Siemens Building Technologies CE1N5622E / 28.10.1998
Landis & Staefa Division 1/4
5622
SONOGYR
energy
Relay Pulse Module WZF-P2
Module with potential-free pulse outputs for the connection of ultrasonic heat
meters SONOGYR energy to systems and remote display units for billingpurposes.
The relay pulse module is used for passing volume- and energy-proportional pulses
from a SONOGYR
energy heat meter for billing purposes to systems or remote displayunits.
Delivery of heat meter data in the form of continuous pulses. The pulses are volume-
and energy-proportional and can also be delivered depending on tariffs or depending on
heating or cooling energy.
The relay pulse module enables the heat meter to communicate with
the billing system SYNERGYR
the control and supervisory systems UNIGYRVISONIK
remote display units using pulse handling interfaces
other devices and systems equipped with pulse handling interfaces
When ordering, please give type reference WZF-P2.
The module can be supplied either fitted in the heat meter or as a separate item. For
details, please contact the Landis & Staefa sales office nearest you.
The relay pulse module must be plugged into the heat meter, which automatically
identifies the type of module fitted.
The module has two relay pulse outputs.
Preset is the delivery of
volume-proportional pulses at terminals 51 and 52 (OUT1) energy-proportional pulses at terminals 53 and 54 (OUT2)
pulses having a pulse length of 54 ms
Use
Function
Equipmentcombinations
Ordering
Technical design
-
7/27/2019 N5622E
2/4
CE1N5622E / 28.10.1998 Siemens Building Technologies
2/4 Landis & Staefa Division
The standard pulse valency presettings are the following:
Nominal flow rate qpof heat meter in m3/h
Energy in
kWh / pulse
Energy in
MJ / pulse
Volume in
l / pulse
0.6 1 1 10
1.0 1 5 10
1.5 1 5 10
2.5 1 5 10
3.5 1 5 10
6.0 10 10 10010 10 50 100
15 10 50 100
25 10 50 100
40 10 50 100
60 100 100 1000
Type of pulse, pulse parameters and pulse valencies can be changed with the service
unit.
The pulses can be evaluated with a suitable device (refer to Technical data).
The relay pulse module is of plug-in design. It is plugged into the front of the heatmeter's electronic unit whose cover must be removed for plugging in.
The module consists of baseplate and printed circuit board, which also carries the
connection terminals.
The pulse outputs are connected to the electronic unit via relays (potential-free). The
terminals of the pulse outputs cannot be mixed up.
The regulations for the use of heat meters must be complied with!
The regulations for electrical installations must be complied with!
All notes contained in the heat meter's data sheet must be observed
The relay pulse module may only be used in electrical circuits where the complete system is isolated from the mains supply by a safety
transformer (SELV circuit)
that are designed as safety extra low voltage circuits with earthing (PELV)
When using a relay pulse module, the heat meter must be powered by a battery
module WZF-BD or mains module WZF-NE or WZF-VE
The connection between relay pulse module and pulse receiver must be established
with a flexible two-wire control cable having a cross-sectional area of max. 2.5 mm2
and being heat-resistant up to at least 105 C. The outside diameter of the control
cable must be 4...6 mm, the diameter of the standard rubber grommet used
Calibration labels on the heat meter may not be damaged or removed! If they are, the
heat meter's warranty and certification become void. User seals may only be removed
by authorized staff for service purposes. They must be replaced
The module is supplied complete with mounting and commissioning instructions
To fit the module, the cover of the electronic unit must be removed, which means that
the user seals must be broken
Within 30 seconds, the heat meter identifies the type of module used and starts
delivering the pulses whose parameters have been set.
With the help of the service unit, the heat meter can deliver test pulses:
At output OUT1: five test pulses
At output OUT2: ten test pulses
If error code appears, the heat meter's power supply module is not suited for the
application.
Mechanical design
Notes
Engineering
Mounting
Commissioning
-
7/27/2019 N5622E
3/4
Siemens Building Technologies CE1N5622E / 28.10.1998
Landis & Staefa Division 3/4
conformity
EMC directive 89/336/EEC
Electromagnetic immunity to EN 50082-1
Electromagnetic emissions to EN 50081-1
Design and testing to EN 61010-1
Safety class lll to EN 60742
European norm for heat meters EN 1434
Environment class C
Pulse length
Range 7.8 ms...1 s
Preset 54 ms
Pulse valency refer to table in Technical design
Number of pulses max. 10 * 106
during the module's life
Perm. ambient temperature
Operation 5...55 C
Storage and transport 25...+70 C (dry)
Perm. ambient humidity
-
7/27/2019 N5622E
4/4
CE1N5622E / 28.10.1998 Siemens Building Technologies
4/4 Landis & Staefa Division
Production centre: Landis & Staefa Produktion GmbH, Werk Rastatt
1998 Siemens Building Technologies Ltd.