Multifamily Ventilation – Best Practice?
Dianne Griffiths
April 29, 2013
![Page 2: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/2.jpg)
Presentation Outline
• Basic Objectives
• Exhaust Systems
• Make-up Air Systems
![Page 3: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/3.jpg)
Two Primary Ventilation Objectives
1) Providing Fresh Air - Whole-House 2) Removing Pollutants - Local Exhaust
Our goal is to find the simplest solution that satisfies both objectives while minimizing cost and energy impacts.
Common Solution: Align local exhaust with fresh air requirements (Ex: 25 Bath + 25 Kitchen)
![Page 4: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/4.jpg)
Exhaust-Driven Fresh Air Design
• Exhaust slightly depressurizes the units
• Outside air enters through leaks, cracks, or planned inlets
• Widely used in the North
![Page 5: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/5.jpg)
Multifamily Ventilation Best Practice
• Step 1: Understand ventilation requirements
• Step 2: Select the simplest design that can achieve both air quality and energy objectives
• Step 3: Build a tight building
• Step 4: Pay attention to installation quality
• Step 5: Check to make sure ventilation works
• Step 6: Educate users
![Page 6: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/6.jpg)
Exhaust: Central and Unitized
Central Exhaust Unitized Exhaust
![Page 7: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/7.jpg)
Standard Central Exhaust Practice
Roof or mushroom fans Vertical shaft with
horizontal take-offs Sidewall or ceiling grilles
at each floor Continuous operation
![Page 8: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/8.jpg)
Mechanical Designers’ Intent
• Balancing damper transferring responsibility to balancing contractor
• Many grilles, many floors, relatively low flow targets, plus wind and weather on balancing day = balancing is difficult
![Page 9: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/9.jpg)
Automatic Balancing Dampers
60 CFM
40 CFM
20 CFM
30 CFM
20 CFM
10 CFM
30 CFM
30 CFM
30 CFM
30 CFM
30 CFM
30 CFM
Balance in two ways: • Provide restriction in size of
opening (increase static pressure)
• Dynamically self-adjust to changes in the system (automatic balancing)
![Page 10: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/10.jpg)
Duct Leakage
Roof curb?
Takeoffs?
Transverse (sectional) joints?
Register connectionsLongitudinal (lengthwise)
joints? can be the largest set of leaks
![Page 11: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/11.jpg)
Best Practice
• Include performance specifications for duct tightness in construction documents
• Call out specific details to be sealed: all joints, takeoffs, connections, registers, etc., etc.
Then test for leakage: • Good =
10 CFM50/register • Better =
5 CFM50/register
![Page 12: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/12.jpg)
Duct Sealing Methods
Aeroseal® aerosol duct sealant sticks to holes in ductwork and seals them
![Page 13: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/13.jpg)
Working elevators and power on the roof are helpful.
• Prepare a plan.
• Check weather report!
![Page 14: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/14.jpg)
Mastic Spray
Rotating spray head -Simple concept applies mastic directly -Very effective on to leaks identified by straight shafts camera
![Page 15: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/15.jpg)
In-Unit Exhaust Systems
Small fans, relatively low flow (50-100 CFM), low power consumption, easier to balance floor to floor
![Page 16: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/16.jpg)
In-Unit Ventilation Quality Control
• Duct sealing • Avoid kinks, long duct
runs; use rigid duct
![Page 17: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/17.jpg)
Exhaust System Design Parameters
Central Systems
• Constant Air Regulating (CAR) dampers to balance flows
• Airtight ductwork, including fan and grille connections
• Tightly compartmentalized units
Unitized Systems
• ENERGY STAR fans with variable speed where appropriate
• Short straight duct runs
• Tightly sealed ducts
• Tightly compartmentalized units
![Page 18: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/18.jpg)
Exhaust-Driven Make-up Air Strategies
Current Research Focus
Where is the make-up air coming from?
• Leaks • Trickle vents • Make-up air supplied to corridor • Vent or fan within PTAC
![Page 19: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/19.jpg)
Trickle Vents - Designed Inlets
• Intentional openings in building envelope that allow a trickle of air into buildings in response to pressure differential
• Trickle Vents often built into window frames
![Page 20: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/20.jpg)
Trickle Vents – Installed Performance
• Flow from trickle vents measured with hot wire anemometer in a building under actual operating conditions.
• Also measured inside/outside pressure difference across exterior window.
![Page 21: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/21.jpg)
Trickle Vent Airflow vs. Pressure Difference
Air flow at typical building operating pressures is expected to be about 5-10 CFM per trickle vent – a “trickle”
AAMA = American Architectural Manufacturers Association
![Page 22: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/22.jpg)
Comparison of trickle vents in two buildings
1st bldg.
2nd bldg.
![Page 23: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/23.jpg)
Airflow patterns in a tight unit with trickle vents
![Page 24: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/24.jpg)
Airflow patterns with trickle vents
![Page 25: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/25.jpg)
This Year’s Research Plan
1. Evaluate performance of more systems in more buildings – Corridor supply systems – Trickle vents – PTAC outside air vents
2. Measure pressure variation within buildings and apartments over time – 2 weeks in winter and 2 weeks in summer
![Page 26: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/26.jpg)
Earlier Testing
• Airflow through gaps in apartment door
![Page 27: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/27.jpg)
Latest Test Rig
Powered Flow Hood Energy Conservatory’s FlowBlasterTM
![Page 28: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/28.jpg)
Other Make-up Air Inlets
![Page 29: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/29.jpg)
Variability in Driving Forces
Typical for Winter – But what about summer, windy days, …
![Page 30: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/30.jpg)
Pressure Monitoring
Locations of pressure sensors
![Page 31: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/31.jpg)
Pressure Monitoring
Data logger
![Page 32: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/32.jpg)
Best Practice Summary
• Step 1: Understand ventilation requirements
• Step 2: Select the simplest design that can achieve both air quality and energy objectives
• Step 2: Build a tight building
• Step 3: Pay attention to installation quality
• Step 4: Check to make sure ventilation works
• Step 5: Educate users
![Page 33: Multifamily Ventilation - Best Practice? · Two Primary Ventilation Objectives. 1) Providing Fresh Air - Whole-House . 2) Removing Pollutants - Local Exhaust . Our goal is to find](https://reader030.fdocuments.net/reader030/viewer/2022040903/5e7571186d0a3e7b014f05a2/html5/thumbnails/33.jpg)