PDI WaveStar Static Transfer Switch - CM...

10
creating the perfect wave PDI W a v eStar Static T r ansfer Switch LOW INRUSH TRANSFER UTILIZING THE PDI VOLT SECOND SYNCHRONIZATION (VSS) METHOD Introduction One of the limiting factors in applying static transfer switch- es (STS) in mission critical facilities has been the inability of the electrical infrastructures to withstand the transformer inrush when switching occurs on the primary (or 480 volt) side of the transformer. Inrush currents can reach as high as 10-12 times the transformer rating, causing breakers and molded case switches in the STS (or devices upstream) to trip, creating an outage in the facility. PDI’s patented Volt Second Synchronization (VSS) transfer algorithm controls magnetic inrush current in transformer loads and limits it to 1.5 times the rated current. The transfer outage time and the waveform distortions during transfers have an effect on non-linear loads that are connected to the secondary side of the transformer. Short transfer outage times and waveform peak conservation algorithms are nec- essary for any STSs that feed non-linear loads. Typically, non-linear loads, servers, and other computers use Switch Mode Power Supplies (SMPS) which generate non-linear load currents. The SMPS receives AC power from the transformer and generates DC power for the internal logic. SMPS only draw power from the peaks of the input power waveforms; RMS values are associated with linear loads and evaluations based on linear RMS loads will not provide accurate data for evaluation of SMPS applications. To conserve all voltage waveform peaks, the transformer outage time of each phase must be short enough to assure that no peaks are lost. Since SMPS generally use single phase power, each individual phase must maintain power at the waveform peaks. There are four methods of achieving low transformer saturation (inrush) currents when the transformer is connected to the load bus of an STS. These methods are as follows: Phase Delay Method (referred to as phase displacement method) Volt Second Balance Method Volt Second Wave Shaping Method (with RMS conservation) PDI Volt Second Synchronization (VSS) Method (with Peak conservation) Phase Delay Method This method measures the half cycle phase delay from the time of the disconnect from one source to the reconnection of the other source with approximately the same half cycle delay; this will maintain volt second continuity. When transferring from one source to the other when the connecting source lags the disconnect source, there is a direct relationship between the size of the phase shift and the length of the outage. If the source phase shifts are small, the transfer outage is of short duration. If the source phase shifts are large, the transfer outage is of long duration. The transfer outage time of at least one phase can exceed 15 Ms, depending on the source phase shift and detect time. When the connecting source leads the disconnecting source, the transfer outage is large at small phase angles. This method is simple to implement but does not support SMPS very well. Volt Second Balancing Method This method determines the volt seconds applied to the magnetic load by the disconnecting source, and determines the volt seconds that will be supplied by the connecting source. The volt seconds applied to the magnetic load can not exceed the maximum rated volt seconds. This basic algorithm must be optimized to obtain the desired waveform during the transfer outage. The Volt Second Wave Shaping Method (with RMS conser- vation) and PDI Volt Second Synchronization (VSS) Method (with Peak conservation), described below, are two separate and distinct solutions to optimize the limitations of the Volt Second Balancing Method. Page 1 vss 9/06

Transcript of PDI WaveStar Static Transfer Switch - CM...

Page 1: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)

creating the perfect wave

PDI WaveStar™ StaticTransfer Switch

LOW INRUSH TRANSFER UTILIZING THE

PDI VOLT SECOND SYNCHRONIZATION (VSS) METHOD

Introduction

One of the limiting factors in applying static transfer switch-es (STS) in mission critical facilities has been the inabilityof the electrical infrastructures to withstand the transformerinrush when switching occurs on the primary (or 480 volt)side of the transformer. Inrush currents can reach as high as10-12 times the transformer rating, causing breakers andmolded case switches in the STS (or devices upstream) totrip, creating an outage in the facility.

PDI’s patented Volt Second Synchronization (VSS) transferalgorithm controls magnetic inrush current in transformerloads and limits it to 1.5 times the rated current. The transferoutage time and the waveform distortions during transfershave an effect on non-linear loads that are connected to thesecondary side of the transformer. Short transfer outagetimes and waveform peak conservation algorithms are nec-essary for any STSs that feed non-linear loads.

Typically, non-linear loads, servers, and other computersuse Switch Mode Power Supplies (SMPS) which generatenon-linear load currents. The SMPS receives AC power fromthe transformer and generates DC power for the internallogic. SMPS only draw power from the peaks of the inputpower waveforms; RMS values are associated with linearloads and evaluations based on linear RMS loads will notprovide accurate data for evaluation of SMPS applications.

To conserve all voltage waveform peaks, the transformeroutage time of each phase must be short enough to assurethat no peaks are lost. Since SMPS generally use singlephase power, each individual phase must maintain power atthe waveform peaks.

There are four methods of achieving low transformer saturation(inrush) currents when the transformer is connected to theload bus of an STS. These methods are as follows:

• Phase Delay Method (referred to as phase displacement method)

• Volt Second Balance Method• Volt Second Wave Shaping Method

(with RMS conservation)• PDI Volt Second Synchronization (VSS) Method

(with Peak conservation)

Phase Delay Method

This method measures the half cycle phase delay from thetime of the disconnect from one source to the reconnectionof the other source with approximately the same half cycledelay; this will maintain volt second continuity.

When transferring from one source to the other when theconnecting source lags the disconnect source, there is adirect relationship between the size of the phase shift andthe length of the outage.

• If the source phase shifts are small, the transfer outageis of short duration.

• If the source phase shifts are large, the transfer outageis of long duration.

The transfer outage time of at least one phase can exceed 15Ms, depending on the source phase shift and detect time.When the connecting source leads the disconnectingsource, the transfer outage is large at small phase angles.

This method is simple to implement but does not supportSMPS very well.

Volt Second Balancing Method

This method determines the volt seconds applied to themagnetic load by the disconnecting source, and determinesthe volt seconds that will be supplied by the connectingsource. The volt seconds applied to the magnetic load cannot exceed the maximum rated volt seconds.

This basic algorithm must be optimized to obtain thedesired waveform during the transfer outage.

The Volt Second Wave Shaping Method (with RMS conser-vation) and PDI Volt Second Synchronization (VSS) Method(with Peak conservation), described below, are two separateand distinct solutions to optimize the limitations of the VoltSecond Balancing Method.

Page 1vss 9/06

Page 2: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)

Volt Second Wave Shaping Method(with RMS conservation)

This method ensures that the maximum volt seconds ratingof the transformer is not exceeded when the STS transferbetween out-of-phase sources. The voltage waveform isshaped during the transfer transition time to maximize the RMSvoltage when transferring. Since RMS voltage is meaningful forlinear load and not non-linear loads, this is not the bestalgorithm for single phase non-linear loads and does notprovide the best transfer algorithms for SMPS.

PDI Volt Second Synchronization (VSS)Method (with Peak conservation)

This transfer algorithm, VSS with peak conservation,reduces magnetic load current inrush and maintains voltagepeaks for the optimum operation of SMPS. The voltagewaveform is shaped during the transfer transition time tomaximize the peak power of the voltage waveform whentransferring. This is the best algorithm for single phase non-linear loads and also maintains RMS voltage for linear loads.

Conclusion

PDI has evaluated algorithms for all the above methods ofreducing transformer current inrush for initial start-up, restart-up and for transfer, and has standardized on the VSS withpeak conservation algorithm for the WaveStar™ STS systems.

Figures 1 and 2 depict transfers at 15 degrees (both laggingand leading, respectively) without the VSS feature. Figures3 and 4 are examples of the same STS and transformer systemwith the VSS method. Figures 5, 6, 7, and 8 depict the sametransfers performed 45 degrees out of phase.

In each case the transfers were performed under no-loadconditions, no-load conditions always result in higherinrush currents.

The waveforms indicate there is no loss in the applied voltagepeaks; this will allow maximum power to be supplied toload SMPS.

When evaluating low inrush algorithms, the peak currentduring transfer is the most critical measure of performance.The PDI VSS method provides the best option to manage thetransfer with less impact on the SMPS and other electricalequipment.

Page 2vss 9/06

Power Distribution Incorporated4200 Oakleys CourtRichmond, VA 23223800.225.4838804.737.1703 faxweb site: www.pdicorp.com

©PDI VSS 9/06

Page 3: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 4: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 5: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 6: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 7: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 8: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 9: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)
Page 10: PDI WaveStar Static Transfer Switch - CM Buckcmbuck.com/.../Power-Distribution-Low-Inrush-Transfer-Algorithms.pdfOne of the limiting factors in applying static transfer switch-es (STS)