Powerware9910-P11 and 9910-P16
High Performance
High Reliability & Availability
Flexible & Configurable
Advanced Communications
Fourth-Generation Online™ topology ensures continuous, clean powerAdvanced Battery Management Plus (ABM Plus™) significantly increases battery lifeExtended Battery Modules (EBMs) prolong backup timesLoad Segments enable scheduled shutdownsTwo-in-One form factor provides versatility2U rack-mount height conserves valuable rack spaceHot-swappable batteries simplify service
Product SnapshotPower Rating: 1000 VA/700 Watt
1500 VA/1050 WattVoltage: 220-240 VacFrequency: 50/60 HzConfiguration: 2U, 19” tower or rackRuntime (in min,): Half/Full load (15/5)Input line cord: IEC-320-C14 Number of outlets: 6 IEC-320-C13 Options: EBM, SNMP, rack kit
and MultiServer
P11 and P16 Features
P11 and P16 ApplicationsThe P11 and P16 were specifically designed, engineered and approved for IBM applications
iSeries and AS/400pSeries and RS/6000xSeries and other eServersStorage and networking devices
9910 UPSs are ideal power protection foriSeries family of servers
9406 7025 7043 7044
P16 with i5 520 Tower
Series 9 Power ProtectionThe P11 and P16 provide double-conversion online power protection from all 9 of the most common power problems that threaten your equipment and data
Power failures High voltage spikes
Power sags Frequency variations
Power surges Switching transients
Brownouts Harmonic distortion
Line noise
Utility Load
Internal Automatic Bypass
Battery
AC to DC Rectifier
DC to AC Inverter
Bi-Directional Power Converter
Filtering
Wide input voltage rangeReduces battery usageReserves batteries for power failures--when you need maximum runtimeExtends UPS service lifeReduces battery replacement costs
EnergyShareUnder extremely poor utility conditions, P11 and P16 models take power from both the utility and batteryReduces battery usageExtends runtime and service life of the battery
P11 and P16 Fourth-Generation Online TopologyTM
Energy Share
EnergyShare range: 120-160V(combined battery and utility)
Battery Power: <120V
Battery Power: >288V
Online voltage regulation: 160-288V
(no battery power needed)
Input Voltage RangeDuring extreme brownouts, the P11 and P16 provide an extra level of protection; the UPS “shares” battery and incoming voltage to continue to provide ±3% of nominal voltage
B CABM® Technology• Doubles battery
service life by charging only when needed
• Optimizes recharge time
• Does not trickle chargeand starve the electrolyte
• Intelligent microprocessor controlled -Only true & automatic battery check (periodic, controlled discharge) for most accurate advanced failure protection
• Sleep Feature - no unnecessary battery “drain”
Compact DesignThe P11 and P16 packs superior power protection in a sleek, compact design.
19”
17”
3.5”
Informative User Interface
On Button(Start-On-Battery)
Overtemperature
Overload
Load Level/Battery LevelBypass Mode
Alarm Silence/Test Button Off Button
Battery Mode
Normal Mode (UPS On)
Site Wiring Fault
Self-Test
Replace Battery (ABM)
Note: rotate 90° for cabinet configuration
Load Segments
Power down sequencing of Load SegmentsExtends runtime for critical devices
Power up sequencing of Load SegmentsOrderly power up of connected devices
Scheduled on/off timesTurn off equipment for security and power conservation
Individual control of two Load Segments
No need to shut down your critical load when replacing batteries
Hot-Swappable Batteries
UPS and two EBMs
Add EBMs to extend backup time
Extended Battery Modules
EBM Connection
EBM #1 EBM #2
P11 Battery RuntimesBattery Runtime (in minutes)*
Standard (Std)Watts Internal Batteries +1 EBM +2 EBMs
140 37 271 546
280 19 142 278
490 9 72 156
595 6 59 124
700 5 48 104
Rack height 2 4 6
* Up to 2 EBMs can be connected to the P11. EBM runtimes include P11 internal batteries. Runtime chart provides typical information. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
P16 Battery RuntimesBattery Runtime (in minutes)*
Standard (Std)Watts Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
280 46 177 331 501 682
490 25 96 180 272 370
595 21 76 142 214 292
700 16 61 115 174 237
875 11 46 87 131 179
1050 8 37 70 106 144
Rack height 2 4 6 8 10* Up to 4 EBMs can be connected to the P16. EBM runtimes include P16 internal batteries. Runtime chart provides typical information. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
P11 and P16 Rear Panel
REPO/Network Transient ProtectorShut down UPS remotely with REPO port; ideal for rack applications
Network Transient Protector provides protection from “back door” disturbances that travel through phone/network lines
Powerware Extensions Software for IBM Director
Seamless UPS and software integration into IBM Director Network Management System (NMS)Real time monitoring, management and alarm notification of all UPSs in the network: e.g. battery status, battery replacement, load level and metering informationAutomatically launches LanSafe and ConnectUPS Web/SNMP Card applications from within DirectorAvailable on Powerware web FREE-OF-CHARGE
Powerware Software SuiteThe industry’s most comprehensive software bundle, The PowerwareSoftware Suite, is free and included with every P11 and P16.
Software Wizard guides you through software selection and installation. In addition to multimedia demonstrations, product data sheets, and video clips, the Software Suite contains the following power management software:• LanSafe™ Network UPS shutdown and monitoring
software• PowerVision® (30-day trial version) UPS performance
analysis and monitoring software
• Foreseer® (demonstration) facility and data center management software
Power Management Software
Software ApplicationPowerware
Extensions for Application LanSafe NetWatch IBM Director
Single pSeries (serial/TTY) non-LPAR
Single pSeries (network) non-LPAR * *
Single pSeries (LPAR) *
Multiple pSeries (non-LPAR) *
Multiple pSeries (LPAR) *
IBM Director Network Device *
* Co-requisite FC 2934 ConnectUPS Web/SNMP network card.
Note: UPS for iSeries applications utilize OS/400 UPS monitoring functions.
AmbientEmail/ SSL/SSH1 Temperature
Application Monitoring Shutdown GUI SMTP Security Humidity
LanSafe Yes Yes Yes Yes / Yes No/No No/No
NetWatch - Yes - No/No No/No No/No
ConnectUPS Web/ Yes2 Yes3 Yes Yes / Yes Yes / Yes Yes / Yes4
SNMP Card (FC 2934)1SSL = Secure Sockets Layer. SSH = Secure Shell. 2Via Web Browser, LanSafe or Network Management System (e.g. IBM Director, Tivoli). 3In conjunction with NetWatch software. 4With optional FC 2938 EMP (Environmental Monitoring Probe) device attached.
Software Comparison
Software Solution zSeries iSeries pSeries xSeries Storage Networking
LanSafe
LanSafe and ConnectUPS MultiServer card (IBM FC 2933)
NetWatch and ConnectUPS !
Web/SNMP card (IBM FC 2934) LPARs
Powerware Extensions forIBM Director
NetWatch
ConnectUPS Relay card andAS/400 cable (IBM FC 2936)!Use ConnectUPS Web/SNMP/xHub card, IBM FC 2934 to support LPAR (POWER 4 Chip Set) servers. For pSeries configurations, each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafesoftware.
ConnectivityWhat you need by application
P11 and P16 CollateralAdditional information available at www.powerware.com/ibm
Select your region. Click “Products”, click “9910 Solutions” then click “Powerware pSeries” or “Powerware iSeries”
Powerware UPS Hotline for IBM1-800-925-4426
Materials availableData sheetApplication overview chartProduct presentationDocuments (manuals)