Test Report
CONFIDENTIAL
Report: BMT/MTP/F13161
Report on the testing of a doorset to BS 6375 Part 1
Issue date: February 2014
Opinions and interpretations expressed herein are outside the scope of UKAS accreditation. This document is confidential and remains the property of Chiltern
International Fire Ltd. The legal validity of this report can only be claimed on the presentation of the complete report.
Page 1 of 7
![Page 2: Page 1 of 7 - Pooja · Exposure category BS 6375: Part 1: 2009 1200 Air leakage at 50pa was 8.8m3/h positive pressure and 7.8m3/h negative pressure. The perimeter length of opening](https://reader034.fdocuments.net/reader034/viewer/2022042208/5eab323740d5bb15195350e6/html5/thumbnails/2.jpg)
The legal validity of this report can only be claimed on presentation of the complete report
Client: Stayfix Ref: BMT/MTP/F13161
Page 2 of 7
BM TRADA – the new name for Chiltern International Fire Ltd From July 1st 2013, Chiltern International Fire Ltd commenced trading under the name of its parent company BM TRADA and at the same time adopted a brand new visual identity. Historically, the group has delivered its services through a number of individual companies: BM TRADA Certification Ltd, TRADA Technology Ltd, Chiltern International Fire Ltd (including Chiltern Dynamics) and a network of international offices. Both BM TRADA Group and these individual companies will now trade under the same name - BM TRADA - and adopt the new visual identity. To coincide with this change, our Technical Reports, Test Reports, Products Assessments, company stationery and marketing collateral have been re-designed to carry the new branding and visual identity. The validity of all documents previously issued by the individual companies including certificates, test reports and product assessments is unaffected by this change and a letter to this effect will be available to download from our website www.bmtradagroup.com. About BM TRADA. With origins dating back to 1934, we have a deep history and services which are highly valued by our customers. We offer independent certification, testing, inspection, training and technical services around the world. In all these areas we continue to use industry-leading experts in their chosen fields to develop and deliver services – an ethos that has been at the heart of our approach since we began. A recent review of our businesses and customers revealed that the individual identities sometimes make communications confusing, and that in an already complex business area, clarity and simplicity in communications is rare, but valued. It also revealed that a single identity and combined offer would help us strengthen our appeal. With this in mind, we brought the companies together under the name BM TRADA and took the opportunity to create a fresh new visual identity. We have modernised our image and combined our strengths. However, our values, our people and the integrity of our services remain the same. I hope you will welcome these changes and the improvements they will bring. Jon Osborn Chief Operating Officer
![Page 3: Page 1 of 7 - Pooja · Exposure category BS 6375: Part 1: 2009 1200 Air leakage at 50pa was 8.8m3/h positive pressure and 7.8m3/h negative pressure. The perimeter length of opening](https://reader034.fdocuments.net/reader034/viewer/2022042208/5eab323740d5bb15195350e6/html5/thumbnails/3.jpg)
Page 3 of 7
Results of Test:BMT/MTP/F13161
Stayfix 53 Park Royal Road
London NW10 7LQ
This document confirms that performance testing was conducted on 16 December 2013. Testing was conducted to the following standard:
BS 6375 Part 1: 2009 Performance of windows and doors – Part 1: Classification for weathertightness and guidance on selection and specification.
The following results were achieved:
Product tested Stayfix Vision Folding Doorset
Summary of testing procedure Result
Test Standard Classification Standard
Air permeability BS EN 1026: 2000 BS EN 12207: 2000 600Pa (Class 4)
Watertightness BS EN 1027: 2000 BS EN 12208: 2000 600Pa (Class 9A)
Wind resistance BS EN 12211: 2000 BS EN 12210: 2000 1200 Pa (Class A2)
Exposure category BS 6375: Part 1: 2009 1200
Air leakage at 50pa was 8.8m
3/h positive pressure and 7.8m
3/h negative pressure. The perimeter
length of opening light was 14.0m.
The results relate only to the specimens tested, as detailed in the technical specification
Kyle Morris - Senior Technical Officer Vincent Kerrigan - Technical Manager Issue date: 31st January 2014
BM TRADA
Chiltern House, Stocking Lane, Hughenden Valley, High Wycombe, HP14 4ND, United Kingdom
Tel: 01494 569800 Fax: 01494 564895
Web: www.bmtradagroup.com Email: [email protected]
This document is confidential and remains the property of Chiltern International Fire Ltd, trading as BM TRADA
![Page 4: Page 1 of 7 - Pooja · Exposure category BS 6375: Part 1: 2009 1200 Air leakage at 50pa was 8.8m3/h positive pressure and 7.8m3/h negative pressure. The perimeter length of opening](https://reader034.fdocuments.net/reader034/viewer/2022042208/5eab323740d5bb15195350e6/html5/thumbnails/4.jpg)
The legal validity of this report can only be claimed on presentation of the complete report
Client: Stayfix Ref: BMT/MTP/F13161
Page 4 of 7
Technical specification document
No: BMT/MTP//F13161
Test For: Stayfix, 53 Park Royal Road, London, NW10 7LQ
Performance testing to BS 6375: Part 1: 2009 was conducted on your doorset on 16 December 2013. The technical specification is detailed below. The specimen was delivered to BM TRADA laboratory on 16 September 2013.
Description of construction The specimen was identified as a Stayfix Vision Folding Doorset. The overall frame dimensions were 3105mm wide x 2135mm high x 70mm deep. The master leaf dimensions were 1020mm wide x 2045mm high x 70mm thick. The 2No. slave leafs dimensions were 1002mm wide x 2045mm high x 70mm thick. The specimen was locked with a removable key.
Master door leaf
Material/type Dimensions (mm)
Lock stile Stayfix aluminium profile (Ref. F1102)* 70 x 58
Lock stile profiles
Stayfix aluminium profile (Ref. F1105)* clipped onto inside edge of lock stile
15 x 17
Stayfix aluminium profile (Ref. F1105)* clipped onto internal edge of lock stile
23 x 20
Hinge stile Stayfix aluminium profile (Ref. F1103)* 70 x 58
Rails Stayfix aluminium profile (Ref. F1102)* 70 x 58
Rebate Single type 68 x 14
Joints Mitred with Stayfix corner plates (Ref. F1001)* and (Ref. F1002)*
-
1No. corner cleat (Ref. F1004)* fixed with 2No. M4 x 9 socket screw
-
Adhesive Polyurethane adhesive* -
* As stated by client, not checked by laboratory
2No. Slave door leafs
Material/type Dimensions (mm)
Stiles Stayfix aluminium profile (Ref. F1103)* 70 x 58
Rails Stayfix aluminium profile (Ref. F1102)* 70 x 58
Rebate Single type on rails and frame stile only 68 x 14
Joints Mitred with Stayfix corner plates (Ref. F1001)* and (Ref. F1002)*
-
1No. corner cleat (Ref. F1004)* fixed with 2No. M4 x 9 socket screw
-
Adhesive Polyurethane adhesive* -
* As stated by client, not checked by laboratory
![Page 5: Page 1 of 7 - Pooja · Exposure category BS 6375: Part 1: 2009 1200 Air leakage at 50pa was 8.8m3/h positive pressure and 7.8m3/h negative pressure. The perimeter length of opening](https://reader034.fdocuments.net/reader034/viewer/2022042208/5eab323740d5bb15195350e6/html5/thumbnails/5.jpg)
The legal validity of this report can only be claimed on presentation of the complete report
Client: Stayfix Ref: BMT/MTP/F13161
Page 5 of 7
Door frame
Material/type Dimensions (mm)
Head & jambs Stayfix aluminium profile (Ref. F1101)* 70 x 54
Rebate Single type 68 x 15
Threshold Stayfix aluminium profile (Ref. F1101)* fixed to cill with 5No. 3.8 x 38 self tapping screws
70 x 54
Cill Stayfix aluminium profile (Ref. 10853)* 150 x 30
Joints Butt joint fixed with Stayfix fixing block (Ref. F1027)*, 1No. M5 x 45 and 1No. M5 x 12 machine screws
-
Adhesive Multi Purpose silicone* -
*As stated by client, not checked by laboratory
Perimeter sealing details
Make/type Size (mm) Location
Leaf Edges
Master 1No. Central Extrusions (Ref. PG010)*
10 wide On rebate upstand on lock side stile and top rail only
2No. Central Extrusions (Ref. FG001/FG002)*
7 x 13 On rebate platform of hinge side stile only
Slave 1 1No. Central Extrusions (Ref. PG010)*
10 wide On rebate upstand on lock stile and top rail only
2No. Central Extrusions (Ref. FG001/FG002)*
7 x 13 On rebate platform of stiles only
Slave 2 1No. Central Extrusions (Ref. PG010)*
10 wide On rebate upstand on frame side stile and top rail only
2No. Central Extrusions (Ref. FG001/FG002)*
7 x 13 On rebate platform of hinge side stile only
Frame reveal 1No. Central Extrusions (Ref. PG010)*
10 wide On rebate upstand
Threshold 1No. Central Extrusions (Ref. PG010)*
10 wide On rebate upstand
Seal continuity Interrupted by hardware - -
*As stated by client, not checked by laboratory
![Page 6: Page 1 of 7 - Pooja · Exposure category BS 6375: Part 1: 2009 1200 Air leakage at 50pa was 8.8m3/h positive pressure and 7.8m3/h negative pressure. The perimeter length of opening](https://reader034.fdocuments.net/reader034/viewer/2022042208/5eab323740d5bb15195350e6/html5/thumbnails/6.jpg)
The legal validity of this report can only be claimed on presentation of the complete report
Client: Stayfix Ref: BMT/MTP/F13161
Page 6 of 7
Hardware
Make/type Size (mm) Fixing details (dimensions in mm)
Hinges 1No. Stayfix roller hinge (Ref. F1005)* for master top
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in master leaf channel 3No. M5 x 12 machine screws into receiving block in slave leaf 1 channel
1No. Stayfix fold hinge (Ref. F1007)* for master middle
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in master leaf channel 3No. M5 x 12 machine screws into receiving block in slave leaf 1 channel
1No. Stayfix roller hinge (Ref. F1006)* for master bottom
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in master leaf channel 3No. M5 x 12 machine screws into receiving block in slave leaf 1 channel
1No. Stayfix fold hinge (Ref. F1007)* for slave 1 top
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in slave 1 leaf channel 3No. M5 x 12 machine screws into receiving block in slave leaf 2 channel
1No. Stayfix fold hinge with pad handle (Ref. F1007)* for slave 1 middle
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in slave 1 leaf channel 3No. M5 x 12 machine screws into receiving block in slave leaf 2 channel
1No. Stayfix fold hinge (Ref. F1007)* for slave 1 bottom
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in slave 1 leaf channel 3No. M5 x 12 machine screws into receiving block in slave leaf 2 channel
1No. Stayfix outer top hinge (Ref. F1025)* for slave 2 top
155 x 35 blade size
3No. M5 x 12 machine screws into receiving block in slave 2 leaf channel 6No. M5 x 12 machine screws into receiving block in frame channel
1No. Stayfix outer hinge (Ref. F1010)* for slave 2 middle
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in slave 2 leaf channel 5No. M5 x 12 machine screws into receiving block in frame channel
1No. Stayfix outer hinge (Ref. F1010)* for slave 2 bottom
115 x 35 blade size
3No. M5 x 12 machine screws into receiving block in slave 2 leaf channel 5No. M5 x 12 machine screws into receiving block in frame channel
Locking mechanism
Fuhr 3 Point Hook Lock (Ref. 621)*
2015 x 15 11No. 3.8 x 45 self tapping screws
Keeps Upper & lower
Stayfix (Ref. 631-P001)*
26 x 100 2No. M5 x 12 machine screws into receiving block in frame channel
Centre Stayfix (Ref. 631-P)* 26 x 187 3No. M5 x 12 machine screws into receiving block in frame channel
* As stated by client, not checked by laboratory
![Page 7: Page 1 of 7 - Pooja · Exposure category BS 6375: Part 1: 2009 1200 Air leakage at 50pa was 8.8m3/h positive pressure and 7.8m3/h negative pressure. The perimeter length of opening](https://reader034.fdocuments.net/reader034/viewer/2022042208/5eab323740d5bb15195350e6/html5/thumbnails/7.jpg)
The legal validity of this report can only be claimed on presentation of the complete report
Client: Stayfix Ref: BMT/MTP/F13161
Page 7 of 7
Hardware continued
Make/type Size (mm) Fixing details (dimensions in mm)
Handles Window Ware Core lever (Ref. HDL60511B)*
120 lever length
2No. M5 x 85 machine screws
Cylinder Yale (Ref. 45-10-45)* 100 length
1No. M5 x 45 machine screw
Slave leaf shootbolt mechanism
Stayfix (Ref. F118),* Stayfix (Ref. 1015/B)* and Titon (Ref. 1032)* gearbox
2010 length
Slotted into profile and fixed with 2No. 5 x 40 machine screw
Shootbolt handle Titon (Ref. 1033)* 135 lever length
Integral to shootbolt mechanism and fixed with 2No. M5 x 50 machine screws
* As stated by client, not checked by laboratory
Glazing
Make/type/size (mm) Location (dimensions in mm)
Glass type & configuration
4 glass, 20 spacer, 4 glass -
Overall size 907 wide x 1950 high -
Sight size 884 wide x 1927 high -
Bead Stayfix aluminium profile 16 x 26 (Ref. F1109)*
Internally beaded
Bead fixing Clipped into profile -
Packers 1No. Stayfix 60 x 32 x 3 plastic packer (Ref. PAK003)*
In all corners
Gaskets Central Extrusions (Ref. PG002)* Between glass and rebate upstand
Central Extrusions (Ref. PG001)* Between glass and bead
Sealants Silicone To retain packers in position
* As stated by client, not checked by laboratory