Asset: P.S. 1 - BROOKLYN, 309 47 STREET, , New York, 11220 Inspection Id Inspection Type Time In Last Edited SA : K001 Architectural - Senior 2018-12-27 9:09 AM 2019-06-04 2:26 PM AA : K001 Architectural - Associate 2018-12-27 8:47 AM 2018-12-27 5:34 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment The following components are inaccessible: 2nd Floor Shower Room due to Storage. Principal(s) Information Principal Name Arlene Ramos Organization P.S. 1 - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? Yes Summary of Principal's Feedback A Principal questionnaire was returned with the following comments: 1. The air conditioning system does not function properly. 2. Ventilation system in the building needs to be serviced. Custodian Was not present Fireman Noel Roman Building Square Footage 91000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 43 Comments on the Year Built 1965 Student Population 1076 Staff Population 139 Weather Fair Facade Photo 46th Street-South View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 K001 PB/A&W Print Date: 6/21/2019 Page 1 of 37

Transcript of NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior...

Page 1: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Asset: P.S. 1 - BROOKLYN, 309 47 STREET, , New York, 11220

Inspection Id Inspection Type Time In Last Edited

SA : K001 Architectural - Senior 2018-12-27 9:09 AM 2019-06-04 2:26 PM

AA : K001 Architectural - Associate 2018-12-27 8:47 AM 2018-12-27 5:34 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment The following components are inaccessible: 2nd Floor Shower Roomdue to Storage.

Principal(s) Information

Principal Name Arlene Ramos

Organization P.S. 1 - Brooklyn

Did you meet with this Principal? No

Did this Principal provide feedback? Yes

Summary of Principal's Feedback A Principal questionnaire was returned with the following comments:1. The air conditioning system does not function properly. 2.Ventilation system in the building needs to be serviced.

Custodian Was not present

Fireman Noel Roman

Building Square Footage 91000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Number of Classrooms 43

Comments on the Year Built 1965

Student Population 1076

Staff Population 139

Weather Fair

Facade Photo

46th Street-South View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 1 of 37

Page 2: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Main Entrance Photo

Facade A - Entry Court

Roof Photo

Roof 1-North View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Partial Interior Door replacement (Auditorium, Cafeteria,Classrooms)

Year: 2017

Systems: Boiler/Mechanical Systems upgrade, Partial Exterior Doorreplacement

Year: 2016

Systems: Chimney Liner replacement

Year: 2015

Systems: Exterior Modernization including full Windows, Guards,Lintels replacement; full Parapets, Coping, Flashing, RoofBarrier replacement; full Bulkhead Windows and Doorsreplacement; full Exterior Wall repointing and graffitiremoval; Partial Exterior Doors replacement and Transomrepair

Year: 2014

Systems: Vinyl Floor replacement 1st Floor Corridor; PartialExterior Door Repairs

Year: 2013

Systems: Partial Interior Glazed Block repairs at Gymnasium

Year: 2011

Systems: Exterior Modernization including full Roof replacement atRoof 1, Flashing, Parapets, Coping, Leaders and Gutters,Bulkhead Doors replacement; full Plaza Deckreplacement; Partial Exterior Wall repairs

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 2 of 37

Page 3: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Roof 1, Flashing, Parapets, Coping, Leaders and Gutters,Bulkhead Doors replacement; full Plaza Deckreplacement; Partial Exterior Wall repairs

Year: 2010

Systems: Auditorium upgrades including new Seating, Curtains,Vinyl Flooring, Wall repainting, Soundproof paneling, onenew HC Lift at Stage; second new HC lift at Foyer intoAuditorium and Gymnasium, Sidewalk replacement at46th and 47th Streets

Year: 2007

Systems: Library upgrades

Year: 2004

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? No

Are SOME floors other than the 1st floor and basement accessible through compliantmeans?

No

Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs

Yes

For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes

Boys and Girls or Unisex accessible toilets exist on the 1st floor? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware No No

Interior Corridors and Lobbies Yes

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms Room B15 Yes No Not on Accessible Route

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 3 of 37

Page 4: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route

No Yes

Cafeteria Basement Yes No Not on Accessible Route No Yes

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms No

Gymnasium 1st Floor Yes No Not on Accessible Route No Yes

Library Room 236 Yes No Not on Accessible Route

Main Office Room 135 Yes No Not on Accessible Route

Multi-purpose Room No

Nurse's Room Room 131 Yes No Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

COPING Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 4 of 37

Page 5: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

COPING

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 4 - Between Fair and Poor

Deficiency ROLL-UP DOOR: DETERIORATED DOOR - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 5 of 37

Page 6: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C-Exit 11

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B-Exit 6

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 6 of 37

Page 7: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

DOORS Inspected

TRANSOM/SIDE LIGHT

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Other

Replacement Quantity 35,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 35,000

Instance Quantity Uom S.F.

Deficiency STUCCO CEMENT SURFACE: CRACKS, SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 7 of 37

Page 8: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

EXTERIOR WALLS Inspected

Roof Plan reference

Elevation

Deficiency Quantity 1,300

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade E

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency CONCRETE: MINOR CRACKS/SPALLING

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 8 of 37

Page 9: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

EXTERIOR SOFFITS

Elevation

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 5,500

Replacement Uom C.F.

InspectedInstance on All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 5,500

Instance Quantity Uom C.F.

Deficiency No deficiencies recorded

PLAZA DECK Inspected

InspectedInstance on Pavers: Above Cafeteria

Instance Condition 1 - Good

Instance Quantity 5,000

Instance Quantity Uom S.F.

Installation Year 2010

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOF Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 9 of 37

Page 10: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

ROOF

Roofing Inspected

Replacement Quantity 30,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: Roof 2-4

Instance Condition 3 - Fair

Instance Quantity 9,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1995

Source of Installation Custodial Staff

Deficiency BUILT-UP: FLASHING: CAP FLASHING DAMAGED

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 2

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 10 of 37

Page 11: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency BUILT-UP: ROOFING: LOSS OF GRAVEL

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action INSTALL NEW GRAVEL

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 2

Violations No violations recorded.

Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Built-Up: Roof 2-4

Deficiency Quantity 9,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

InspectedInstance on Modified Bitumen: Roof 1

Instance Condition 2 - Between Good and Fair

Instance Quantity 21,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2010

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOFING DRAINS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 11 of 37

Page 12: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

ROOF

Roofing

ROOFING DRAINS

Condition 3 - Fair

Deficiency DETERIORATED

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 2

Violations No violations recorded.

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 3 - Fair

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: CMUCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 12 of 37

Page 13: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Purpose of Action LEVEL 2

Deficiency Photo1

BH3

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

SKYLIGHT/ROOF VENT Inspected

Material Type(s) Glass

Condition 3 - Fair

Deficiency BROKEN GLASS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

SK

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 13 of 37

Page 14: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

ROOF Inspected

Specialties Inspected

SKYLIGHT/ROOF VENT Inspected

Violations No violations recorded.

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Does not Exist

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B-Exit 6

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 10,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 14 of 37

Page 15: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

EXTERIOR

WINDOWS

WINDOWS

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 1 - Good

Instance Quantity 10,000

Instance Quantity Uom S.F.

Installation Year 2014

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement-MER

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement-MER

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Basement-Storage Room, Electrical Room

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 15 of 37

Page 16: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo1

Basement-Storage Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Inspected

InspectedInstance on 1st Floor (459 Seats)

Ceiling

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 1st Floor (459 Seats)

Fixed Seating

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor (459 Seats)

Stage

InspectedInstance on 1st Floor (459 Seats)

Stage Inspected

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency DAMAGED FLOOR

Deficiency Location/Instance Near radiator

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 16 of 37

Page 17: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

AUDITORIUM

Stage

Stage

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near radiator

Violations No violations recorded.

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 1st Floor (459 Seats)

Condition 3 - Fair

Deficiency WORN/DETERIORATED

Deficiency Location/Instance Left side of Stage

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Left side of Stage

Violations No violations recorded.

Walls

InspectedInstance on 1st Floor (459 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor (459 Seats)

CAFETERIA Inspected

InspectedInstance on Basement

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 17 of 37

Page 18: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

CAFETERIA

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Center

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Center

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Door(s)

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on Basement

Floor Finish

InspectedInstance on Basement

Condition 1 - Good

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 18 of 37

Page 19: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on Basement

Stage

Does not ExistInstance on Basement

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Corridor near Cafeteria

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Cafeteria

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 202, 226, 307, 327, 338, and others

Deficiency Quantity 10

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 19 of 37

Page 20: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Deficiency Photo1

Room 307

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency SHEET VINYL: BROKEN/DETERIORATED

Deficiency Location/Instance Room 134

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 134

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Room 202

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 20 of 37

Page 21: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish Inspected

Room 202

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Corridor near Room 323

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 323

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency WOOD: DAMAGED/DETERIORATED

Deficiency Location/Instance Near Office, Near Drinking Fountain

Deficiency Quantity 70

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 21 of 37

Page 22: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

GYMNASIUM

Floor Finish

Deficiency Photo1

Near Office

Violations No violations recorded.

Seating

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency MASONRY: CRACKS/SPALLING

Deficiency Location/Instance Left side

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Left side

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 22 of 37

Page 23: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

INTERIOR GUARDS Inspected

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Basement

Condition 5 - Poor

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Serving Area Entrance

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Serving Area Entrance

Violations No violations recorded.

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 236

Built-in Furnishing

InspectedInstance on Room 236

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Ceiling

InspectedInstance on Room 236

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 236

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 23 of 37

Page 24: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

LIBRARY

Door(s)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 236

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 236

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Inspected

InspectedInstance on 2nd Floor (60 Lockers)

Alternative use Yes

Ceiling

InspectedInstance on 2nd Floor (60 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 2nd Floor (60 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 2nd Floor (60 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Locker Room Lockers

InspectedInstance on 2nd Floor (60 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 2nd Floor (60 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Inspected

InaccessibleInstance on 2nd Floor

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 24 of 37

Page 25: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Corridor near Gymnasium

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Gymnasium

Violations No violations recorded.

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance Stair C/3, Exit 12 Stair inside Gymnasium

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/3

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Stairs C/1, 2

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 25 of 37

Page 26: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/1

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Stair C/Basement

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/Basement

Violations No violations recorded.

Deficiency METAL: RUST - MAJOR

Deficiency Location/Instance Stair B/Basement

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/Basement

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 26 of 37

Page 27: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings Inspected

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 113

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 113

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 27 of 37

Page 28: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish

Deficiency Location/Instance Room 213

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 213

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 213

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 213

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Rooms 109, 209

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 28 of 37

Page 29: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Walls

Deficiency Photo1

Room 209

Violations No violations recorded.

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED COVER

Deficiency Location/Instance Walkway near Exits 7 & 9

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Walkway near Exits 7 & 9

Violations No violations recorded.

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Inspected

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 29 of 37

Page 30: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

DRINKING FOUNTAINS Inspected

Deficiency No deficiencies recorded

FENCES Inspected

Condition 4 - Between Fair and Poor

Deficiency CHAIN LINK: DAMAGED POST/RAIL

Deficiency Location/Instance South side of Building

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South side of Building

Violations No violations recorded.

Deficiency CHAIN LINK: RUST - MAJOR

Deficiency Location/Instance South side of Building

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South side of Building

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance North side of Building behind Mini Building, 46th Street

Deficiency Quantity 750

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 30 of 37

Page 31: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

FENCES Inspected

Deficiency Photo1

North side of Building behind Mini Building

Violations No violations recorded.

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance North side of Building, 46th Street, 47th Street

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Building

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency HEAVING

Deficiency Location/Instance 47th Street Garden

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 31 of 37

Page 32: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

PAVING

Student Use

Concrete

Deficiency Photo1

47th Street Garden

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance North side of Building, 47th Street Garden

Deficiency Quantity 250

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Building

Violations No violations recorded.

Pavers Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MINOR

Deficiency Location/Instance Behind Mini Building

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency POTHOLES

Deficiency Location/Instance Walkway between Mini Building and Main Building

Deficiency Quantity 10

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 32 of 37

Page 33: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Asphalt

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Walkway between Mini Building and Main Building

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency HEAVING

Deficiency Location/Instance South side of Building

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South side of Building

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance North side of Building, Main Entrance, 47th Street, South side ofBuilding

Deficiency Quantity 275

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 33 of 37

Page 34: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Concrete

Deficiency Photo1

North side of Building

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency HEAVING

Deficiency Location/Instance 46th Street

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

46th Street

Violations No violations recorded.

Deficiency DAMAGED CURBS

Deficiency Location/Instance 46th Street, 47th Street

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 34 of 37

Page 35: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo1

47th Street

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 46th Street, 47th Street

Deficiency Quantity 450

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

47th Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Adjacent to Mini-School Building

InspectedInstance on Courtyard (Plaza Deck)

Benches

Does not ExistInstance on Adjacent to Mini-School Building

Does not ExistInstance on Courtyard (Plaza Deck)

Fence

Does not ExistInstance on Adjacent to Mini-School Building

Does not ExistInstance on Courtyard (Plaza Deck)

Pavement

Does not ExistInstance on Adjacent to Mini-School Building

Does not ExistInstance on Courtyard (Plaza Deck)

Play Equipment

InspectedInstance on Adjacent to Mini-School Building

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 35 of 37

Page 36: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

PLAYGROUNDS

Play Equipment

Deficiency No deficiencies recorded

Does not ExistInstance on Courtyard (Plaza Deck)

Safety Surfacing

InspectedInstance on Adjacent to Mini-School Building

Condition 2 - Between Good and Fair

Deficiency DETERIORATED/MISSING

Deficiency Location/Instance North side

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side

Violations No violations recorded.

Unpaved Area

Does not ExistInstance on Courtyard (Plaza Deck)

Does not ExistInstance on Adjacent to Mini-School Building

PLAYING SURFACE Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR

Deficiency Location/Instance 47th Street

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance 46th Street, 47th Street

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 36 of 37

Page 37: NYC Department of Education - NYCSCASystems: Boiler/Mechanical Systems upgrade, Partial Exterior Door replacement Year: 2016 Systems: Chimney Liner replacement Year: 2015 Systems:

Question Response

SITE

RETAINING WALLS

Deficiency Photo1

46th Street

Violations No violations recorded.

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K001

PB/A&W Print Date: 6/21/2019Page 37 of 37