Practical PMU Applications for Utilities University of Washington EE Graduate Seminar November 1 st , 2012 Manu Parashar Douglas Wilson

Transcript of Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution...

Page 1: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Practical PMU Applications for Utilities

University of Washington EE Graduate Seminar

November 1st, 2012

Manu Parashar

Douglas Wilson

Page 2: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

SynchroPhasor Technology

− Next generation measurement technology. (voltages, currents, frequency, frequency

rate-of-change, etc)

− Higher resolution scans (e.g. 30 samples/second). ─ Improved visibility into dynamic

grid conditions.

─ Early warning detection alerts.

− Precise GPS time stamping. ─ Wide-area Situational Awareness. ─ Faster Post-Event Analysis.

PMU ‘Sub-second’

Resolution

SCADA ‘Seconds’

Resolution

Phasor Measurement Units (PMUs)

Page 3: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

PMU Deployment within North America

Currently 200+

PMUs Installed.

Expected to exceed

800+ PMUs by 2013 (under SGIG Investments)

Source: NASPI Website (www.naspi.org)

Page 4: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

SynchroPhasors & Energy Management Systems

Control Center -PDC

PMU MEASUREMENT-BASED Analysis

(PhasorPoint)

Traditional MODEL-BASED Analysis

(EMS)

SCADA & Alarms

WAMS

State Estimator

State Measurement

Other EMS Applications

New Applications

Small Signal Stability

Oscillation Monitoring

Transient & Voltage Stability

Stability Monitoring & Control

Island Management

Island Detection, Resync,& Blackstart

Page 5: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Look Ahead and Predictive Operations Capability in Control Rooms

• Reduces the impact of variability and uncertainty on real-time decision making in the control room

Page 6: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

SynchroPhasor Benefits

RELIABILITY

• Situational Awareness

• Identifying sources of oscillations

• Vulnerability detection

• Automated wide area protection

• Identifying equivalent dynamic models

• Analysis tools e.g.

• Post Mortem

• Dynamic model validation

• Baselining

CONSTRAINT RELIEF

• Stability (damping) constraints

• Angle constraints

• WAMS + DSA (integration of “measurement-based” and “model-based” security assessment).

• Angle based control

SUSTAINABILITY

• Renewable connections

• Impact of renewables on stability

• Distribution management

Page 7: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Operational Benefits Improved Reliability

August 10, 1996 Blackout

Monitor wide-area grid stress.

August 14, 2003 Blackout

Early detection of dynamic instability.

Dynamic Instability (Negative Damping)

~ 3% (LOW) Damping (after Keeler Allston line trips)

Page 8: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Australia Queensland – NSW Interconnector

Great Britain Scotland – England Interconnector

Transmission Corridor Net Transfer Capacity

+300MW

+300MW

Model limit

with margin

Limit with

measured

damping

Thermal limit

AREA 1

AREA 2

Asset Management Congestion Relief

Page 9: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Planning Benefits Dynamic Model Validation

Western Interconnection August 10th, 1996 Blackout Dynamic models predicted stable system when the system was in fact unstable.

PMU provide necessary dynamic data to calibrate dynamic power system models.

Page 10: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Timely control actions necessary for them to be effective!

Protection & Control

Page 11: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

PMU Basics: What is a PMU?

FIBRE OPTIC

1 pps

IRIG-B

un-modulated

ANALOG

Electrical

Signal

A/D DIGITISED

SAMPLE PROTECTION

and MEASUREMENT

PROCESSORS

Microprocessors

Areva P847 PMU

P594 GPS

RECEIVER

IEEE C37.118 DATA

Data frame

over Serial or Ethernet

(TCP/UDP)

ETHERNET

PROCESSOR

Page 12: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Fundamental WAMS Components

Analog Channels

− Va, Vb ,Vc,V1, V2,V0 − I1 , I2 , I0, Ia , Ib ,Ic − Frequency & Rate of Change of Frequency

Digital Channels

− Any 8 status signals available

Phasor Measurement Unit (PMU) (MiCOM P847 Series)

Phasor Data Concentrator (PDC) (PhasorPoint PDC, OpenPDC)

Time align measurements received from

multiple PMU/PDC streams.

Perform data validation.

Provide time-aligned data at desired periodicity

and formats to downstream applications.

Page 13: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Typical WAMS Architecture

Source: NASPI Website (www.naspi.org)

Page 14: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

IMPROVED RELIABILITY: OSCILLATORY STABILITY MANAGEMENT

1/F MODE FREQUENCY

MODE AMPLITUDE

A

MODE DECAY TIME

EXP(-t/ )

MODE PHASE

Mode Frequency

Mode Amplitude

Mode decay time

Mode Phase

Exp(-t/ )

Measured P / f /

Simultaneous multi-oscillation detection and characterisation direct from

measurements

For each oscillation detected, alarm on:

• mode damping and/or

• mode amplitude for

Operations

Planning & Analysis, Plant Performance

Unlimited oscillation frequency sub-bands

Individual alarm profiles for each sub-band

In operational use since 1995 Does not use system model

Post-event analysis

Dynamic model validation

Damping controller performance assessment

Dynamic performance baselining

Early warning of poor damping (two level alarms)

Fast Modal Analysis: Alarms

Trend Modal Analysis: Analysis

Wide area mode alarms Mode locus plot with alarm thresholds

Oscillatory Stability Management

Page 15: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Oscillatory Modes Observed in Colombia (2009)

Ecuador Mode 0.49Hz

Governor Mode 0.06Hz

Inter-area mode at 0.49Hz (Colombia-

Ecuador). Opposing phase in South

Governor common-mode: whole

system oscillates in coherent phase

Page 16: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Islanding, Resynchronization and Blackstart

System split

Colour: Frequency

Vectors: Voltage Phasors

Identify islanding quickly

Alarm raised

Islands clearly visualized

Reduce time to resynchronize

Improve system visibility in

blackstart

Ice slide destroys 2 transmission

towers, IRB used to monitor system to

maintain synchronisation for 2 weeks

Page 17: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

PSS Tuning & Generator Commissioning – Iceland (2006)

Mod

e A

mpl

itud

e (M

W)

Mode Decay Time Constant (sec)

1.2Hz Mode

Before PSS tuning After PSS tuning

PhasorPoint Oscillatory Stability Management:

• Wide area real-time damping visualization and alarms

• Dynamics baselining & trending

• Wide area event analysis

Page 18: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

In distribution network, increase connection capacity by constraining by angle

Marginal reduction of

capacity factor

More capacity

More energy

Renewables Integration – Scotland (2012)

Page 19: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control

Wide Area Protection Scheme – Iceland (2012)

SW FREQ

E FREQ

Smelter load

132kV ring power

Main generation area

Loss of Large Smelter in SW

Frequency rises rapidly

Nearby generators change speed/angle quickly

Frequency rises more slowly

Trip Gen proportionally in correct zone

Angle difference increase