GROUNDING PRINCIPLE
21
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
INDOOR GROUNDING CABLINGIndoor Cable Tray
UltraSite grounding cable size is 25mm2. DDF grounding cable size is 16mm2. EMP busbar grounding cable size is 25mm2. Right cable lugs have to be suitable for grounding cable. All cables have to be labeled on both end of the cable. Proper tools have to be used during grounding cable installation. All cables have to be fixed properly.
DDF
Label
MAIN GROUNDING BUSBAR
22
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
INDOOR GROUNDING CABLING Example of good installation of grounding busbar
23
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
USE OF PROPER TOOLS Proper tools has to be always used. If crimping fails, cable lug has to be changed and new crimping applied. Lugs should match the cable size. Hex crimp have to be used.
Not OK : Crimping not acceptable
24
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
MAKE ACCEPTABLE CONNECTION Proper tools has to be always used. Lugs should match the cable size. Strip cable correctly. Hex crimp have to be used. Connection have to be protected by heat shrink or plastic sleeve. Do not use electrical tape.
25
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
MAKE ACCEPTABLE CONNECTION Cable lug correctly hex crimped.. Connection have to be protected by heat shrink. Do not use electrical tape.
26
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
MAKE ACCEPTABLE CONNECTION
Correct plastic sleeve on crimp joint Correct heat shrink on crimp joint
27
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER GROUNDING CABLINGFEEDER GROUNDING KIT POSITIONS
External Jumper 1
Antenna
Grounding Points
Equipment Room 3 Internal Jumper 2
If vertical rise of the RF cable is > 40m then center earth kit is required to be installed
Feeder Cable BTS Cable Entry Gland Plate
28
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER GROUNDING CABLING Feeders have to be grounded before feeder entry of cabin / equipment room. All feeder grounding kits have to be connected to feeder entry grounding busbar . Feeder grounding kit manufacturer material have to be used. All cables have to be labeled on both end of the cable. Proper tools have to be used during grounding cable installation. All cables have to be fixed properly.
Shelter/ Room Outdoor Cable tray
Feeder Grounding Kit
FEEDER ENTRY GROUNDING BUSBAR
29
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER GROUNDING CABLINGAntenna Jumper Cables
Feeders have to be grounded after antenna jumper connection. All feeder grounding kits have to be connected to feeder grounding busbar .Feeder label
Feeder grounding kit manufacturer material have to be used.Feeder Grounding Kit
All cables have to be labeled on both end of the cable. Proper tools have to be used during grounding cable installation. All cables have to be fixed properly.
FEEDER GROUNDING BUSBAR
30
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER GROUNDING CABLING Feeders have to be grounded approx. 5001000mm before horizontal bending. All feeder grounding kits have to be connected to feeder grounding busbar . Feeder grounding kit manufacturer material have to be used.Feeder Grounding Kit
Used cable lugs have to be suitable for used grounding cable. All cables have to be labeled on both end of the cable.
FEEDER GROUNDING BUSBAR
Proper tools have to be used during grounding cable installation. All cables have to be fixed properly.
31
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
GROUNDING CABLINGC-CRIMP INSTALLATIONWrap joint with rubber tape or use heat shrink Main Cable
Copper C Crimp
Joining Cable
NOTE: The copper C crimp must be the correct size for the cables e.g.. 25/16, 25/25, etc and the crimp tool must have the correct size C CRIMP dyes installed or selected.32 NOKIA SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER GROUNDING CABLING The grounding kit must always be positioned on the straight part of feeder cable and never on a bend or curve in the cable. Grounding kit's earthing cable can be cut or extended to make grounding cable connection to busbar as straight as possible.
Good installation
33
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
COMMON MACRO :ANTENNA LINE SYSTEM ItemDescription
1 2 3 4 5 6 7 8
The antennas can be either vertically polarised or cross polarised and directional or omni-directional antenna. The jumper cable is a flexible low loss cable (1/2"), which is used at the ends of the feeder. It protects the connectors from the forces caused by the feeder cable. 7/16 connector are made of silver plated brass or a special grade of copper. All connectors are IP68-classified. The grounding kit ensures that the Antenna line is DC grounded as a protection against lightning. The RF-feeder is corrugated coaxial cable. It can be of different sizes, i.e. 1/2, 7/8 and 1 5/8, depending on the length of the mast and the desired attenuation. Cable clamps are made of stainless steel and plastic and they are easy and quick to install. Design of the clamps prevents over tightening of a feeder cable. A compact EMP protector protects the BTS against lightning and over voltage that may occur down the antenna line. The wall feed through kit facilitates the connection of the feeders to the inside of a building without the ingress of water.Outdoor Indoor
1
2
3 4 5 6
4
8
3
2
7
Fig 1. Antenna Line System without MHA34 NOKIA SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER CABLING SUPPORT
35
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
FEEDER CABLING SUPPORT
36
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
GROUNDING KIT INSTALLATION
37
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
JUMPER CABLES INSTALLATIONOK Not OK Jumper Cables have to be installaed as straight as possible. Avoid additional bendings. Follow manufacturers bending instructions. Proper tools have to be used during jumper installation. All cables have to be fixed properly. Prefabricated jumpers have to be used always when possible. On existing sites most practical solution should be used. Think about future.
38
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
JUMPER CABLES INSTALLATION Jumpers Cables have to be installaed as straight as possible. Avoid additional bendings. Follow manufacturers bending instructions. Proper tools have to be used during jumper installation. All cables have to be fixed properly. Prefabricated jumpers have to be used always when possible. On existing sites most practical solution should be used. Think about future.
39
NOKIA
SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential
JUMPER CABLES INSTALLATION The distance clamps for jumper cables is about 500mm It is vitally important that the internal and external jumper cables have to be supported securely. For the 1,5m jumper, minimum 2(two) points of support are to be used, and for the 3m jumpers, minimum 4(four) points.
1.5m jumper, used 2 securing point
Securing has to be near of the connection < 150mm40 NOKIA SITE ENGINEERING STANDARDS/ANIL KOUL
Company Confidential