heating

Page 22: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

IP RANGE Product Guide Models 8 - 21

20 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW D8-12 D17-21

1940

685 1250 1840

Main Features General: Packaged systems with integral air-cooled condensers. Airflow: Upflow and Downflow models, with various return and discharge configurations. Construction: Rigid “Aluzink” frame with class ”O” insulated hinged panels. Serviced exclusively

from the front. Designed and built in accordance with BS EN ISO 9001. Coils: The DX coils are made up of 3/8” inner grooved copper tubes with aluminium fins

and fitted with stainless steel condensate trays. Coils are inclined on Models 8 – 42 and are “V” (downflow) or “A” (upflow) on Models 24 and 34. An Electronic Expansion Valve option is available.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Each fitted with back-seating isolating valves with an oil level sight glass on larger models. High and low pressure switches provided, and an LP alarm delay kit is standard on “A” versions for low temperature applications.

VRF: Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increase in compressor life and greater cooling control.

Fans: All models have one or two double width forward curved fans with double inlets and an integral 3-speed direct-drive motor, with the lowest speed for dehumidification. Models 24 and 34 only have double inlet, double width forward curved fans with individual motors with adjustable belt drives.

Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with stainless steel fins as standard with one or two stage

heating control, and safety cut out. LPHW heating also available. Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Freecooling: A run-around coil arrangement can be incorporated to provide indirect freecooling at

low external ambient conditions. Ancillaries: A wide range of matching optional extras is available.

Page 23: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide IP RANGE Models 8 - 21

PR-2006-0294-GB Subject to modifications 01/2007 21

8 10 12 17 19 21

Standard Airflow m³/s m³/hr

0.70 2520

0.80 2880

1.00 3600

1.40 5040

1.60 5760

1.80 6480

Number of Fans - 1 1 1 2 2 2

Total NETT Duty kW Sensible Duty kW

9.0 8.4

11.8 10.1

13.7 11.7

15.0 14.7

16.8 16.5

18.3 17.9

Heating Steps - Heating Capacity kW

1 6.0

1 6.0

1 6.0

2 12.0

2 12.0

2 12.0

Humidifier Capacity kg/hr Humidifier Power kW Water Feed Size mm Drain Size mm

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

Filters (Std – EU4) - Length mm Width mm Depth mm

2 442 505 50

2 442 505 50

2 442 505 50

2 885 505 50

2 885 505 50

2 885 505 50

Scroll Compressor ZR Number fitted -

34K 1

48K 1

61K 1

61K 1

72K 1

81K 1

Full Load Current Amps 19.9 20.9 23.0 32.7 34.0 36.1

Weight kg 370 370 370 560 560 560

Cooling performances are NETT and based on: - Standard airflow and filtration (EU4) - Minimum of 50 Pa external static - Air on at 24°C, 45%RH - Ambient temperature 32°C Full Load Current depends on worst condition on any single phase when operating automatically and could be: - Fan + Cooling + Humidifying - Fans + Heating + Humidifying - Fans + Cooling + Re-heating (Dehum)

Page 24: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

IP RANGE Product Guide Models 23 - 42

22 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW U/D23-28 U/D32-37-42

1940

654 2450 3050

END VIEW U/D 24-34

1940

800

2502

Main Features General: Packaged systems with integral air-cooled condensers. Airflow: Upflow and Downflow models, with various return and discharge configurations. Construction: Rigid “Aluzink” frame with class ”O” insulated hinged panels. Serviced exclusively from

the front. Designed and built in accordance with BS EN ISO 9001. Coils: The DX coils are made up of 3/8” inner grooved copper tubes with aluminium fins and

fitted with stainless steel condensate trays. Coils are inclined on Models 8 – 42 and are “V” (downflow) or “A” (upflow) on Models 24 and 34. An Electronic Expansion Valve option is available.

Compressors: Fully hermetic scroll compressors, installed with AV mounts. Each fitted with back-seating isolating valves with an oil level sight glass on larger models. High and low pressure switches provided, and an LP alarm delay kit is standard on “A” versions for low temperature applications.

VRF: Variable Refrigerant Flow. With two compressors per circuit, an intermediate cooling stage can be achieved which offers significantly higher efficiency, economy, increase in compressor life and greater cooling control.

Fans: All models have two or three double width forward curved fans with double inlets and an integral 3-speed direct-drive motor, with the lowest speed for dehumidification. Models 24 and 34 only have double inlet, double width forward curved fans with individual motors with adjustable belt drives.

Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with stainless steel fins as standard with one or two stage

heating control, and safety cut out. LPHW heating also available. Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Freecooling: A run-around coil arrangement can be incorporated to provide indirect freecooling at low

external ambient conditions. Ancillaries: A wide range of matching optional extras is available.

Page 25: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide IP RANGE Models 23 - 42

PR-2006-0294-GB Subject to modifications 01/2007 23

23 28 32 37 42 24 34 Standard Airflow m³/s m³/hr

2.00 7200

2.17 7810

2.50 9000

2.90 10440

3.30 11880

2.20 7920

2.60 9360

Number of Fans - 2 2 3 3 3 1 1

Total NETT Duty kW Sensible Duty kW

24.1 22.3

27.8 24.3

29.6 28.3

33.0 31.5

35.8 34.1

26.2 25.1

36.0 31.2

Heating Steps - Heating Capacity kW

2 12.0

2 12.0

2 12.0

2 12.0

2 12.0

2 12.0

2 12.0

Humidifier Capacity kg/hr Humidifier Power kW Water Feed Size mm Drain Size mm

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

3.0 2.3 15 22

8.0 6.0 15 22

8.0 6.0 15 22

Filters (Std – EU4) - Length mm Width mm Depth mm

2 885 505 50

2 885 505 50

3 885 505 50

3 885 505 50

3 885 505 50

2 640 525 100

2 640 525 100

Scroll Compressor ZR Number fitted -

48K 2

61K 2

61K 2

72K 2

81K 2

48K 2

81K 2

Full Load Current Amps 41.8 46.0 46.0 48.6 52.8 38.1 49.1

Weight kg 665 665 740 740 740 790 790 Cooling performances are NETT and based on: - Standard airflow and filtration (EU4) - Minimum of 50 Pa external static - Air on at 24°C, 45%RH - Ambient temperature 32°C Full Load Current depends on worst condition on any single phase when operating automatically and could be: - Fan + Cooling + Humidifying - Fans + Heating + Humidifying - Fans + Cooling + Re-heating (Dehum)

Page 26: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

HS RANGE Product Guide

24 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW U34 X/C U54 X/C

1940

800 1275 1865

END VIEW U74 X/C U94 X/C

1940

800

2450 3040

Main Features Airflow: Upflow models, with various return and discharge configurations. Construction: Rigid “Aluzink” frame with class ”O” insulated hinged panels. Serviced exclusively

from the front, due to swing-out electrical box. Designed and built in accordance with BS EN ISO 9001.

Coils: The coils are made up of 3/8” copper tubes, DX coils are inner grooved, with aluminium fins at 12 fpi. The coils are arranged in a “A” formation and fitted with stainless steel condensate trays. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C”version units.

Fans: Belt driven fans are either double-inlet, double-width, forward or backward curved dependent on the static required, whilst direct drive fans are double-inlet, double-width, backward curved. Belt driven fans have individual EFF1 motors with adjustable belt drives. All fans are fitted with quiet “sealed for life” ball or roller bearings on anti-vibration mountings.

Filters: Disposable pleated filters to EU7 (F7) as standard. Humidifier: Electrode boiler type with proportional control. Heaters: Electric heating elements with stainless steel fins as standard with two or three stage

heating control, and safety cut out. LPHW heating also available. Controls: Denco C3-05 controls as standard. A three port modulating valve is fitted to the “C”

version. By-pass: Coil by-pass damper can be fitted for adjustment of air off condition. Ancillaries: A wide range of matching optional extras is available.

Page 27: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide HS RANGE

PR-2006-0294-GB Subject to modifications 01/2007 25

All Versions U34 U54 U74 U94

Nominal Airflow m³/s Max. External Static Pa

2.0 800

3.0 800

4.0 800

6.0 800

LPHW Capacity kW LPHW Flow Rate l/s

22.0 0.5

34.0 0.77

45.0 1.0

65.0 1.45

Electric Heater Capacity kW Number of Steps -

12.0 2

12.0 2

18.0 3

18.0 3

Humidifier Capacity kg/hr Humidifier Power kW

8.0 6.0

15.0 11.3

15.0 11.3

15.0 11.3

Full Load Current Amps Locked Rotor Amps

36.1 38.4

49.8 76.8

64.9 115.2

64.9 115.2

Unit Length mm Unit Depth mm Unit Height mm Unit Weight kg

1275 800

1940 345

1865 800

1940 485

2450 800

1940 735

3040 800

1940 795

All Versions U34 U54 U74 U94

Coil Bypass Air % Coil Face Area m²

0 1.2

50 0.6

0 1.8

50 0.9

0 2.4

50 1.2

0 3.2

50 1.6

6 Row Coil Data

Total Cooling kW Sensible Cooing kW

40.6 33.2

20.3 16.6

62.1 50.5

31.0 25.3

82.6 67.4

41.3 33.7

120.0 98.4

60.0 49.2

Unit CW Flow Rate l/s Unit CW Pressure Drop kPa Air Off Temperature °C

1.94 121.4 11.1

0.97 107.9 18.0

2.97 128.0 10.8

1.49 109.6 17.8

3.96 95.7 10.8

1.98 91.5 17.7

5.74 166.4 11.4

2.87 153.318.2

DX Condensing Units - Number Off -

CP81 2

CP81 1

CL12 2

CL12 1

CL19 2

CL19 1

CL12 4

CL122

4 Row Coil Data

Total Cooling kW Sensible Cooing kW

29.2 27.3

14.6 13.6

45.7 41.9

22.9 20.9

60.3 55.8

30.2 27.9

88.3 81.1

44.2 40.6

Unit CW Flow Rate l/s Unit CW Pressure Drop kPa Air Off Temperature °C

1.40 56.9 13.5

0.70 49.8 19.2

2.19 61.5 13.2

1.10 51.3 18.9

2.88 44.9 13.1

1.44 42.6 18.9

4.22 81.6 13.7

2.11 74.5 18.2

DX Condensing Units - Number Off -

CM61 2

CM61 1

CP90 2

CP90 1

CL11 2

CL11 1

CP90 4

CP902

2 Row Coil Data

Total Cooling kW Sensible Cooing kW

19.9 19.2

9.9 9.6

31.0 29.6

15.5 14.8

41.1 39.4

20.5 19.7

57.2 55.7

28.6 27.8

Unit CW Flow Rate l/s Unit CW Pressure Drop kPa Air Off Temperature °C

0.95 41.1 16.8

0.48 37.6 20.8

1.48 47.7 16.5

0.74 42.9 20.6

1.97 35.4 16.5

0.98 34.4 20.6

2.74 46.9 17.2

1.37 43.9 21.0

DX Condensing Units - Number Off -

CS40 2

CS40 1

CM61 2

CM61 1

CP72 2

CP72 1

CM48 4

CM482

All Duties are GROSS with standard airflow at 24°C, 45%RH, standard filtration (EU7 – F7), 50 Pa external static pressure and the following: - “C” Version - Chilled water in 7°C and temperature rise of 5K. - “X” Version - 32°C ambient temperature, Refrigerant R407C, suction line loss 1.5K. - Locked Rotor Amps with no inverter. Full Load Current depends on worst condition on any single phase when operating automatically and could be: - Fan + Cooling + Humidifying - Fans + Heating + Humidifying - Fans + Cooling + Re-heating (Dehum)

Page 28: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

ZONE UNIT RANGE Product Guide

26 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW

ZD/ZU12 ZD/ZU28 ZD/ZU42

1940

654 (ZD) 647 1247 1847 854 (ZU)

Main Features Airflow: Supply and return via floor void and downflow models, with various return and

discharge configurations. Construction: Rigid welded angle steel frame with class ”O” insulated hinged panels. Serviced

exclusively from the front. Designed and built in accordance with BS EN ISO 9001. Coils: The coils are made up of 3/8” copper tubes, DX coils are inner grooved, with

aluminium fins and fitted with stainless steel condensate trays. Coils are inclined for maximum face area, minimum pressure drop and noise reduction. An Electronic Expansion Valve option is available. A three port modulating valve is fitted to the “C” version units.

Fans: Units have either one, two or three double-width forward curved fans with double

inlets and frequency converted variable speed motors. Filters: Disposable pleated filters to EU4 (G4) as standard, EU7 (F7) available. Humidifier: Electrode boiler type with proportional control. Heaters: LPHW heater battery as standard. Other heating options are either electric heating

elements with stainless steel fins and safety cut out or reverse cycle DX (heat pump) heating.

Controls: Denco C3-05 controls as standard. Powerful microprocessor controller with graphical

liquid crystal display. Full range of communications interfaces available. Ancillaries: A wide range of matching optional extras is available.

Page 29: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide ZONE UNIT RANGE

PR-2006-0294-GB Subject to modifications 01/2007 27

Toscana ZU / ZD - All Versions 12 28 42

Coil Face Area m2 0.414 0.864 1.382

Nominal Air Volume No. of Fans Fan Heat Absorbed

m3/s m3/hr - kW

0.5 1800

1 0.18

1.0 3600

2 0.35

1.5 5400

3 0.51

LPHW (if fitted): Heating Capacity Flowrate LPHW In Temperature LPHW Out Temperature LPHW Mod Valve: Valve Size

kW l/s °C °C ins

7.0 0.15 82 71

3/4

16.0 0.35 82 71

1

23.0 0.5 82 71 1

Electric Reheat (if fitted): No. of Steps Capacity

- kW

1

3.0

2

6.0

2

6.0

Humidifier Capacity (if fitted): Power

kg/hr kW

3.0 2.3

3.0 2.3

3.0 2.3

Filters (Standard G4): No. of Pieces Length Width Depth

- mm mm mm

2

442 505 50

2

885 505 50

3

885 540 50

"X" Versions

Sensible Cooling Duty kW 7.8 16.0 24.5

Standard Cond Unit Number Off

- -

CS28 1

CP61 1

CL90 1

Suction Connection Liquid Connection

ins ins

1-1/8 1/2

1-3/8 5/8

1-3/8 3/4

Full Load Current Amps 10.2 15.7 22.8

Weight kg 210 345 420

"C" Versions

Sensible Cooling Duty kW 8.0 15.9 24.7

Connections: Chilled Water In Chilled Water Out Humidifier Feed Drain

mm mm mm mm

22 22 15 22

28 28 15 22

35 35 15 22

Chilled Water Flow Chilled Water Pressure Loss

l/s kPa

0.3 16

0.6 15

1.0 20

Full Load Current Amps 5.0 5.0 6.0

Weight kg 215 355 430 “X” Version – 32°C Ambient Temperature, Refrigerant R407C, suction line loss 1.5K. “C” Version – Chilled Water at 7°C, temperature rise 6K. Full Load Current depends on worst condition on any single phase when operating automatically.

Page 30: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

LECU – LOCAL ENVIRONMENTAL CONTROL UNIT Product Guide

28 PR-2006-0294-GB Subject to modifications 01/2007

Description The Denco Local Environment Control Unit (LECU) is an intelligent, underfloor air distribution terminal, combining the benefits of displacement ventilation, induction and fan coil technologies. When used in conjunction with Denco Zone units, the area served by each LECU is maintained at occupant-defined conditions, by recirculation of a varying mix of room return and underfloor conditioned air. Requiring only a small single-phase power supply, units can be moved around as required to suit ever-changing office layouts, with no more disruption than that caused by the relocation of a desk. It is this flexibility that offers a real alternative to traditional rigid methods of providing air conditioning within the workspace.

Main Features Airflow: Variable between a nominal 0.1 m3/s giving 1.0 kW cooling at a noise level of NR20

and a nominal 0.2 m3/s giving 2.5 kW cooling at a noise level of NR45. Construction: Components mounted within sheet metal tray, with separate side mounted controls

section. Designed and built in accordance with BS EN ISO 9001. Operation: A modulating damper dictates proportion of room or underfloor air to be supplied,

according to load in the local space, local set point and underfloor air condition. Fans: Dual double inlet, double width forward curved centrifugal fans are directly driven by

a five speed, enclosed motor. Heaters: Although not usually required, the LECU can incorporate a small electric heater

battery to give more precise control. Controls: Units incorporate user-friendly local stand-alone controllers, each complete with large

LCD display. Options are available for networked controls, with or without local display.

Fresh Air: An adjustable orifice gives each LECU a controlled and continuous supply of underfloor oxygenated air at all load conditions, meeting statutory ventilation requirements.

Ancillaries: Air grilles can be supplied to match the height and compliment the colour of any desired floor finish.

Variants: Special “Slimline” units can be supplied using tangential fans, for applications with restricted height raised floor voids.

Local Environmental Control Unit “LECU” The LECU is dimensioned to fit within a standard 600mm x 600mm raised floor tile and can be supplied with matching grilles and surface covering. Units can be positioned as dictated by day-to-day office operational requirements.

“ZU” ZONE UNIT See Zone Unit Range data.

Page 31: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide CA RANGE WATER CHILLERS

PR-2006-0294-GB Subject to modifications 01/2007 29

END VIEW CAT, CAS, CAM and CAP Models CAL Models

B

C

A

A

Main Features Airflow: Horizontal Discharge. Construction: Rigid “Aluzink” steel base enclosed by plastic coated cover and side panels, and

supported by plastic coated steel channel feet. Compressor and electrics housed in a sealed compartment at the left hand end of unit.

Coils: Made from 3/8” grooved copper tubes with aluminium fins at 14 per inch. Evaporator: Brazed pressed stainless steel heat exchanger provides high velocity and low

pressure drop. Compressors: Robust, hermetic scroll type with back-seating isolating valves and crankcase heater.

Internal self-setting overload protection fitted with external high and low pressure switches.

Fans: Plastic-bladed propeller fans mounted on an “Aluzink” steel diaphragm complete with fan guard.

Controls: Electronic microprocessor controller fitted as standard. Ancillaries: A range of matching optional extras is available including on board hydronic modules.

Model CAT-07-1 CAS-10-1 CAM-15-1 CAP-20-1 CAL-30-1 CAL-40-1

Fluid Flowrate l/s l/hr

0.33 1190

0.47 1700

0.70 2510

1.02 3655

1.52 5480

2.13 7650

Inlet Temperature °C Outlet Temperature °C

15.0 10.0

15.0 10.0

15.0 10.0

15.0 10.0

15.0 10.0

15.0 10.0

Cooling Duty kW 6.96 9.90 14.65 21.32 31.97 44.63

Pressure Drop kPa 21.1 42.1 31.7 46.6 40.5 42.9

Ambient Temp °C 32 32 32 32 32 32

Fluid Flowrate l/s l/hr

0.30 1080

0.43 1540

0.63 2275

0.92 3325

1.38 4965

1.94 6985

Inlet Temperature °C Outlet Temperature °C

12.0 7.0

12.0 7.0

12.0 7.0

12.0 7.0

12.0 7.0

12.0 7.0

Cooling Duty kW 6.30 8.96 13.27 19.38 28.97 40.74

Pressure Drop kPa 20.5 37.5 29.0 41.4 36.3 38.6

Ambient Temp °C 32 32 32 32 32 32

Compressor ZR 28K 40K 61K 90K 12M 19M

Length “A” mm Height “B” mm Depth “C” mm Weight kg

1030 590 480 90

1180 690 480 110

1410 850 560 160

1610 910 710 250

2310 910 710 300

2310 910 710 350

Full Load Current Amps Locked Rotor Current Amps

2.5 32

6.9 46

10.5 66

15.4 99

21.8 127

29.9 198

Alternative duties available, please enquire for details. The “CA” Water Chiller modules may be stacked for higher duties, up to 130 kW, using purpose built stacking frames.

Page 32: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

C RANGE Product Guide AIR COOLED CONDENSING UNITS

30 PR-2006-0294-GB Subject to modifications 01/2007

END VIEW CT, CS,CM, CP and CPV Models CL and CLV Models

B

C

A A

Main Features Airflow: Horizontal Discharge. Construction: Rigid “Aluzink” steel base enclosed by plastic coated cover and side panels, and

supported by plastic coated steel channel feet. Compressor and electrics housed in a sealed compartment at the left hand end of unit.

Coils: Made from 3/8” grooved copper tubes with aluminium fins at 14 per inch. Compressors: Robust, hermetic scroll type with back-seating isolating valves and crankcase heater.

Internal self-setting overload protection fitted with external high and low pressure switches.

Fans: Plastic-bladed propeller fans mounted on an “Aluzink” steel diaphragm complete with fan guard.

Model

Duty (kW) R407C

Duty (kW) R134a

FLA 1 ph

FLA 3 ph

A (mm)

B mm

C (mm)

Suction (ins)

Liquid (ins)

Weight(kgs)

CT18 4.52 N/A 8.2 - 3/4 3/8 74

CT22 5.36 3.68 10.3 4.3 1030 590 480 3/4 3/8 75

CT28 6.64 4.75 13.0 5.2 3/4 3/8 77

CS28 7.15 4.95 - 5.2 7/8 1/2 85

CS34 8.24 5.72 - 6.2 1180 690 480 7/8 1/2 85

CS40 9.40 6.54 - 6.9 7/8 1/2 90

CM40 9.90 6.74 - 7.3 1-1/8 5/8 125

CM48 11.89 8.01 - 8.4 1410 850 560 1-1/8 5/8 125

CM61 13.97 10.03 - 10.5 1-1/8 5/8 130

CP61 14.89 10.39 - 10.7 1-1/8 3/4 185

CP72 17.16 12.19 - 12.0 1610 910 710 1-1/8 3/4 185

CP81 18.99 13.43 - 14.1 1-1/8 3/4 190

CP90 21.03 14.45 - 15.4 1-1/8 3/4 215

CL90 23.19 15.24 - 16.8 1-3/8 7/8 245

CL11 27.32 18.53 - 19.4 1-3/8 7/8 245

CL12 31.00 21.21 - 21.8 2310 910 710 1-3/8 7/8 245

CL16 36.77 25.48 - 25.8 1-3/8 7/8 260

CL19 42.51 29.70 - 29.9 1-5/8 7/8 275

CPV48 22.14 15.37 - 15.8 1610 910 710 1-1/8 3/4 200

CLV48 24.76 16.43 - 15.8 1-3/8 7/8 225

CLV61 29.38 20.63 - 21.4 2310 910 710 1-3/8 7/8 225

CLV72 33.82 24.14 - 24.0 1-3/8 7/8 230

CLV81 37.30 26.60 - 28.2 1-3/8 7/8 230

Duties are Evaporator Duty (kW) available based on 35°C Ambient Temperature and 5°C Evaporating Temperature. Full Load Current (FLA) at 10°C Evaporating Temperature, 60°C Condensing Temperature with R407C.

Page 33: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

C RANGE Product Guide AIR COOLED CONDENSING UNITS

30 PR-2006-0294-GB Subject to modifications 01/2007

Vertical Airflow Version

End View Single Fan Twin Fan Three Fan Horizontal Airflow Version

End View Single Fan Twin Fan

Three Fan

Main Features Airflow: Horizontal or Vertical Discharge. Construction: The coil is housed in a single piece, Aluzink or sheet steel casing with epoxy powder

coating. Coils: Made from 3/8” grooved copper tubes with aluminium fins at 14 per inch. Fans: Axial flow type fans with profiled aluminium blades fitted to an external rotor motor,

all supported in a wire guard. Units available in Standard (6 pole) or Quiet/Residential (8 pole) versions. For special applications Super Quiet (12 pole) versions can be supplied. Fans providing up to 50 Pa external static pressure can be supplied for plant room mounted units.

Standard 08-6 13-6 21-6 26-6 32-6 50-6 75-6

Standard Airflow m³/s Number of Fans -

0.72 1

1.20 1

2.0 1

2.4 1

2.6 1

4.8 2

6.7 3

Duty kW 7.7 13.5 21.4 26.5 31.4 54.0 75.0

Full Load Current Amps 0.87 1.65 3.30 3.30 3.30 6.60 9.90

Quiet/Residential 05-8 10-8 15-8 20-8 25-8 40-8 60-8

Standard Airflow m³/s Number of Fans -

0.45 1

0.8 1

1.15 1

1.6 1

1.95 1

3.0 2

4.2 3

Duty kW 5.6 10.0 15.0 20.0 25.0 40.0 60.0

Full Load Current Amps 0.61 0.72 1.15 1.25 1.65 2.50 3.75

All Versions 08-6 / 05-8

13-6 / 10-8

21-6 / 15-8

26-6 / 20-8

32-6 / 25-8

50-6 / 40-8

75-6 / 60-8

Dry Weight kg 35 45 50 70 80 135 210

Overall Dimensions – Horizontal Airflow Type

Length mm Width mm Height mm

645 530 602

826 600 738

975 600 888

1125 620

1042

1225 620

1142

2095 620

1088

2760 620

1088

Overall Dimensions – Vertical Airflow Type

Length mm Width mm Height mm

645 581 690

825 717 790

975 867 810

1125 1021 945

1225 1121 945

2095 1067 945

2760 1067 945

Page 34: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

DDRA Product Guide RANGE DRYCOOLERS

30 PR-2006-0294-GB Subject to modifications 01/2007

Vertical Airflow Version

End View Single Fan Twin Fan Three Fan Horizontal Airflow Version

End View Single Fan Twin Fan

Three Fan

Main Features Airflow: Horizontal or Vertical Discharge Construction: The coil is housed in a single piece, sheet steel casing with zinc / aluminium coating Coils: Made from 3/8” grooved copper tubes with aluminium fins at 14 per inch. Fans: Axial flow type fans with profiled aluminium blades fitted to an external rotor motor,

all supported in a wire guard. Units available in Standard (6 pole) or Quiet/Residential (8 pole) versions. For special applications Super Quiet (12 pole) versions can be supplied. Fans providing up to 50 Pa external static pressure can be supplied for plant room mounted units.

Variants: “P” version available with on-board pump and expansion vessel.

Standard Version

6 Pole Model

Capacity kW

Flowl/s

No. of Fan(s)

Pressure Loss kPa

Length mm

Depth mm

Height mm

Weight kg

Connectionsmm

DDRA 32 - 6 22.7 0.767 1 15.7 1230 1121 945 90 35

DDRA 50 - 6 48.8 1.646 2 24.5 2100 1067 945 180 42

DDRA 75 - 6 71.9 2.426 3 27.3 2780 1067 945 270 54

Quiet / Residential Version

8 Pole Model

Capacity kW

Flowl/s

No. of Fan(s)

Pressure Loss kPa

Length mm

Depth mm

Height mm

Weight kg

Connectionsmm

DDRA 25 - 8 17.4 0.586 1 11.6 1230 1121 945 90 35

DDRA 40 - 8 32.7 1.106 2 13.0 2100 1067 945 180 42

DDRA 60 - 8 51.2 1.729 3 15.6 2780 1067 945 270 54

All the above performances are based on a 25% ethylene glycol solution, flow at 40°C with return at 47.5°C (i.e. 7.5K ∆T) and in

an ambient of 32°C (i.e. 8K ∆T Approach Temperature). (Equivalent to Glycol Leaving Temperature minus Ambient Temperature). For greater duties than above use multiple modular units.

Page 35: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide C3-05 CONTROLS DISPLAY DETAILS

PR-2006-0294-GB Subject to modifications 01/2007 33

Graphical Display comprises: - Unit ON/OFF key, providing "master" control of the local unit. - Graphical liquid crystal display, providing icon status of the unit functions,

parameter menus, historic data logging, alarm buffer and access to other controllers via the network system.

- Four programming keys, providing access to display features. - Alarm key to view active alarms.

Graphical Display Icons and Functions Unit Functions are indicated via icons. These are:

UNIT RUN - shown when Unit fan(s) are running

COOL - shown when cooling demand is greater than 0%.

HEAT - shown when heating demand is greater than 0%.

HUMIDIFY - shown when humidification demand is greater than 0%.

DEHUMIDIFY - shown when dehumidification demand is greater than 0%. The 8 row LCD indicates Unit Function via the icons on rows 1 and 2. The remaining rows show the selected data, updated in real time.

The programming keys ( ↓ ↑ ← → ) have to be pressed in a coded sequence in order to enter or change the function currently being accessed.

Current Alarm status can be reviewed by using the ← key to access the Alarm Buffer from the time-out display.

Page 36: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

C3-05 CONTROLS Product Guide HARDWARE STRUCTURE

34 PR-2006-0294-GB Subject to modifications 01/2007

24V AC Supply

Supply For Ratiometric Pressure Transducers

Optional Field Card Port

Analogue Inputs 1 to 3

Analogue Inputs 4 & 5

Power Supply LED & pLAN Healthy LED’s

Analogue Outputs 1 to 4

Optional Serial Card Port

Digital Inputs 15 & 16

Analogue Inputs 6 to 8

Digital Inputs 9 to 12

Digital Inputs 13 & 14

Spare RJ 11 Port

Connection To Display

Connection to pLAN

Optional Service Card Port

Digital Outputs 1 to 13

Digital Inputs 17 & 18

Analogue Inputs 9 & 10

Analogue Outputs 5 & 6

Expansion I/O Connection

Digital Inputs 1 to 8

Digital Outputs 14 to 18

Page 37: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

Product Guide C3-05 CONTROLS INPUTS AND OUTPUTS TABLE

PR-2006-0294-GB Subject to modifications 01/2007 35

The following inputs and outputs are available on the Base Controller:

INPUTS

Digital

ID1 Unit Remote On/Off 24V AC

ID2 Airflow Fail 24V AC

ID3 Filter Blocked 24V AC

ID4 Klixon Trip 24V AC

ID5 HP Trip Comp 1 (Or Tandem Circuit 1) 24V AC

ID6 HP Trip Comp 2 (Or Tandem Circuit 2) 24V AC

ID7 LP Trip Comp 1 (Or Tandem Circuit 1) 24V AC

ID8 LP Trip Comp 2 (Or Tandem Circuit 2) 24V AC

ID9 Water On Floor / Drip Tray Detection 24V AC

ID10 Humidifier Water Level 24V AC

ID11 Aux Alarm 24V AC

ID12 Generator Run 24V AC

ID13 Combicool Change-over 24V AC

ID14 Spare 24V AC

ID15 HP Trip Comp 3 24V AC

ID16 HP Trip Comp 4 24V AC

ID17 LP Trip Comp 3 24V AC

ID18 LP Trip Comp 4 24V AC

Analogue

B1 Return Air Hum 4 – 20 mA

B2 Condensing Pressure 1 0 – 5V

B3 Condensing Pressure 2 0 – 5V

B4 Return Air Temp NTC

B5 Supply Air Temp NTC

B6 Supply Air Humidity 4-20 mA

B7 Humidifier Conductivity 0 – 1V

B8 Humidifier Current 0 – 1V

B9 Freecool / CW Temperature NTC

OUTPUTS

Digital

NO1 Unit Fan Relay – N/O Contact

NO2 Dehumidification Relay – N/O Contact

NO3 -Heater 1

-DODC Heat Open

-Thyristor Enable

Relay – N/O Contact

NO4 -Heater 1

-DODC Heat Close

Relay – N/O Contact

NO5 -Compressor 1

-DODC Cool Open

-Combicool Secondary CW Open

Relay – N/O Contact

NO6 -Compressor 2

-DODC Cool Close

-Combicool Secondary CW Close

Relay – N/O Contact

NO7 Compressor 3 Relay – N/O Contact

NO8 Compressor 4 Relay – N/O Contact

NO9 Humidifier Power Contactor Relay – N/O Contact

NO10 Hum Fill Valve Relay – N/O Contact

NO11 Hum Drain Valve Relay – N/O Contact

NO12 Critical Alarm Relay – N/O Contact

NO13 Maintenance Alarm Relay – N/O Contact

NO14 Freecool / Combicool Primary CW

DODC Open

Relay – N/O Contact

NO15 Freecool / Combicool Primary CW

DODC Close

Relay – N/O Contact

NO16 Dry Cooler Fan 1 Relay – N/O Contact

NO17 Dry Cooler Fan 2 Relay – N/O Contact

Analogue

Y1 Fan 1 0 – 10 VDC

Y2 Heating 0 – 10 VDC

Y3 Cooling / Condenser Fan 0 – 10 VDC

Y4 Hum 0 – 10 VDC

Notes:

- - A high digital input condition will be within the voltage band –25% to +20% 50 Hz or 60 Hz. (High > 18.5V, Low < 16.5V). - All digital inputs are opto-isolated complete with reverse voltage protection diodes. - HP / LP 3 and 4 Alarm inputs only available when C3-05 large controller fitted. - All digital outputs are relay contacts rated at 24 VDC – 240 VAC 10A fitted with surge suppressor network. - All PCB tracks rated to withstand let through energy of a 24 VAC control fuse (10A). - All output relay contacts common to 24 VAC (except alarm relays). - Valve open / close on heating / cooling / freecool outputs refer to drive open / drive close valves only. - Drycooler fans and Freecool Valve open / close outputs only available when C3-05 large controller fitted. - The fan output is to operate concurrently with the cooling, heating, humidification and dehumidification demands. - Cooling and heating outputs shall operate concurrently with digital / DODC outputs according to the demand calculations. - A high digital input condition will be within the voltage band –25% to +20% 50 Hz or 60 Hz. (High > 18.5V, Low < 16.5V). - All digital inputs are opto-isolated complete with reverse voltage protection diodes. - HP / LP 3 and 4 Alarm inputs only available when C3-05 large controller fitted.

Page 38: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0
Page 39: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0
Page 40: PRODUCT GUIDE GEA Close Controldeltagci.com/pdf/DencoCloseControlProductGuide.pdf · Std W/C Condenser B - - - 8/30 8/30 8/30 10/30 10/30 10/30 Full Load Current Amps 19.9 20.9 23.0

GB Denco Ltd.UK-HR4 8DS HerefordTel. +44 / 1432 / 277 277

N GEA Klimaprodukter ASN-0484 OsloTel. +47 / 220 / 27990

UA GEA Ukraina t.o.v.UA-01135 KyivTel. +38 / 044 / 4619356

TR ISISANTR-80700 BalmumcuIstanbulTel. +90 / 212 / 2757171

SLO GEA KlimatizacijskaTehnika d.o.o.SI-1000 LjubljanaTel. +386 / 1 / 2573850

SK GEA Klimatizácia s.r.o.SK-83104 BratislavaTel. +421 / 7 / 44457917

GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955

SRB

S GEA EXOSVentilation ABS-74528 EnköpingTel. +46 / 171 / 85530

RUS GEA KondicionerMoskvaRU-105094 MoskvaTel. +7 / 495 / 9566674

P Nónio, Lda.P-1269-090 LisboaTel. +351 / 21 / 3826160

LV GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

LT GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

L GEA Happel LuxembourgL-4940 BascharageTel. +352 / 26 / 502970

IS Rafn JenssonIS-110 ReykjavikTel. +354 / 56 / 780-30

PL GEAKlimatyzacja Sp. z o.o.PL-54610 WroclawTel. +48 / 71 / 3737952

HR GEA Klima-rashladnatehnika d.o.o.HR-10000 ZagrebTel. +385 / 1 / 6064900

FIN OY TEKNOCALOR ABFIN-01300 VantaaTel. + 358 / 9 / 82546020

F GEA Happel France sarlF-59436 Roncq CedexTel. +33 / 3 / 20689020

EST GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

E GEA Air TreatmentMarketing ServicesInt. GmbH - oficina EspañaE-28036 MadridTel. +34 / 91 / 3837701

DK GEA Klimateknik ApSDK-2610 RødovreTel. +45 / 38 / 887070

H GEA Klimatechnika KftH-1037 BudapestTel. +36 / 1 / 4393200

D GEA HappelKlimatechnik GmbHD-44625 HerneTel. +49 / 2325 / 468-00

CZCZ-46312 LiberecTel. +420 / 48 / 5225-111GEA Klimatizace spol. s r.o.CZ-46312 LiberecTel. +420 / 48 / 5225-303

GEA LVZ, a.s.

CH GEA KlimatecSchweiz AGCH-3065 Bolligen-StationTel. +41 / 31 / 9171919

BY GEA Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060

BIH GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955

BG EVISS Ltd.BG-7000 RousseTel. +359 / 82 / 81000

B GEA Happel Belgium N.V.B-1130 BrusselsTel. +32 / 2 / 2406161

A GEAKlimatechnik GmbHA-4673 GaspoltshofenTel. +43 / 7735 / 8000-0

NL GEA HappelNederland B.V.NL-2909 LLCapelle a/d IjsselTel. +31 / 10 / 2350606

RO GEA Klimatechnik s.r.l.RO-300222 TimisoaraTel. +40 / 356 / 423703

GEA KlimatehnikaRS-11070 Novi BeogradTel. +381 / 11 / 3193955

MWE

Our Market in Europe

Air Treatment Division For detailed information on all corporate areas,go to www.gea-airtreatment.com or contactus by email [email protected] company of GEA Group

PR-2

006-

0294

-D •

Su

bje

ct t

o m

od

ific

atio

ns

• St

atu

s 01

/200

7 C

op

yrig

ht

GEA

Air

Tre

atm

ent