NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: VALUE WINDOWS & DOORS SERIES/MODEL: Eurotek 70 Inswing/Outswing Door Report Number: Report Date: H5300.01-301-45 09/20/17 2524 E. Jensen Avenue Fresno, CA 93706 p. 559.233.8705 f. 717.764.4129 www.archtest.com www.intertek.com/building

Transcript of NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE...

Page 1: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

NFRC U-FACTOR, SHGC, VT, &

CONDENSATION RESISTANCE

COMPUTER SIMULATION REPORT

Rendered to:

VALUE WINDOWS & DOORS

SERIES/MODEL:

Eurotek 70 Inswing/Outswing Door

Report Number:

Report Date:

H5300.01-301-45

09/20/17

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 2: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE

COMPUTER SIMULATION REPORT

Rendered to:

VALUE WINDOWS & DOORS

1830 Flower Avenue

Duarte, California 91010

Report Number:

Simulation Date:

Report Date:

Project Summary:

Standards:

Software:

Simulations Specimen Description:

Series/Model: Eurotek 70 Inswing/Outswing Door

Type: Swinging Door, Single Leaf Entrance Door 

Frame Material: VA Head/Jambs: Vinyl w/All Members Reinforced

AV Sill: Aluminum/Vinyl Composite

Sash Material: VA Vinyl w/ All Members Reinforced 

Standard Size: 960mm x 2090mm

Frame and Edge Modeling: THERM 7.4.4

Center-of-Glass Modeling: WINDOW 7.4.14

Total Product Calculations: WINDOW 7.4.14

*NFRC's Condensation Resistance rating is NOT equivalent to a Condensation Resistance

Factor (CRF) determined in accordance with AAMA 1503.

ANSI/NFRC 100-2017: Procedure for Determining Fenestration Product U-Factors

ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

Gain Coefficient and Visible Transmittance at Normal Incidence

NFRC 500-2017: Procedure for Determining Fenestration Product Condensation

Resistance Values

H5300.01-301-45

09/20/17

09/20/17

Architectural Testing, Inc., an Intertek Company (Intertek-ATI) was contracted to perform U-

Factor, Solar Heat Gain Coefficient, Visible Transmittance, and Condensation Resistance*

computer simulations in accordance with the National Fenestration Rating Council (NFRC).

The products were evaluated in full compliance with NFRC requirements to the standards listed

Spectral Data Library: IGDB 55.0

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 3: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 2 of 18

Modeling Assumptions/Technical Interpretations:

1) To prevent air infiltration, tape was applied to all interior sash crack locations.

2) Glazing beads vary based on overall insulated glass sizes per ANSI/NFRC 100-2017,

Section 4.2.1.D.

3) 0.188" x 0.625" and 0.188" x 0.750" grids do not need modeling per ANSI/NFRC

100-2017, Section 4.2.4.1.D.ii.a.

4) 0.250" x 0.625" and 0.313" x 1.000" grids do not need modeling in some options per

ANSI/NFRC 100-2017, Section 4.2.4.1.D.ii.a.

5) Inswing and Outswing doors are individual products within a product line per

ANSI/NFRC 100-2017, Section 5.2.2.F. and 4.2.1.I.iv.

Specialty Products Table:

SHGC = SHGC0 + SHGCc (SHGC1 - SHGC0)

VT = VT0 + VTc (VT1 - VT0)

Validation Matrix:

Outswing

No Dividers Dividers < 1 Dividers > 1

SHGC0 0.007275 0.010110 0.012732

SHGC1 0.608614 0.525075 0.447833

VT0 0.000000 0.000000 0.000000

VT1 0.601340 0.514964 0.435101

VT0 0.000000 0.000000 0.000000

VT1 0.604422 0.517843 0.437774

SHGC0 0.006910 0.009753 0.012381

SHGC1 0.611333 0.527595 0.450155

The specialty products method allow the manufacturer to determine the overall product SHGC

and VT for any glazing option. The center of glass SHGC and/or VT must be determined using

WINDOW 7.4.14. The method gives overall product SHGC and VT indexed on center of glass

properties. All values used in the calculations are truncated to six decimal place precision.

No Dividers Dividers < 1 Dividers > 1

Inswing

The following products are part of a validation matrix. Only one is required for validation

testing.

Product Line Report Number

None -

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 4: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 3 of 18

Spacer Option Description

Grid Option Description

Reinforcement Option Description

Gas Filling Technique Description

Edge-of-Glass Construction

Weatherstripping

Frame/Sash Materials Finish

Window ID Description

Grid Size Grid Type Grid Pattern

0.188" x 0.625" Aluminum Rectangular Grid (Painted) NFRC Standard

Spacer Type Primary Secondary Code

Quanex Super Spacer Standard Butyl Rubber OF-S

Sealant

Head and jambs Galvanized

Steel

Fill Type Method

90% Argon Single Prober Timed

0.313" x 1.000" Aluminum Contour Grid (Painted) NFRC Standard

Location Material

All members of the panel Galvanized

Steel

0.188" x 0.750" Aluminum Rectangular Grid (Painted) NFRC Standard

0.250" x 0.625" Aluminum Contour Grid (Painted) NFRC Standard

EPDM compression bulb gasket 1 row Bottom rail

Flexible vinyl sweep 1 row Bottom rail

EPDM compression bulb gasket 1 row Head and jambs

EPDM compression gasket 1 row All members of the panel

Interior Condition EPDM gasket between glass and glazing bead

Exterior Condition EPDM gasket between glass and glazing stop

Type Quantity Location

EPDM gasket 1 row Sill and bottom rail of outswing profile

Interior Vinyl/Aluminum - Anodized

Exterior Vinyl/Aluminum - Anodized

Window Description Report ID Numbers

Inswing #1-16

Outswing #17-32

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 5: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 4 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

AIR CL OF-S N,G

Condensation

Resistance

1 Inswing: Clr / Air / Clr - 25.7mm (6mm-6mm)

0.224 0.563 0.224

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC)

Grids (None / <1 / >=1)

Visible Transmittance (VT)

Grids (None / <1 / >=1)

ARG90 0.022(#2) CL OF-S N,G

CR 46

2 Inswing: E366 / Arg / Clr - 25.7mm (6mm-6mm)

0.225 0.563 0.224

U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35

AIR CL OF-S N,G

CR 61

3 Inswing: Clr / Air / Clr - 31.6mm (3mm-3mm)

0.118 1.000 0.118

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

AIR CL OF-S N,G

CR 46

Inswing: Clr / Air / Clr - 33.2mm (4mm-4mm)

0.154 1.000 0.154

U-Factor 0.40 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.43 / 0.36

AIR CL OF-S N,G

CR 46

Inswing: Clr / Air / Clr - 25.2mm (3mm-3mm)

0.118 0.750 0.118

U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36

AIR CL OF-S N,G

CR 46

Inswing: Clr / Air / Clr - 26.8mm (4mm-4mm)

0.154 0.750 0.154

U-Factor 0.40 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.43 / 0.36

AIR CL OF-S N,G

CR 46

Inswing: Clr / Air / Clr - 20.5mm (3mm-3mm)

0.118 0.563 0.118

U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36

AIR CL OF-S N,G

CR 46

Inswing: Clr / Air / Clr - 22.1mm (4mm-4mm)

0.154 0.563 0.154

U-Factor 0.40 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.43 / 0.36

ARG90 0.022(#2) CL OF-S N,G

CR 46

4 Inswing: E366 / Arg / Clr - 31.6mm (3mm-3mm)

0.117 1.000 0.118

U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 33.2mm (4mm-4mm)

0.153 1.000 0.154

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.34 / 0.28

CR 62U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 6: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 5 of 18

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.022(#2) CL OF-S N,G

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

Inswing: E366 / Arg / Clr-PVB-Clr - 35.26mm (3mm-Lami)

0.117 1.000 0.362 ARG90

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

CR 62

Inswing: E366 / Arg / Clr-PVB-Clr - 36.06mm (4mm-Lami)

0.153 1.000 0.362

CR 62

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.34 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 25.2mm (3mm-3mm)

0.117 0.750 0.118

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

Inswing: E366 / Arg / Clr - 26.8mm (4mm-4mm)

0.153 0.750 0.154

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

Inswing: E366 / Arg / Clr-PVB-Clr - 28.86mm (3mm-Lami)

0.117 0.750 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr-PVB-Clr - 29.66mm (4mm-Lami)

0.153 0.750 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.34 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 20.5mm (3mm-3mm)

0.117 0.563 0.118

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 22.1mm (4mm-4mm)

0.153 0.563 0.154

U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35

AIR CL OF-S N,G

CR 62

5 Inswing: Clr / Air / Clr - 34.8mm (5mm-5mm)

0.185 1.000 0.185

U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35

AIR CL OF-S N,G

Inswing: Clr / Air / Clr - 36.8mm (6mm-6mm)

CR 47

0.224 1.000 0.224

CR 47

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 7: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 6 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

AIR

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

AIR CL OF-S N,G

CR 47

Inswing: Clr / Air / Clr - 30.4mm (6mm-6mm)

0.224 0.750 0.224

CL OF-S N,G

U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35

Inswing: Clr / Air / Clr - 28.4mm (5mm-5mm)

0.185 0.750 0.185

AIR CL OF-S N,G

CR 47

Inswing: Clr / Air / Clr - 23.7mm (5mm-5mm)

0.185 0.563 0.185

U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35

ARG90 0.022(#2) CL OF-S N,G

CR 47

6 Inswing: E366 / Arg / Clr - 34.8mm (5mm-5mm)

0.187 1.000 0.185

U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 36.8mm (6mm-6mm)

0.225 1.000 0.224

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr-PVB-Clr - 36.86mm (5mm-Lami)

0.187 1.000 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr-PVB-Clr - 37.86mm (6mm-Lami)

0.225 1.000 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 28.4mm (5mm-5mm)

0.187 0.750 0.185

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr - 30.4mm (6mm-6mm)

0.225 0.750 0.224

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Inswing: E366 / Arg / Clr-PVB-Clr - 30.46mm (5mm-Lami)

0.187 0.750 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

CR 62U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 8: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 7 of 18

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.022(#2) CL OF-S N,G

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

Inswing: E366 / Arg / Clr-PVB-Clr - 31.46mm (6mm-Lami)

0.225 0.750 0.362 ARG90

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 49

CR 62

Inswing: E366 / Arg / Clr - 23.7mm (5mm-5mm)

0.187 0.563 0.185

CR 62

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

7 Inswing: E366 / Arg / i89 - 34.8mm (5mm-5mm)

0.187 1.000 0.187

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

Inswing: E366 / Arg / i89 - 36.8mm (6mm-6mm)

0.225 1.000 0.223

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

Inswing: E366 / Arg / i89 - 28.4mm (5mm-5mm)

0.187 0.750 0.187

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 30.4mm (6mm-6mm)

0.225 0.750 0.223

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 23.7mm (5mm-5mm)

0.187 0.563 0.187

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 25.7mm (6mm-6mm)

0.225 0.563 0.223

U-Factor 0.22 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.36 / 0.31 / 0.26

ARG90 0.022(#2) CL OF-S N,G

CR 49

8 Inswing: E366 / Arg / Clr / Arg / Clr - 37.9mm (3mm-3mm-3mm)

0.117 0.563 0.118 0.563 0.118

U-Factor 0.22 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.35 / 0.30 / 0.26

ARG90 0.022(#2) CL OF-S N,G

Inswing: E366 / Arg / Clr / Arg / Clr - 40.3mm (4mm-4mm-4mm)

CR 72

0.153 0.563 0.154 0.563 0.154

CR 72

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 9: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 8 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.118 ARG90

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G

CR 72

Inswing: E366 / Arg / Clr) / Arg / E366(5) - 37.9mm (3mm-3mm-3mm)

0.117 0.563 0.118 0.563 0.117

0.022(#2) / 0.022(#4) CL OF-S N,G

U-Factor 0.18 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

9 Inswing: E366 / Arg / E366(4) / Arg / Clr - 37.9mm (3mm-3mm-3mm)

0.117 0.563 0.117 0.563

ARG90 0.022(#2) / 0.022(#4) CL OF-S N,G

CR 72

Inswing: E366 / Arg / E366(4) / Arg / Clr - 40.3mm (4mm-4mm-4mm)

0.153 0.563 0.153 0.563 0.154

U-Factor 0.18 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.12 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G

CR 72

Inswing: E366 / Arg / Clr) / Arg / E366(5) - 40.3mm (4mm-4mm-4mm)

0.153 0.563 0.154 0.563 0.153

U-Factor 0.18 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S N

CR 72

10 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)

0.117 0.472 0.362 0.472 0.117

U-Factor 0.18 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.12 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

ARG90 0.022(#2) / 0.022(#4) CL OF-S N

CR 72

Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)

0.117 0.472 0.117 0.472 0.362

U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27

ARG90 0.022(#2) / 0.022(#5) CL OF-S N

CR 72

Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)

0.153 0.472 0.362 0.472 0.153

U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27

ARG90 0.022(#2) / 0.022(#4) CL OF-S N

CR 72

Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)

0.153 0.472 0.153 0.472 0.362

U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

CR 72

11 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)

0.117 0.472 0.362 0.472 0.117

U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

CR 72

Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)

0.117 0.472 0.117 0.472 0.362

U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23

CR 72U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 10: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 9 of 18

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.022(#2) / 0.022(#5) CL OF-S G

U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23

Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)

0.153 0.472 0.362 0.472 0.153 ARG90

U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

CR 72

CR 72

Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)

0.153 0.472 0.153 0.472 0.362

CR 72

U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

CR 72

12 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)

0.117 0.472 0.362 0.472 0.117

U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)

0.117 0.472 0.117 0.472 0.362

U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)

0.153 0.472 0.362 0.472 0.153

U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

CR 72

Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)

0.153 0.472 0.153 0.472 0.362

U-Factor 0.23 SHGC (N) 0.16 VT (N) 0.34

ARG90 0.022(#2) CL OF-S N

CR 72

13 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)

0.117 0.394 0.362 0.394 0.362

U-Factor 0.23 SHGC (<1) 0.14 VT (<1) 0.29

ARG90 0.022(#2) CL OF-S G

CR 71

14 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)

0.117 0.394 0.362 0.394 0.362

U-Factor 0.24 SHGC (>1) 0.12 VT (>1) 0.25

ARG90 0.022(#2) CL OF-S G

CR 70

15 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)

0.117 0.394 0.362 0.394 0.362

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

16 Inswing: E366 / Arg / i89 - 31.6mm (3mm-3mm)

CR 70

0.117 1.000 0.117

CR 49

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 11: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 10 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

ARG90

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 25.2mm (3mm-3mm)

0.117 0.750 0.117

0.022(#2) / 0.149(#4) CL OF-S N,G

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

Inswing: E366 / Arg / i89 - 33.2mm (4mm-4mm)

0.153 1.000 0.160

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 26.8mm (4mm-4mm)

0.153 0.750 0.160

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 20.5mm (3mm-3mm)

0.117 0.563 0.117

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Inswing: E366 / Arg / i89 - 22.1mm (4mm-4mm)

0.153 0.563 0.160

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

AIR CL OF-S N,G

CR 49

17 Outswing: Clr / Air / Clr - 25.7mm (6mm-6mm)

0.224 0.563 0.224

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 46

18 Outswing: E366 / Arg / Clr - 25.7mm (6mm-6mm)

0.225 0.563 0.224

U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35

AIR CL OF-S N,G

CR 61

19 Outswing: Clr / Air / Clr - 31.6mm (3mm-3mm)

0.118 1.000 0.118

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

AIR CL OF-S N,G

CR 46

Outswing: Clr / Air / Clr - 33.2mm (4mm-4mm)

0.154 1.000 0.154

U-Factor 0.41 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.42 / 0.36

AIR CL OF-S N,G

CR 46

Outswing: Clr / Air / Clr - 25.2mm (3mm-3mm)

0.118 0.750 0.118

U-Factor 0.41 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36

CR 46U-Factor 0.41 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.42 / 0.36

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 12: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 11 of 18

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

CL OF-S N,G

U-Factor 0.41 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36

Outswing: Clr / Air / Clr - 26.8mm (4mm-4mm)

0.154 0.750 0.154 AIR

U-Factor 0.41 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.42 / 0.36

AIR CL OF-S N,G

CR 46

CR 46

Outswing: Clr / Air / Clr - 20.5mm (3mm-3mm)

0.118 0.563 0.118

CR 46

U-Factor 0.41 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36

AIR CL OF-S N,G

CR 62

Outswing: Clr / Air / Clr - 22.1mm (4mm-4mm)

0.154 0.563 0.154

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

20 Outswing: E366 / Arg / Clr - 31.6mm (3mm-3mm)

0.117 1.000 0.118

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

Outswing: E366 / Arg / Clr - 33.2mm (4mm-4mm)

0.153 1.000 0.154

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr-PVB-Clr - 35.26mm (3mm-Lami)

0.117 1.000 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr-PVB-Clr - 36.06mm (4mm-Lami)

0.153 1.000 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 25.2mm (3mm-3mm)

0.117 0.750 0.118

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 26.8mm (4mm-4mm)

0.153 0.750 0.154

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

Outswing: E366 / Arg / Clr-PVB-Clr - 28.86mm (3mm-Lami)

CR 62

0.117 0.750 0.362

CR 62

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 13: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 12 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

ARG90

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 20.5mm (3mm-3mm)

0.117 0.563 0.118

0.022(#2) CL OF-S N,G

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

Outswing: E366 / Arg / Clr-PVB-Clr - 29.66mm (4mm-Lami)

0.153 0.750 0.362

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 22.1mm (4mm-4mm)

0.153 0.563 0.154

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

AIR CL OF-S N,G

CR 62

21 Outswing: Clr / Air / Clr - 34.8mm (5mm-5mm)

0.185 1.000 0.185

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28

AIR CL OF-S N,G

CR 46

Outswing: Clr / Air / Clr - 36.8mm (6mm-6mm)

0.224 1.000 0.224

U-Factor 0.40 SHGC (N / <1 / >1) 0.45 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35

AIR CL OF-S N,G

CR 46

Outswing: Clr / Air / Clr - 28.4mm (5mm-5mm)

0.185 0.750 0.185

U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35

AIR CL OF-S N,G

CR 46

Outswing: Clr / Air / Clr - 30.4mm (6mm-6mm)

0.224 0.750 0.224

U-Factor 0.40 SHGC (N / <1 / >1) 0.45 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35

AIR CL OF-S N,G

CR 46

Outswing: Clr / Air / Clr - 23.7mm (5mm-5mm)

0.185 0.563 0.185

U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35

ARG90 0.022(#2) CL OF-S N,G

CR 46

22 Outswing: E366 / Arg / Clr - 34.8mm (5mm-5mm)

0.187 1.000 0.185

U-Factor 0.40 SHGC (N / <1 / >1) 0.45 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 36.8mm (6mm-6mm)

0.225 1.000 0.224

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

CR 62U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 14: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 13 of 18

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.022(#2) CL OF-S N,G

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

Outswing: E366 / Arg / Clr-PVB-Clr - 36.86mm (5mm-Lami)

0.187 1.000 0.362 ARG90

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

CR 62

Outswing: E366 / Arg / Clr-PVB-Clr - 37.86mm (6mm-Lami)

0.225 1.000 0.362

CR 62

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 28.4mm (5mm-5mm)

0.187 0.750 0.185

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

Outswing: E366 / Arg / Clr - 30.4mm (6mm-6mm)

0.225 0.750 0.224

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

Outswing: E366 / Arg / Clr-PVB-Clr - 30.46mm (5mm-Lami)

0.187 0.750 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr-PVB-Clr - 31.46mm (6mm-Lami)

0.225 0.750 0.362

U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) CL OF-S N,G

CR 62

Outswing: E366 / Arg / Clr - 23.7mm (5mm-5mm)

0.187 0.563 0.185

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 62

23 Outswing: E366 / Arg / i89 - 34.8mm (5mm-5mm)

0.187 1.000 0.187

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 36.8mm (6mm-6mm)

0.225 1.000 0.223

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

Outswing: E366 / Arg / i89 - 28.4mm (5mm-5mm)

CR 49

0.187 0.750 0.187

CR 49

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 15: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 14 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

ARG90

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 23.7mm (5mm-5mm)

0.187 0.563 0.187

0.022(#2) / 0.149(#4) CL OF-S N,G

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

Outswing: E366 / Arg / i89 - 30.4mm (6mm-6mm)

0.225 0.750 0.223

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 25.7mm (6mm-6mm)

0.225 0.563 0.223

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 49

24 Outswing: E366 / Arg / Clr / Arg / Clr - 37.9mm (3mm-3mm-3mm)

0.117 0.563 0.118 0.563 0.118

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27

ARG90 0.022(#2) CL OF-S N,G

CR 71

Outswing: E366 / Arg / Clr / Arg / Clr - 40.3mm (4mm-4mm-4mm)

0.153 0.563 0.154 0.563 0.154

U-Factor 0.23 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.36 / 0.30 / 0.26

ARG90 0.022(#2) / 0.022(#4) CL OF-S N,G

CR 71

25 Outswing: E366 / Arg / E366(4) / Arg / Clr - 37.9mm (3mm-3mm-3mm)

0.117 0.563 0.117 0.563 0.118

U-Factor 0.23 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.35 / 0.30 / 0.25

ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G

CR 72

Outswing: E366 / Arg / Clr) / Arg / E366(5) - 37.9mm (3mm-3mm-3mm)

0.117 0.563 0.118 0.563 0.117

U-Factor 0.19 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

ARG90 0.022(#2) / 0.022(#4) CL OF-S N,G

CR 72

Outswing: E366 / Arg / E366(4) / Arg / Clr - 40.3mm (4mm-4mm-4mm)

0.153 0.563 0.153 0.563 0.154

U-Factor 0.19 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.12 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G

CR 72

Outswing: E366 / Arg / Clr) / Arg / E366(5) - 40.3mm (4mm-4mm-4mm)

0.153 0.563 0.154 0.563 0.153

U-Factor 0.19 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S N

CR 72

26 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)

0.117 0.472 0.362 0.472 0.117

U-Factor 0.19 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.11 VT (N / <1 / >1) 0.28 / 0.24 / 0.20

CR 71U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 16: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 15 of 18

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.022(#2) / 0.022(#4) CL OF-S N

U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27

Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)

0.117 0.472 0.117 0.472 0.362 ARG90

U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27

ARG90 0.022(#2) / 0.022(#5) CL OF-S N

CR 71

CR 71

Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)

0.153 0.472 0.362 0.472 0.153

CR 71

U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27

ARG90 0.022(#2) / 0.022(#4) CL OF-S N

CR 71

Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)

0.153 0.472 0.153 0.472 0.362

U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

27 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)

0.117 0.472 0.362 0.472 0.117

U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)

0.117 0.472 0.117 0.472 0.362

U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

CR 71

Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)

0.153 0.472 0.362 0.472 0.153

U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

CR 71

Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)

0.153 0.472 0.153 0.472 0.362

U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

CR 71

28 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)

0.117 0.472 0.362 0.472 0.117

U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#4) CL OF-S G

CR 71

Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)

0.117 0.472 0.117 0.472 0.362

U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20

ARG90 0.022(#2) / 0.022(#5) CL OF-S G

Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)

CR 71

0.153 0.472 0.362 0.472 0.153

CR 71

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 17: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 16 of 18

NFRC 100/200/500 Summary Sheet

Eurotek 70 Inswing/Outswing Door

ID

Pa

ne

Th

ick

nes

s 1

Ga

p W

idth

1

Pa

ne

Th

ick

nes

s 2

Ga

p W

idth

2

Pa

ne

Th

ick

nes

s 3

0.362 ARG90

Gri

d T

yp

e

U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation

Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance

Ga

p W

idth

3

Pa

ne

Th

ick

nes

s 4

Ga

p F

ill

Lo

w-e

(S

urf

ace

#)

Tin

t

Sp

ace

r

ARG90 0.022(#2) CL OF-S N

CR 71

29 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)

0.117 0.394 0.362 0.394 0.362

0.022(#2) / 0.022(#4) CL OF-S G

U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20

Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)

0.153 0.472 0.153 0.472

ARG90 0.022(#2) CL OF-S G

CR 70

30 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)

0.117 0.394 0.362 0.394 0.362

U-Factor 0.23 SHGC (N) 0.16 VT (N) 0.34

ARG90 0.022(#2) CL OF-S G

CR 70

31 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)

0.117 0.394 0.362 0.394 0.362

U-Factor 0.23 SHGC (<1) 0.14 VT (<1) 0.29

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 70

32 Outswing: E366 / Arg / i89 - 31.6mm (3mm-3mm)

0.117 1.000 0.117

U-Factor 0.24 SHGC (>1) 0.12 VT (>1) 0.24

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 33.2mm (4mm-4mm)

0.153 1.000 0.160

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 25.2mm (3mm-3mm)

0.117 0.750 0.117

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 26.8mm (4mm-4mm)

0.153 0.750 0.160

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 20.5mm (3mm-3mm)

0.117 0.563 0.117

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G

CR 49

Outswing: E366 / Arg / i89 - 22.1mm (4mm-4mm)

0.153 0.563 0.160

U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28

CR 49U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 18: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 17 of 18

SIMULATED BY: REVIEWED BY:

Elizabeth A. Moser Kenny C. White

Simulation Technician Laboratory Manager

Simulator-In-Responsible-Charge

EAM:eam

H5300.01-301-45

Attachments (pages): This report is complete only when all attachments listed are included.

Results obtained are simulated values and were secured by using the designated test methods.

This report does not constitute certification of this product nor an opinion or endorsement by

this laboratory. It is the exclusive property of the client so named herein and relates only to the

product simulated. This report may not be reproduced, except in full, without the written

approval of Intertek-ATI

For INTERTEK-ATI:

Appendix A: Drawings and Bills of Material (23)

The Condensation Resistance results obtained from this procedure are for controlled laboratory

conditions and do not include the effects of air movement through the specimen, solar radiation,

and the thermal bridging that may occur due to the specific design and construction of the

fenestration system opening.

Ratings values included in this report are for submittals to an NFRC-licensed IA and are not

meant to be used directly for labeling purposes. Only those values identified on a valid

Certification Authorization Report (CAR) by an NFRC accredited Inspection Agency (IA) are

to be used for labeling purposes. The ratings values were rounded in accordance to NFRC 601,

NFRC Unit and Measurement Policy.

Intertek-ATI is an NFRC accredited simulation laboratory and all simulations were conducted

in full compliance with NFRC approved procedures and specifications. The values included in

this report are not considered in compliance with ANSI/NFRC 100, ANSI/NFRC 200, and/or

NFRC 500 unless the associated validation test requirements have been satisfied, as applicable.

Intertek-ATI will service this report for the entire test record retention period. Test records that

are retained such as detailed drawings, datasheets, representative samples of test specimens, or

other pertinent project documentation will be retained by Intertek-ATI for the entire test record

retention period. The test record retention end date for this report is September 20, 2022.

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 19: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

H5300.01-301-45

Page 18 of 18

Revision Log

Rev. # Date Page(s) Revision(s)

This report produced from controlled document template ATI 00037, Revised 10/2/2012.

.01R0 09/20/17 All Original Report Issue. Work Requested by

Mr. Shawn Wan of Value Windows &

Doors.

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 20: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat

All drawings and Bills of Material used to simulate this product are enclosed in this Appendix

Appendix AH5300.01-301-45

2524 E. Jensen AvenueFresno, CA 93706

p. 559.233.8705f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 21: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
Rejected
emoser
H5300
emoser
Rejected
emoser
Rejected
emoser
Rejected
emoser
Rejected
emoser
Rejected
Page 22: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 23: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 24: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
Rejected
emoser
H5300
emoser
Rejected
emoser
Rejected
emoser
Rejected
emoser
Rejected
emoser
Rejected
Page 25: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 26: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 27: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 28: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 29: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 30: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 31: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 32: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 33: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 34: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 35: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 36: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 37: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 38: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 39: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 40: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 41: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300
Page 42: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
Text Box
Grids are placed in the outer gap in the triple glazed options
emoser
Accepted
emoser
Accepted
emoser
Accepted
emoser
Accepted
emoser
Rejected
emoser
Text Box
Modeled
emoser
Text Box
Modeled
emoser
Text Box
Did not need modeling
emoser
Text Box
Did not need modeling
emoser
H5300
Page 43: NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE ...eurotekwindows.com/wp-content/uploads/2017/11/...ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
emoser
H5300