Automatic Transfer Switch (ATS) Generator Transfer...

16
Automatic Transfer Switch (ATS) Generator Transfer Switch (GTS) Installation Manual 020-161-B0 Rev. – 01 / 07 Alpha Technologies ATS GTS

Transcript of Automatic Transfer Switch (ATS) Generator Transfer...

Page 1: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

Automatic Transfer Switch (ATS)Generator Transfer Switch (GTS)

Installation Manual020-161-B0 Rev. – 01 / 07

Alpha Technologies

ATS GTS

Page 2: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

PowerAlpha Technologies ®

Page 3: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

From Alpha Technologies (www.alpha.com)020-161-B0 Rev. – 01 / 07

Installation ManualAutomatic Transfer Switch (ATS) Generator Transfer Switch (GTS)

Page 4: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

Save This Manual: It contains important installation and operating instructions. Keep it in a safe place.

Table of ContentsThe emergency shutdown procedure is on the inside rear cover

1 Safety Checklists ........................................ 1

2 Overview...................................................... 2

3 Mounting the ATS/GTS ............................... 3

4 Wiring the ATS/GTS to the UPS ................. 5

Specifications ................................................ 8

DANGERRisk of Electrical Shock

To reduce the risk of electrical shock and to ensure the safe operation of the ATS/GTS, the symbols below are used throughout this manual. Where they appear, only qualified personnel should carry out these instructions.

A dangerous voltage exists in this area. Use extreme caution at all times.

Attention: Important operating instructions. Follow them exactly.

Page 5: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

1

The ATS and/or GTS are to be installed by people trained in the safe use of high-energy power supplies and their batteries. Also assumed is knowledge of the local electrical code(s) and their safe application.

DANGER: NEVER let water from rain, a hose, tap or a sprinkler’s output, road splash or other water sources enter the enclosure of the ATS/GTS to prevent accidental shorts, shocks or electrocutions.

DANGER: This unit does NOT have an on/off switch. Whenever it is connected to line or battery power, power is present at the output. Use extreme caution at all times.

Do not work alone under hazardous conditions.Read this manual. If you have any questions about safe installation, operation or maintenance, contact Alpha Technologies’s customer service department.Use this manual together with the Operator’s Manual of the UPS.Carefully unpack the components. Report any shipping or other damage at once.Always assume electrical connections or conductors are live. Turn off all circuit breakers and double-check with a voltmeter before performing installation or maintenance.Before installation, verify the input voltage and current requirements of the load are met by the UPS’s output (See specifications). Verify the line voltage and current meet the UPS’s input requirements.The ATS/GTS have more than one live circuit. AC power may be present at their outputs even if the UPS is disconnected from line or battery power.The ATS/GTS can be operated to a maximum operating temperature of 55°C. Also see the specifications section for temperature ratings.At high ambient temperature conditions, the enclosure’s surface can be very hot to the touch.

1 Safety Checklists

11

PR

ELIM

INA

RY: For Inform

ation Only

Doc# 020-161-B0 Rev. – 01 / 07

Page 6: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

2

2 Overview

The Automatic Transfer Switch (ATS) (Figure 2.1) and the Generator Transfer Switch (GTS) (Figure 2.2) are optional add-on switching units specifically designed for (but not limited to) the FXM family (FXM 650, 1100, 1500 and 2000) and the Novus Micro family (Micro 300/600/1000, Standard, XL and XL3) of UPS. These switching units provide power and/or bypass capacity (automatic or manual) so that the operator may safely disconnect the UPS from line or genera-tor power for easy removal and servicing. In bypass mode, the loads are directly connected to the line or generator power without any conditioning. The ATS and/or GTS allow the use of 3 different back-up sources (line, batteries and/or generator).

PR

ELIM

INA

RY: For Inform

ation Only

Figure 2.1 Automatic Transfer Switch (ATS)

Figure 2.2 Generator Transfer Switch (GTS)

CB2

SW1

CB1

120 VAC Output option (NEMA 5-15R)

SW1

ATS/GTS Installation Manual

Doc# 020-161-B0 Rev. – 01 / 07

Page 7: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

3

3 Mounting the ATS/GTS

The ATS and GTS can be mounted as stand alone, chassis (e.g. on the external bottom enclo-sure of the Novus Micro family UPS) or rack (e.g. inside the end system enclosure of the FXM family UPS). The following diagrams illustrate some of the possible configurations.

Top

SideFront

Figure 3.1 – ATS mounting views (stand alone)MOUNTINGEAR- TOPMOUNTED

MOUNTINGEAR-REARMOUNTED

Figure 3.2 – ATS mounting view (chassis mounted)

Figure 3.3 – ATS mounting view (rack mounted)

33

PR

ELIM

INA

RY: For Inform

ation Only

Doc# 020-161-B0 Rev. – 01 / 07

Page 8: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

Figure 3.� – GTS mounting view (rack mounted)

Figure 3.5 – ATS & GTS mounting view (rack mounted)

PR

ELIM

INA

RY: For Inform

ation Only

ATS/GTS Installation Manual

Doc# 020-161-B0 Rev. – 01 / 07

Page 9: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

5

� Wiring the ATS/GTS to the UPS

The ATS/GTS should be wired to the UPS as shown in Figure �.1 below.

The ATS/GTS/UPS end system must be correctly grounded for proper operation.

Older facilities may have inadequate electrical grounding. Inspection must be performed by a qualified electrician before installation to ensure that grounding meets the local electrical code.

To provide branch circuit protection, the utility line attached to the ATS/GTS/UPS’s input MUST be protected by a circuit breaker certified for this use as per the local or national electrical code.

The breaker’s minimum size is calculated by the following formula:

Minimum Breaker Size= UPS’s maximum input current / 0.8

The unit’s maximum input current is read off of the UPS’s nameplate. For example, if the nameplate gives the maximum input current as 25A, the circuit breaker should be rated at least 30A.

The input and output lines to and from the ATS/GTS/UPS system MUST have disconnect devices attached.

If stranded wires are used, ferrules or equivalent crimping terminals must be used.

Figure �.1 – ATS/GTS to UPS Wiring Diagram

55

PR

ELIM

INA

RY: For Inform

ation Only

1

1

2

2

3

3

4

4

5

5

6

6

D D

C C

B B

A A

LOAD

FXM FAMILY

ATS

INPUT OUTPUT

L N G

TO UPS FROM UPS

L

N LINE IN LINE OUT

G

SCREW LUG

GTSLINE IN

GEN

SCREW LUG

TO UPS

SCREW LUG

LOAD/UPS INPUT

SCREW LUG

GTS

LINE IN

GEN

SCREW LUG

ATS LINE IN

SCREW LUG

SCREW LUG

LINE OUT

SCREW LUG

LINE OUT

L N G

L N G

L N G

L

N

G

L

N

G

L

N

G

L

N

G

UPSINPUT OUTPUT

LOAD

L

N

G

L

N

G

L

N

G

TO UPS FROM UPS

L N G L N G

L

N

G

L

N

G

UPS

WIRING DIAGRAM

Fig 1. ATS & UPS

Fig 2. GTS

FXM FAMILY

FXM FAMILY

Fig 3. ATS & GTS

LINE OUT

Doc# 020-161-B0 Rev. – 01 / 07

Page 10: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

6

ATSWith SW1 & CB1 On – Unit is in UPS Mode

With SW1 Off, CB1 On – Unit is in Bypass Mode

With SW1 On, CB1 Off – UPS Inverter is supplying power (Not recommended)

With SW1 & CB1 Off – Unit is in Bypass – Service Mode

Figure �.2 – ATS schematic diagram

GTSWith SW1 On – Automatic Generator Transfer is Enabled

With SW1 Off – Generator Transfer is Disabled

Figure �.3 – GTS schematic diagram

PR

ELIM

INA

RY: For Inform

ation Only

ATS/GTS Installation Manual

Doc# 020-161-B0 Rev. – 01 / 07

Page 11: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

7

Figure �.� – ATS & GTS Schematic diagram

Servicing the UPS

ATS: Turn off CB1, SW1 and battery CB of the UPS.

GTS (UPS connected to Line Out): The main source branch CB protection coming either from Generator or Line has to be turn-off. Likewise, battery CB of the UPS has to be turn-off.

ATS and GTS combine: Turn off CB1, SW1 and battery CB of the UPS.

Other Note:Simplex 5-15R receptacle is for 120V (rated 5A) only.

2 position mate and lock connector is for 230V only.

••

••

77

PR

ELIM

INA

RY: For Inform

ation Only

Doc# 020-161-B0 Rev. – 01 / 07

Page 12: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

8

ATS/GTS – Mechanical SpecificationsDimensions, in (mm)

H x W x D3.25 x 5.3 x �.5(82 x 135 x 11�)

Weight, lb (kg) (stand alone)

3 (1.36)

Material sheet metal, 1.2 mm thick

Color Black

Mounting options Stand alone, chassis or rack mounted

ConnectionsLine In

Line OutFrom UPS or Gen

To UPS

••

••

2 position TB Weco #327-HDS-02 or equivalent. 2 position TB Weco #327-HDS-02 or equivalent. 3 position TB Weco #32�-HDS-03 or equivalent. 3 position TB Weco #32�-HDS-03 or equivalent.

Recommended Wire SizeLine In

Line OutFrom UPS or Gen

To UPS

••

••

AWG #1� – #6 AWG AWG #1� – #6 AWG AWG #22 – #10 AWG AWG #22 – #10 AWG Note: Terminate all stranded wires with ferrules or equivalent crimp terminals.

HumidityOperating (non-condensing)

Storage•

Up to 95% (RH) Up to 95% (RH)

Temperature Range, °C Operating

Storage (non-operating)•

–20 to 55*–�0 to 75 * capable of operating up to 75°C for 8 hours

Altitude, ft (m)Operating

Storage (non-operating)

Up to 12,000* (3658)Up to 15,000 (�572) * de-rate 2°C per 1000 ft above �500 ft. >15000 ft

ATS/GTS – Electrical SpecificationsInput

Voltage (nominal), VAC 120 or 230

Frequency, Hz, ±5% 50/60

Current, Amps (@ nominal Vin) 30/16 @120/230VAC

Power, VA 3600

Power Factor 0.8 to 1.0

OutputVoltage (nominal), VAC per UPS, Line or Generator

Frequency, Hz, ±5% 50/60

Power, W/VA 3600

RegulatoryElectrical Safety CSA 107.3–05

Immunity CE (for 230V version)

Due to ongoing product improvements, specifications are subject to change without notice

PR

ELIM

INA

RY: For Inform

ation Only

ATS/GTS Installation Manual

Doc# 020-161-B0 Rev. – 01 / 07

Page 13: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

This page is intentionally left blank.

Page 14: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

This page is intentionally left blank.

Page 15: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

Emergency Shutdown Procedure The ATS/GTS does not have an on/off switch. Whenever it senses battery or line power, there is power present at the outputs and the unit is active.

1. Turn off the circuit breaker providing line power to the unit.

2. Disconnect the batteries from the UPS.

3. Turn OFF the attached generator (if connected).

For emergency technical support 7 days a week/2� hours a day, call:

USA: 1 800 863 336� Canada: 1 800 667 87�3

www.alpha.comComplete the following for your records

Serial # ________________________________________

Options ________________________________________

Purchase Date __________________________________

This Novus Micro Secure 100 was purchased from

Dealer _________________________________________

City ___________________________________________

State/Province ___________________________________

Zip/Postal Code __________________________________

Country ________________________________________

Telephone # ____________________________________

Fax # _________________________________________

E Mail Address __________________________________

Page 16: Automatic Transfer Switch (ATS) Generator Transfer …interprovincial.com/files/manuals/alpha/ATS_GTS Installation Manual... · Automatic Transfer Switch (ATS) Generator Transfer

PowerAlpha Technologies ®

Due to continuing product improvements, Alpha reserves the right to change specifications without notice. Copyright © 2007 Alpha Technologies, Inc. All rights reserved. Alpha is a registered trademark of Alpha Technologies. 020-161-B0 Rev. – 01/ 07.

Alpha Technologies3767 Alpha WayBellingham, WA 98226USATel: +1 360 6�7 2360Fax: +1 360 671 �936Web: www.alpha.com

Alpha Technologies Ltd.�08� McConnell CourtBurnaby, BC, V5A 3N7CANADATel: +1 60� �30 1�76Fax: +1 60� �30 8908

Alpha TechnologiesEurope Ltd.Twyford HouseThorleyBishop's StortfordHertfordshire CM22 7PAUNITED KINGDOMTel: +�� 0 1279 501110Fax: +�� 0 1279 659870

Alpha Technologies GmbHHansastrasse 8D 91126 SchwabachGERMANYTel: +�9 9122 79889 0Fax: +�9 9122 79889 21

Alphatec, LtdP.O. Box 56�68Limassol, CyprusCYPRUSTel: +357 25 375675Fax: +357 25 359595

AlphaTEK oooKhokhlovskiy Pereulok 16Stroenie 1, office 403109028 MoscowRUSSIATel: +7 �95 916 185�Fax: +7 �95 916 13�9

Alphatec Baltics S. Konarskio G. �9Vilnius 2009LITHUANIATel: +350 5 210 5291Fax: +350 5 210 5292

Alpha Technologies5 Avenue Victor HugoF 921�0 Calmart FranceFRANCETel: +33 3 �1 90 07 07Fax: +33 1 �1 90 93 12