Powering New Generation Miners

5
R ap t o r P o we r S ystems | (800) 258 - 0129 | ww w . r ap t o rp owe r . u s | in f o @ r ap t o rpo we r systems.co m ] [ Crypto /KPQWT Powering New Generation Miners 'IRIǻXW SJ 9XMPM^MRK E (V]TXS 2MRSXEYV MR 2MRMRK &TTPMGEXMSRW TLI (V]TXS 2MRSXEYV MW E EQT VEXIH VEGO QSYRXIH 5)9 FYMPX WTIGMǻGEPP] JSV QMRMRK ETTPMGEXMSRW Unparalleled Density 8LI (V]TXS 2MRSXEYV MW TEGOIH [MXL \ ( SYXPIXW XLEX GER FI PSEHIH [MXL EQTW IEGL *UYMTTIH [MXL FEROW SJ EQT W[MXGLIH GMVGYMX FVIEOIVW HIVEXIH XS EQTW XLI 2MRSXEYV GER TS[IV YT XS EQTW SJ WMRKPITLEWI PSEH TIGMEPP] QEHI WTPMXXIV GEFPIW HSYFPI XLI 2MRSXEYVƶW SYXPIX GETEGMX] ERH WXVIEQPMRIW XLI MRWXEPPEXMSR SJ ERH SXLIV HYEP MRTYX QMRIVW Lower Set Up and Installation Costs 8]TMGEP QMRIV 5)9 WIXYTW VIUYMVI QER] WQEPP 5)9W XLEX PIEZI E PEVKI TSVXMSR SJ XLI SYXPIXW RSX YXMPM^IH 8LI 2MRSXEYV VIHYGIW XLI EQSYRX SJ 5)9W XLEX RIIH XS FI MRWXEPPIH 8LMW WEQI FIRIǻX ETTPMIW XS XLI RYQFIV SJ GMVGYMX FVIEOIVW XLEX RIIH XS FI MRWXEPPIH Future Proofed ( SYXPIXW EVI XLI PEVKIWX GSQQIVGMEPP] EZEMPEFPI .*( WXERHEVH SYXPIX YXMPM^IH JSV IPIGXVSR MG IUYMTQIRX 8LI 2MRSXEYV EPPS[W XLI QE\MQYQ TS[IV SYXTYX SJ EPP SJ MXW ( SYXPIXW WMQYPXERISYWP] ;LIR RI[IV KIRIVEXMSR SJ QMRIVW EVI VIPIEWIH XLI 2MRSXEYV [MPP FI YT XS XLI XEWO Remote Control 4TXMSREPP] GSRXVSP IEGL SYXPIX ZME TVSTVMIXEV] LEVH[EVI ERH WSJX[EVI (SQQYRMGEXI [MXL XLI 2MRSXEYV ZME *XLIVRIX [MXL E [IFTEKI MRXIVJEGI SV ER -885 &5. USA Manufacturing 8LI 2MRSXEYV MW HIWMKRIH EWWIQFPIH ERH XIWXIH MR XLI 9& 1SGEP QERYJEGXYVMRK ERH WSYVGMRK EPPS[W JSV UYMGO PIEH XMQIW ERH JEWX VIEHMP] EZEMPEFPI WYTTSVX 4*2 ERH [LMXI PEFIPMRK MW EZEMPEFPI

Transcript of Powering New Generation Miners

Page 1: Powering New Generation Miners

Raptor Power Systems | (800) 258-0129 | www.raptorpower.us | [email protected]

][Crypto Powering New Generation Miners

T

Unparalleled Density

Lower Set Up and Installation Costs

Future Proofed

Remote Control

USA Manufacturing

Page 2: Powering New Generation Miners

Raptor Power Systems | (800) 258-0129 | www.raptorpower.us | [email protected]

][Crypto Powering New Generation Miners

Control and Monitoring Descrip on Speci ca on Communica on Port Type (Ethernet, serial, USB, Wireless, 4G LTE)

Op onal

Communica on Protocol (Webpage IP Addressable, SNMP, HTTP API Commands, Standalone Windows So ware)

Op onal

Control (on/o control for each output, total system or a speci c group of outputs)

Op onal

Monitoring (temp, humidity, current, voltage for each output, total system or a speci c group of outputs)

No

Output Speci ca ons Descrip on Speci ca on Type of outputs and quan ty of each (NEMA, IEC, terminals etc.)

24 x C-13 OR 24 x C-19 OR 24 x 7-15R

Voltage 208V, 240V, 277V Do the outputs need to be in speci c banks? Yes – 2 outlets per bank LCD Meter (volts, amps, temp) No Circuit Breaker (current ra ng and either switched standard, switched illuminated, switched standard with LED indica on or push bu on pop breakers)

12 x 50A Switched Circuit Breakers

Circuit Breaker Type (UL 489, UL 1077) UL 1077 Do the circuit breakers need to be in speci c banks?

Yes – 1 Circuit Breaker per 2 Outlets

On/O switches for outputs (not current protected)

No

Physical/Environmental Descrip on Speci ca on Enclosure Type (rack, wall, standalone etc.) 0U Dimension/size restraint 38 x 6 x 4 Material Type (aluminum/steel) Alm/Stl Opera ng Environment (temp, humidity, IP ra ng)

0-45C

Radiated EMI Protected Enclosure No

Input Speci ca ons Descrip on Speci ca on Single or Dual Input Single Voltage 208V, 240V, 415V, 480V Current 384 Amps Input Connector Internal Hardwire Frequency (25Hz, 50Hz, 60Hz, 100Hz, 400Hz) 50/60Hz Circuit Breaker (current ra ng and either switched standard, switched illuminated, switched standard with LED indica on or push bu on pop breakers)

No

Circuit Breaker Type (UL 489, UL 1077) N/A Power Cord Type (SOOW, etc.) N/A Power Cord Length N/A LCD Meter (volts, amps, temp) N/A

33.00

5.12

4.00

2.02

Page 3: Powering New Generation Miners

Installation, Warnings,& Usage Instructions

128A Power StripRPS-PDU-CM-5

NOTE: Before installation read these instructions carefully and completely. These installationinstructions can not cover every possible installation, operation or maintenance situation.

NOTE: This Power strip is constructed in accordance with UL 62368-1.

WARNING: Never work on power strip if power is applied!

WARNING: Do not exceed 60C ambient operating temperature.

1. Prior to applying power on mains put all output circuit breakersinto the OFF position.2. Apply power via upstream 150A (wye) per phase UL 489 circuit breaker.3. Set output ciruit breakers to the ON position in the correspondingbanks that are to supply power to connected loads.

Usage Instructions

Powerspec Inc. 25 4th Street Somerville, NJ 08876 (800) 258-0129DOC# RPS-PDU-CM-5

Mounting Instructions1. Power strip is to be permanently mounted withvendor supplied mounting brackets.2. Use only supplied hardware for mounting3. To be installed by a quali�ed personnel according to local code

1. Do not exceed 128 amps on any single input connector.2. Ensure input and output power connections are secure.3. Never detach input or output power while load is active.4. Only supply power that is circuit protected upstream to a maximum of 150A.5. Disconnect device shall be provided as part of the building installation

Electrical Precautions

1. Remove access panel located at top of unit.2. Insert power cord through top entry strain relief.3. Power cord should be a minimum of 1/0 per conductor.4. Attach bare wire ends of the conductors and ground to the corresponding contact and hand tighten.5. Replace access panel cover.

Input Power Connection

! WARNING: Reduced Air Flow - Installation of the equipment in a rack should be such that theamount of air�ow required for safe operation of the equipment is not compromised.

! WARNING: Mechanical Loading - Mounting of the equipment in the rack should be such that ahazardous condition is not reached due to uneven mechanical loading.

!WARNING: Circuit Overloading - Consideration should be given to the connection of theequipment to the supply circuit and the e�ect that overloading of the circuits migh have onover-current protection and supply wiring. Appropriate consideration of equipment nameplateratings should be used when addressing this concern. For North America permissible loads,refer to Article 210.23 of the National Electrical Code.

! CAUTION: Failure to properly ground this PDU or fully insert the PDU into the equipment rackcan create a hazardous condition to the installer and the equipment.

! CAUTION: Prior to connecting input power cables, ensure that the upstream power is turned o�.

!WARNING: Elevated Ambient Temperature - If installed in a closed or multi-rack unit assembly,the operating ambient temperature of the rack environment may be greater than room ambient. Considerations should be given to installing the equipment compatible with themaximum rated ambient temperature.

Page 4: Powering New Generation Miners

PARTS LISTDESCRIPTIONPART NUMBERQTYITEM

CHASSIS BODYC041119-11180 AMP SINGLE POLE BREAKER - DIN RAILASSEMBLY

12

CHASSIS LID ASSEMBLYC041119-213POWER DISTRIBUTION BLOCK 400 AMP RATEDLK40044DIN RAIL 35 MM - 4.5" LONGDINR4.5I25

C041119-316QUALTEK C-19 RECEPTICAL746W-15/08247HEYCO LIQUID TIGHT CORD GRIPMXXX18100° Flat Countersunk Head Machine Screw -UNC - Inch

ANSI B18.6.3 - 8-32 UNC x 0.2549

1

1

2

2

3

3

4

4

A A

B B

C C

D D

SHEET 1 OF 1

DRAWN

CHECKED

QA

MFG

APPROVED

M.T. 4/10/2019

DWG NO

C041019-1

TITLE

C041019-1

SIZE

Custom Size (inches)SCALE

RAPTOR POWER SYSTEMS

REV

A

33.00

5.12

2.03

2.56

9

6

7

2

4

8

REVISION HISTORYREV DESCRIPTION DATE APPROVED

A INITIAL RELEASE FOR REVIEW 4/11/2019 EEK

CHASSIS MATERIAL: 16 GAUGE 5052 ALUMINUMFINISH: FLAT BLACK POWDER COAT

Page 5: Powering New Generation Miners

.

A

.

B

.

C

.

G

50A

.

A

.

B

.

C

.

N

.

G

50A

4 WIRE

5 WIRE

x12 BANKS

4 AB, 4 BC, 4 CA

OUTLET OPTIONS

24 x C-13 (max current 15 A)

24 x C-19 (max current 20 A)

24 x 7-15R (max current 15 A)

x12 BANKS

4 AN, 4 BN, 4 CN

Input/Output Configurations

Input Configuration Output

Max Load Per

Outlet

120/208V 5 wire 120 V 2400 W

120/208V 4 wire 208 V 4100 W

240/415V 5 wire 240 V 4800 W

277/480V 5 wire 277 V 5540 W

8

A

B

7 6 5

C

8

D

7 6 5

DATE

4 3 2

SCALE

SIZE DWG NO.

SHEET

1

REV

A

B

4 3 2

ZONE REV

C

1

REVISIONS

DESCRIPTION

D

APPROVEDDATE

THIS DRAWING IS THE

PRIVATE AND CONFIDENTIAL

PROPERTY OF RAPTOR

POWER SYSTEMS AND MUST

NOT BE LOANED, COPIED, OR

REPRODUCED WITHOUT

WRITTEN PERMISSION, AND

MUST BE RETURNED TO

RAPTOR POWER SYSTEMS

UPON REQUEST

Raptor Power Systems

CryptoMinotaur

James Norcross

PN: RPS-PDU-CM-4/RPS-PDU-5

10/16/19

A

Initial Release 10/16/19 EEK