Page1of10
P.O.Box000000 Anchorage,AK99523Phone:1-907-694-8326Fax:1-907-375-2980
November14,2016
123 Sample Drive Anchorage, AK 99504 Inspection #: 00000
Dear Bill Smith,
On 11/14/2016 HomeTeam Inspection Service made a visual inspection of the property referenced above. The inspection was performed in full compliance with the Standards of Practice adopted by the State of Alaska Department of Commerce and Economic Development.
Enclosed please find a written, narrative summary of our findings and report. Please read the entire report carefully as it contains important information about the condition of this property. Although maintenance items may have been addressed verbally at the time of the inspection, they may not be included in the enclosed report.
I trust the enclosed information is helpful. If we can be of further assistance, please feel free to call us at the above telephone number.
Sincerely,
HomeTeam Inspection ServiceMike HannemanAlaska State Registered Inspectors #54, 130 and 201
Each office is independently owned and operated. | ©2013 The HomeTeam Inspection Service, Inc. All rights reserved.
homE inspEction rEport
Home. Safe. Home.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page2of10
RecommendationPage
123 Sample Drive, Anchorage, AK 99504
Inspection Date: November 14, 2016
Anyrepairsaccomplishedshouldbedoneinamannerconsistentwithanymanufacturersinstallationinstructions,anycurrentcode,andcurrent tradepractices.Thedescriptionsof itemsrecommendedfor repairon thissummarypageareaguidetoidentifytheitemforrepairandshouldnotbeconsideredinstructionsonhowtoperformarepair.
NOTE:HealthandLifeSafetyItemsmayincludeitemsthatbymunicipalamendmentorothersources,areconsidered"notgrandfathered"regardlessoftheageofthebuilding.
HEALTHANDLIFESAFETY1. Theexteriordryerventhaslintaccumulationwhichdoesnotallowthebackdraftpreventertocloseandisconsideredafirehazard.Professionallycleantheductingfromthedryertotheexterior.
2. RecommendaprofessionalservicingandinspectionoftheheatingsystemandwaterheaterbyaqualifiedHVACtechniciantoincludecleaningifnotcompletedwithinthepast12months.Manufacturersrecommendannualservicingandrepairtoensureproperoperationoftheheatingsystem.Technicalinspectionandexhaustivesystemoperationcheckisnotwithinthescopeofthisinspection.RepairasfurtherrecommendedbyHVACtechnician.Receiptrequireduponreinspection.
SIGNIFICANTREPAIRITEMS1. Thesinkfaucetinthekitchenleaksatthestem.Repairorreplacethefaucetasneededtoensurealeakfreeoperation.
2. Theflametothefireplacepulsateswhileonandduringtheinitialstartuptheflamewentout.Furtherreviewandrepairstobecompletedbyaqualifiedfireplacecontractor.
3. Thegarageunitheaterdidnotrespondtothethermostatatthetimeoftheinspection.RepairstobecompletedbyaqualifiedHVACtechnician.
4. Themasterbedroomwindowisnotsealedtothesiding.Caulkthewindowtothesidingtopreventpossiblemoistureintrusion.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page3of10
GENERALINFORMATION
Throughoutthisreport,theterms"right"and"left"areusedtodescribethebuildingasviewedfromthestreet.Thepurposeofthehomeinspectionistoidentifymajor,visually-observabledefectsthatarepresentatthetimeoftheinspectionandthat,intheHomeTeam'sopinion,mightaffectthetypicalhomebuyer'spurchasedecisionortheuseofthepropertyforitsintendedpurpose.TheHomeTeaminspectsforevidenceofstructuralfailure,significantrepairitems,andsafetyconcernsonly.Allconditionsarereportedastheyexistedatthetimeoftheinspection.
Thisinspectionislimitedtothereadilyaccessible,visiblecomponentsofthestructureanddoesnotaddresstheinsurabilityoftheproperty.Identifyingitemsincludedinmanufacturerrecallsarenotwithinthescopeoftheinspection.Thisisnotacodeinspection.Zoning,easements,set-backs,restrictions,orhomeownersassociationrules,by-laws,orcodesarenotwithinthescopeofthisinspection.
Routinemaintenanceitemsarenotwithinthescopeofthisinspectionunlesstheyotherwiseconstitutemajor,visuallyobservabledefects.Althoughsomemaintenanceitemsmaybedisclosed,thisreportdoesnotincludeallmaintenanceitems,andshouldnotberelieduponforsuchitems.
RECOMMENDATIONPAGE
Therecommendationpageconsolidatesthestructuralfailure,significantrepair,andsafetyitemsobservedduringtheinspection.Repairand/orcorrectionoftheseitemsishighlyencouragedtoprolongtheintegrityofthebuildinganditssystems,alongwithprotectingthesafetyofitsoccupants.
REPORTTEXT
Thebody,orspecificcomponentsections,inthisreportcontaininformationpertainingtotheconstruction,components,andlayoutofthehome.Generalmaintenanceitems,observationsspecifictothisproperty,andsomeminordefectsmaybedescribedinthebodyofthereportforinformationalpurposes,butdoesnotconstituteacompletelistofanyoralloftheseitems.
PROPERTYGENERALDESCRIPTION
Theinspectedstructureconsistedofatwo-levelwood-framedzero-lotlinewithT-1-11sidingthatwasoccupiedatthetimeoftheinspection.
Theageofthestructure,asreportedbythepropertydescriptionwassaidtobe8years.Theapproximatetemperatureatthetimeoftheinspectionwas30degreesFahrenheit,andtheweatherwaspartlycloudy.Theutilitieswereonatthetimeoftheinspection.
Thestructurewassituatedonalevel/lightlyslopedlot.Thesitewaspartiallysnowcovered;theexteriorfeaturessuchasgrounds,walkways,porches,decks,anddrivewaywereinspectedformajorvisualdefects.Thegeneralgradeappearedtobeadequatetodirectrainwaterawayfromthefoundation.Theexteriorgradingdidnotcontactthesiding.Directcontactofthesoiltowoodsidingcancausewoodrotoverlongexposureperiods.
Theexteriordryerventhaslintaccumulationwhichdoesnotallowthebackdraftpreventertocloseandisconsideredafirehazard.Professionallycleantheductingfromthedryertotheexterior.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page4of10
WALKWAYSANDPORCHES
Therewasanasphaltwalkwayleadingtotheentrywayofthehome.
DRIVEWAY
Therewasanasphaltdrivewaywhichledtothegarage.Thedrivewaysurfacewasvisuallyinspected.
GARAGE
Theattachedgaragewasdesignedfortwocarswithaccessprovidedbyoneoverhead-styledoor.Theconcretegaragefloorwasinserviceablecondition.
GARAGEDOOROPENER
Thefunctionalityofremotetransmitters,keylessentryorotheropeningdevicesisnottestedduringthehomeinspection.Theelectricgaragedooropenerwastestedandfoundtobefunctional.Theautomaticsafetyreverseonthegaragedoorwastestedandfoundtobefunctional.
GARAGEFIRESEPARATION
Thegaragefireseparationwallsandceilingwereinspectedanddidappeartobeadequate.
BALCONY
Abalconywaslocatedatthefrontofthestructure.Theredidnotappeartobedeteriorationofthewood.Thesupportwasvisibleatthetimeoftheinspection.Awoodbalconyshouldbecleanedandsealedregularlytopreventdeterioration.
ROOFSTRUCTURE
Theroofwasaventilated,gabledesigncoveredwithcompositionshingles.Theroofwascoveredwithsnoworfrostwhichdidnotallowcompleteinspection.Observationofthevisibleroofsurfacesandflashingwasperformedfromthegroundlevelduetofrost.Theageoftheroofcoveringwasapproximately8years,asdisclosed.
Thisvisualroofinspectionisnotintendedasawarrantyoranestimateontheremaininglifeoftheroof.Anyroofmetal,especiallytheflashingandvalleys,mustbekeptwellpaintedwithapaintspeciallyformulatedforthatuse.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page5of10
RAINGUTTERS
Theroofdrainagesystemconsistedofmetalguttersanddownspoutswhichappearedtobeinserviceableconditionatthetimeoftheinspection.Guttersanddownspoutsshouldreceiveroutinemaintenancetopreventprematurefailure.
FOUNDATION
Thefoundationwasconcreteblock.Therewasnoabnormalcracking,movement,orsettlingofthefoundationnoted.Asingleinspectioncannotdeterminewhetheranymovementinafoundationhasceased.Anycracksinthefoundationorfooting,nomatterhowsmall,shouldbemonitoredregularly.Soilconditionsaroundandunderthefoundationarenotwithinthescopeofanormalhomeinspection.
CRAWLSPACE
Thecrawlspacewasaccessibleatthetimeoftheinspection,andwasdry.Thecrawlspacehadapolyvinylvaporbarriercompletelycoveringthesurfaceofthesoils.Thecrawlspacedidhaveadequateventilationtoaidincontrollingthemoisturelevelswithinthearea.
FLOORSTRUCTURE
ThevisiblefloorstructureconsistedofOSBplywoodsub-floor,supportedbytwo-inchbyten-inchplybeamsspaced16-inchesoncenter.Therewasaponywallsystemforloadbearingsupport.Therimjoistandsillplatewasinspectedinfourrepresentativelocations.
PLUMBING
Thevisiblewatersupplylineswerepolyethylenepipe.Thewaterwassuppliedbyapublicsource.ThevisiblewastelinesconsistedofABSpipe.Thestructurewasconnectedtoapublicsewersystem.Allplumbingfixturesnotpermanentlyattachedtoahouseholdappliancewereoperatedandinspectedforvisibleleaks.Waterflowthroughoutthestructurewasaverage.
BATHROOMS
Thestructurecontainedtwobathrooms.Aradiofrequencymoisturemeterisusedonallshowerenclosuresandthefloorareasaroundtoilets.Thesemetersmaydetectpossiblelatentdefects,duetowaterintrusion,notvisibleduringanormalinspection.Anymoistureindicationnotedintherecommendationpageshouldbefollowedbyfurtherinvestigationandrepairofanymoisturedamagedmaterialencountered.Werecommendthathomeswithtiledshowerenclosureshavethegroutcleanedandsealedannually.
GASMETER
Thegasmeterwaslocatedontheexteriorwall.Althoughnoactualtestingwasperformedtodetectthepresenceofgasfumes,therewasnonoticeableodorofgasdetectedatthetimeoftheinspection.
ELECTRICSERVICE
Theundergroundelectricservicewireenteredthestructureontheexteriorwall.Theelectricmeterwaslocatedontheexteriorwall.
TheservicewireenteredaSiemensservicepanel,locatedontheinteriorwallwitha100ampand120/240voltratedcapacity.Thebranchcircuitswithinthepanelwerecopper.
ThevisiblehousewiringconsistedprimarilyoftheRomextypeandappearedtobeingoodcondition.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page6of10
Arepresentativenumberofinstalledlightingfixtures,switches,andreceptacleslocatedthroughoutthestructurewereinspectedandwerefoundtobefunctioning.Thegroundingandpolarityofarepresentativenumberofreceptacles,andthoseattachedtogroundfaultcircuitinterrupters(GFCI),ifpresent,werealsotested.Thisbuildinghasagroundedelectricalsystem.Olderhomesmaybegroundedtothewaterpipingsystemand/ortoanexteriorgroundingrod.Anexteriorgroundingrodwasnotvisible.AllGFCIreceptaclesandGFCIcircuitbreakersshouldbetestedmonthly.TherewereGFCIprotectedcircuitslocatedinthehome.
ThefreezerinthegarageisonaGFCIprotectedcircuit.AllgarageoutletsarerequiredtobeGFCIprotected,however,themanufacturerrecommendsthatappliancesnotbepluggedintoaGFCIprotectedcircuittopreventtripping.
Alarms,electronickeypads,remotecontroldevices,landscapelighting,telephoneandtelevision,andallelectriccompanyequipmentarebeyondthescopeofthisinspection.
SMOKEALARMS
Therewereadequatesmokealarmsfoundinthestructure.Forsafetyreasons,thesmokealarmsshouldbetesteduponoccupancy.Thebatteries(ifany)shouldbereplacedwithnewoneswhenyoumoveintothehouse,andtestedonamonthlybasisthereafter.
CARBONMONOXIDEDETECTORS
Therewereadequatecarbonmonoxidedetector/swithinthelivingspace.Installationofthisdeviceishighlyencouragedandmonthlytestingoftheunitusingitsbuilt-intesterisrecommended.AnchoragemunicipalordinanceAO2004-64requiresinstallationofaplug-in,withbatteryback-up,carbonmonoxidedetector,andAlaskaStateLawrequiresinstallationofaplug-inorbatteryback-uponeachlevelofthehomeandoutsideanysleepingareasinresidentialbuildings.Thesemaybecombinedwithsmokealarmscurrentlyinstalled.
WINDOWS,DOORS,WALLSANDCEILINGS
Arepresentativenumberofaccessiblewindowsanddoorswereoperatedandfoundtobefunctional.Possibleproblemareasmaynotbeidentifiedifthewindowsordoorshavebeenrecentlypainted.
Theprimarywindowswereconstructedofvinyl,slidingstyle,withdoublepaneglass.Foggingand/orcondensationbetweenwindowpaneshasmanycausesandcanoccurunderchangingclimacticconditions.Thelossofinsulatingvalueofthewindowduetoathermalsealfailureisminimal,andthereforeconsideredacosmeticdefect.
Somehomesmayproducecondensationontheinsidepanesofthewindowglassandcausedeteriorationofthefinishesandwoodframing.Highhumiditylevelswithinahomecanaccentuatethiseffect.Excessivecondensationmayalsorunontothewallstructurebelowthewindowscausingpainttopeel.Periodicmaintenancemayberequiredtomaintainthesewindowsandframes.
Themasterbedroomwindowisnotsealedtothesiding.Caulkthewindowtothesidingtopreventpossiblemoistureintrusion.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page7of10
Theinteriorwallandceilingsurfaceswerefinishedwithdrywall.Possibleproblemareasmaynotbeidentifiediftheinteriorwallandceilingsurfaceshavebeenrecentlypainted.TheHomeTeaminspectsforevidenceofstructuralfailureandsafetyconcernsonly.Thecosmeticconditionofthepaint,wallcovering,carpeting,windowcoverings,etc.,arenotaddressed.
HANDRAILSANDBALUSTERS
Theinteriorandexteriorhandrailbalusterseparationinsomehomesmayexceedthecurrentcodestandardofnotmorethanfour-inchseparationduetohavingbeenacceptableatthetimeoftheoriginalconstruction.Handrailheight,constructionandmaterialsmayalsovary.Thisconditionmaybeofconcerntofamilieswithsmallchildrenandconsiderationshouldbegiventorepairingorreplacinghandrailstothecurrentcodestandard.
EXTERIORDOORS
Allexteriordoorswereoperated.Theexteriordoorlocksshouldbechangedorre-keyeduponoccupancy.
KITCHEN
Thevisibleportionsofthecabinetsandcountertopswereingoodcondition.Theapplianceswereturnedontocheckoperationalfunctiononly.Nowarranty,expressorimplied,isgivenforthecontinuedoperationalintegrityoftheappliancesortheircomponents.
Thesinkfaucetinthekitchenleaksatthestem.Repairorreplacethefaucetasneededtoensurealeakfreeoperation.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page8of10
Theelectricrangewasinspectedanddidappeartobefunctional.Theaccuracyoftheclock,timersandsettingsonovensarenotwithinthescopeofthisinspection.
Therangehood/microwavewasinspectedandappearedtobefunctional.Therangehood/microwaveappearedtobeventedtotheexteriorofthebuilding.Theexhaustcapacityisnotwithinthescopeofthisinspection.Periodicallycleaningthefanandfiltermayincreasetheexhaustcapability.
Therefrigeratorwasinspectedanddidappeartobefunctional.Thetemperaturesettingandicemaker,ifpresent,arenotwithinthescopeoftheinspection.
Thedishwasherwasobservedthroughacompletecycleanddidappeartobefunctionalwhensetonthe"wash"and"drain"cycle.
Thedisposalwasinspectedandwasfunctional.Theefficiencyratingisnotwithinthescopeoftheinspection.
DRYERCONNECTIONSANDVENT
Thisnoteissuppliedforinformationalpurposesonly,asmanyclientswanttoknowthetypeofdryerconnectionsavailabletothem.A240voltoutletforanelectricdryerwasinstalledinthelaundryarea.Adryerventwasinstalledandthevisibleportionofthedryerventwasinspected.
FIREPLACE
Aventedgasfireplacewaslocatedinthelivingroom.Theunitwasvisuallyinspectedanddidnotappeartobefunctional.Manyoftheseunitsarecontrolledbyawallmountedswitch.Someoperatebyremotecontrol,whileothersarecontrolledfromthebaseoftheunit.Theseunitsusuallycomewithaninstructionplatethatisattachedtotheunitinsidethecontrolaccesspanel.Besuretoreadandunderstandtheoperatingprocedurespriortooperatingtheunit.
Theflametothefireplacepulsateswhileonandduringtheinitialstartuptheflamewentout.Furtherreviewandrepairstobecompletedbyaqualifiedfireplacecontractor.
ATTICSTRUCTURE
Atticaccesswaslocatedintheceiling.Theatticwasinsulatedwithloose-fillinsulation,approximately10-inchesindepth.Ventilationthroughouttheatticwasprovidedbyridgeandsoffitvents.Theroofstructureconsistedoftwo-inchbysix-inchwoodtrussesspaced24-inchesoncenterandOSBplywoodsheathing.
Becauseoftheconfigurationoftheframing,whichlimitedaccess,itwasnotpossibletoinspectallareasoftheattic.Therewasnomoisturevisibleintheatticspace.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page9of10
WATERHEATER
Therewasa48-galloncapacity,naturalgaswaterheaterlocatedinthegarage.Informationonthewaterheaterindicatedthatitwasmanufacturedapproximately8yearsago.Thetemperatureandpressure(T&P)valvewaspresentanddidhaveadripleginstalled.Thewaterheaterdidhaveapprovedseismicstrapsinstalled.Thewaterheaterwasfunctional.
HVACINSPECTIONREPORT
Annualmaintenanceoftheheatingequipmentisessentialforsafeandefficientperformance,whichwillmaximizethesystem'susefullife.Periodicpreventivemaintenanceisrecommendedtokeeptheheatingsystemingoodworkingcondition.Duetotheseriousnatureofcombustionairrequirementsandcarbonmonoxidehazardsassociatedwithgasfiredequipment,werecommendthesetestsbeperformedbycertifiedheatingandventilationspecialists.Theresultsofourvisualandoperationalinspectionoftheheatingsystemaredescribedbelow.
Thestructurewasheatedbyanaturalgasforcedairfurnacelocatedinthegarage.
Theheatingsystemwasfoundtobefunctional.
RecommendaprofessionalservicingandinspectionoftheheatingsystemandwaterheaterbyaqualifiedHVACtechniciantoincludecleaningifnotcompletedwithinthepast12months.Manufacturersrecommendannualservicingandrepairtoensureproperoperationoftheheatingsystem.Technicalinspectionandexhaustivesystemoperationcheckisnotwithinthescopeofthisinspection.RepairasfurtherrecommendedbyHVACtechnician.Receiptrequireduponreinspection.
FILTERTYPE
Thedisposablefiltershouldbereplacedonaregularbasistomaintaintheefficiencyofthesystem.Theefficiencyratingisnotwithinthescopeofthisinspection.
HEATINGSYSTEMCONTROLS
Thecontrolfortheheatingsystemwasa24voltthermostatlocatedontheinteriorwallofthehome.Thethermostatwasfunctionalatthetimeoftheinspection.
GARAGEUNITHEATER
Thegaragewasseparatelyheated.Thethermostaticallycontrollednaturalgasunitheaterwasnotfunctionalatthetimeoftheinspection.Theheatingcapacityofagarageunitheaterisnotwithinthescopeofanormalhomeinspection.
Thegarageunitheaterdidnotrespondtothethermostatatthetimeoftheinspection.RepairstobecompletedbyaqualifiedHVACtechnician.
MOLD
Thepossiblehealtheffectsfromexposuretoelevatedlevelsofmoldwithinahomehasbeenagrowingconcernoverthepastfewyears.Healtheffectsingeneralarenotwellstudied,anddosage,exposure,andsensitivitythresholdsarenotwellknownandcanpotentiallyvarytremendouslydependingonvariousconditionsandontheparticularindividuals.
Thepresenceofmoldwithinahome,visibleorhidden,maybeofconcernandwerecommendconsultingqualifiedprofessionalsforanydetection,identification,and/orremediationneeds.Therewasnovisiblemoldobservedinthestructureatthetimeofthisinspection.
FileNumber:00000
AddressofInspection:123 Sample Drive
Page10of10
REASONABLEEXPECTATIONSREGARDINGAPROFESSIONALHOMEINSPECTION:
Theremaycomeatimewhenyoudiscoversomethingwrongwiththehouse,andyoumaybeupsetordisappointedwithyourhomeinspection.Therearesomethingswe'dlikeyoutokeepinmind.
Intermittentorconcealedproblems:Someproblemscanonlybediscoveredbylivinginahouse.Theycannotbediscoveredduringthefewhoursofahomeinspection.Forexample,someshowerstallsleakwhenpeopleareintheshower,butdonotleakwhenyousimplyturnonthetap.Someroofsandbasementsonlyleakwhenspecificconditionsexist.Someproblemswillonlybediscoveredwhencarpetsarelifted,furnitureismovedorfinishesareremoved.
Noclues:Theseproblemsmayhaveexistedatthetimeoftheinspection,buttherewerenocluesastotheirexistence.Ourinspectionsarebasedonthepastperformanceofthehouse.Iftherearenocluesofapastproblem,itisunfairtoassumeweshouldforeseeafutureproblem.
Wealwaysmisssomeminorthings:Somesayweareinconsistentbecauseourreportsidentifysomeminorproblemsbutnotothers.Theminorproblemsthatareidentifiedwerediscoveredwhilelookingformoresignificantproblems.Wenotethemsimplyasacourtesy.Theintentoftheinspectionisnottofindthe$200problems;itistofindthe$1000problems.Thesearethethingsthataffectpeople'sdecisionstopurchase.
Contractor'sadvice:Acommonsourceofdissatisfactionwithhomeinspectorscomesfromcommentsmadebycontractors.Contractors'opinionsoftendifferfromours.Don'tbesurprisedwhenthreeroofersallsaytheroofneedsreplacement,whenwesaidthattheroofwouldlastafewmoreyearswithsomeminorrepairs.
"Lastmanin"theory:Whileouradvicerepresentsthemostprudentthingtodo,manycontractorsarereluctanttoundertaketheserepairs.Thisisbecauseofthe"lastmanin"theory.Thecontractorfearsthatifheisthelastpersontoworkontheroof,hewillgetblamediftheroofleaks,regardlessofwhetherornottheroofleakishisfault.Consequently,hewon'twanttodoaminorrepairwithhighliability,whenhecouldre-rooftheentirehouseformoremoneyandreducethelikelihoodofacallback.Thisisunderstandable.
Mostrecentadviceisbest:Thereismoretothe"lastmanin"theory.Itsuggeststhatitishumannatureforhomeownerstobelievethelastbitofexpertadvicetheyreceive,evenifitiscontrarytopreviousadvice.Ashomeinspectors,weunfortunatelyfindourselvesinthepositionof"firstmanin"andconsequentlyitisouradvicethatisoftendisbelieved.
Whydidn'tweseeit?:Contractorsmaysay,"Ican'tbelieveyouhadthishouseinspected,andtheydidn'tfindthisproblem."Thereareseveralreasonsfortheseapparentoversights:
Conditionsduringinspection:Itisdifficultforhomeownerstorememberthecircumstancesinthehouseatthetimeoftheinspection.Homeownersseldomrememberthatitwassnowing,therewasstorageeverywhereorthatthefurnacecouldnotbeturnedonbecausetheairconditioningwasoperating,etc.It'simpossibleforcontractorstoknowwhatthecircumstanceswerewhentheinspectionwasperformed.Thiswisdomofhindsight:Whentheproblemmanifestsitself,itisveryeasytohave20/20hindsight.Anybodycansaythatthebasementiswetwhenthereis2"ofwateronthefloor.Predictingtheproblemisadifferentstory.Alonglook;Ifwespenthalfanhourunderthekitchensinkor45minutesdisassemblingthefurnace,we'dfindmoreproblems,too.Unfortunately,theinspectionwouldtakeseveraldaysandwouldcostconsiderablymore.We'regeneralists:Wearegeneralists;wearenotspecialists.Theheatingcontractormayindeedhavemoreheatingexpertisethanwedo.Thisisbecauseweareexpectedtohaveheatingexpertiseandplumbingexpertise,structuralexpertise,electricalexpertise,etc.Aninvasivelook:Problemsoftenbecomeapparentwhencarpetsorplasterareremoved,whenfixturesorcabinetsarepulledout,andsoon.Ahomeinspectionisavisualexamination.Wedon'tperforminvasiveordestructivetests.
Notinsurance:Inconclusion,ahomeinspectionisdesignedtobetteryourodds.Itisnotdesignedtoeliminateallrisk.Forthatreason,ahomeinspectionshouldnotbeconsideredaninsurancepolicy.Thepremiumthataninsurancecompanywouldhavetochargeforapolicywithnodeductible,nolimitandanindefinitepolicyperiodwouldbeconsiderablymorethanthefeewecharge.Itwouldalsonotincludethevalueaddedbytheinspection.ReprintedfromASHIReporter,ByPermissionofAlanCarson,CarsonDunlop&Assoc.