Power Substation Automation & Communication_IEC 61850

27
Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Power Systems Communications

Transcript of Power Substation Automation & Communication_IEC 61850

Page 1: Power Substation Automation & Communication_IEC 61850

Implementation of IEC61850 in a Substation Environment

26 October 2009 Reference VEE4700-01 Revision 0

Power Systems Communications

Page 2: Power Substation Automation & Communication_IEC 61850

Document Control

Document ID: DOCUMENT1

Rev No Date Revision Details Typist Author Verifier Approver

0 20/10/2009 Document Created Team Team Team

Page 3: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE i

Contents Section Page

1. Introduction 1

1.1 IEC 61850 Standard 2

1.2 Peer-to-Peer Message (GOOSE) 2

1.3 Process Bus Interface 2

1.4 True Interoperability 2

2. Generator Protection 3

2.1 Chosen Relay for Generator Protection 3

2.2 Key Benefits and Features of G60 Relay 3

2.3 Wiring Diagrams for Generator Protection 4

3. Transformer protection 7

3.1 Key Features 7

3.2 User Benefits 7

3.3 Single line diagram of how relay connected to the transformer 8

4. Switchgear Protection 9

4.1 Busbar Protection 9

4.2 The important issues of switchgear protection can be summarized 9

4.3 The requirements for good protection 9

4.4 330kV Busbars 10

4.5 Intelligent Electronic Device (IED) 10

4.5.1 Functional Block Diagram (GE Multilin) 11

4.5.2 Substation Monitoring (Human Machine Interface) 11

4.6 Differential Busbar Protection 12

5. Line Protection 15

5.1 Line Distance Protection 15

5.2 IED61850 Application 16

5.3 Distance IED Communications Application 18

6. Substation Communications Network (IED61850 Network) 19

6.1 Implementation of IEC61850 19

6.2 Redundant Network 19

7. Conclusion 20

Page 4: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 1

1. Introduction

The aim of the project is to design the protection solution for the given system which has to be in compliance with IEC61850 standard. It is also required to work out the infrastructure of the next generation power system communications including the communication and telecommunication protocols.

Figure 1: Given system

Page 5: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 2

1.1 IEC 61850 Standard

IEC 61850 is the global standard for communication in substations. It enables integration of all protection, control, measurement and monitoring functions within a substation, and additionally provides the means for high-speed substation protection applications, interlocking and intertripping. The comprehensive implementation facilitates integration of the relays into IEC 61850-based Substation Automation Systems and at the same time it allows the interface with different vendors' Merging Units over the IEC 61850 Process Bus. It combines the convenience of Ethernet with the performance and security which is essential in substations today. IEC 61850-enabled relays are fitted with an integral Ethernet card providing both copper and fiber Ethernet. No external adaptors or data concentrators are necessary and only standard Ethernet equipment such as switches and substation grade switches etc are required.

1.2 Peer-to-Peer Message (GOOSE)

Generic Object-Oriented Substation Event (GOOSE) messages can be used for interlocking, disturbance recording cross-triggering, breaker failure protection tripping, directional comparison bus protection and many other advanced applications, thus eliminating extensive hardwiring in equipment bays and so reducing the cost of implementing advanced distributed protection and control schemes. The implementation of the IEC GOOSE messaging provides faster end-to-end transfer than using hardwiring.

1.3 Process Bus Interface

Analog interface units (or Merging Units) located in the substation yard interface with conventional or non-conventional instrument transformers and send the sampled current and voltage values over fiber, thus significantly reducing (actually eliminating) the copper wires between the substation primary equipment and the protection, control and measuring devices.

1.4 True Interoperability

One protocol is all that is needed in the substation. Costly gateways and split path communications are thus avoided. Peer-to-peer messages, control commands, disturbance files transfer or event driven reports are interleaved on a single Substation Bus network. Multiple clients can be integrated, allowing authorized operators and engineers to interrogate and control the substation IEDs. The Substation Configuration Language defined in the standard represents a leap in the engineering process related. The self-descriptive nature of IEC 61850-compatible IEDs means that system integration and commissioning are easier. Standardized data classes and services mean IEC 61850-enabled IEDs can operate seamlessly in multi-vendor environments.

Page 6: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 3

2. Generator Protection

Industrial and commercial power systems may include generators as a local source of energy. These generators supply all or part of the total energy required, or they provide emergency power if the normal source of energy fails. The application of generators can be classified as single-isolated generators, multiple-isolated generators, unit-connected generators, cogeneration generators, and induction generators. Generator protective schemes vary depending on the objectives to be achieved. Generator protection requires the consideration of many abnormal conditions that are not present with other system elements. The abnormal conditions that may occur with generators include:

• Overheating

• Stator (due to overload or loss of cooling)

• Rotor (due to overexcitation, loss of cooling)

• Winding faults

• Stator (phase and ground faults)

• Rotor (ground faults and shorted turns)

• Overspeed and underspeed

• Overvoltage

• Loss of excitation

• Motoring

• Unbalanced current operation

• Out of step

• Subsynchronous oscillations

• Inadvertent energization

• Nonsynchronized connection

2.1 Chosen Relay for Generator Protection

The relays selected for generator protection is manufactured by GE Multilin.

Figure2: GE Multilin G60- Comprehensive protection for generators

2.2 Key Benefits and Features of G60 Relay

Complete IEC 61850 Process Bus solution providing resource optimization. Secure high-speed protection elements for complete generator protection, compliant with IEEE C37.102.

Page 7: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment Implementation of IEC61850 standard in a Substation Environment

FILES

Reduced relay to relay wiring and associated installation costs through highcommunications. Redundant architecture for dependability and securityNetworking interfaces –C37.94. Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870104, Ethernet Global Data (EGD)

2.3 Wiring Diagrams

This relay can perform the followinshown below in single line diagram: Figure 3

For our particular system single line diagram showing VT & CT connections is given below:

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX

Reduced relay to relay wiring and associated installation costs through high-

Redundant architecture for dependability and security. – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, and

IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870104, Ethernet Global Data (EGD).

Wiring Diagrams for Generator Protection

orm the following ANSI functions if configured using standard schemeshown below in single line diagram:

For our particular system single line diagram showing VT & CT connections is given

LOCAL SETTINGS\TEMPORARY INTERNET

POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009

-speed inter-relay

Optic Ethernet, RS485, RS232, RS422, G.703, and

IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-

g ANSI functions if configured using standard scheme as

For our particular system single line diagram showing VT & CT connections is given

Page 8: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009

200MVAGenerator

22kV/330kV

Transformer

CT/VT Connection

Circuit Breaker Trip

110V

VT Metering

Generator Protection

GE G60 – Multilin IED

Protection Employed

8781O/81U

67N59N

50G/51G27P/27TN

24

Generator Protection87

81O/81U67N59N

50G/51G

27P/27TN24

GE G60 Multilin IED

Figure 4

Page 9: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 6

Three CT’s and one VT were used to implement the generator protection and the protection functions employed were:

ANSI Device Number Function 87 Generator Stator Differential 81O Overfrequency 81U Underfrequency 67N Neutral Directional Overcurrent 59N Neutral Overvoltage 50G Ground Instantaneous Overcurrent 51G Ground Time Overcurrent 27P Phase Undervoltage 27TN Third Harmonic Neutral Undervoltage 24 Volts Per Hertz

Page 10: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 7

3. Transformer protection

Transformers are high capital cost assets in electrical power systems. Elimination of all electrical and mechanical stresses desirable to preserve transformer life is impractical. Adaptive techniques to measure and alarm in such instances and advise on service duty can help to schedule preventive maintenance. Internal faults are a risk for all transformers. With short circuits dissipating the highest lacalized energy. Unless cleared quickly the possibility to rewind windings reduces and core damages may become irreparable. The MiCOM P642, P643 and P645 from AREVA address all the issues - preserving service life, and offering fast protection for transformer faults. The P642 incorporates differential, REF, thermal, and overfluxing protection, plus backup protection for uncleared external faults. So we decided to use P642 as it is cheap and suitable for our substation design.

3.1 Key Features

• High-speed transformer differential protection. A proven 2nd harmonic current scheme is used

• Simple setting – wizard requires only nameplate data

• Restricted earth fault (REF) boosts trip sensitivity

• Voltage, frequency, thermal and overfluxing elements

• CT, VT, trip circuit and self-supervision:

• Patented CT supervision ensures no trip for CT or wiring failures

• Integrated backup overcurrent per winding

• Readily interfaces to multiple automation protocols, including IEC 61850

3.2 User Benefits

• Universal IED for all transformer configurations

• Simple to specify, set and commission

• Backup and logging of faults

• Protection , control , measurements and recording in one device

Page 11: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment Implementation of IEC61850 standard in a Substation Environment

FILES

3.3 Single line diagram of how relay connected to the transformer

CTs on both side of the transformer are for differential protection. Grounding CT is to tell weather the connection is delta/star or star/deltaOvercurrent backup protection indicates from dotted red line.

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX

Single line diagram of how relay connected to the transformer

CTs on both side of the transformer are for differential protection. Grounding CT is to tell weather the connection is delta/star or star/delta Overcurrent backup protection indicates from dotted red line.

LOCAL SETTINGS\TEMPORARY INTERNET

POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009

Single line diagram of how relay connected to the transformer

CTs on both side of the transformer are for differential protection. Grounding CT is to tell weather the

Page 12: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 9

Page 13: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 10

4. Switchgear Protection

4.1 Busbar Protection

Busbars are one of the most important components in a substation. There can be open busbars in an outdoor switch yard or contained inside a metal clad cubicle restricted within a limited enclosure with minimum phase-to-phase and phase-to ground clearances. Busbars form an electrical node where many circuits come together, feeding in and feeding out power. It is very clear that for any reason the busbars fails, it could lead to shutdown of all distribution loads connected through them, even if the power generation is normal and the feeders are operating normally.

4.2 The important issues of switchgear protection can be summarized

• Loss very serious and sometimes catastrophic

• Switchgear damaged beyond repair

• Multi-panel boards not available ‘off-the-shelf’

• Numerous joints

• Air enclosure

• Dust build-up

• Insect nesting

• Ageing of insulation

• Frequency of stress impulses

• Long earth fault protection tripping times

4.3 The requirements for good protection

The successful protection can be achieved subject to compliance with the following:

• Speed – Limit damage at fault point – Limit effect on fault stability

• Selectivity – Trip only the faulted equipment – Important for busbars divided into zones

• Stability – Not to operate for faults outside the zone – Most important for busbars – Stability must be guaranteed

• Reasons for loss of stability – Interruption of CT circuits – imbalance – Accidental operation during testing

• Tripping can be arranged ‘two-out-of-two’ – Zone and check relays

Page 14: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 11

4.4 330kV Busbars

This is the 330kV busbars that require busbar protection.

4.5 Intelligent Electronic Device (IED)

IEDs selected to protect the 330kV busbars.

Page 15: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 12

4.5.1 Functional Block Diagram (GE Multilin)

4.5.2 Substation Monitoring (Human Machine Interface)

Page 16: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 13

4.6 Differential Busbar Protection

The busbars will be protected by two IEDs; the purpose of the two IEDs is to provide reliability and backup protection. If one IED fails, one busbar will still be protected.

Page 17: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 14

Page 18: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 15

Page 19: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 16

Page 20: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 17

5. Line Protection

This part of the report will be covering the transmission line protection of the substation. The main faults that can occur on the transmission lines are:

• Line to Line

• Line to ground

• Double line to ground

• Three phase line to ground These faults can be caused by simply things such as birds, snakes, bushfires, and branches falling on to the line. They can also be caused by lightning and deterioration of insulation. This section will be focusing on the four transmission lines for the 2 buses which have to lines each as shown below.

Figure 5.1 Four transmission lines

5.1 Line Distance Protection

In order to protect these four lines two relays from different vendors has been chosen. The first relay chosen is the ABB REL 670 Distance relay (figure 2). The REL 670 relay is fully IEC61850 complaint and features Control, monitoring and protection integrated in to the one IED. This relay is also chosen because of its maximum reliability and performance optimized for Figure 2. ABB relay transmission overhead lines and cables.

Page 21: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 18

The way in which The ABB REL 760 relay is connected to the transmission line is in the Dual breaker configuration instead of a simply configuration which uses 1 VT and 1 CT. The Dual breaker configuration uses 2 VTs and 2VTs it will cost more but is a lot more reliable. The connection scheme can be seen in figure 3. The second relay used in the system is the GE D90Plus (figure 4) . The D90Plus is also fully IEC61850 and also features back up protection such as time over current. The D90Plus is also selected because of the fact that it can use fibre optic communication. The D90Plus is connected on the same scheme as the ABB in which it is connected in a Dual breaker scheme with 2 VTs and 2 CTs.(Figure 5) Figure 4. GE D90Plus

Figure 5. D90Plus connection

5.2 IED61850 Application

When all the relays have been place in the substation, the relays from the two vendors are connected together by the fibre optic link on the process bus as can be seen in figure 6. One each bus we have 4 CTs and 4VTs with 3 circuit breakers with one of those circuit breakers being used by both relays.

Page 22: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 19

Page 23: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 20

5.3 Distance IED Communications Application

This report covers the transmission line protection of a new substation but Figure 7 shows a larger picture of the system with the top half being the new substation and the bottom half being another substation xxx Kilometres away, the top substation uses a ABB relay while the bottom substation uses a GE relay and the two are connected by a fibre optic cable xxx Kilometres away.

Page 24: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 21

Page 25: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 22

6. Substation Communications Network (IED61850 Network)

6.1 Implementation of IEC61850

6.2 Redundant Network

• Redundant bay controller has default settings • Local servers store all real time data • operate substation in the event of network hack, security breach or corrupted data

transmitted to control centre • can only take instructions from the local HMI • Require passwords • A SMS message will be sent using a mobile phone or other similar device via a message

broker in an emergency

Page 26: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 23

Page 27: Power Substation Automation & Communication_IEC 61850

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET

FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX 26 OCTOBER 2009 REVISION 1 PAGE 24

7. Conclusion

The IEC61850 standard will become the most widely used standard for substation communications. The main features being interoperability, reliability (easy to replace IED’s with different vendor IED’s), advanced protection, advanced automation and control (smart grid compatibility), advanced metering and easier/simplified human interface with the power system.