PlumbingCodeinCommercialKitchens 5.9.12

55
Plumbing Code in Commercial Kitchens NH BOA May 9, 2012

description

Code Compliance for Commercial Kitchen

Transcript of PlumbingCodeinCommercialKitchens 5.9.12

  • Plumbing Code in

    Commercial Kitchens

    NH BOA

    May 9, 2012

  • Main Topics

    Grease Interceptors

    Indirect Waste Receptors

    Cleaning Chemical Dispensers

    Thermal Expansion

  • IPC - Chapter 10

    Traps

    Interceptors

    Separators

  • Section 1002 Trap Requirements

    1002.1 Fixture Traps. Each fixture shall be

    separately trapped by a liquid-seal trap , except as

    otherwise permitted by this code. The vertical

    distance from the fixture outlet to the trap weir shall

    not exceed 24 inches, and the horizontal distance

    shall not exceed 30 inches measured from the

    centerline of the fixture outlet to the centerline of

    the inlet of the trap. The height of a clothes washer

    standpipe above trap shall conform to Section 802.4.

    A fixture shall not be double trapped.

  • Section 1002.1

    Exception #3 A grease interceptor intended to serve as a fixture

    trap in accordance with the manufacturers installation

    instructions shall be permitted to serve as the trap for a single

    fixture or a combination sink of not more than three

    compartments where the vertical distance from the fixture outlet

    to the inlet of the interceptor does not exceed 30 inches and the

    developed length of the waste pipe from the most upstream

    fixture outlet to the inlet of the interceptor does not exceed 60

    inches.

  • ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY 14733

    Phone: 1-800/906-5060 Fax: 716/665-3126 World Wide Web: www.zurn.com

    Form # JS2 Date: 3/13/09 C.N. No. 99791 Rev. F Page 1 of 2

    GT2700Grease Interceptor Installation & Cleaning Instructions

    INSTALLATION

    1. Zurn Light Commercial Grease Interceptors

    should be installed as close as possible to the

    fixture being served. Always install where there

    is easy access for cover removal and cleaning.

    2. A flow control must be installed as close as

    possible to the underside of the fixture. The

    flow control must be installed with the vent or

    (air intake) on the downstream side of the orifice

    plate. The vent connection is positioned to the

    top of the flow control fitting and piped upward

    higher than source of water, or to building vent

    system

    3. It is recommended that a cleanout tee be

    installed before the flow control to access the

    flow control orifice and clear debris.

    4. The cleanout plug should be installed over the

    outlet of the interceptor.

    5. The interceptor is to be installed using no-hub

    couplings.

    6. Outlet piping should be connected to the

    sanitary drain, and pipe size should be equal

    to or larger than the inlet piping. Outlet pipe

    should also be vented so the interceptor is not

    siphoned.

    7. Solid waste should not go into an interceptor.

    Food grinder waste and other solids should

    be captured in the sink or by a solids interceptor

    before reaching the grease interceptor.

    Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at

    ( ) gpm and a properly sized flow control fitting.

  • 1002.2 Design of traps. Fixture traps shall be self-scouring. Fixture traps

    shall not have interior partitions, except where such traps are integral wih

    the fixture or where such traps are constructed of an approved material that

    is resistant to corrosion and degradation.

    1002.3 Prohibited Traps

    6. Drum traps

    Exception: Drum traps used as solids interceptors and drum traps

    serving chemical waste systems shall not be prohibited.

    1002.4 Trap seals. Each fixture trap shall have a liquid seal of not less than

    2 inches and not more than 4 inches or deeper for for special designs relating

    to accessible fixtures.

  • 1003.1 Where required.

    Interceptors and separators shall be provided to

    prevent the discharge of oil, grease, sand and

    other substances harmful or hazardous to the

    building drainage system, the public sewer, the

    private sewage disposal system or the sewage

    treatment plant or processes.

  • 1003.2 Approval.

    The size, type and location of each interceptor

    and of each separator shall be designed and

    installed in accordance with the manufacturers instructions and the requirements of this section

    based on the anticipated conditions of use.

    Wastes that do not require treatment or separation

    shall not be discharged into any interceptor or

    separator.

  • 1003.2 Approval.

    The size, type and location of each interceptor

    and of each separator shall be designed and

    installed in accordance with the manufacturers instructions and the requirements of this section

    based on the anticipated conditions of use.

    Wastes that do not require treatment or separation

    shall not be discharged into any interceptor or

    separator.

  • 1003.3.1 Grease Interceptors and Automatic

    Grease Removal Device required. (cont.)

    Fixtures and equipment shall include:

    pot sinks

    pre-rinse sinks

    soup kettles or similar devices

    wok stations

    floor drains or sinks into which kettles are drained

    automatic hood wash units

    dishwashers without pre-rinse sinks.

  • 1003.3.2 Food Waste Grinders

    Where food waste grinders connect to grease interceptors, a solids interceptor shall separate the

    discharge before connecting to the grease

    interceptor. Solids interceptors and grease

    interceptors shall be sized and rated for the

    discharge of the food waste grinder. Emulsifiers,

    chemicals, enzymes and bacteria shall not

    discharge into the food waste grinder.

  • ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY 14733

    Phone: 1-800/906-5060 Fax: 716/665-3126 World Wide Web: www.zurn.com

    Form # JS2 Date: 3/13/09 C.N. No. 99791 Rev. F Page 1 of 2

    GT2700Grease Interceptor Installation & Cleaning Instructions

    INSTALLATION

    1. Zurn Light Commercial Grease Interceptors

    should be installed as close as possible to the

    fixture being served. Always install where there

    is easy access for cover removal and cleaning.

    2. A flow control must be installed as close as

    possible to the underside of the fixture. The

    flow control must be installed with the vent or

    (air intake) on the downstream side of the orifice

    plate. The vent connection is positioned to the

    top of the flow control fitting and piped upward

    higher than source of water, or to building vent

    system

    3. It is recommended that a cleanout tee be

    installed before the flow control to access the

    flow control orifice and clear debris.

    4. The cleanout plug should be installed over the

    outlet of the interceptor.

    5. The interceptor is to be installed using no-hub

    couplings.

    6. Outlet piping should be connected to the

    sanitary drain, and pipe size should be equal

    to or larger than the inlet piping. Outlet pipe

    should also be vented so the interceptor is not

    siphoned.

    7. Solid waste should not go into an interceptor.

    Food grinder waste and other solids should

    be captured in the sink or by a solids interceptor

    before reaching the grease interceptor.

    Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at

    ( ) gpm and a properly sized flow control fitting.

  • In compliance?

  • 1003.3.4.2 Rate of flow controls

    Grease interceptors shall be equipped with

    devices to control the rate of water flow so that the

    water flow does not exceed the rated flow. The

    flow- control device shall be vented and terminate

    not less than 6 inches (152 mm) above the flood

    rim level or be installed in accordance with the

    manufactures instructions.

  • ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY 14733

    Phone: 1-800/906-5060 Fax: 716/665-3126 World Wide Web: www.zurn.com

    Form # JS2 Date: 3/13/09 C.N. No. 99791 Rev. F Page 1 of 2

    GT2700Grease Interceptor Installation & Cleaning Instructions

    INSTALLATION

    1. Zurn Light Commercial Grease Interceptors

    should be installed as close as possible to the

    fixture being served. Always install where there

    is easy access for cover removal and cleaning.

    2. A flow control must be installed as close as

    possible to the underside of the fixture. The

    flow control must be installed with the vent or

    (air intake) on the downstream side of the orifice

    plate. The vent connection is positioned to the

    top of the flow control fitting and piped upward

    higher than source of water, or to building vent

    system

    3. It is recommended that a cleanout tee be

    installed before the flow control to access the

    flow control orifice and clear debris.

    4. The cleanout plug should be installed over the

    outlet of the interceptor.

    5. The interceptor is to be installed using no-hub

    couplings.

    6. Outlet piping should be connected to the

    sanitary drain, and pipe size should be equal

    to or larger than the inlet piping. Outlet pipe

    should also be vented so the interceptor is not

    siphoned.

    7. Solid waste should not go into an interceptor.

    Food grinder waste and other solids should

    be captured in the sink or by a solids interceptor

    before reaching the grease interceptor.

    Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at

    ( ) gpm and a properly sized flow control fitting.

  • 1003.3.3 Grease interceptors and automatic

    grease removal devices not required.

    A Grease interceptor or an automatic grease

    removal device shall not be required for individual

    dwelling units or any private living quarters.

  • Chapter 8

    Indirect/Special Waste

  • 802.1 Where Required.

    Food-handling equipment and clear-water waste

    shall discharge through an indirect waste pipe as

    specified in Sections 802.1.1 through 802.1.8.

  • Section 802.1.1 Food Handling.

    Equipment and fixtures utilized for the storage,

    preparation and handling of food shall discharge

    through an indirect waste pipe by means of an air

    gap.

  • 802.2.1 Air gap.

    The air gap between the indirect waste pipe and the

    flood level rim of the waste receptor shall be a

    minimum of twice the effective opening of the indirect

    waste pipe.

    Chapter 2 Definitions:

    Air Gap (Drainage System): The unobstructed vertical

    distance through the free atmosphere between the outlet

    of the waster pipe and the flood level rim of the receptacle

    into which the waste pipe is discharging.

    Floor Level Rim: The edge of the receptacle from which

    water overflows.

  • 2 x D

    Waste

    Receptor

  • 802.3 Waste Receptors.

    Every waste receptor shall be of an approved

    type. A removable strainer or basket shall cover

    the waste outlet of waste receptors. Waste

    receptors shall be installed in ventilated spaces.

    Waste receptors shall not be installed in

    bathrooms or toilet rooms or in any inaccessible or

    unventilated space such as a closet or storeroom.

    Ready access shall be provided to waste

    receptors.

  • 802.3.1 Size of Receptors.

    A waste receptor shall be sized for the maximum

    discharge of all indirect waste pipes served by the

    receptor. Receptors shall be installed to prevent

    splashing or flooding.

  • 802.3.2 Open hub waste receptors.

    Waste receptors shall be permitted in the form of a

    hub or pipe extending not less than 1 inch (25.4

    mm) above a water-impervious floor and are not

    required to have a strainer.

  • The 3 Bay Sink

  • 802.1.8 Food Utensils, Dishes, Pots and

    Pan Sinks

    Sinks used for the washing, rinsing or sanitizing of

    utensils, dishes, pots, pans, or service ware used in

    the preparation, servicing or eating of food shall

    discharge indirectly through an air gap or an air break

    or directly connect to the drainage system.

  • WASH RINSE SANITIZE WITH GREASE

    INTERCEPTION, DIRECTLY

    CONNECTED

  • Wash, rinse and sanitize with grease interception,

    indirectly connected using an approved waste receptor

  • CHEMICAL DISPENSERS

    AT THE MOP SINK

  • Expansion Tanks Required?

    Section 607 Hot Water Supply System

    607.3 Thermal expansion control. A means of controlling increased pressure

    caused by thermal expansion shall be provided where required in accordance with

    Sections 607.3.1 and 607.3.2.

    607.3.1 Pressure-reducing valve. For water service system sizes up to and

    including 2 inches, a device for controlling pressure shall be installed where,

    because of thermal expansion, the pressure on the downstream side of a

    pressure-reducing valve exceeds the pressurereducing valve setting.

    607.3.1. Backflow prevention device or check valve. Where a backflow

    prevention device, check valve or other device is installed on a water supply

    system utilizing storage water heating equipment such that thermal expansion

    causes an increase in pressure, a device for controlling pressure shall be

    installed.

    IRC P2903.4

  • Plumbing Safety & Licensing

    Inspectors

    Ron Lemere 603-223-4289 Ext. 25269

    [email protected];

    Sam Zannini Jr. 603 223-4289 Ext. 25271

    [email protected];

    Earl Middlemiss 603-223-4289 Ext. 25270

    [email protected]

    Contact Jeff Cyr 603-223-4289 Ext. 25241

    [email protected];

    mailto:[email protected]