PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator...

6
Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply voltage : 220~240 V AC / 380~415 V AC Operating Limits : -15% + 10% Consumption : 10 VA max Rated frequency : 50 Hz or 60 Hz OUTPUT CONTACTS Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 / PFR80 / PFR120 / PFR140 ) Rated voltage : 250 V AC Contact rating : 5 A Expected electrical life : 100,000 operations at rated current Expected mechanical life : 5 x 10 6 operations Max current for the common terminals : 12 A continuous CURRENT INPUT Rated current ( In ) : 5 A Operating Limits : 0.05 A to 6.5 A Rated Frequency : 50 Hz or 60 Hz CONTROL RANGE Power factor setting : 0.8 Ind - 0.8 Cap C/K setting : 0.03 - 1.20 / Automatic Switching sensitivity : 5 - 600 s/step Reconnection time for same step : 5 - 240 s THD threshold : 0.20 - 3.00 ( 20% - 300% ) / OFF Switching Program : Automatic / Automatic Rotate / 4-quadrant / Manual Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 / 12 / 16 ( Automatic if C/K set to Auto ) PFR140 PFR120 PFR80 PFR60 Features Microprocessor based intelligent auto switching control Automatic C/K and rated step adjustment Automatic CT polarity correction Display of power factor, current & total harmonic distortion of current Programmable sensitivity Last step can be used as alarm/fan output Under/over voltage alarm, under/over compensate alarm & high harmonic distortion alarm User-friendly setting Complies with IEC 61000-6-2 standard ENVIRONMENTAL CONDITIONS Temperature : -5˚C to +55˚C Humidity : 56 days at 93% RH and 40˚C non-condensing MECHANICAL Mounting : Panel mounting Dimension (mm) : 144(w) x 144(h) x 90(d) Enclosure protection : IP54 at the panel Approximate weight : 1.2 kg

Transcript of PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator...

Page 1: PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply

Power Factor Regulator

PFR 140 / 120 / 80 / 60

Technical Data

RATINGS AUXILIARY POWER SUPPLYCurrent Supply voltage : 220~240 V AC /

380~415 V ACOperatingLimits : -15%+10%Consumption : 10 VA maxRated frequency : 50 Hz or 60 Hz

OUTPUT CONTACTSNumbers of outputs : 6 / 8 / 12 / 14 ( PFR60

/ PFR80 / PFR120 / PFR140 )

Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at

rated currentExpected mechanical life : 5 x 106 operationsMax current for the common terminals : 12 A continuous

CURRENT INPUTRated current ( In ) : 5 AOperating Limits : 0.05 A to 6.5 ARated Frequency : 50 Hz or 60 Hz

CONTROL RANGEPowerfactorsetting :0.8Ind-0.8CapC/Ksetting :0.03-1.20/AutomaticSwitchingsensitivity :5-600s/stepReconnection time for samestep :5-240sTHDthreshold :0.20-3.00(20%-300%)/

OFFSwitching Program : Automatic / Automatic

Rotate/4-quadrant/Manual

Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 / 12 / 16

( Automatic if C/K set to Auto )

PFR140PFR120PFR80PFR60

Features• Microprocessorbasedintelligentautoswitching

control

• AutomaticC/Kandratedstepadjustment

• AutomaticCTpolaritycorrection

• Displayofpowerfactor,current&totalharmonicdistortion of current

• Programmablesensitivity

• Last step can be used as alarm/fan output

• Under/overvoltagealarm,under/overcompensatealarm & high harmonic distortion alarm

• User-friendlysetting

• ComplieswithIEC61000-6-2standard

ENVIRONMENTAL CONDITIONSTemperature :-5˚Cto+55˚CHumidity : 56 days at 93% RH and

40˚Cnon-condensing

MECHANICALMounting : Panel mountingDimension (mm) : 144(w) x 144(h) x 90(d)Enclosure protection : IP54 at the panelApproximateweight :1.2kg

Page 2: PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply

MAIN

P1

P2

FUSE

K14 K13 K2 K1

24232221201918171615

14

13

12111098

14131211

7654321

10987654321

AUXVOLTAGE

CURRENT/ 5 A

Pow

er F

acto

r Reg

ulat

or

L1L2L3N

380~415 V AC

1615

14

13 AUXVOLTAGE

For 220~240 V AC Model Only

220~240 V AC

LOAD

Typical Application Diagram

Case Dimensions Ordering Information144 mm

138 mm

138

mm

76 mm90 mm

144

mm

Front

Side

PanelCutout

MODEL

PFR60-415-50

PFR80-415-50

PFR120-415-50

PFR140-415-50

PFR60-220-50

PFR80-220-50

PFR120-220-50

PFR140-220-50

PFR60-415-60

PFR80-415-60

PFR120-415-60

PFR140-415-60

PFR60-220-60

PFR80-220-60

PFR120-220-60

PFR140-220-60

DESCRIPTION

6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

Power Factor Regulator

PFR 140 / 120 / 80 / 60

Page 3: PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply

Technical Data

RATINGS AUXILIARY POWER SUPPLYModel PFR96 : 110 ~ 120 V AC / 220 ~ 240 V ACModel PFR96P : 380 ~ 415 V ACOperatingLimits :-15%+10%Consumption : 10 VA maxRated frequency : 50 Hz or 60 Hz

OUTPUT CONTACTSNumbers of outputs : 6Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at

rated currentExpected mechanical life : 5 x 106 operationsMax current for the common terminals : 12 A continuous

CURRENT INPUTRated current ( In ) : 5 AOperating Limits : 0.15 A to 6.5 ARated frequency : 50 Hz or 60 Hz

CONTROL RANGEPowerfactorsetting :0.8Ind-0.8CapC/Ksetting :0.03-1.20/AutomaticSwitchingsensitivity :5-600s/stepReconnection time for samestep :5-240sSwitching Program : Automatic / Automatic

Rotate/4-quadrant/Manual

Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 / 12 / 16

( Automatic if C/K set to Auto )

PFR96PFR96P

Features• Microprocessor based intelligent auto

switching control

• AutomaticC/Kandratedstepadjustment

• Automatic CT polarity correction

• Display of power factor & current

• Programmablesensitivity

• Laststepcanbeusedasalarm/fanoutput

• Under/overvoltagealarm,under/overcompensate alarm

• User-friendlysetting

• ComplieswithIEC61000-6-2standard

ENVIRONMENTAL CONDITIONSTemperature :-5˚Cto+55˚CHumidity : 56 days at 93% RH and

40˚Cnon-condensing

MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximateweight :0.6kg

For PFR 96• Forsingle-phasesystem

For PFR 96P• For3-phasesystem

Power Factor Regulator

PFR 96 / 96P

Page 4: PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply

K1 K6K5

FUSE

Pow

er F

acto

r Re

gula

tor

VOLTAGE380~415V AC

MAINL1L2L3N

8

7

6

5

4

3

2

1

CURRENT/ 5 A

6

5

4

3

2

1

16

15

14

13

12

11

10

9P2

P1

FUSE

LOAD

K1 K6K5

FUSE

FUSE

Pow

er F

acto

r Re

gula

torVOLTAGE

220 V AC /110 V AC

MAINL1L2L3N

8

7

6

5

4

3

2

1

CURRENT/ 5 A

6

5

4

3

2

1

16

15

14

13

12

11

10

9P2

P1

LOAD

Typical Application Diagram

Ordering Information

Diagram 2 - For model PFR96PDiagram 1 - For model PFR96

Case Dimensions96 mm

91.0 ± 0.5 mm

91.0

± 0

.5 m

m

70 mm90 mm

96m

m Front

Side

PanelCutout

MODEL

PFR96 - 220 - 50

PFR96 - 220 - 60

PFR96 - 110 - 50

PFR96 - 110 - 60

PFR96P - 415 - 50

PFR96P - 415 - 60

DESCRIPTION

6 Steps, for 50 Hz system, auxiliary voltage 220~240 V AC

6 Steps, for 60 Hz system, auxiliary voltage 220~240 V AC

6 Steps, for 50 Hz system, auxiliary voltage 110~120 V AC

6 Steps, for 60 Hz system, auxiliary voltage 110~120 V AC

6 Steps, for 50 Hz system, auxiliary voltage 380~415 V AC

6 Steps, for 60 Hz system, auxiliary voltage 380~415 V ACPow

er Factor RegulatorPFR 96 / 96P

Page 5: PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply

Typical Application Diagram

Power Factor Regulator

PFR LCD

PFRLCDFeatures• 2” inch, 64 x 128 dot matrix LCD display

withbacklighting

• Three phase and single phase detection of reactive power

• 12 (or 8 for 8 step model) output with two additional

• Independent contact for signal alarm output and fan output

• Three phase compensation mode

• 5 different switching program

• Automatic detection of C/K and rated step value

• No Voltage release

• Variousconfigurablealarmsettings

• Alarmlinkedsignalcontact

• Programmable fan control

• ModBus-RTUcommunication

• Active, reactive, apparent power

• Temperature

• Phase voltage and phase current

• Frequency

• Up till 31st order Harmonics measurement in graphical and table format

• Power Factor and Displacement Power Factor (Cosφ)

Measurement Parameters

L1 L2 NL3

3435

3344

3243

4241

3938

3736

40

2120

2214

2313

1211

98

76

104

32

15

SIGFAN

12

45

67

39

1011

128

2430 Thermistor

T1

P+

N-RP

T2

31

GND

PFR

LC

D

FANSIG

AUX

NL

S2S2

S1S1

S2S1

L3L2

L1N

CT2

CT1

CT3

RS485 Modbus-RTU

FUSE

FUSE

P1P2

P1P2 P1

P2

K12 K2 K1

PFRLCD120P3-230-50

LOAD

L1 L2 NL3

3435

3344

3243

4241

3938

3736

40

2120

2214

2313

1211

98

76

104

32

15

SIGFAN

12

45

67

39

1011

128

2430 Thermistor

T1

P+

N-RP

T2

31

GND

PFR

LC

D

FANSIG

AUX

NL

Out

InL3

L2L1

NC

T1

RS485 Modbus-RTU

FUSE

FUSE

P1P2

K12 K2 K1

PFRLCD120P1-230-50

LOAD

PFRLCD Connection diagram for 3 Phase 12 Step model PFRLCD Connection diagram for 1 Phase 12 Step model

Page 6: PFR140 PFR120 PFR80 PFR60 - thegioidien.com - Power Factor Regulator.pdf · Power Factor Regulator PFR 140 / 120 / 80 / 60 Technical Data RATINGS AUXILIARY POWER SUPPLY Current Supply

Ordering Information

Case Dimensions

Front View

Panel Cutout

144mm

Side View

122mm102mm

144m

m

138mm

138mm

Power Factor Regulator

Technical DataCURRENT INPUT (EACH PHASE)Nominal Current : 5 A rmsOperatingLimits :0.01-10ArmsRated frequency : 50 Hz or 60 Hz

VOLTAGE INPUT (EACH PHASE with respect to neutral)Nominal Voltage : 230 VrmsOperatingLimits :0-277VL-NConsumption : 0.05 VARated Frequency : 50 Hz or 60 HzCatagory : III

THERMISTOR INPUT Thermistor Temperature range : 0 – 100 °C

AUXILIARYAuxiliaryInputVoltageRange :85-265VrmsConsumption : 10 VA maxRated Frequency : 50 Hz or 60 Hz

OUTPUT CONTACTSNumber of outputs : 14 (model dependent)Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at

rated currentExpected mechanical life : 5 x 106 operations

CONTROL RANGETarget Power factor : 0.80 Inductive – 0.80

Capacitive C/K setting : 0.03 – 1.20 / Automatic

detectSensitivity :5-300s/StepReconnection time : 5 – 240s Switching program : Automatic/ Manual/

Four-quadrant/Rotational/ Linear

Rated step coefficient : 0/ 1/ 2/ 3/ 4/ 5/ 6/ 8/ 12/ 16/ Fixed

Detection mode : L1 / L2 / L3 / Max Load / Three Phase

Fan Setting : Fixed on / Output On / Temperature / None

SignalContact :Linkedto10differentprogrammable alarm / None

ALARM SETTING RANGE%THDI :20-300%/OFFOver Voltage : 253 – 264 V/ OFFUnder Voltage : 195 – 204 V/ OFFOver Current : 5.50 – 7.00 A/ OFFUnder Current : 0.01 – 0.15 A/ OFFUnder Compensate : On / OFFOver Compensate : On / OFF*CT Polarity Error : On / OFFStep Error : On / OFFTemperature : 36 – 70 °C / OFF

DISPLAY %THDI & %THDV : 0 – 500%Harmonics Resolution : Up till 31st Harmonics Active power : 0– 3000 WReactive power : 0 – 3000 VARApparent power : 0 – 3000 VAVoltage : 0 – 300 VACCurrent : 0.00 – 10.0 A rmsTemperature : 0 – 100 °CFrequency : 45 – 65HzPowerFactor :-1.00–1.00DisplacementPowerFactor:-1.00–1.00

ENVIRONMENT CONDITIONSTemperature :-5°Cto+55°CHumidity : 56 days at 93%RH and

40°Cnon-condensingPollution Degree : IIDielectricWithstand :IEC61010-1Altitude : 2000 m

ELECTROMAGNETIC COMPATIBILITY (EMC)Part6-2:Genericstandards :IEC61000-6-2Immunity for industrial environmentsPart6-4:Genericstandards :IEC61000-6-4Emission standard for industrial environments

MECHANICAL Mounting : Panel mountingDimension (mm) : 144(w) x 144(h) x 122(d)Enclosure protection : IP54 at the panel IP20 at the bodyApproximateweight :1.2kg (for three phase model), 1kg (for single phase model)

MODEL

PFRLCD120P3-230-50

PFRLCD80P3-230-50

PFRLCD120P1-230-50

PFRLCD80P1-230-50

PFRLCD120P3-230-60

PFRLCD80P3-230-60

PFRLCD120P1-230-60

PFRLCD80P1-230-60

DESCRIPTION

12 Step, 3 Phase, 230Vrms, 50Hz Model

8 Step, 3 Phase, 230Vrms, 50Hz Model

12 Step, 1 Phase, 230Vrms, 50Hz Model

8 Step, 1 Phase, 230Vrms, 50Hz Model

12 Step, 3 Phase, 230Vrms, 60Hz Model

8 Step, 3 Phase, 230Vrms, 60Hz Model

12 Step, 1 Phase, 230Vrms, 60Hz Model

8 Step, 1 Phase, 230Vrms, 60Hz Model

PFR LCD