Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily...

45
Saving Energy in Existing Multifamily Buildings Duluth Energy Design Conference February, 2016 Corrie Bastian Center for Energy and Environment

Transcript of Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily...

Page 1: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Saving Energy in Existing Multifamily Buildings

Duluth Energy Design Conference February, 2016

Corrie Bastian Center for Energy and Environment

Page 2: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

InaccordancewiththeDepartmentofLaborandIndustry’sstatute326.0981,Subd.11,

“ThiseducaDonalofferingisrecognizedbytheMinnesotaDepartmentofLaborandIndustryas

saDsfying1hourofcredittowardBuildingOfficialsconDnuingeducaDonrequirements.”

ForaddiDonalconDnuingeducaDonapprovals,pleaseseeyourcredittrackingcard.

Page 3: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 3

Topics

• Who is CEE •  Energy use in multifamily buildings •  Perspective: Understanding the industry •  Retrofit highlights

•  Energy impact •  Marketability •  Ensuring success: I, O & M best practices

Page 4: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 4

Who is CEE

The Center for Energy and Environment (CEE) is a nonprofit organization that promotes energy efficiency to strengthen the economy while improving the environment We conduct research and develop programs so that:

•  Businesses operate more efficiently and profitably; •  Government agencies and nonprofits spend less on facilities

and functions; •  Utilities achieve their energy-efficiency goals at least-cost; and •  Households save money and improve comfort.

Page 5: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 5

What we do

•  Energy Program Design and Delivery •  Engineering Services •  Public Policy •  Lending Center •  Innovation Exchange

•  Research •  Education and Outreach

Page 6: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 6

CEE multifamily experience

•  Facility assessments of over 2,000 buildings in Minnesota

•  Completed over 20 research projects

Page 7: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 7

Current multifamily research projects

•  Condensing boiler optimization • Multifamily ventilation optimization •  Demand Controller recirculation loop controls • Multifamily aerosol envelope air sealing •  Indoor pool optimization

All funded through the MN Department of Commerce’s Conservation Applied Research and Development grant program.

Page 8: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 8

Current multifamily energy efficiency programs

•  Energy Star multifamily 3rd party verifier • One Stop Efficiency Shop lighting program with

Xcel Energy • Multifamily Energy Savings program with

MN Energy Resources

Page 9: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Understanding multifamily buildings

Page 10: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 10

What we know about multifamily buildings

“Multifamily buildings are a tough energy efficiency nut to crack”

Why? •  “Split incentive” / diverging interests between

resident and owner •  “Lots of players in the orchestra” •  Perception that technical challenges outweigh

financial benefits

Page 11: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 11

Market research on multifamily building owners and managers reveals perceptions of energy efficiency

•  “Expensive” •  “Complex maintenance and upkeep” •  “Realized savings are questionable” •  “Improved comfort is a big benefit” •  “Has to be durable” •  “Trustworthy energy

efficiency advice is needed”

Page 12: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 12

MN multifamily buildings are relatively “fit” buildings

SOURCE:MinnesotaMulDfamilyRentalCharacterizaDonStudy,EnergyCenterofWisconsinandFranklinEnergy,2013;sampled120bldgsinMN(78inTwinCiDes,66GreaterMN)

•  Natural gas = common

heating fuel (~66%) •  Central hydronic =

common heat system (83%)

4-6BTU/`2/HDD

Page 13: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 13

…And yet outliers in (almost) every category

SOURCE:MinnesotaMulDfamilyRentalCharacterizaDonStudy,EnergyCenterofWisconsinandFranklinEnergy,2013;sampled120bldgsinMN(78inTwinCiDes,66GreaterMN)

Page 14: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 14

Water and space heating costs dominate

SOURCE:MinnesotaMulDfamilyRentalCharacterizaDonStudy,EnergyCenterofWisconsinandFranklinEnergy,2013;sampled120bldgsinMN(78inTwinCiDes,66GreaterMN)

=40%

=15%

=10%

=34%

Average Multifamily Utility Costs (per unit / year)

Page 15: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 15

…And yet they are a small piece of the expense pie

Payroll&Benefits19%

Insurance4%

Taxes17%

MgmntFee8%

Admin4%

Water&

Sewer5%

Elec.3%

Gas4%

Trash,Cable,Misc.4%

Repairs27%

MarkeUng2%

Other3%

UUliUes=12%

Source:2013MNMul*HousingAssocia*onExpensesurvey.388mulDfamilyproperDessurveyed

Average MN Multifamily operating expenses

Page 16: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

A good investment…

q Has aggressive energy paybacks

q  Lowers O & M costs q  Improves building comfort q  Makes things easier for staff q  Is “tried and true” q  Is easy to implement

i.e. Energy efficiency marketability goes well beyond payback

Page 17: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Marketable energy efficiency strategies for MN multifamily

Page 18: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 18

Good opportunities for energy savings – beyond “the laundry list”

•  Optimizing existing condensing boilers •  Building ventilation modifications •  Demand-based hot water recirculation loop controls •  Aerosol envelope air sealing

Page 19: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 19

Acknowledgements

Projects discussed are supported in part by a grant from the Minnesota Department of Commerce, Division of Energy Resources through a Conservation Applied Research and Development (CARD) program

Page 20: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Optimizing condensing boilers

Page 21: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Conventional boiler

ßSupply

ßReturn

Page 22: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 22

Condensing boiler

Page 23: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 23

Achieving rated efficiency (>90% efficiency)

CONDENSINGTEMPS

Return water temperature

Page 24: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 24

Condensing?

Page 25: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Benefits

•  4-10% of gained efficiency •  Eliminate short-cycling • Getting what you paid “extra” for

Page 26: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

THE KEY: Driving down return water temperature

• Maximize heat transfer at heating elements •  Send lower temp water out to the building • Make sure boiler output matches demand • Make sure your piping isn’t dumping supply water into

return • Make sure domestic hot water is not integrated with

space heating boiler

Page 27: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

How?

•  Considerations for an existing condensing system •  Proper excess air levels •  Adjusting outdoor reset and sequencing/staging controls •  Reducing maximum output temp •  VFD pumping for increased heat transfer

• OR Considerations at time of replacement •  Boiler room piping •  Choosing a boiler with good on board reset and sequencing/

staging controls

Page 28: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 28

Excess air can dictate boiler efficiency

Imagesource:industrialheaDng.com

A

DJU

STM

ENT

RA

NG

E

Measured as % Oxygen in flue gas

Page 29: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 29

Condensing boiler sensitivity to excess air

•  Controlling excess air very important •  Excess air reduces concentration of

water vapor •  Dewpoint decreases

LowExcessAir

HighExcessAir

Page 30: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 30

Oxygen levels in flue gas

Page 31: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Heating elements: You’re stuck with them •  It isn’t cost effective to add more •  Dirty or blocked radiation affects heat transfer

Page 32: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Control boilers for lowest possible output

• Optimized outdoor reset •  Finding the lowest max output temp for the building •  Sequencing and staging for optimal efficiency

Page 33: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 33

Control the boiler so it doesn’t exceed demand

20°F in March

Page 34: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Pg. 34

Outdoor reset lowers boiler water temperature As outdoor temps get warmer, the building heating load gets smaller and the boiler water

temperature can be lowered.

-20°F

0°F

20°F

40°F

60°F

80°F

100°F

120°F

140°F

160°F

180°F

Boilerwatertemperaturewithoutdoorreset

Space75°F

Boilerwatertemperature,nocontrol

Page 35: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Optimizing outdoor reset

MinOATforcondensingmovedfrom34°Fto22°FCanyougolower?

Boilerw

aterte

mp

OutdoortempAdjustedsupplycurve

Adjustedreturncurve

Page 36: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Outdoor reset adjustment

14 unit building: 9.5% space heating savings (no cost) Reduced building over-heating

Page 37: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

At replacement: Identify boiler control limitations •  This boiler control’s non-adjustable minimum outside

temp of 0°F is not ideal for MN

Page 38: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Boiler sequence and firing stage controls: matching output to load for best efficiency

Loweroutputfiringstageshaveincreasedthermalefficiency

Imagesource:Lochinvar.com

Page 39: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Lochinvar Knight boiler cascade strategies:

Imagesource:lochinvar.com

Page 40: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Sequencing boilers: mixed efficiency

41 unit building: 11% space heating savings 3 year payback Reduced short-cycling

Page 41: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Sequencing/staging: All firing on at once because they can’t talk to each other

32 unit building: 6% space heating savings 5 year payback Reduced short-cycling

Page 42: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Variable speed pumps (VFDs, VSDs)

•  Reduce the pump flow during part-load (when zones close)

•  Allows for lowered return water temperature—more potential boiler condensing conditions

•  Electricity savings

Page 43: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Little difference between boiler supply and return temperatures indicates potential for improvement

1- Adjust reset temps as low as possible 2- VFD pump control optimizes heat transfer as zones

open and close

Page 44: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Boiler room piping: address at replacement

1

2

3

4

RETURNBuildingloop

Not ideal: Adjacent boilers warm return water

Page 45: Saving Energy in Existing Multifamily Buildings...• Condensing boiler optimization • Multifamily ventilation optimization • Demand Controller recirculation loop controls •

Better piping

1

2

3

4

RETURNBuildingloop