PACKAGED ELECTRIC / ELECTRIC KC Landmark™ Rooftop Units 60 HZ Bulletin No. 210550 April 2010 Supersedes March 2010 ENGINEERING DATA MODEL NUMBER IDENTIFICATION 7.5 to 12.5 Tons Net Cooling Capacity − 86,500 to 138,000 Btuh Optional Electric Heat - 7.5 to 60 kW K C A 120 S 4 B N 1 Y Brand/Family K = Landmark™ Unit Type C = Packaged Electric Cooling w/ optional Electric Heat Major Design Sequence A = 1st Generation Nominal Cooling Capacity - Tons 092 = 7.5 Tons 102 = 8.5 Tons 120 = 10 Tons 150 = 12.5 Tons Cooling Efficiency S = Standard Efficiency Refrigerant Type 4 = R-410A Blower Type B = Belt Drive Factory Installed Electric Heat N = No Heat C = 7.5 kW Electric Heat E = 15 kW Electric Heat G = 22.5 kW Electric Heat J = 30 kW Electric Heat K = 45 kW Electric Heat L = 60 kW Electric Heat Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz ASHRAE 90.1 COMPLIANT

Transcript of Paquete Lenox

Page 1: Paquete Lenox

P A C K A G E D E L E C T R I C / E L E C T R I C

KCLandmark™ Rooftop Units

60 HZBulletin No. 210550

April 2010Supersedes March 2010

E N G I N E E R I N G D ATA

MODEL NUMBER IDENTIFICATION

7.5 to 12.5 TonsNet Cooling Capacity − 86,500 to 138,000 Btuh

Optional Electric Heat - 7.5 to 60 kW

K C A 120 S 4 B N 1 Y

Brand/Family K = Landmark™

Unit Type C = Packaged Electric Cooling w/ optional Electric Heat

Major Design Sequence A = 1st Generation

Nominal Cooling Capacity - Tons 092 = 7.5 Tons102 = 8.5 Tons120 = 10 Tons

150 = 12.5 Tons

Cooling EfficiencyS = Standard Efficiency

Refrigerant Type4 = R-410A

Blower TypeB = Belt Drive

Factory Installed Electric HeatN = No HeatC = 7.5 kW Electric HeatE = 15 kW Electric HeatG = 22.5 kW Electric HeatJ = 30 kW Electric HeatK = 45 kW Electric HeatL = 60 kW Electric Heat

Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision3 = 3rd Revision

Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz

ASHRAE 90.1COMPLIANT

Page 2: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 2

FEATURES AND BENEFITS

APPROVALS

ETL and CSA listed.Efficiency rating verified by CSA.Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.All models are certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360-2007.All models are ASHRAE 90.1-2007 compliant.ISO 9001 Registered Manufacturing Quality System.

A

B

I

J

CD

E

F

G

H

K

L

Unit shown with optional

Economizer and Outdoor Air Hoods

Landmark™ rooftop units from Lennox are the new standard for reliable, efficient rooftop units built for long-lastingperformance that can significantly improve indoor and outdoor environments. Landmark rooftop units feature:

• R-410A Refrigerant - Environmentally friendly• Scroll Compressors - Single speed scroll compressors are furnished on all models.• High Pressure Switches - Protect compressor.• Isolated Compressor Compartment - Allows performance check during normal compressor operation without

disrupting airflow.• Independent Motor Mounts - Allows for easy and efficient service access without removing the top panel.• Downflow or Horizontal Airflow - Easy field conversion.• Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost any angle.• Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved

serviceability.• Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.• MERV 8 or MERV 13 Filters - Available as field installed option, provide an enhanced level of indoor air quality, and

can help the building qualify for additional LEED credits.

Page 3: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 3

FEATURES AND BENEFITS

APPROVALS

ETL and CSA listed.Efficiency rating verified by CSA.Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.All models are certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360-2007.All models are ASHRAE 90.1-2007 compliant.ISO 9001 Registered Manufacturing Quality System.

A

WARRANTY

Limited five years on compressors.Limited one year all other covered components.

COOLING SYSTEM

Designed to maximize sensible and latent cooling performance at design conditions.System can operate from 30°F to 125°F without any additional controls.R-410A RefrigerantNon-chlorine based, ozone friendly, R-410A.Scroll CompressorsScroll compressors on all models for high performance, reliability and quiet operation.Resiliently mounted on rubber grommets for quiet operation.Compressor Crankcase Heaters (150 Models only)Protects against refrigerant migration that can occur during low ambient operation.Thermal Expansion ValvesAssures optimal performance throughout the application range.Removable element head.Filter/DriersHigh capacity filter/drier protects the system from dirt and moisture.

B

High Pressure SwitchesProtects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation.FreezestatsProtects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant charge.Coil ConstructionCopper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer. Factory leak tested.Evaporator CoilCross row circuiting with rifled copper tubing optimizes both sensible and latent cooling capacity.Condenser CoilSingle formed coil.Condensate Drain PanPlastic pan, sloped to meet drainage requirements of ASHRAE 62.1.Side or bottom drain connections.Reversible to allow connection at back of unit.Outdoor Coil Fan MotorsThermal overload protected, totally enclosed, permanently lubricated ball bearings, shaft up, wire basket mount.Outdoor Coil FansPVC coated fan guard furnished.

REQUIRED SELECTIONS

Cooling CapacitySpecify nominal cooling capacity of the unit

C

D

Contents

Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . 19Electric Heat Capacities. . . . . . . . . . . . . . . . . . . . . . . . . . . 23Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . 1Optional Conventional Temperature Control Systems . . . . . . . . . . . 24Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Page 4: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 4

COOLING SYSTEM (CONTINUED)

OPTIONS/ACCESSORIES

Field InstalledCompressor Crankcase Heaters (092 through 120 Models)Protects against refrigerant migration that can occur during low ambient operation. Furnished on 150 models.Condensate Drain TrapAvailable in copper or PVC.Low Ambient KitCycles the outdoor fans while allowing compressor operation in the cooling cycle. This intermittent fan operation allows the system to operate without icing the evaporator coil and losing capacity. Designed for use in ambient temperatures no lower than 0°F.Low Ambient Kit also controls the compressor crankcase heaters.

CABINET

ConstructionHeavy-gauge steel panels and full perimeter heavy-gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation.Base rails have rigging holes.Three sides of the base rail have forklift slots.Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building.Airflow ChoiceUnits are shipped in downflow (vertical) configuration, can be field converted to horizontal airflow with optional Horizontal Discharge Kit.Duct FlangesProvided for horizontal duct attachment.Power EntryElectrical lines can be brought through the unit base or through horizontal access knock-outs

E

Exterior PanelsConstructed of heavy-gauge, galvanized steel with a two-layer enamel paint finish.InsulationAll panels adjacent to conditioned air are fully insulated with non-hygroscopic fiberglass insulation.Unit base is fully insulated. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation.Access PanelsAccess panels are provided for the filter section, heating/blower section, and the compressor/controls section.

OPTIONS/ACCESSORIES

Factory InstalledCorrosion ProtectionA completely flexible immersed coating with an electrodeposited dry film process. (AST ElectroFin E-Coat) Meets Mil Spec MIL-P-53084, ASTM B117 Standard Method Salt Spray Testing, ASTM 1153 Standard Specification for Methyl Isobutyl Ketone.Hinged Access PanelsLarge access panels are hinged and have quarter-turn latches for quick and easy access to maintenance areas (filter, compressor / controls, heating / blower).Field InstalledCoil GuardsPainted, galvanized steel wire guards to protect outdoor coil.Not used with Hail Guards.Hail GuardsConstructed of heavy gauge steel, painted to match cabinet, helps protect outdoor coils from hail damage.Not used with Coil Guards.

Horizontal Discharge KitConsists of duct covers to block off downflow supply and return air openings for horizontal applications.Also includes return air duct flanges for end return air when economizer is used in horizontal applications.NOTE - When configuring unit for horizontal application with economizer, a separate Horizontal Barometric Relief Damper with Hood must be ordered separately for installation in the return air duct.

Return Air Adaptor PlateFor same size L Series® and T-Class™ unit replacement.Installs on return air opening in unit to match return air opening on existing roof curbs. Also see Accessory Air Resistance table.

BLOWER

A wide selection of supply air blower options are available to meet a variety of airflow requirements.MotorOverload protected, equipped with ball bearings. Belt drive motors are offered on all models and are available in several different sizes to maximize air performance.Supply Air BlowerForward curved blades, double inlet, blower wheel is statically and dynamically balanced. Equipped with ball bearings and adjustable pulley (allows speed change),.Blower assembly slides out of unit for servicing.

REQUIRED SELECTIONS

Order blower motor horsepower and drive kit number required when base unit is ordered, see Drive Kit Specifications Table.

F

FEATURES AND BENEFITS

Page 5: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 5

CONTROLS

Unit ControlAll control voltage is provided via a 24V (secondary) transformer with built-in circuit breaker protection.Heat/Cool Staging - Capable of up to 2 heat / 2 cool staging with a third party DDC control system or thermostat.Low Voltage Terminal Block - Provides screw terminal connections for thermostat or controller wiring.Night Setback Mode - Saves energy by closing outdoor air dampers and operating supply fan on thermostat demand only.

OPTIONS/ACCESSORIES

Field InstalledSmoke DetectorPhotoelectric type, installed in supply air section, return air section or both sections. Available with power board and single sensor (supply or return) or power board and two sensors (supply and return).Commercial Control SystemsL Connection® NetworkComplete building automation control system for single or multi-zone applications. Options include local interface, software for local or remote communication, and hardware for networking other control functions.See L Connection Network Engineering Handbook Bulletin for details.ThermostatsControl system and thermostat options. Aftermarket unit controller options. See page 24.

G

ELECTRICAL

REQUIRED SELECTIONS

Voltage ChoiceSpecify when ordering base unit.

OPTIONS/ACCESSORIES

Factory or Field InstalledDisconnect SwitchAccessible from outside of unit, spring loaded weatherproof cover furnished. Main power to the unit is field connected to the disconnect which allows all power to be shut off for service. See Electrical/Electric Heat tables for ordering information, page 19.Field InstalledElectric HeatHelix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block is furnished as standard. See Options / Accessories tables for ordering information.GFI Service Outlets (2)115V ground fault circuit interrupter (GFCI) type.

INDOOR AIR QUALITY

Air FiltersDisposable 2 inch filters furnished as standard.

OPTIONS/ACCESSORIES

Field InstalledHealthy Climate® High Efficiency Air FiltersDisposable MERV 8 or MERV 13 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2 inch pleated filters.

Replacement Filter Media Kit With FrameReplaces existing pleated filter media. Includes washable metal mesh screen and metal frame with clip for holding replaceable non-pleated filter.

H

I

J

Healthy Climate® UVC Germicidal Lamps

Germicidal lamps emit ultra-violet (UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds. This process either destroys the organism or controls its ability to reproduce.UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan).Lamps are field installed in the blower/evaporator coil section.All necessary hardware for installation is included.Lamps operate on 208/230V power supply. Step-down transformer must be field supplied when used with 460V and 575V rooftop units.Magnetic safety interlock terminates power when access panels are removed.Approved by ETL.Indoor Air Quality (CO2) SensorsMonitors CO2 levels, reports to the Unit Controller which adjusts economizer dampers as needed.

FEATURES AND BENEFITS

Page 6: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 6

FEATURES AND BENEFITS

SERVICEABILITY

Designed to streamline general maintenance and decrease troubleshooting time.Marked & Color-Coded WiringAll electrical wiring is color-coded and marked to identify which components it is connecting.Electrical PlugsPositive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation.Access PanelsLarge access panels for quick and easy access to maintenance areas (filter, compressor / controls/ blower / heat section).Blower AccessSupply air blower parts are located near the access door for easy servicing and adjustment.Thermal Expansion ValvesThermal expansion valves are located near the perimeter of the unit for easier access.Removable element head allows change out of element and bulb without removing the TXV.Coil CleaningFormed condenser coil allows separation for easier cleaning.Standard ComponentsA large number of common maintenance parts are standard throughout the entire range of sizes (3-30 tons), reducing the need to carry a lot of different parts to the job or maintain in inventory.Compressor CompartmentCompressors are located near the perimeter of the unit for easier access.Compressors are isolated from the condenser airflow allowing system operation checks to be done without changing the airflow across the outdoor coils.

Page 7: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 7

OPTIONS / ACCESSORIES

ECONOMIZER/EXHAUST OPTIONS

Factory or Field InstalledEconomizer with Temperature Control - Downflow or Horizontal With Barometric Relief Dampers and HoodsParallel gear-driven action return air and outdoor air dampers, plug-in connections to unit, nylon bearings, neoprene seals, 24-volt, fully-modulating, spring return motor, adjustable minimum damper position. Economizer includes outdoor air hood and barometric relief dampers with exhaust hood.Single temperature control is furnished with economizer. Temperature sensor enables the economizer when the outdoor air temperature is below the configured setpoint.Barometric Relief Dampers allow relief of excess air.Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle.Exhaust hood with bird screen furnished.For use in downflow applications only.NOTE - Outdoor Air and Barometric Relief Exhaust Hoods are included when economizer is factory installed and are furnished with economizer when ordered for field installation.Single Enthalpy Temperature ControlOutdoor air enthalpy sensor enables economizer if the outdoor enthalpy is less than the setpoint of the control. Single enthalpy control is furnished with economizer.

K

L

Field InstalledDifferential Enthalpy ControlOrder two Single Enthalpy Control Kits. One is field installed in the return air section, the other in the outdoor air section. Allows the economizer control board to select between outdoor air or return air, whichever has lower enthalpy.Horizontal Barometric Relief DampersFor use when unit is configured for horizontal applications requiring an economizer.Allows relief of excess airAluminum blade dampers prevent blow back and outdoor air infiltration during off cycle.Field installed in return air duct.Exhaust hood with bird screen furnished.Requires Horizontal Discharge Kit.Power Exhaust FanInstalls internal to unit for downflow applications only with economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fan runs when outdoor air dampers are 50% open (adjustable), motor is overload protected. Requires Economizer with Outdoor Air Hood and Barometric Relief Dampers. Fan is 20 in. diameter with 5 blades (K1PWRE10B) WITH 1/3 hp motor.

OUTDOOR AIR OPTIONS

Factory or Field InstalledOutdoor Air Damper - Downflow or Horizontal With Air HoodLinked mechanical dampers, 0 to 25% (fixed) outdoor air adjustable, installs in unit. Includes outdoor air hood.Automatic model features fully modulating spring return damper motor with plug-in connection.Manual model features a slide damper.Maximum mixed air temperature in cooling mode: 100°F.

ROOF CURBS (DOWNFLOW)

Nailer strip furnished, mates to unit, US National Roofing Contractors Approved, shipped knocked down.Clip Curbs - Uses interlocking tabs to fasten corners together. No tools required.Standard Curbs - Curb corners fasten together with furnished hardware.

CEILING DIFFUSERS

Ceiling Diffusers (Flush or Step-Down)Aluminum grilles, large center grille, insulated diffuser box with flanges, hanging rings furnished, interior transition (even air flow), internally sealed (prevents recirculation), adapts to T-bar ceiling grids or plaster ceilings.Transitions (Supply and Return)Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated.

Page 8: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 8

OPTIONS / ACCESSORIES

Item Description Model Number

Catalog Number

Unit Model No092 102 120 150

COOLING SYSTEM

Compressor Crankcase Heater 208/230V- 3ph - K1CCHT02B-1Y 54W17 X X X

460V-3ph - K1CCHT02B-1G 54W18 X X X

575V-3ph - K1CCHT02B-1J 54W19 X X X

Condensate Drain Trap PVC - LTACDKP09/36 76M18 X X X X

Copper - LTACDKC09/36 76M19 X X X X

Corrosion Protection Factory O O O O

Efficiency Standard O O O O

Low Ambient Kit K1SNSR33B-1 54W16 X X X X

Refrigerant Type R-410A O O O O

BLOWER - SUPPLY AIR

Motors Belt Drive - 2 hp Factory O O O O

Belt Drive - 3 hp Factory O O O O

Belt Drive - 5 hp Factory O O O O

Drive KitsSee Blower Data Tables for selection

Kit #1 590-890 rpm Factory O O O O

Kit #2 800-1105 rpm Factory O O O O

Kit #3 795-1195 rpm Factory O O O O

Kit #4 730-970 rpm Factory O O O O

Kit #5 940-1200 rpm Factory O O O O

Kit #6 1015-1300 rpm Factory O O O O

Kit #10 900-1135 rpm Factory O O O O

Kit #11 1040-1315 rpm Factory O O O O

Kit #12 1125-1425 rpm Factory O O O O

CABINET

Coil Guards K1GARD20B-1 55W08 X X X X

Hail Guards K1GARD10B1 55W11 X X X X

Hinged Access Panels Factory O O O O

Horizontal Discharge Kit K1HECK00B-1 51W25 X X X X

Return Air Adaptor Plate (for L Series® and T-Class™ replacement) C1CONV10B-1 54W96 X X X X

CONTROLS

Commercial Controls L Connection® Building Automation System - - - X X X X

Smoke Detector - Supply or Return (Power board and one sensor) C1SNSR44B-1 53W80 X X X X

Smoke Detector - Supply and Return (Power board and two sensors) C1SNSR43B-1 53W81 X X X XNOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed

Page 9: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 9

OPTIONS / ACCESSORIES

Item Description Model Number

Catalog Number

Unit Model No092 102 120 150

INDOOR AIR QUALITY

Air FiltersHealthy Climate® High Efficiency Air Filters20 x 25 x 2 (Order 4 per unit)

MERV 8 - C1FLTR15B-1 50W61 X X X XMERV 13 - C1FLTR40B-1 52W41 X X X X

Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media)

C1FLTR30B-1- Y3063 X X X X

Indoor Air Quality (CO2) SensorsSensor - Wall-mount, off-white plastic cover with LCD display C0SNSR50AE1L 77N39 X X X XSensor - Wall-mount, off-white plastic cover, no display C0SNSR52AE1L 87N53 X X X XSensor - Black plastic case with LCD display, rated for plenum mounting C0SNSR51AE1L 87N52 X X X X

Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting C0MISC19AE1 87N54 X X X X

CO2 Sensor Duct Mounting Kit - for downflow applications C0MISC19AE1- 85L43 X X X XAspiration Box - for duct mounting non-plenum rated CO2 sensors(87N53 or 77N39) C0MISC16AE1- 90N43 X X X X

UVC Germicidal Lamps1 Healthy Climate® UVC Light Kit (208/230v-1ph) C1UVCL10B-1 54W62 X X X XELECTRICAL

Voltage 60 hz 208/230V - 3 phase Factory O O O O460V - 3 phase Factory O O O O575V - 3 phase Factory O O O O

Disconnect Switch - See Electrical/Electric Heat tables for selection 80 amp - C1DISC080B-1 54W56 OX OX OX OX150 amp - C1DISC150B-1 54W57 OX OX OX OX

GFI Service Outlets LTAGFIK10/15 74M70 X X X XELECTRIC HEAT

7.5 kW 208/230V-3ph - C1EHO075B-1Y 56W38 X X460V-3ph - C1EHO075B-1G 56W39 X X575V-3ph - C1EHO075B-1J 56W40 X X

15 kW 208/230V-3ph - C1EHO015B-1Y 56W41 X X X X460V-3ph - C1EHO150B-1G 56W42 X X X X575V-3ph - C1EHO150B-1J 56W43 X X X X

22.5 kW 208/230V-3ph - C1EHO225B-1Y 56W44 X X X X460V-3ph - C1EHO225B-1G 56W45 X X X X575V-3ph - C1EHO225B-1J 56W46 X X X X

30 kW 208/230V-3ph - C1EHO300B-1Y 56W47 X X X X460V-3ph - C1EHO300B-1G 56W48 X X X X575V-3ph - C1EHO300B-1J 56W49 X X X X

45 kW 208/230V-3ph - C1EHO450B-1Y 56W50 X X X X460V-3ph - C1EHO450B-1G 56W51 X X X X

575V-3ph - C1EHO450B-1J 56W52 X X X X60 kW 208/230V-3ph - C1EHO600B-1Y 55W02 X X

460V-3ph - C1EHO600B-1G 55W03 X X575V-3ph - C1EHO600B-1J 55W04 X X

1 Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supplymay be used to directly power the UVC ballast(s)

NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed

Page 10: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 10

OPTIONS / ACCESSORIES

Item Description Model Number

Catalog Number

Unit Model No092 102 120 150

ECONOMIZER

EconomizerEconomizer with Single Temperature Control - Downflow or Horizontal With Barometric Relief Dampers (downflow) and Air Hoods

K1ECON20B-1 54W55 OX OX OX OX

Economizer ControlsSingle Enthalpy Control C1SNSR64FF1 53W64 OX OX OX OXDifferential Enthalpy Control (order 2) C1SNSR64FF1 53W64 X X X XHorizontal Barometric Relief Dampers With Exhaust HoodHorizontal Barometric Relief Dampers - Exhaust Hood Furnished LAGEDH03/15 53K04 X X X X

OUTDOOR AIR

Outdoor Air DampersMotorized Dampers with outdoor air hood C1DAMP20B-1 53W49 OX OX OX OXManual Dampers with outdoor air hood C1DAMP10B-1 53W48 OX OX OX OX

POWER EXHAUST

Standard Static 208/230V-3ph - K1PWRE10B-1Y 53W44 X X X X460V-3ph - K1PWRE10B-1G 53W45 X X X X575V-3ph - K1PWRE10B-1J 53W46 X X X X

ROOF CURBS - DOWNFLOW

Clip Curb8 in. height C1CURB23B-1 54W46 X X X X14 in. height C1CURB20B-1 54W47 X X X X18 in. height C1CURB21B-1 54W48 X X X X24 in. height C1CURB22B-1 54W49 X X X XStandard8 in. height C1CURB12B-1 54W44 X X X X14 in. height C1CURB10B-1 54W43 X X X X24 in. height C1CURB11B-1 54W45 X X X XAdjustable Pitched Curb14 in. height C1CURB55B-1 54W50 X X X X

CEILING DIFFUSERS

Step-Down - Order one RTD11-95 29G04 XRTD11-135 29G05 X XRTD11-185 29G06 X

Flush - Order one FD11-95 29G08 XFD11-135 29G09 X XFD11-185 29G10 X

Transitions (Supply and Return) - Order one LASRT08/10 24L14 XLASRT10/12 49K55 X X

LASRT15 49K56 XNOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed

Page 11: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 11

SPECIFICATIONSGeneral Data Nominal Tonnage 7.5 Ton 8.5 Ton 10 Ton 12.5 Ton

Model Number KCA092S4B KCA102S4B KCA120S4B KCA150S4BEfficiency Type Standard Standard Standard Standard

Blower Type Constant Air Volume CAV

Constant Air Volume CAV

Constant Air Volume CAV

Constant Air Volume CAV

Cooling Performance

Gross Cooling Capacity - Btuh 88,900 100,483 119,640 144,8001 Net Cooling Capacity - Btuh 86,000 97,000 115,000 138,000

AHRI Rated Air Flow - cfm 3,000 3,400 3,800 4,300Total Unit Power - kW 7.7 8.7 10.3 12.5

1 EER (Btuh/Watt) 11.2 11.2 11.2 112 IEER (Btuh/Watt) 11.4 11.4 11.4 11.2

Refrigerant Type R-410A R-410A R-410A R-410ARefrigerant

Charge Furnished

Circuit 1 7 lbs. 8 oz. 8 lbs. 8 oz. 10 lbs. 0 oz. 14 lbs. 0 oz.Circuit 2 7 lbs. 0 oz. 8 lbs. 8 oz. 10 lbs. 0 oz. 12 lbs. 0 oz.

Electric Heat Available - See page 9 7.5,15,22.5,30 & 45 KW 15,22.5,30,45 & 60 KWCompressor Type (number) Scroll (2) Scroll (2) Scroll (2) Scroll (2)Outdoor Coils

Net face area (total) - sq. ft. 20.42 24.5 28.0 28.0Tube diameter - in. 3/8 3/8 3/8 3/8

Number of rows 2 2 2 3Fins per inch 20 20 20 20

Outdoor Coil Fans

Motor - (No.) hp (2) 1/3 (2) 1/3 (2) 1/3 (2) 1/2Motor rpm 1075 1075 1075 1075

Total Motor watts 670 670 670 830Diameter - (No.) in. (2) 24 (2) 24 (2) 24 (2) 24

Number of blades 3 3 3 3Total Air volume - cfm 7200 7400 7800 8,800

Indoor Coils

Net face area (total) - sq. ft. 12.78 12.78 12.78 13.54Tube diameter - in. 3/8 3/8 3/8 3/8

Number of rows 2 2 3 4Fins per inch 14 14 14 14

Drain connection - Number and size

(1) 1 in. NPT coupling

Expansion device type Balance port TXV, removable head3 IndoorBlower and Drive Selection

Nominal motor output 2 hp, 3 hp, 5 hp 2 hp, 3 hp, 5 hp 2 hp, 3 hp, 5 hp 2 hp, 3 hp, 5 hpMaximum usable motor output

(US Only)2.3 hp, 3.45 hp,

5.75 hp2.3 hp, 3.45 hp,

5.75 hp2.3 hp, 3.45 hp,

5.75 hp2.3 hp, 3.45 hp,

5.75 hpMotor - Drive kit number 2 hp

4 Kit 1 590-890 rpmKit 2 800-1105 rpmKit 3 795-1195 rpm

3 hp Kit 4 730-970 rpmKit 5 940-1200 rpm Kit 6 1015-1300 rpm

5 hp Kit 10 900-1135 rpmKit 11 1040-1315 rpmKit 12 1125-1425 rpm

2 hp 4 Kit 1 590-890 rpmKit 2 800-1105 rpmKit 3 795-1195 rpm

3 hp Kit 4 730-970 rpmKit 5 940-1200 rpm Kit 6 1015-1300 rpm

5 hp Kit 10 900-1135 rpmKit 11 1040-1315 rpmKit 12 1125-1425 rpm

2 hp Kit 1 590-890 rpmKit 2 800-1105 rpmKit 3 795-1195 rpm

3 hp 4 Kit 4 730-970 rpmKit 5 940-1200 rpm Kit 6 1015-1300 rpm

5 hp Kit 10 900-1135 rpmKit 11 1040-1315 rpmKit 12 1125-1425 rpm

2 hp Kit 1 590-890 rpmKit 2 800-105 rpmKit 3 795-1195 rpm

3 hp Kit 4 730-970 rpmKit 5 940-1200 rpm Kit 6 1015-1300 rpm

5 hp 4 Kit 10 900-1135 rpmKit 11 1040-1315 rpmKit 12 1125-1425 rpm

Blower wheel nominal diameter x width - in.

(1) 15 X 15 (1) 15 X 15 (1) 15 X 15 (1) 15 X 15

Filters Type of filter DisposableNumber and size - in. (4) 20 x 25 x 2

Electrical characteristics 208/230V, 460V or 575V - 60 hertz - 3 phaseNOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 Certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure. 2 Integrated Energy Efficiency Ratio tested at 80°F outdoor air temperature.3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. 4 Standard motor and drive kit furnished with unit.

Page 12: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 12

RATINGSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

8.5 TON STANDARD EFFICIENCY KCA102S4 (1ST STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F2720 50.6 2.43 .62 .75 .91 48.8 2.74 .63 .77 .93 46.9 3.10 .64 .79 .96 44.9 3.51 .65 .81 .993400 53.2 2.44 .65 .82 1.00 51.3 2.75 .66 .85 1.00 49.2 3.11 .68 .87 1.00 46.9 3.52 .70 .90 1.004080 55.1 2.45 .69 .90 1.00 53.0 2.76 .71 .92 1.00 50.8 3.12 .73 .95 1.00 48.3 3.52 .75 .98 1.00

67°F2720 52.9 2.44 .50 .60 .71 51.1 2.75 .51 .61 .73 49.2 3.11 .51 .62 .75 47.0 3.52 .52 .63 .773400 55.7 2.45 .52 .63 .78 53.7 2.77 .53 .64 .80 51.6 3.12 .53 .66 .83 49.2 3.53 .54 .67 .864080 57.7 2.46 .54 .67 .85 55.6 2.77 .55 .68 .88 53.3 3.13 .56 .70 .91 50.8 3.54 .56 .72 .94

71°F2720 55.0 2.45 .39 .49 .58 53.1 2.76 .39 .49 .59 51.1 3.12 .40 .50 .60 49.0 3.53 .40 .51 .613400 58.0 2.46 .40 .51 .62 55.9 2.78 .40 .52 .62 53.7 3.13 .39 .52 .64 51.3 3.54 .39 .53 .654080 60.1 2.47 .41 .53 .65 57.9 2.79 .40 .54 .66 55.6 3.14 .41 .55 .68 53.0 3.55 .41 .56 .70

8.5 TON STANDARD EFFICIENCY KCA102S4 (2ND STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F2720 96.0 6.28 .70 .83 .97 91.7 7.12 .71 .85 .99 87.2 8.12 .72 .88 1.00 82.0 9.27 .74 .91 1.003400 100.6 6.30 .74 .90 1.00 95.9 7.13 .75 .92 1.00 91.0 8.13 .77 .95 1.00 85.5 9.30 .80 .99 1.004080 103.9 6.32 .78 .96 1.00 98.8 7.15 .80 .99 1.00 93.7 8.13 .83 1.00 1.00 88.6 9.30 .86 1.00 1.00

67°F2720 100.5 6.31 .56 .68 .80 96.1 7.14 .57 .69 .82 91.4 8.13 .57 .70 .84 86.1 9.28 .59 .72 .873400 105.4 6.32 .58 .72 .86 100.5 7.15 .59 .73 .89 95.5 8.13 .60 .75 .92 89.9 9.29 .62 .78 .954080 108.9 6.34 .61 .76 .93 103.9 7.17 .61 .78 .96 98.6 8.16 .63 .80 .98 92.6 9.30 .64 .83 1.00

71°F2720 104.5 6.32 .43 .54 .65 100.1 7.16 .43 .55 .67 95.2 8.14 .43 .56 .68 89.8 9.28 .43 .57 .703400 109.8 6.35 .43 .57 .70 104.9 7.18 .43 .58 .71 99.6 8.15 .44 .59 .73 94.0 9.30 .44 .60 .754080 113.6 6.37 .45 .60 .74 108.4 7.19 .44 .61 .76 103.0 8.17 .45 .62 .78 96.9 9.31 .46 .64 .81

7.5 TON STANDARD EFFICIENCY KCA092S4 (1ST STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F2400 45.5 2.10 .61 .74 .92 43.8 2.37 .62 .76 .94 42.0 2.68 .63 .79 .97 40.1 3.03 .64 .81 1.003000 47.8 2.11 .64 .82 1.00 46.0 2.38 .65 .85 1.00 44.0 2.69 .67 .88 1.00 42.0 3.04 .69 .91 1.003600 49.6 2.12 .68 .90 1.00 47.6 2.39 .70 .93 1.00 45.4 2.69 .72 .97 1.00 43.3 3.05 .75 .99 1.00

67°F2400 47.6 2.11 .49 .59 .70 45.9 2.38 .50 .60 .72 44.0 2.69 .50 .61 .74 42.0 3.04 .51 .62 .773000 50.1 2.12 .51 .62 .78 48.2 2.39 .52 .63 .80 46.2 2.70 .53 .65 .83 44.0 3.05 .53 .66 .873600 52.0 2.13 .53 .66 .86 49.9 2.40 .53 .67 .88 47.8 2.70 .55 .70 .92 45.4 3.05 .55 .72 .96

71°F2400 49.5 2.12 .38 .48 .57 47.7 2.39 .38 .48 .58 45.8 2.69 .39 .49 .59 43.7 3.05 .39 .50 .603000 52.2 2.13 .39 .50 .60 50.2 2.40 .39 .51 .62 48.1 2.71 .38 .51 .63 45.9 3.05 .39 .52 .643600 54.2 2.14 .39 .52 .64 52.1 2.41 .39 .53 .65 49.9 2.71 .39 .54 .67 47.5 3.06 .39 .55 .70

7.5 TON STANDARD EFFICIENCY KCA092S4 (2ND STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F2400 85.0 5.41 .68 .82 .98 81.0 6.12 .69 .85 1.00 76.7 6.95 .71 .88 1.00 72.2 7.92 .73 .91 1.003000 89.1 5.42 .72 .90 1.00 84.8 6.14 .74 .93 1.00 80.1 6.96 .76 .97 1.00 75.2 7.93 .79 1.00 1.003600 91.8 5.44 .77 .97 1.00 87.6 6.15 .79 1.00 1.00 82.8 6.97 .82 1.00 1.00 78.1 7.93 .86 1.00 1.00

67°F2400 89.0 5.42 .54 .66 .79 84.9 6.14 .55 .67 .81 80.4 6.96 .56 .69 .84 75.7 7.93 .57 .71 .873000 93.3 5.44 .57 .70 .86 88.9 6.15 .58 .72 .89 84.1 6.98 .59 .74 .93 78.9 7.94 .60 .77 .973600 96.6 5.46 .59 .75 .94 91.8 6.16 .60 .77 .97 86.7 6.99 .61 .80 .99 81.2 7.95 .63 .83 1.00

71°F2400 92.6 5.44 .42 .53 .64 88.3 6.15 .42 .54 .65 83.8 6.98 .42 .55 .67 78.8 7.93 .42 .56 .683000 97.3 5.46 .42 .56 .68 92.7 6.17 .43 .57 .69 87.9 6.99 .43 .58 .71 82.5 7.95 .43 .59 .743600 100.8 5.48 .42 .58 .72 95.9 6.18 .43 .59 .74 90.6 7.00 .44 .61 .77 84.9 7.96 .45 .63 .81

Page 13: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 13

RATINGSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

12.5 TON STANDARD EFFICIENCY KCA150S4 (1ST STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F3800 72.5 3.64 .64 .78 .96 70.1 4.03 .65 .81 .98 67.1 4.46 .66 .83 1.00 64.0 4.93 .67 .86 1.004400 75.0 3.66 .67 .84 1.00 72.3 4.04 .68 .87 1.00 69.4 4.47 .69 .89 1.00 66.1 4.94 .71 .93 1.005000 77.0 3.67 .70 .90 1.00 74.2 4.06 .71 .92 1.00 71.2 4.48 .74 .96 1.00 67.7 4.95 .76 .99 1.00

67°F3800 76.7 3.67 .51 .62 .74 74.1 4.06 .52 .63 .76 71.1 4.48 .52 .64 .78 67.7 4.95 .53 .65 .814400 79.4 3.69 .52 .65 .80 76.5 4.07 .53 .66 .82 73.3 4.49 .54 .67 .85 69.8 4.96 .54 .68 .885000 81.3 3.70 .54 .67 .85 78.4 4.08 .55 .68 .88 75.0 4.50 .55 .70 .91 71.5 4.97 .57 .73 .95

71°F3800 81.3 3.70 .39 .50 .60 78.5 4.08 .39 .50 .60 75.3 4.50 .39 .51 .62 72.1 4.97 .40 .52 .634400 83.6 3.72 .40 .51 .62 80.8 4.10 .40 .52 .63 77.7 4.52 .40 .53 .65 74.0 4.98 .40 .53 .665000 85.7 3.73 .41 .53 .65 82.7 4.11 .40 .54 .66 79.2 4.53 .41 .54 .67 75.4 4.99 .41 .55 .70

12.5 TON STANDARD EFFICIENCY KCA150S4 (2ND STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F3800 139.0 9.09 .70 .86 1.00 132.4 10.04 .72 .88 1.00 125.2 11.10 .74 .91 1.00 117.7 12.30 .76 .95 1.004400 143.4 9.11 .73 .91 1.00 136.7 10.06 .75 .94 1.00 129.1 11.13 .78 .97 1.00 121.3 12.32 .81 1.00 1.005000 147.3 9.13 .78 .96 1.00 140.2 10.09 .79 .99 1.00 132.9 11.15 .83 1.00 1.00 125.4 12.34 .86 1.00 1.00

67°F3800 147.0 9.13 .56 .68 .82 140.1 10.08 .57 .69 .84 132.8 11.14 .57 .71 .87 124.9 12.34 .59 .73 .904400 151.7 9.16 .57 .71 .87 144.6 10.11 .58 .73 .89 136.9 11.17 .60 .75 .93 128.6 12.37 .62 .78 .975000 155.4 9.18 .59 .74 .92 148.1 10.13 .60 .77 .95 140.3 11.19 .62 .80 .99 131.7 12.39 .64 .83 1.00

71°F3800 156.1 9.18 .42 .54 .66 149.2 10.14 .42 .55 .67 141.2 11.20 .43 .56 .69 132.8 12.40 .43 .57 .714400 160.7 9.21 .43 .56 .69 153.3 10.16 .43 .57 .70 145.2 11.23 .44 .58 .72 136.2 12.42 .44 .60 .755000 164.1 9.23 .44 .58 .72 156.4 10.18 .44 .59 .74 148.1 11.24 .45 .60 .76 138.9 12.44 .46 .62 .80

10 TON STANDARD EFFICIENCY KCA120S4 (1ST STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F3200 61.0 2.83 .63 .77 .95 58.7 3.21 .64 .79 .98 56.2 3.64 .65 .82 1.00 53.4 4.11 .66 .85 1.004000 63.7 2.86 .67 .87 1.00 61.2 3.24 .68 .89 1.00 58.5 3.67 .69 .93 1.00 55.7 4.14 .72 .97 1.004800 65.7 2.89 .71 .96 1.00 63.2 3.27 .74 .99 1.00 60.4 3.69 .76 1.00 1.00 57.7 4.17 .80 1.00 1.00

67°F3200 64.2 2.87 .50 .61 .72 61.7 3.25 .51 .62 .74 59.2 3.68 .51 .63 .77 56.3 4.15 .52 .64 .804000 67.1 2.90 .52 .65 .82 64.5 3.29 .53 .66 .85 61.7 3.71 .54 .67 .88 58.7 4.19 .55 .69 .924800 69.3 2.93 .55 .69 .92 66.4 3.31 .56 .71 .95 63.4 3.74 .57 .74 .98 60.2 4.21 .58 .77 1.00

71°F3200 67.4 2.91 .38 .49 .59 64.8 3.29 .38 .49 .60 62.1 3.72 .39 .50 .61 59.2 4.19 .39 .51 .624000 70.4 2.94 .39 .51 .63 67.6 3.33 .39 .52 .64 64.7 3.75 .40 .53 .65 61.7 4.23 .40 .54 .674800 72.6 2.97 .40 .54 .67 69.7 3.36 .41 .55 .69 66.5 3.78 .41 .56 .71 63.2 4.26 .42 .57 .74

10 TON STANDARD EFFICIENCY KCA120S4 (2ND STAGE)

Entering Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil85°F 95°F 105°F 115°F

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry Bulbcfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

63°F3200 115.2 7.30 .68 .84 1.00 109.6 8.25 .69 .87 1.00 103.8 9.34 .71 .90 1.00 97.5 10.59 .73 .94 1.004000 119.9 7.36 .72 .93 1.00 114.3 8.32 .75 .97 1.00 108.2 9.41 .78 1.00 1.00 101.8 10.65 .81 1.00 1.004800 123.7 7.42 .79 1.00 1.00 118.4 8.38 .82 1.00 1.00 112.4 9.47 .85 1.00 1.00 106.2 10.72 .90 1.00 1.00

67°F3200 121.4 7.38 .53 .66 .79 115.6 8.34 .54 .67 .82 109.6 9.42 .55 .69 .86 102.9 10.67 .57 .71 .904000 126.5 7.45 .56 .70 .89 120.3 8.41 .57 .72 .93 113.6 9.49 .59 .75 .97 106.5 10.73 .60 .79 1.004800 129.9 7.50 .59 .76 .98 123.4 8.45 .61 .79 1.00 116.6 9.54 .62 .83 1.00 108.7 10.76 .64 .87 1.00

71°F3200 127.4 7.47 .40 .52 .64 121.4 8.42 .41 .53 .65 115.1 9.51 .41 .54 .67 108.1 10.76 .42 .55 .694000 132.7 7.54 .42 .55 .68 126.3 8.50 .42 .56 .70 119.3 9.58 .43 .58 .72 112.0 10.82 .43 .59 .764800 136.2 7.60 .43 .58 .74 129.7 8.55 .44 .60 .77 122.4 9.63 .44 .61 .80 114.4 10.86 .45 .63 .85

Page 14: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 14

BLOWER DATA

092 AND 102 BELT DRIVE BLOWER − BASE UNITBLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD:1 − Wet indoor coil air resistance of selected unit.2 − Any factory installed options air resistance (heat section, economizer, etc.)3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)Then determine from blower table blower motor output required.See page 17 for blower motors and drives.See page 17 for wet coil and option/accessory air resistance data.MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)7.5 kW, 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm

Total Air

Volume cfm

Total Static Pressure − in. w.g.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2250 - - - - - - - - - - - - 707 0.14 753 0.50 800 0.84 847 1.15 892 1.38 934 1.53 979 1.65 1051 1.86 1126 2.12 1183 2.36 1238 2.62

2500 - - - - - - - - - - - - 714 0.29 758 0.64 803 0.97 849 1.26 893 1.48 936 1.63 983 1.75 1052 1.96 1124 2.22 1184 2.49 1241 2.77

2750 - - - - - - 680 0.11 721 0.45 763 0.78 807 1.09 852 1.37 896 1.58 940 1.74 989 1.88 1053 2.08 1121 2.34 1185 2.63 1244 2.93

3000 - - - - - - 689 0.29 728 0.61 770 0.93 812 1.23 856 1.49 901 1.70 947 1.87 996 2.02 1055 2.21 1120 2.47 1186 2.78 1248 3.10

3250 661 0.17 698 0.46 737 0.78 777 1.09 819 1.38 862 1.63 908 1.84 955 2.01 1004 2.17 1059 2.36 1122 2.62 1189 2.94 1252 3.28

3500 672 0.36 708 0.65 746 0.95 786 1.25 827 1.53 870 1.78 916 1.99 965 2.17 1013 2.33 1065 2.52 1126 2.79 1193 3.12 1257 3.47

3750 684 0.56 719 0.85 756 1.14 795 1.43 836 1.70 880 1.95 927 2.16 976 2.34 1023 2.51 1073 2.71 1133 2.98 1198 3.32 1263 3.67

4000 697 0.78 731 1.05 768 1.34 807 1.62 848 1.89 892 2.13 940 2.34 988 2.53 1034 2.71 1083 2.91 1141 3.19 1205 3.53 1270 3.89

4250 710 1.00 745 1.27 781 1.55 819 1.83 861 2.09 906 2.33 954 2.55 1001 2.74 1046 2.93 1094 3.14 1151 3.42 1214 3.76 1278 4.12

Page 15: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 15

BLOWER DATA

120 BELT DRIVE BLOWER − BASE UNITBLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD:1 − Wet indoor coil air resistance of selected unit.2 − Any factory installed options air resistance (heat section, economizer, etc.)3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)Then determine from blower table blower motor output required.See page 17 for blower motors and drives.See page 17 for wet coil and option/accessory air resistance data.MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm60 kW - 4000 cfm

Total Air

Volume cfm

Total Static Pressure − in. w.g.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3000 - - - - - - 677 0.24 719 0.55 764 0.87 813 1.18 866 1.45 920 1.67 975 1.82 1026 1.96 1076 2.13 1126 2.35 1176 2.63 1225 2.92

3250 650 0.14 688 0.43 730 0.73 775 1.04 823 1.34 875 1.60 930 1.81 985 1.97 1036 2.12 1086 2.31 1136 2.54 1186 2.83 1235 3.13

3500 663 0.35 700 0.63 741 0.92 786 1.22 834 1.5 886 1.76 942 1.96 997 2.14 1048 2.31 1097 2.51 1147 2.75 1196 3.04 1245 3.35

3750 676 0.57 714 0.84 754 1.12 798 1.41 846 1.68 899 1.93 956 2.14 1010 2.32 1060 2.51 1109 2.72 1158 2.98 1207 3.27 1255 3.58

4000 691 0.79 728 1.05 768 1.33 812 1.61 860 1.88 914 2.12 971 2.34 1023 2.53 1072 2.73 1121 2.95 1169 3.22 1218 3.51 1266 3.83

4250 706 1.03 743 1.28 783 1.55 827 1.82 876 2.09 931 2.33 987 2.55 1037 2.76 1085 2.97 1133 3.20 1181 3.47 1229 3.76 1277 4.08

4500 722 1.27 759 1.52 799 1.78 844 2.05 894 2.31 949 2.56 1003 2.79 1052 3.00 1098 3.22 1145 3.46 1193 3.73 1241 4.03 1289 4.34

4750 739 1.53 776 1.77 817 2.03 862 2.30 913 2.56 968 2.81 1020 3.04 1066 3.27 1112 3.49 1158 3.74 1205 4.01 1253 4.30 1301 4.61

5000 757 1.79 794 2.04 835 2.30 882 2.56 934 2.83 988 3.08 1036 3.32 1081 3.55 1125 3.78 1171 4.02 1218 4.29 1265 4.59 1312 4.89

Page 16: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 16

BLOWER DATA

150 BELT DRIVE BLOWER − BASE UNITBLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD:1 − Wet indoor coil air resistance of selected unit.2 − Any factory installed options air resistance (heat section, economizer, etc.)3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)Then determine from blower table blower motor output required.See page 17 for blower motors and drives.See page 17 for wet coil and option/accessory air resistance data.MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm60 kW - 4000 cfm

Total Air

Volume cfm

Total Static Pressure − in. w.g.

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3750 689 0.68 731 0.97 775 1.27 820 1.56 865 1.81 911 2.02 957 2.19 1004 2.35 1051 2.53 1100 2.74 1151 2.99 1204 3.29 1258 3.61

4000 706 0.92 748 1.22 792 1.51 836 1.78 881 2.02 926 2.22 972 2.39 1018 2.57 1065 2.76 1113 2.98 1163 3.25 1217 3.55 1271 3.87

4250 725 1.18 766 1.47 810 1.75 854 2.02 899 2.25 943 2.44 988 2.61 1033 2.81 1079 3.01 1127 3.25 1178 3.52 1230 3.82 1284 4.14

4500 744 1.45 786 1.73 829 2.01 873 2.27 917 2.49 961 2.67 1005 2.87 1050 3.07 1096 3.29 1143 3.53 1193 3.81 1245 4.11 1298 4.43

4750 764 1.73 806 2.01 849 2.28 893 2.53 936 2.74 980 2.94 1023 3.15 1068 3.37 1113 3.60 1160 3.84 1210 4.12 1261 4.42 1314 4.74

5000 785 2.02 827 2.30 870 2.57 914 2.81 957 3.02 1000 3.23 1043 3.46 1087 3.69 1131 3.92 1178 4.17 1227 4.44 1278 4.74 1330 5.05

5250 807 2.33 850 2.61 893 2.87 937 3.11 979 3.33 1021 3.55 1064 3.80 1107 4.03 1151 4.27 1197 4.51 1245 4.78 1295 5.08 1347 5.38

5500 831 2.66 874 2.94 917 3.2 960 3.43 1002 3.67 1043 3.91 1085 4.16 1127 4.39 1171 4.63 1216 4.87 1264 5.14 1313 5.42 1364 5.72

5750 856 3.00 899 3.29 943 3.55 985 3.79 1026 4.04 1066 4.30 1107 4.55 1149 4.78 1192 5.00 1237 5.24 1284 5.50 - - - - - - - - - - - -

6000 883 3.38 927 3.66 970 3.93 1010 4.19 1050 4.46 1089 4.72 1129 4.95 1171 5.17 1213 5.40 1257 5.63 - - - - - - - - - - - - - - -

6250 912 3.78 956 4.07 997 4.35 1036 4.63 1074 4.90 1113 5.15 1152 5.37 1193 5.58 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 17: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 17

FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.

Air Volume cfm

Wet Indoor Coil Electric Heat Economizer

Filters Return Air Adaptor

Plate092, 102 120 150 MERV 8 MERV 13

2250 0.07 0.10 0.13 0.04 0.08 0.01 0.04 0.002500 0.09 0.12 0.15 0.04 0.11 0.01 0.05 0.002750 0.09 0.12 0.17 0.05 0.12 0.02 0.05 0.003000 0.11 0.15 0.19 0.06 0.13 0.02 0.06 0.023250 0.13 0.18 0.23 0.06 0.15 0.02 0.06 0.023500 0.14 0.21 0.26 0.09 0.15 0.03 0.07 0.043750 0.16 0.23 0.29 0.09 0.15 0.03 0.08 0.074000 0.17 0.25 0.31 0.09 0.19 0.04 0.08 0.094250 0.20 0.27 0.34 0.13 0.19 0.04 0.09 0.114500 0.21 0.30 0.37 0.14 0.22 0.04 0.09 0.124750 0.23 0.32 0.40 0.17 0.25 0.05 0.10 0.165000 0.26 0.35 0.43 0.20 0.29 0.06 0.10 0.185250 0.27 0.36 0.46 0.22 0.32 0.06 0.11 0.195500 0.29 0.40 0.50 0.25 0.34 0.07 0.12 0.225750 0.32 0.43 0.56 0.31 0.45 0.07 0.12 0.256000 0.33 0.46 0.59 0.33 0.52 0.08 0.13 0.27

BLOWER DATA

FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONSNominal

hpMaximum

hpDrive Kit Number RPM Range

2 2.3 1 590 - 8902 2.3 2 800 - 11052 2.3 3 795 - 11953 3.45 4 730 - 9703 3.45 5 940 - 12003 3.45 6 1015 - 13005 5.75 10 900 - 11355 5.75 11 1040 - 13155 5.75 12 1125 - 1425

POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure Air Volume Exhausted

in. w.g. cfm 0 3175

0.05 29550.10 26850.15 24100.20 21650.25 19200.30 14200.35 1200

Page 18: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 18

BLOWER DATA

CEILING DIFFUSERS AIR RESISTANCE - in. w.g.RTD11 Step-Down Diffuser

FD11 Flush DiffuserUnit Size Air Volume

cfm 2 Ends Open 1 Side, 2 Ends Open

All Ends & Sides Open

092 Models

2400 0.21 0.18 0.15 0.142600 0.24 0.21 0.18 0.172800 0.27 0.24 0.21 0.203000 0.32 0.29 0.25 0.253200 0.41 0.37 0.32 0.313400 0.50 0.45 0.39 0.373600 0.61 0.54 0.48 0.443800 0.73 0.63 0.57 0.51

102 & 120 Models

3600 0.36 0.28 0.23 0.153800 0.40 0.32 0.26 0.184000 0.44 0.36 0.29 0.214200 0.49 0.40 0.33 0.244400 0.54 0.44 0.37 0.274600 0.60 0.49 0.42 0.314800 0.65 0.53 0.46 0.355000 0.69 0.58 0.50 0.395200 0.75 0.62 0.54 0.43

150 Models

4200 0.22 0.19 0.16 0.104400 0.28 0.24 0.20 0.124600 0.34 0.29 0.24 0.154800 0.40 0.34 0.29 0.195000 0.46 0.39 0.34 0.235200 0.52 0.44 0.39 0.275400 0.58 0.49 0.43 0.315600 0.64 0.54 0.47 0.355800 0.70 0.59 0.51 0.39

CEILING DIFFUSER AIR THROW DATA

Model No.Air Volume

1 Effective Throw RangeRTD11 Step-Down FD11 Flush

cfm ft. ft.

092 Models

2600 24 - 29 19 - 242800 25 - 30 20 - 283000 27 - 33 21 - 293200 28 - 35 22 - 293400 30 - 37 22 - 30

102, 120 Models

3600 25 - 33 22 - 293800 27 - 35 22 - 304000 29- 37 24 - 334200 32 - 40 26 - 354400 34 - 42 28 - 37

150 Models

5600 39 - 49 28 - 375800 42 - 51 29 - 386000 44 - 54 40 - 506200 45 - 55 42 - 516400 46 - 55 43 - 526600 47 - 56 45 - 56

1 Throw is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.

Page 19: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 19

ELECTRICAL/ELECTRIC HEAT DATA 7.5 TON7.5 TON STANDARD EFFICIENCY (R-410A) KCA092S4

1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 13.1 6.1 4.4

Locked Rotor Amps 83.1 41 33Compressor 2 Rated Load Amps 13.1 6.1 4.4

Locked Rotor Amps 83.1 41 33Outdoor FanMotors (2)

Full Load Amps 2.4 1.3 1(total) (4.8) (2.6) (2)

Power Exhaust(1) 0.33 HP

Full Load Amps 2.4 1.3 1

Service Outlet 115V GFI (amps) 15 15 15Indoor BlowerMotor

Horsepower 2 2 2Full Load Amps 7.5 3.4 2.7

2 MaximumOvercurrentProtection

Unit Only 50 25 15With (1) 0.33 HP

Power Exhaust50 25 20

3 MinimumCircuitAmpacity

Unit Only 42 20 15With (1) 0.33 HP

Power Exhaust45 22 16

ELECTRIC HEAT DATAElectric Heat Voltage 208V 240V 480V 600V2 MaximumOvercurrentProtection

Unit+Electric Heat

7.5 kW 50 50 25 1515 kW 50 60 30 25

22.5 kW 70 80 40 3530 kW 90 100 50 4045 kW 150 150 80 60

3 MinimumCircuitAmpacity

Unit+Electric Heat

7.5 kW 42 42 20 1515 kW 49 55 27 22

22.5 kW 69 78 39 3130 kW 88 100 50 4045 kW 127 145 72 58

2 MaximumOvercurrentProtection

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

7.5 kW 50 50 25 2015 kW 60 60 30 25

22.5 kW 80 90 40 3530 kW 100 110 60 4545 kW 150 150 80 60

3 MinimumCircuitAmpacity

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

7.5 kW 45 45 22 1615 kW 52 58 29 23

22.5 kW 72 81 40 3230 kW 91 103 51 4145 kW 130 148 74 59

ELECTRICAL ACCESSORIESDisconnect 7.5 kW 54W56 54W56 54W56 54W56

15 kW 54W56 54W56 54W56 54W5622.5 kW 54W56 54W56 54W56 54W56

30 kW 54W57 54W57 54W56 54W5645 kW 54W57 54W57 54W56 54W56

1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Page 20: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 20

ELECTRICAL/ELECTRIC HEAT DATA 8.5 TON8.5 TON STANDARD EFFICIENCY (R-410A) kCA102S4

1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 14.5 6.4 4.8

Locked Rotor Amps 98 50 40Compressor 2 Rated Load Amps 14.5 6.4 4.8

Locked Rotor Amps 98 50 40Outdoor FanMotors (2)

Full Load Amps 2.4 1.3 1(total) (4.8) (2.6) (2)

Power Exhaust(1) 0.33 HP

Full Load Amps 2.4 1.3 1

Service Outlet 115V GFI (amps) 15 15 15Indoor BlowerMotor

Horsepower 2 2 2Full Load Amps 7.5 3.4 2.7

2 MaximumOvercurrentProtection

Unit Only 50 25 20With (1) 0.33 HP

Power Exhaust60 25 20

3 MinimumCircuitAmpacity

Unit Only 45 21 16With (1) 0.33 HP

Power Exhaust48 22 17

ELECTRIC HEAT DATAElectric Heat Voltage 208V 240V 480V 600V2 MaximumOvercurrentProtection

Unit+Electric Heat

7.5 kW 50 50 25 2015 kW 50 60 30 25

22.5 kW 70 80 40 3530 kW 90 100 50 4045 kW 150 150 80 60

3 MinimumCircuitAmpacity

Unit+Electric Heat

7.5 kW 45 45 21 1615 kW 49 55 27 22

22.5 kW 69 78 39 3130 kW 88 100 50 4045 kW 127 145 72 58

2 MaximumOvercurrentProtection

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

7.5 kW 60 60 25 2015 kW 60 60 30 25

22.5 kW 80 90 40 3530 kW 100 110 60 4545 kW 150 150 80 60

3 MinimumCircuitAmpacity

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

7.5 kW 48 48 22 1715 kW 52 58 29 23

22.5 kW 72 81 40 3230 kW 91 103 51 4145 kW 130 148 74 59

ELECTRICAL ACCESSORIESDisconnect 7.5 kW 54W56 54W56 54W56 54W56

15 kW 54W56 54W56 54W56 54W5622.5 kW 54W56 54W56 54W56 54W56

30 kW 54W57 54W57 54W56 54W5645 kW 54W57 57W57 54W56 54W56

1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Page 21: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 21

ELECTRICAL/ELECTRIC HEAT DATA 10 TON10 TON STANDARD EFFICIENCY (R-410A) KCA120S4

1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 16 7.8 5.7

Locked Rotor Amps 110 52 38.9Compressor 2 Rated Load Amps 16 7.8 5.7

Locked Rotor Amps 110 52 38.9Outdoor FanMotors (2)

Full Load Amps 2.4 1.3 1(total) (4.8) (2.6) (2)

Power Exhaust(1) 0.33 HP

Full Load Amps 2.4 1.3 1

Service Outlet 115V GFI (amps) 15 15 15Indoor BlowerMotor

Horsepower 3 3 3Full Load Amps 10.6 4.8 3.9

2 MaximumOvercurrentProtection

Unit Only 60 30 20With (1) 0.33 HP

Power Exhaust60 30 25

3 MinimumCircuitAmpacity

Unit Only 52 25 19With (1) 0.33 HP

Power Exhaust54 27 20

ELECTRIC HEAT DATAElectric Heat Voltage 208V 240V 480V 600V2 MaximumOvercurrentProtection

Unit+Electric Heat

15 kW 60 60 30 2522.5 kW 80 90 40 35

30 kW 100 110 60 4545 kW 150 150 80 6060 kW 150 175 80 70

3 MinimumCircuitAmpacity

Unit+Electric Heat

15 kW 53 59 29 2322.5 kW 72 81 40 32

30 kW 92 104 52 4145 kW 131 149 74 6060 kW 139 158 79 63

2 MaximumOvercurrentProtection

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

15 kW 60 70 35 2522.5 kW 80 90 45 35

30 kW 100 110 60 4545 kW 150 175 80 7060 kW 150 175 80 70

3 MinimumCircuitAmpacity

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

15 kW 56 62 31 2522.5 kW 75 84 42 34

30 kW 95 107 53 4345 kW 134 152 76 6160 kW 142 161 80 64

ELECTRICAL ACCESSORIESDisconnect 15 kW 54W56 54W56 54W56 54W56

22.5 kW 54W57 54W57 54W56 54W5630 kW 54W57 54W57 54W56 54W5645 kW 57W57 54W57 54W56 54W5660 kW 4 Not available 4 Not available 54W56 54W56

1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Disconnect must be field furnished.

Page 22: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 22

ELECTRICAL/ELECTRIC HEAT DATA 12.5 TON12.5 TON STANDARD EFFICIENCY (R-410A) KCA150S4

1 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 19 9.7 7.4

Locked Rotor Amps 123 62 50Compressor 2 Rated Load Amps 19 9.7 7.4

Locked Rotor Amps 123 62 50Outdoor FanMotors (2)

Full Load Amps 3 1.5 1.2(total) . (6) . (3) . (2.4)

Power Exhaust(1) 0.33 HP

Full Load Amps 2.4 1.3 1

Service Outlet 115V GFI (amps) 15 15 15Indoor BlowerMotor

Horsepower 5 5 5Full Load Amps 3.9 2 2

2 MaximumOvercurrentProtection

Unit Only 70 35 25With (1) 0.33 HP

Power Exhaust70 35 25

3 MinimumCircuitAmpacity

Unit Only 53 27 22With (1) 0.33 HP

Power Exhaust56 29 23

ELECTRIC HEAT DATAElectric Heat Voltage 208V 240V 480V 600V2 MaximumOvercurrentProtection

Unit+Electric Heat

15 kW 70 70 35 2522.5 kW 4 70 80 40 30

30 kW 4 90 100 50 4045 kW 4 125 150 80 6060 kW 150 150 80 70

3 MinimumCircuitAmpacity

Unit+Electric Heat

15 kW 53 53 27 2222.5 kW 64 73 37 30

30 kW 84 96 48 3945 kW 123 141 71 5760 kW 130 150 75 61

2 MaximumOvercurrentProtection

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

15 kW 70 70 35 2522.5 kW 4 70 80 40 35

30 kW 4 90 100 50 4045 kW 150 150 80 6060 kW 4 150 175 80 70

3 MinimumCircuitAmpacity

Unit+Electric Heatand (1) 0.33

HPPower Exhaust

15 kW 56 56 29 2322.5 kW 67 76 38 31

30 kW 87 99 50 4045 kW 126 144 72 5860 kW 133 153 77 62

ELECTRICAL ACCESSORIESDisconnect 15 kW 54W56 54W56 54W56 54W56

22.5 kW 54W57 54W57 54W56 54W5630 kW 54W57 57W57 54W56 54W5645 kW 4 Not available 4 Not available 54W56 54W5660 kW 4 Not available 4 Not available 54W57 54W56

1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Disconnect must be field furnished.

Page 23: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 23

A

C

DBD

OPTIONALOUTDOORAIR HOOD

D

1 Unit ClearanceA B C D Top

Clearancein. mm in. mm in. mm in. mmService Clearance 60 1524 36 914 36 914 60 1524

UnobstructedMinimum Operation Clearance 36 914 36 914 36 914 36 914NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface. 1 Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation.

UNIT CLEARANCES - INCHES (MM)

ELECTRIC HEAT CAPACITIES

Volts Input

7.5 kW 15 kW 22.5 kW 30 kW 45 kW 60 kWkW

Input Btuh

Output No. of Stages

kW Input

Btuh Output

No. of Stages

kW Input

Btuh Output

No. of Stages

kW Input

Btuh Output

No. of Stages

kW Input

Btuh Output

No. of Stages

kW Input

Btuh Output

No. of Stages

208 5.6 19,100 1 11.3 38,600 1 16.9 57,700 2 22.5 76,800 2 33.8 115,300 2 45.0 153,600 2

220 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2

230 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

240 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

440 6.9 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2

460 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

480 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

550 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2

575 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

600 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

Page 24: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 24

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS - FIELD INSTALLED

COMMERCIAL TOUCHSCREEN THERMOSTATIntuitive Touchscreen Interface - Two Stage Heating / Two Stage Cooling Conventional or Heat Pump - Seven Day Programmable - Four Time Periods/Day - Economizer Output - Title 24 Compliant - ENERGY STAR® Qualified - Backlit Display - Automatic Changeover

C0STAT02AE1L(14W81)

Sensors For Touchscreen Thermostat1 Remote non-adjustable wall mount 20k temperature sensor ......................... C0SNZN01AE2-

(47W36)1 Remote non-adjustable wall mount 10k averaging temperature sensor ........ C0SNZN73AE1-

(47W37)1 Remote non-adjustable duct mount temperature sensor ............................... C0SNDC00AE1-

(19L22)Outdoor temperature sensor ............................................................................ C0SNSR03AE1-

(X4148)Accessories For Touchscreen Thermostat

Locking cover (clear) ........................................................................................ C0MISC15AE1-(39P21)

1 Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1-, (2) C0SNZN73AE1-, (2) C0SNZN01AE1- and (1) C0SNZN73AE1-, (4) C0SNZN01AE1-, (3) C0SNZN01AE1- and (2) C0SNZN73AE1.

DIGITAL NON-PROGRAMMABLE THERMOSTATSIntuitive Interface - Automatic Changeover - Simple Up and Down Temperature ControlTwo-stage heating / cooling conventional systems ....................................... C0STAT10AE1L

(13K98)Sensor For Digital Non-Programmable Thermostats AboveRemote wall mounted temperature sensor....................................................... C0SNZN00AE1-

(26K57)Intuitive Interface - Automatic Changeover - Backlit Display - Simple Up and Down Temperature ControlOne-stage heating / cooling conventional systems .......................................... C0STAT12AE1L

(51M32)Sensor For Digital Non-Programmable Thermostats AboveOutdoor temperature sensor ............................................................................ C0SNSR04AE1-

(X2658)Accessories For Digital Non-Programmable Thermostats AboveOptional wall mounting plate ............................................................................ C0MISC17AE1-

(X2659)

OUTDOOR SOUND DATA

Unit Model Number

Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ 1 Sound RatingNumber (dB)125 250 500 1000 2000 4000 8000

092, 102 and 120 76 79 84 83 79 73 66 88

150 77 80 85 84 79 74 66 88

Note - The octave sound power data does not include tonal corrections. 1 Sound Rating Number according to AHRI Standard 370-2001.

Page 25: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 25

WEIGHT DATA

Model NumberNet Shipping

lbs. kg lbs. kg092 Base Unit 942 427 1027 466092 Max. Unit 1099 499 1184 537102 Base Unit 962 436 1047 475102 Max. Unit 1119 508 1204 546120 Base Unit 1002 455 1087 493120 Max. Unit 1166 529 1251 567150 Base Unit 1092 495 1177 534150 Max. Unit 1256 570 1341 608

OPTIONS / ACCESSORIES

Model Number Shipping Weightlbs. kg

CEILING DIFFUSERSStep-Down

RTD11-95 88 40RTD11-135 205 93RTD11-185 392 178

FlushFD11-95 75 34

FD11-135 174 79FD11-185 289 131

Transitions LASRT08/10 30 14LASRT10/12 32 15

LASRT15 36 16ECONOMIZER / OUTDOOR AIR / EXHAUSTEconomizerEconomizer Dampers 55 25Barometric Relief Dampers (downflow) 8 4Barometric Relief Damper Hood (downflow) 25 11Outdoor Air Hood (downflow) 23 10Outdoor Air DampersOutdoor Air Damper Section (downflow) - Automatic 9 4Outdoor Air Damper Section (downflow) - Manual 2 1Outdoor Air Damper Hood (downflow) 9 4Power Exhaust 31 14ELECTRIC HEAT7.5 kW 50 2315 kW 50 2322.5 kW 57 2630 kW 57 2645 kW 59 2760 kW 68 31ROOF CURBS - CLIP CURBDownflow8 in. height 89 4014 in. height 109 4918 in. height 126 5724 in. height 150 68ROOF CURBS - STANDARDDownflow8 in. height 91 4114 in. height 115 5224 in. height 153 69PACKAGINGLTL Packaging (less than truck load) 105 48

Page 26: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 26

DIMENSIONS - INCHES (mm)

Model No.

CORNER WEIGHTS CENTER OF GRAVITYAA BB CC DD EE FF

Base Max. Base Max. Base Max. Base Max. Base Max. Base Max.lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm in. mm in. mm

092 236 107 282 128 212 96 246 112 231 105 263 119 263 119 308 140 46.5 1181 45.5 1181 24.5 622 25.5 648102 241 109 287 130 217 98 250 114 236 107 268 122 268 122 314 142 46.5 1181 45.5 1181 24.5 622 25.5 648120 251 114 299 135 226 102 261 118 246 111 279 127 279 127 327 148 46.5 1181 45.5 1181 24.5 622 25.5 648150 274 124 322 146 246 112 281 128 268 121 301 136 305 138 352 160 46.5 1181 45.5 1181 24.5 622 25.5 648

Base Unit - The unit with NO INTERNAL OPTIONS.Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit or high static power exhaust.

END VIEW

60-1/8(1527)

58-1/8

46-7/8(1191)

3-1/2(89)

43-3/8(1102)

(1476)

SIDE VIEW(Horizontal Openings)

HORIZONTALRETURN AIR

OPENING

HORIZONTALSUPPLY AIR

OPENING

CONDENSATEDRAIN (BACK) 5-3/8

(137)6-1/8(156)

12-1/8(308)

15-1/2(394)

1-5/8(41)

31-1/2(800)

30(762)

66-3/8(1686)

15-1/2(394)

30(762)

7 (178)

BASE60-1/8 (1527) CENTER OF

GRAVITY

TOP VIEW

BOTTOM RETURNAIR OPENING

24(610)

10-3/4(273)

5-5/8(143)

6-1/8(156)

6-1/8(156)

6-5/8(168)

28(711)

27(686)

20(508)

AA

DD

EEFF

BOTTOMCONDENSATE

101-1/4(2572)

BB

CC

BOTTOM SUPPLYAIR OPENING

34-7/8(886)

BASE

7 (178)

BOTTOMPOWER ENTRY5-1/2 (140) Dia.

SIDE VIEW

LIFTING HOLES(FOR RIGGING)

101-1/4(2572)

99-1/4(2521)OPTIONAL DISCONNECT

(FACTORY INSTALLED)

1(25)

34-7/8(886)

5-3/8(137)

46-7/8(1191)

FORKLIFT SLOTS(BOTH SIDES)

CONDENSATEDRAIN (FRONT)

ELECTRICINLETS

Page 27: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 27

ACCESSORY DIMENSIONS - INCHES (MM)

OUTDOOR AIR HOOD DETAIL

EXHAUST AIR HOOD(Furnished, Field Installed)

OUTDOOR AIR HOOD(Furnished with Economizer or

Outdoor Air Damper)

21−3/8(543)

Page 28: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 28

ACCESSORY DIMENSIONS - INCHES (MM)

HORIZONTAL BAROMETRIC

(On Unit)

(984)38-3/4

(762)

(394)

BACK VIEW

HORIZONTALSUPPLY AIR

OPENING

6-1/8(156)

15-1/2

30

(Field Installed)

27-3/4(705)

END VIEW

6(152)

4-1/8(105)

19-3/4(502)

This opening not used in Horizontal

Applicationswith

Economizer

HORIZONTAL ECONOMIZER APPLICATION(with Optional Horizontal Barometric Relief Dampers and Horizontal Discharge Kit)

NOTE - Return Air Duct and Transition must be supported.

HORIZONTAL RELIEF HOOD DIMENSIONSWidth - 31-5/8 in. (803 mm)Height - 14-1/2 in. (368 mm)

RETURN AIR DUCT(Field Fabricated - Must be sized to

accommodate Horizontal Barometric ReliefHood and Return Air Requirements)

TOP VIEW

DUCT TRANSITION(Field fabricated and

installed on unit)

ECONOMIZERDAMPERS

RETURNAIR

INLETSUPPLYAIR

OUTLET

RETURN AIR DUCT INLET(Field Fabricated - Must be sized to

accommodate Horizontal BarometricRelief Hood and Return Air Requirements)

RELIEF DAMPERS(Optional - Must be Ordered Extra and

Field Installed on Field fabricatedReturn Air Duct)

RETURN AIRDUCT TRANSITION(Field fabricated and

installed on unit)

OUTDOOR AIR HOOD(Furnished with Economizer)

EXHAUSTAIR

OUTDOORAIR

HORIZONTALRETURN AIR

OPENING

SUPPLY AIR DUCT(Field Provided)

21-3/8(543)

HORIZONTALBAROMETRIC RELIEF DAMPERS AND HOOD

OPTIONAL RETURN AIR OPENINGWITH ECONOMIZER AND HORIZONTAL

DISCHARGE KIT (required)

HORIZONTAL BAROMETRIC RELIEF DAMPERS(Field installed in horizontal return air duct adjacent to unit)

1 13

(300)

14-1/2(368)

FRONT VIEW SIDE VIEW

31-5/8 (803)6-1/2(165)1 29-1/2 (749)

1 NOTE - Opening size required in return air duct.

RETURN AIR

Page 29: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 29

ACCESSORY DIMENSIONS - INCHES (MM)

CLIP CURBS - DOUBLE DUCT OPENING

DETAIL ROOF CURB

FACTORY INSTALLEDPERIMETER WOODNAILER STRIP

1-13/16(46)

8 (203)14 (356)18 (457)24 (610)

2 (51)

1-13/16(46)

54-1/4(1378)

50-5/8(1286)

1-13/16(46)

NOTE - Roof deck may be omitted within confines of curb.

RETURNOPENING

SUPPLYOPENING

95-3/8(2423)

91-3/4(2330)

7-1/8(181)

8 (203)14 (356)18 (457)24 (610)

21-3/4(552)

29-3/4(756)

8-1/2(216)

26-3/4(679)

29-3/4(756)

TYPICAL FLASHING DETAIL FOR ROOF CURB

ROOF CURB(Extends around entire

perimeter of unit)

FIBERGLASSINSULATION

(Furnished)COUNTER FLASHING(Field Supplied)

BASE BOTTOM

RIGID INSULATION(Field Supplied)

ROOFINGMATERIAL

CANT STRIP(Field Supplied)

PACKAGEDUNIT

NAILER STRIP(Furnished)

Page 30: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 30

ACCESSORY DIMENSIONS - INCHES (MM)

STANDARD ROOF CURBS - DOUBLE DUCT OPENING

1-13/16(46)

54-1/4(1378)

50-5/8(1286)

1-13/16(46)

NOTE - Roof deck may be omitted within confines of curb.

RETURNOPENING

SUPPLYOPENING

95-3/8(2423)

91-3/4(2330)

7-1/8(181)

8 (203)14 (356)24 (610)

21-3/4(552)

29-3/4(756)

8-1/2(216)

26-3/4(679)

29-3/4(756)

TYPICAL FLASHING DETAIL FOR ROOF CURB

ROOF CURB(Extends around entire

perimeter of unit)

FIBERGLASSINSULATION

(Furnished)COUNTER FLASHING(Field Supplied)

BASE BOTTOM

RIGID INSULATION(Field Supplied)

ROOFINGMATERIAL

CANT STRIP(Field Supplied)

PACKAGEDUNIT

NAILER STRIP(Furnished)

DETAIL ROOF CURB

1-13/16(46)

FACTORY INSTALLEDPERIMETER WOODNAILER STRIP

2 (51)

8 (203)14 (356)24 (610)

Page 31: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 31

ACCESSORY DIMENSIONS - INCHES (MM)

ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS

8 (203)

2 (51)

17-3/4(451)

27-3/4 (705)LASRT10/1235-3/4 (908)LASRT15

31 (787)LASRT10/1239 (991)LASRT15

LASRT10/12 & LASRT15 RECTANGULAR TRANSITIONS(for 102 thru 150 models with FD11−135−185, RTD11−135−185 Diffusers)

30(762)

1−1/2(38)Typ.

20 IN. (508 mm)Diameter

31(787)

8(203)

30(762)

1−1/2(38)Typ.

LASRT08/10 ROUND TRANSITIONS(for 092 models with FD11−95, RTD11−95 Diffusers)

2 (51)

(102)

SUPPLYAIR

OPENING

TOP VIEW

RETURNAIR

OPENING

31-1/2 (800)LASRT08/10LASRT10/1239-1/2 (1003)LASRT15

30-1/2(775)

30-1/2(775)

4

Page 32: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 32

ACCESSORY DIMENSIONS - INCHES (MM)

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERSSTEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER

L A

J

C

HH

DG

G

FE

B

K

2 (51)

A

C

HH

DG

G

FE

B

2 (51)

Model Number RTD11-95A in. 47-5/8

mm 1159B in. 29-5/8

mm 752C in. 14-3/8

mm 365D in. 27-1/2

mm 699E in. 45-1/2

mm 1158F in. 22-1/2

mm 572G in. 11-1/2

mm 292H in. 13-3/4

mm 349J in. 45-1/2

mm 1156K in. 27-1/2

mm 699L in. 8-1/8

mm 206Duct Size in. 20 round

mm 508 round

Model Number FD11-95A in. 47-5/8

mm 1159B in. 29-5/8

mm 752C in. 16-5/8

mm 422D in. 27

mm 686E in. 45

mm 1143F in. 22-1/2

mm 572G in. 11-1/4

mm 286H in. 13-1/2

mm 343Duct Size in. 20 round

mm 508 round

Page 33: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 33

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERSRESUFFID GNILIEC HSULFRESUFFID GNILIEC NWOD-PETS

L

A

C

HJG

FE

B

M

N

K

DG

2 (51)

A

C

HJG

FE

B

K

DG

2 (51)

ACCESSORY DIMENSIONS - INCHES (MM)

Model Number RTD11-135 RTD11-185A in. 47-5/8 47-5/8

mm 1210 1210B in. 35-5/8 47-5/8

mm 905 1210C in. 20-5/8 24-5/8

mm 524 625D in. 33-1/2 45-1/2

mm 851 1156E in. 45-1/2 45-1/2

mm 1156 1156F in. 4-1/2 4-1/2

mm 114 114G in. 18 18

mm 457 457H in. 2-1/2 2-1/2

mm 64 64J in. 28 36

mm 711 914K in. 2-3/4 4-3/4

mm 70 121L in. 45-1/2 45-1/2

mm 1156 1156M in. 33-1/2 45-1/2

mm 851 1156N in. 9-1/8 10-1/8

mm 232 257Duct Size in. 18 x 28 18 x 36

mm 457 x 711 457 x 914

Model Number FD11-135 FD11-185A in. 47-5/8 47-5/8

mm 1210 1210B in. 35-5/8 47-5/8

mm 905 1210C in. 23-1/4 29-1/4

mm 591 743D in. 33 45

mm 838 1143E in. 45 45

mm 1143 1143F in. 4-1/2 4-1/2

mm 114 114G in. 18 18

mm 457 457H in. 2-1/4 2-1/4

mm 57 57J in. 28 36

mm 711 914K in. 2-1/2 4-1/2

mm 64 114Duct Size in. 18 x 28 18 x 36

mm 457 x 711 457 x 914

Page 34: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 34

Page 35: Paquete Lenox

Landmark™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 35

Page 36: Paquete Lenox

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2010 Lennox Industries, Inc.

Visit us at www.lennox.com

For the latest technical information, www.lennoxcommercial.com

Contact us at 1-800-4-LENNOX

REVISIONS

Sections Description of Change

Blower Data Blower tables updated.