Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

36
StacoVAR: Power Factor Correction

Transcript of Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

Page 1: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

StacoVAR: Power Factor Correction

Page 2: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

POWER FACTOR CORRECTION (PFC)

Power Factor (PF):

Term used in regard to the efficiency of

an electrical power distribution system.

Power factor is a measurement

between the current and voltage phase

shift waveforms.

Page 3: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

PF COMPONENTS

Power factor consist of 3 components:

• KW, which is the working, or real, power

(does the actual work)

• KVA, which is called the apparent power

(relationship between KW and KVAR)

• KVAR, or reactive power

(does not do any beneficial work)

Page 4: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

DETERMINE YOUR PF

Divide the working power (KW) by the

apparent power (KVA)

PF of 1, or unity, being the highest (or best)

power factor possible.

When correcting PF, in general, a measurement of .9 or higher is considered good.

Page 5: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

INDUSTRIES KNOWN TO HAVE POOR PF

Industries where power factor problems

are common:

o Steel/Foundries

o Chemicals

o Textiles

o Pulp and paper processing

o Automotive and other automated assembly

o Rubber and plastics processing

o Breweries

o Electroplating

Page 6: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

CAUSES OF PF PROBLEMS

Loads that cause power factor problems:

o Induction motors

o Electric arc furnaces

o Machining

o Stamping

o Welding

o Variable Frequency Drives (VFDs)

o Fluorescent lights with magnetic ballasts

o Computers

o Computer controlled equipment

Page 7: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

BENEFITS OF IMPROVING PF

Improving PF:

o Lowers your electrical cost

o Increases KVA capacity (increase the KW used for the same KVA)

o Improves voltage regulation

o Allows for the size reductions in cables, transformers and switchgear

o Allows for expansion without additional electrical improvements

Page 8: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

UTILITY COMPANY’S POINT OF VIEW

Raising the average operating PF of the entire grid network from .70 to .90 means:

oReduced costs from inefficiencies

o Increased generation and distribution potential

oLower demand on the grid

Page 9: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

BETTER PF MEANS

Utilities can save hundreds of thousands of tons of fuel (and produce fewer emissions), have more transformers available, and reduce building new power plants and their support systems.

This is why more utility companies are starting to charge a “Power Factor Penalty” so they can recover additional cost they incur from supporting an inefficient system.

Page 10: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

PF IMPROVEMENT EXAMPLE

Assume you have a load of 100kVA with a PF

of .80, then you have enough power to light 800

100-wattlight bulbs. If you improve the PF to .95,

you now have enough power to light 950 100-watt

light bulbs.

Page 11: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

PF IMPROVEMENTS CAN SAVE $

Because power factor correction capacitors:

o Use less energy

o Lengthen the life of equipment

o Reduce electrical requirements for any new or future equipment that is installed

Page 12: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

UTILITY KVA BILLING

Most utilities use the kVA billing method therefore:

o You are charged for the current your system draws from the grid

o Many utilities add a surcharge or adjustment for PF.

o Special tariffs applied

o Interruptible rates applied

o Off-peak rates

Some utilities give credits or bonuses for higher than average

PF, or one that is above a predetermined level

Page 13: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

EXAMPLE

Most utilities use the kVA billing method therefore:

o You are charged for the current your system draws from the grid

o Many utilities add a surcharge or adjustment for PF.

o Special tariffs applied

o Interruptible rates applied

o Off-peak rates

Some utilities give credits or bonuses for higher than average

PF, or one that is above a predetermined level

Page 14: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

RETURN ON INVESTMENT (ROI)

Using the previous example, if you are billed at $11.22 per kVA:

o100kW @ .70 PF = 142 kVA, or $1,593

o100kW @ .95 PF = 105 kVA, or $1,178

This represents a monthly savings of $415, or

$4,980 annually. Assuming the equipment cost

was $5,600 the ROI would be about 14 months.

After this period there can be an ongoing 26%

savings.

Page 15: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

PF CORRECTION CAPACITORS

A capacitor’s function is to:

oProvide kilovars to a system at the point of connection

o Improve PF

oReduce lagging components on the circuit

oReduce power losses

oReduce kVA load.

oProvide reactive power to replace the VARs wasted by an inefficient load

Page 16: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

PF CORRECTION CAPACITORS

Are the most economical means of improving PF because of their:

oRelative Low Cost

oEasy Installation

oLow Installation Cost

oMinimal Maintenance

oHigh Efficiency and Low Losses

Page 17: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

DETERMINING THE PF

Find poor PF problems by:

oMonitoring at the incoming service entrance or at specific loads can identify problems within a facility

oConduct a Facility Power Study and have reviewed by a power analyst / consultant

Some utilities offer analysis for businesses wanting to improve their efficiency.

Page 18: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

TYPES OF CAPACITOR SYSTEMS

oSimple small fixed capacitors can be installed at a single motor to be switched on and off with the load, this is ideal.

• However, this can be expensive, and can create technical problems, since it may require a large number of low-power units at several points throughout the facility, making it difficult to monitor and maintain over time

Page 19: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

TYPES OF CAPACITOR SYSTEMS

oAutomatic capacitor bank installed on the bus bars of the distribution panel. This method provides centralized PF correction for an entire facility.

• It also allows for fixed capacitors to be added to correct the power of any piece of equipment that causes a significant problem.

Page 20: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

INSTALLATIONS LOCATIONS

Page 21: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

NEXT STEP - DETERMINE THE KVAR

After you have determined what type capacitor

system you need, the next step is to determine

the size or amount of kVAR, you need to correct

the PF.

Staco Energy Products Co. has easy to use

tables that will assist you in determining the

required kVAR you need to add to your system

to improve the PF.

Page 22: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

NEXT STEP

Example: If your existing PF is .71 and you want to bring it

up to .95, the number in the table is .663 (kW multiplier).

Multiply .663 by the number of kW your system uses (say

590). The total kVAR would require 390 kVAR, which would

be rounded up to 400 kVAR. Therefore a 400kVAr rated unit

would be used.

Page 23: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

FINAL STEP

Purchase a Staco

Automatic Switched

400 kVAR StacoVAR

System,

OF COURSE!

Page 24: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

FIXED CAPACITOR ASSEMBLIES

Fixed capacitor assemblies, also called motor load

capacitors, are ideal for improving PF where

induction motors are located. They are also used

anywhere there are small kVAR requirements.

You can achieve maximum benefits from capacitors

when located at the load. Because the capacitor is

Usually switched on and off with the load, over

correction is also avoided

Page 25: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

SIZING FIXED CAPACITORS

Capacitors must be carefully sized when switched

with the motor as a unit, because:

o Dangerous over voltages and transient torques can occur if the kVAR exceeds the motor’s magnetizing current

Page 26: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

WHAT YOU NEED TO KNOW!

When sizing fixed capacitors you need the following

Motor information:

oU-Frame (U, T etc.)

oNEMA Class (B, 2B, C, D etc.)

oA or B Normal Starting Torque – Normal Running Current

Page 27: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

INSTALLATION LOCATIONS

1. Motor Side of Overload Relayo Use this for new motor installations where overloads

can be sized in reference to reduced current draw

o Existing motors where no overload change is needed

2. Motor Side of Startero Use this for existing motors when the overload rating

exceeds code

3. Line Side of Startero Use this for Multi-speed motors

o Motors that are jogged or reversed

o Motors that star frequently

o Starters that disconnect/reconnect capacitors during cycle and starters with open transitions

o High inertia loads, when disconnecting the motor with the capacitor turns the motor into a self-exciting generator

Page 28: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

INSTALLATION LOCATIONS

Page 29: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

MOTOR REFERENCE TABLES

Staco Energy Products Co. has all the reference tables available to make it easier to select and size the correct StacoVAR Motor Load Capacitor for your application.

Page 30: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

STACOVAR SOLUTIONS

Staco Energy provides various solutions,

specific to correction of poor power

factor and/or harmonics. Equipment

available:

oFixed capacitors from 2 to 400kvar.

oAutomatically switched type from 75 to 600kvar (240vac) and 100 to 2400kvar (480 and 600vac).

Page 31: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

STACOVAR FIXED MODELS

Fixed Power Factor Correction: PF Model

o Wall mounted/freestanding motor load “ML” products include liquid filled long life three phase power capacitors and freestanding (larger kvar) products with heavy duty, dry type three phase power capacitors, and both types include discharge resistors and over pressure protection.

o Fixed only, no switching, no control, located at individual motor loads.

Page 32: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

STACOVAR STANDARD FEATURES

Automatic Power Factor Correction Standard Features:

o NEMA 1 enclosure, with bottom entry access and modular design allowing for easy future expansion.

o UL 508A listed, complete assembly.

o Heavy duty, dry type three phase power capacitors, with discharge resistors and over pressure protection.

o PA units accommodate up to 10% THD environment.

o (PH, PT, and PR units use 480 volt rated capacitors for 240 volt system and 690 volt rated capacitors for 480 volt system, for even higher harmonic level protection).

o 5-year warranty on the capacitors.

o Individual step fuse protection (200kaic) with blown fuse indication.

o Control power transformer with fused primary & secondary, and nickel-plated electrical grade cooper bus bar system.

Page 33: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

STACOVAR AUTOMATIC PA MODELS

Automatic Power Factor Correction:

PA ModelAdditional features:

o Type of Switching: Electro-mechanical contactors with damping resistors to reduce switching inrush currents.

o Controller: adjustable (0.5 to 300) second response microprocessor based power factor controller (twelve-step regulation) with front panel LED display.

o Automatically switched (contactors), basic, economical. Product accommodates most requirements.

Page 34: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

STACOVAR AUTOMATIC PH MODELS

Automatic Power Factor Correction:

PH Model

Additional features:

o Type of Switching: Electro-mechanical, heavy duty contactors.

o Controller: adjustable (0.5 to 300) second response microprocessor based power factor controller (twelve-step regulation) with front panel LED display.

o Reactor: Three phase 5TH order, iron-core reactors with a 227hz tuning frequency.

o Automatically switched (contactors), for a harmonic environment where capacitors may be damaged. Use of iron-core reactors necessary for a detuning - majority of requirements for the 5th order. Product accommodates many applications and is cost effective.

Page 35: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

STACOVAR OPTIONS

Automatic Power Factor Correction

Options:

o Circuit Breakers: Circuit breakers are three-pole molded case type, with a thermal-magnetic trip. Amperes are based upon breaker frame size. Circuit Breaker option may increase standard cabinet dimensions, consult factory for sizing.

o TVSS – Surge Protection.

o CT – Current Transformer: multi-tap, (3000:5, 2500:5, 2200:5, 2000:5, 1500:5, 1200:5, 1000:5, 800:5, 500:5, 300:5), split core type for ease of installation. CT’s shipped loose. 1-5% accuracy depending on ratio.

Page 36: Product: Power Factor & Harmonics: StacoVAR: Lets Discuss Power Factor Correction

QUESTIONS?