Power Mod - Siemens · n 750kcmil AL wire options ... Dimensions (inches)a Factory installed line...
Transcript of Power Mod - Siemens · n 750kcmil AL wire options ... Dimensions (inches)a Factory installed line...
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-56
Mul
ti-f
amil
y M
eter
ing
Power Mod Main Disconnects: WB Circuit Breaker Main Introduction
Standard Circuit Breaker MainsStandard breaker modules (type WB) offer a balance between functionality, feature, and size constraints.
Features include:n QuickSystem™ features
n Compression lug landing pads (field install up to 1200 Amps, standard feature up to 2000 Amps)
n Combination overhead and underground feed up to 1200 Amps, dedicated overhead or underground feed up to 2000 Amps
n 750kcmil AL wire options
n 65K AIC standard, 100K AIC available for all models
n Removable blank bottom endwall
n Externally accessible breaker handle with padlock capability
n Broad ampacity ratings up to 2000 Amps with non-standard amperages available (such as 700, 900, etc.)
n Field installable shunt trips
Standard Circuit Breaker Mains Quick Reference
n 200-2000A
n 1200A thru-bus rating
n UL Standard # UL67
n UL file # E27100
n AIC rating (65k & 100k)
n Voltage:
- Single phase 120/240V AC max
- Three phase 240V AC max
n All swing latches and rivets are stainless steel
n NEMA 3R rated
n G90 galvanized steel
n ANSI 61 paint
n Custom options now available! Details on page 2-109
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-57
Multi-fam
ily M
etering
Product Category: RESI
Power Mod Main Disconnects: WB Circuit Breaker Mains – 1Ø
Circuit breaker service entrance modules: 1-phase, 3-wire SN, 120/240V AC
Catalog number (65k AIC)d
Catalog number (100k AIC)b d
Ampere rating
Service feed
Breaker typee
Dimensions (inches)aFactory installedline side connections
Knockout DiagramHeight Width Depth
WB1200Cb WB1200CU 200 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1250Cb WB1250CU 250 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1300Cb WB1300CU 300 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1350Cb WB1350CU 350 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1400C WB1400CU 400 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1450Cb WB1450CU 450 OH/UG LXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1500Cb WB1500CU 500 OH/UG LXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1600C WB1600CU 600 OH/UG LXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB1700Cb WB1700CU 700 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2, page 2-59
WB1800C WB1800CU 800 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2, page 2-59
WB1900Cb WB1900CU 900 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3, page 2-59
WB11000C WB11000CU 1000 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3, page 2-59
WB11200C WB11200CU 1200 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3, page 2-59
WB11400Tbc WB11400TUc
1400OH PXD6 72.06 31.34 14.66
3 Sets of 2 Studs
(lugs not included)
KB-4, page 2-59
WB11400Bbc WB11400BUc UG PXD6 72.06 31.34 14.66 KB-5, page 2-59
WB11600Tc WB11600TUc
1600OH PXD6 72.06 31.34 14.66 KB-4, page 2-59
WB11600Bc WB11600BUc UG PXD6 72.06 31.34 14.66 KB-5, page 2-59
WB11800B WB11800BU1800
UG RXD6 72.06 31.34 14.66 KB-5, page 2-59
WB11800Wbc WB11800WUbc OH/UG RXD6 72.06 50.56 14.66 KB-6, page 2-59
WB12000Bc WB12000BUc
2000UG RXD6 72.06 31.34 14.66 KB-5, page 2-59
WB12000Wbc WB12000WUbc OH/UG RXD6 72.06 50.56 14.66 KB-6, page 2-59
a Dimensions shown are representative of outside box dimensions and do not include allowances for mount-ing bumps, hubs, or hardware protrusions.
b 100K and non-standard amperage devices require addi-tional lead time. Please contact sales office for details on lead time.
Factory installed lugs are standard on 200-1200A stan-dard breaker main modules. Additional lug kit options are available for 750 conductor size. Refer to page 2-110 for lug kit options on 200-1200A standard main breakers. In addition, a field installable compression lug landing pad is also available. Refer to page 2-109 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility.
Lugs are NOT included on 1400A-2000A stan-dard breaker main modules and must be ordered separately. Refer to page 2-110 for lug size options.
c 1200 amp maximum feed per side - must be used as a center fed main.
d Factory installed lugs standard on 200-1200A standard breaker main modules. Additional lug kit options avail-able for 750 conductor size. Refer to page 2-110 for lug kit options on 200-1200A standard main breakers. Field installable compression lug landing pad also available.
Refer to page 2-109 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility.
Lugs NOT included on 1400A-2000A standard breaker main modules and must be ordered separately. Refer to page 2-110 for lug size options.
e All breakers have a non-interchangeable trip unit.
• Revised •05/09/12
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-58
Mul
ti-f
amil
y M
eter
ing
Power Mod Main Disconnects: WB Circuit Breaker Mains – 3Ø
Circuit breaker service entrance modules: 3-phase, 4-wire SN, 240V AC max
Catalog number (65k AIC)d
Catalog number (100k AIC)b d
Ampere rating
Service feed
Breaker typee
Dimensions (inches)aFactory installedline side connections
Knockout DiagramHeight Width Depth
WB3200Cb WB3200CU 200 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3250Cb WB3250CU 250 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3300Cb WB3300CU 300 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3350Cb WB3350CU 350 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3400C WB3400CU 400 OH/UG JXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3450Cb WB3450CU 450 OH/UG LXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3500Cb WB3500CU 500 OH/UG LXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3600C WB3600CU 600 OH/UG LXD6 39.19 15.20 11.03 (2) 3/0-500 kcmil CU(2 )4/0-500 kcmil AL KB-1, page 2-59
WB3700Cb WB3700CU 700 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2, page 2-59
WB3800C WB3800CU 800 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2, page 2-59
WB3900Cb WB3900CU 900 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3, page 2-59
WB31000C WB31000CU 1000 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3, page 2-59
WB31200C WB31200CU 1200 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3, page 2-59
WB31400Tbc WB31400TUc
1400OH PXD6 72.06 31.34 14.66
3 Sets of 2 Studs
(lugs not included)
KB-4, page 2-59
WB31400Bbc WB31400BUc UG PXD6 72.06 31.34 14.66 KB-5, page 2-59
WB31600Tc WB31600TUc
1600OH PXD6 72.06 31.34 14.66 KB-4, page 2-59
WB31600Bc WB31600BUc UG PXD6 72.06 31.34 14.66 KB-5, page 2-59
WB31800B WB31800BU1800
UG RXD6 72.06 31.34 14.66 KB-5, page 2-59
WB31800Wbc WB31800WUbc OH/UG RXD6 72.06 50.56 14.66 KB-6, page 2-59
WB32000Bc WB32000BUc
2000UG RXD6 72.06 31.34 14.66 KB-5, page 2-59
WB32000Wbc WB32000WUbc OH/UG RXD6 72.06 50.56 14.66 KB-6, page 2-59
a Dimensions shown are representative of outside box dimensions and do not include allowances for mount-ing bumps, hubs, or hardware protrusions.
b 100K and non-standard amperage devices require addi-tional lead time. Please contact sales office for details on lead time.
Factory installed lugs are standard on 200-1200A stan-dard breaker main modules. Additional lug kit options are available for 750 conductor size. Refer to page 2-110 for lug kit options on 200-1200A standard main breakers. In addition, a field installable compression lug landing pad is also available. Refer to page 2-109 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility.
Lugs are NOT included on 1400A-2000A stan-dard breaker main modules and must be ordered separately. Refer to page 2-110 for lug size options.
c 1200 amp maximum feed per side - must be used as a center fed main.
d Factory installed lugs standard on 200-1200A standard breaker main modules. Additional lug kit options avail-able for 750 conductor size. Refer to page 2-110 for lug kit options on 200-1200A standard main breakers. Field installable compression lug landing pad also available.
Refer to page 2-109 for lug landing pad options. NEMA II Stud Pattern compression lugs must be installed by user or utility.
Lugs NOT included on 1400A-2000A standard breaker main modules and must be ordered separately. Refer to page 2-110 for lug size options.
e All breakers have a non-interchangeable trip unit.
Product Category RESI
• Revised •05/09/12
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-59
Multi-fam
ily M
etering
TO BOTTOM OFQUICK ROLL
BRACKET
46-21/32
TONEUTRAL
STUDS
29-3/8
72-1/16
TOCROSS BUS
CENTER
35-1/32
6
3
14-21/32
31-11/32
TOPHASESTUDS
27-3/8
WB31400TWB31400TUWB31600TWB31600TUWB32000TWB32000TU
}1-3/4 NEMASTUD SPACING
6 TYPE "HD" 4" MAX HUB OPENINGS
FACTORY INSTALLEDCOVER PLATES
31-11/32
14-21/32
TOCROSS BUS
CENTER
37-1/32
TOPHASESTUDS
27-3/8 TONEUTRAL
STUDS
29-3/8
11-29/32
18-5/32
72-1/16
28-5/8
REMOVABLEBOTTOM
ENDWALLOPENING
}
TOBOTTOM OFQUICK ROLL
BRACKET
48-21/32
1-3/4 NEMASTUD SPACING
KB-1
WB3200XXWB3250XXWB3300XXWB3350XXWB3400XXWB3450XXWB3500XXWB3600XX
WB1200XX WB1250XXWB1300XXWB1350XXWB1400XX WB1450XXWB1500XXWB1600XX
KB-2
WB3700XXWB3800XX
WB1700XXWB1800XX
KB-3
WB3900XXWB31000XXWB31200XX
WB1900XXWB11000XXWB11200XX
KB-4
WB31400TXWB31600TXWB32000TX
WB11400TXWB11600TXWB12000TX
KB-6
WB12000WWB12000WUWB11800W
WB11800WU
WB31800WWB31000WUWB32000W
WB32000WU
KB-5
WB31400BXWB31600BXWB31800BXWB32000BX
WB11400BXWB11600BXWB11800BXWB12000BX
Power Mod Main Disconnects: WB Circuit Breaker Mains Knockout Diagrams
• Revised •05/09/12
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-60
Mul
ti-f
amil
y M
eter
ing
Power Mod Main Disconnects: WEB Circuit Breaker – Pullbox Combinations Introduction
Circuit Breaker-Pullbox CombinationsEUSERC - compliant breaker - pullbox combination modules (type WEB) offer EUSERC compatibility, a wider range of lug options, and extra space for pulling in conductors.
Features include:n QuickSystem™ features
n Factory installed NEMA II studs
n 750 kcmil AL wire options
n 65K AIC standard, 100K AIC available for all models
n Removable blank bottom endwall
n Externally accessible breaker handle with padlock capability
n Field installable shunt trips
n Large removable ground wire trough with generous space for grounding conductors
Circuit Breaker-Pullbox Combinations Quick Reference
n 200-1200A
n 1200A thru-bus
n UL standard # UL67
n UL file # E27100
n AIC rating (65k & 100k)
n Voltage
- Single phase 120/240V AC Max
- Three phase 240V AC Max
n All swing latches and rivets are stainless steel
n NEMA 3R rated
n G90 galvanized steel
n ANSI 61 paint
n EUSERC drawing number 347
n Custom options now available! Details on page 2-109
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-61
Multi-fam
ily M
etering
a Dimensions shown are representative of outside box dimensions and do not include allowances for mount-ing bumps, hubs, or hardware protrusions.
b Non standard module. Has longer ordering lead times, contact sales office for additional ordering information.
Lugs not included. Refer to page 2-110for lug size options. Lug kits available for 750 conductor size. NEMA II Stud Pattern Compression lugsmust be provided by user or utility.
Combination circuit breaker and pullbox modules: 1-phase, 3-wire SN, 120/240V AC max Meets EUSERC requirements
Catalog number (65k AIC)
Catalog number (100k AIC)b
Ampere rating
Service feed
Breaker typed
Dimensions (inches)aLine sidec
connections(lugs not included)
Knockout DiagramHeight Width Depth
WEB1200Bb WEB1200BU 200 UG JXD6 54.88 28.28 13.06
1 set of2 studs
EB-1 page 2-63
WEB1250Bb WEB1250BU 250 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB1300Bb WEB1300BU 300 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB1350Bb WEB1350BU 350 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB1400B WEB1400BU 400 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB1500Bb WEB1500BU 500 UG LXD6 54.88 28.88 13.06
2 sets of 2 studs
EB-2 page 2-63
WEB1600B WEB1600BU 600 UG LXD6 54.88 28.28 13.06 EB-2 page 2-63
WEB1700Bb WEB1700BU 700 UG MXD6 59.34 34.22 12.47 EB-3 page 2-63
WEB1800B WEB1800BU 800 UG MXD6 59.34 34.22 12.47 EB-3 page 2-63
WEB1900Bb WEB1900BUb 1000 UG NXD6 59.34 34.22 12.47
3 sets of 2 studs
EB-4 page 2-63
WEB11000B WEB11000BU 1000 UG NXD6 59.34 34.22 12.47 EB-4 page 2-63
WEB11200B WEB11200BU 1200 UG NXD6 59.34 34.22 12.47 EB-4 page 2-63
c Lugs not included. Refer to page 2-110 for lug size options. Lug kits available for 750 conductor size.
NEMA II Stud Pattern Compression lugs must be pro-vided by user or utility.
d All breakers have a non-interchangeable trip unit.
Available options include:
n 200-1200 Amps
n 65k AIC or 100k AIC
n Up to 750 kcmil lugs available
Power Mod Main Disconnects: WEB Circuit Breaker – Pullbox Combinations – 1Ø
Product Category RESI
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-62
Mul
ti-f
amil
y M
eter
ing
Lugs not included. Refer to page 2-110 for lug size options. Lug kits available for 750 conductor size. NEMA II Stud Pattern Compression lugsmust be provided by user or utility.
Dimensions shown are representative of outside box dimensions and do not include allowances for mount-ing bumps, hubs, or hardware protrusions.
Combination circuit breaker and pullbox modules: 3-phase, 4-wire SN, 240V AC max Meets EUSERC requirements
Catalog number (65k AIC)
Catalog number (100k AIC)
Ampere rating
Service feed
Breaker type
Dimensions (inches)Line side connections(lugs notincluded)
Knockout DiagramHeight Width Depth
WEB3200B WEB3200BU 200 UG JXD6 54.88 28.28 13.06
1 set of2 studs
EB-1 page 2-63
WEB3250B WEB3250BU 250 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB3300B WEB3300BU 300 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB3350B WEB3350BU 350 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB3400B WEB3400BU 400 UG JXD6 54.88 28.28 13.06 EB-1 page 2-63
WEB3500B WEB3500BU 500 UG LXD6 54.88 28.28 13.06
2 sets of 2 studs
EB-2 page 2-63
WEB3600B WEB3600BU 600 UG LXD6 54.88 28.28 13.06 EB-2 page 2-63
WEB3700B WEB3700BU 700 UG MXD6 59.34 34.22 12.47 EB-3page 2-63
WEB3800B WEB3800BU 800 UG MXD6 59.34 34.22 12.47 EB-3page 2-63
WEB3900B WEB3900BU 900 UG NXD6 59.34 34.22 12.47
3 sets of2 studs
EB-4page 2-63
WEB31000B WEB31000BU 1000 UG NXD6 59.34 34.22 12.47 EB-4page 2-63
WEB31200B WEB31200BU 1200 UG NXD6 59.34 34.22 12.47 EB-4page 2-63
Non standard module. Has longer ordering lead times, contact sales office for additional ordering information.
Lugs not included. Refer to page 2-110 for lug size options. Lug kits available for 750 conductor size.
NEMA II Stud Pattern Compression lugs must be pro-vided by user or utility.
All breakers have a non-interchangeable trip unit.
Product Category RESI
Available options include:
■ 200-1200 Amps
■ 65k AIC or 100k AIC
■ Up to 750 kcmil lugs available
Power Mod Main Disconnects: WEB Circuit Breaker – Pullbox Combinations – 3Ø
• Revised •05/09/12
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-63
Multi-fam
ily M
etering
Power Mod Main Disconnects: WEB Circuit Breaker – Pullbox Combinations Knockout Diagrams
EB-1
WEB1200BWEB3200BWEB1250BWEB3250BWEB1300B
WEB3300BWEB1350BWEB3350B WEB1400BWEB3400B
WEB1200BWEB3200BUWEB1250BWEB3250BUWEB1300B
WEB3300BUWEB1350BWEB3350BUWEB1400BUWEB3400BU
EB-2
WEB1500BWEB3500B WEB1600BWEB3600B
WEB1500BUWEB3500BU WEB1600BUWEB3600BU
29-1/8
TOCROSS BUS
CENTER
33-1/4
TO PHASE AND
NEUTRALSTUDS
26-25/32
59-11/32
34-7/32
12-15/32
32
TOBOTTOM OFQUICK ROLL
BRACKET
44-7/8
8-5/83/4 KO
REMOVABLEBOTTOM
ENDWALLOPENING
}
1-3/4" NEMASTUD SPACING
8-5/8
29-1/8
TOCROSS BUS
CENTER
33-1/4
TO PHASE AND
NEUTRALSTUDS
26-25/32
59-11/32
34-7/32
12-15/32
TOBOTTOM OFQUICK ROLL
BRACKET
44-7/8
32
}
1-3/4" NEMASTUD SPACING
3/4 KO
REMOVABLEBOTTOM
ENDWALLOPENING
EB-4
WEB11000BWEB11200BWEB31000BWEB31200B
WEB11000BUWEB11200BUWEB31000BUWEB31200BU
EB-3
WEB1700BWEB3700BWEB1800BWEB3800B
WEB1700BUWEB3700BU WEB1800BU WEB3800BU
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-64
Mul
ti-f
amil
y M
eter
ing
Power Mod Main Disconnects: WS Switch Mains Introduction
Standard Switch MainsStandard switch modules (type WS) are designed for flexibility, space savings, & durability.
Features include:n QuickSystem™ features
n Standard compression lug capability
n Invertibility: 400-800 Amp devices can be rotated to accommodate the desired incoming feed direction
n 750 kcmil AL wire options for most models
n 100K AIC standard for all models
n Class T fuse provisions
n Front mounted handle - removes the need for spac-ers on the side
n Broad ampacity ratings up to 1200 Amps
Standard Switch Mains Quick Reference
n 200-1200A
n 1200A thru-bus
n UL Standard # UL98
n UL file #E25506
n AIC rating (100k AIC)
n Voltage:
- Single phase 120/240V AC max
- Three phase 240V AC max
n All swing latches and rivets are stainless steel
n NEMA 3R rated
n G90 galvanized steel
n ANSI 61 paint
n Custom options now available! Details on page 2-109
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-65
Multi-fam
ily M
etering
Power Mod Main Disconnects: WS Switch Mains – 1Ø and 3Ø
Lugs not included. NEMA II stud pattern lugs must be installed by user or utility. Refer to page 2-110 for lug size options.
Main Features:n Invertibility for 400 to
800 amps
n Class T (300V) fuse provisions
n Up to 750 kcmil lugs available
a Dimensions shown are representative of outside box dimensions and do not include allowances for mount-ing bumps, hubs, or hardware protrusion.
b Module is invertible - rotate device to point hub open-ings to appropriate feed direction.
Fusible switch service entrance modules: 1-phase, 3-wire SN, 120/240V AC, 100k AICd
Catalog number
Rating amps
Service feed
Fuse typed
Dimensions (inches)a Line side connections
Knockout DiagramHeight Width Depth
WMP02Ug 200 OH/UG T 33.00 12.00 13.00 (1) #6 - 250 KCMIL S-0 page 2-66
WS1400CUe 400 OH/UGb T 50.13 15.19 16.31 1 set of 2 studs
(lugs not included)
S-1 page 2-66
WS1600CUe 600 OH/UGb T 50.13 15.19 16.31
WS1800CUe 800 OH/UGb T 50.13 15.19 16.31
2 sets of 2 studs
(lugs not included)
S-2 page 2-66
WS11200BUcf 1200 UG T 50.06 20.22 16.06 (4) 250- 500 kcmil S-3 page 2-66
Fusible switch service entrance modules: 3-phase, 4-wire WN, 240V AC Max., 100k AICd
Catalog number
Rating amps
Service feed
Fuse typed
Dimensions (inches)a Line side connections
Knockout DiagramHeight Width Depth
WMP024Ug 200 OH/UG T 33.00 12.00 13.00 (1) #6 - 250 KCMIL S-0 page 2-66
WS3400CUe 400 OH/UGb T 50.13 15.19 16.31 1 set of 2 studs
(lugs not included)
S-1 page 2-66
WS3600CUe 600 OH/UGb T 50.13 15.19 16.31
WS3800CUe 800 OH/UGb T 50.13 15.19 16.31
2 sets of 2 studs
(lugs not included)
S-2 page 2-66
WS31200BUcf 1200 UG T 50.06 20.22 16.06 (4) 250-500 kcmil S-3 page 2-66
c 500 kcmil max wire range size.d Fuses not included.e Lugs not included. NEMA II stud pattern compression
lugs must be installed by user or utility. Refer to page 2-110 for lug size options.
f Device uses a molded case switch (looks like a breaker). Class T fuses must be installed in conjunction with the molded case switch for proper operation.
g Fusible pull-out switch. No QuickSystem features offered for this catalog number. Additional lead time required. Contact sales office for details on lead time.
Product Category RESI
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-66
Mul
ti-f
amil
y M
eter
ing
Power Mod Main Disconnects: WS Switch Mains Knockout Diagrams
20- 7/32
16 -1/16
50- 1/16
16- 15/16TO PHASE
LUGS15- 3/4 T ONEUTRAL
LUGS
35- 1/8 T OBOTTOM OFQUICK ROLL
BRACKET23- 1/2 T O
CROSS BUSCENTER
18- 5/16
15- 7/32 T OGROUND
LUG
REMOVABLEBOTTOM ENDWALL
17- 23/32
12 -23/32
S-1
WS1400CUWS1600CU
WS3400CUWS3600CU
S-2
WS1800CU WS3800CU
S-0
WMP02U WMP024U
S-3
WS11200BU WS31200BU
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-67
Multi-fam
ily M
etering
Switch-Pullbox CombinationsEUSERC - compliant switch-pullbox combination modules (type WES) offer EUSERC compatibility, a wider range of lug options, and extra space for pulling in conductors.
Features include:n QuickSystem™ features
n Factory installed NEMA II studs
n Broad ampacity ratings up to 1200 Amps
n 750kcmil AL wire options
n 100K AIC standard for all models
n Removable blank bottom endwall
n Front mounted handle - removes the need for spacers on the side
n Class T fuse provisions
n Large removable ground wire trough with generous space for grounding conductors
n Extra ground lugs in each device
Switch-Pullbox Combinations Quick Reference
n 400-1200A
n 1200A thru-bus
n UL standard # UL98
n UL file # E25506
n AIC Rating (100k AIC)
n Voltage: - Single phase 120/240V AC max
- Three phase 240V AC max
n All swing latches and rivets are stainless steel.
n NEMA 3R rated
n G90 galvanized steel
n ANSI 61 paint
n EUSERC drawing number 347
n Custom options now available! Details on page 2-109
Power Mod Main Disconnects: WES Switch-Pullbox Combinations Introduction
2M
ETER
CE
NTER
S
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog2-68
Mul
ti-f
amil
y M
eter
ing
Power Mod Main Disconnects: WES Switch-Pullbox Combinations – 1Ø and 3Ø
a Dimensions shown are representative of outside box dimensions and do not include allowances for mount-ing bumps, hubs, or hardware protrusions
b Fuses not included
Combination fusible switch and pullbox modules: 1-phase, 3-wire SN, 120/240V AC Meets EUSERC requirements, 100k AIC b
Catalog number
Rating Amps
Service feed
Fuse type c
Dimensions (inches) a
Line sidec connections(lugs not included)
Knockout DiagramHeight Width Depth
WES1400BU 400 UG T 54.06 29.19 15.941 set of 2 studs ES-1
page 2-69
WES1600BU 600 UG T 54.06 29.19 15.94 2 sets of 2 studs ES-2
page 2-69WES1800BU 800 UG T 54.06 29.19 15.94
WES11200BUd 1200 UG T 68.97 34.25 13.47
3 sets of 2 studs ES-3
page 2-69
Combination fusible switch and pullbox modules: 3-phase, 4-wire SN, 240V AC max. Meets EUSERC requirements, 100k AIC b
Catalog number
Rating Amps
Service feed
Fuse type
Dimensions (inches) a
Line sidec connections(lugs not included)
Knockout Diagramon pageHeight Width Depth
WES3400BU 400 UG T 54.06 29.19 15.94
1 set of 2 studs
ES-1 page 2-69
WES3600BU 600 UG T 54.06 29.19 15.942 sets of 2 studs
ES-2 page 2-69
WES3800BU 800 UG T 54.06 29.19 15.94
WES31200BUd 1200 UG T 68.97 34.25 13.47
3 sets of 2 studs
ES-3 page 2-69
c Lugs not included. NEMA II Stud Pattern compression lugs must be installed by user or utility. Refer to page 2-110 for lug size options.
d Device uses a molded case switch (looks like a breaker). Class T fuses must be installed in conjunction with the molded case switch for proper operation.
Lugs not included. NEMA II Stud Pattern lugs must be installed by user or utility. Refer to page 2-110 for lugsize options.
Product Category RESI
Main Features:n 400 to 800 amp models
n Class T (300V) fuse provisions
n Up to 750 kcmil lugs available
2M
ETER CENTERS
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 2-69
Multi-fam
ily M
etering
Power Mod Main Disconnects: WES Switch-Pullbox Combinations Knockout Diagrams
ES-1
WES1400BU WES3400BU
ES-2
WES1600BUWES1800BU
WES3600BUWES3800BU
1- 3/4" NEMASTUD SPACING
44- 7/8 T O BOTTOM OFQUICK ROLL
BRACKET
26 -9/16
33 -1/4 T O CROSS BUS
CENTER26 -13/16 T OPHASE A ND
NEUTRAL STUDS
34 -1/4
13 -15/32
68 -31/32
}
29 -1/8
8- 5/8
(3) 3/4" KOs
3 -7/8
1 -1/8REMOVABLE BOTTOM
ENDWALL OPENING
ES-3
WES11200BU WES31200BU