MRC CONNECTED LOAD AND HVAC SURVEY
Transcript of MRC CONNECTED LOAD AND HVAC SURVEY
H. LEE MOFFITT CANCER CENTERMRC CONNECTED LOAD AND HVAC SURVEY
12902 USF MAGNOLIA DRIVE TAMPA, FLORIDA
CERTIFIED TEST; ADJUST; BALANCE REPORT
ARCHITECT: NOT APPLICABLE
ENGINEER: NOT APPLICABLE
CONTRACTOR: NOT APPLICABLE
PROJECT # P3604
DATE: 09/09/2021
Phone: 813-621-5888 Fax: 813-621-5885
Table of Contents
Report Summary 1Instrument List 2Abbreviations 3Air Handling Unit 4Balance Valve 21
September 9, 2021
H. Lee MoffittMRC Connected Load & HVAC Survey12902 USF Magnolia DriveTampa, Florida
General: The data contained in this report has been accumulated from the equipment and systems
actually installed at the project. The results of our testing and balancing service are documented in
the following report. All measurements and procedures follow the 2019-Ninth Edition of the
Procedural Standard for Testing, Adjusting, and Balancing of Environmental Systems published by
the National Environmental Balancing Bureau and are true and correct as of our test date and are
within the limits of field error.
Ceiling mounted grilles and registers were measured using a calibrated flow hood or
traverse method. Sidewall grilles and registers were measured using a rotating vane anemometer,
digital anemometer, or flow hood. There were no adjustments made to the HVAC systems. The
data was measured and recorded to document existing conditions.
We believe this report is self-explanatory in its entirety. However, if any questions arise;
please do not hesitate to contact us.
Pro-Tech Diversified Services, Inc.
1
INSTRUMENTATION LIST
Model Number Serial Number Calibration Date
EBT-731 04/26/21
EBT-731 04/26/21
RVA801
73181406
73181406
A05266 10/12/20
HM-680 70748148 10/28/20
RH-390 180813979 10/09/20
EA10 120802154 09/23/20
325 44160607WS 09/22/20
MT-200 B184B5012P 09/23/20
160-18
N/A
160-24
N/A
160-36
N/A
160-48
N/A
Instrument
TSI Balometer
TSI Micromanometer
TSI Rotating Vane Anemometer
TSI Hydronic Manometer
Extech Digital Psychrometer
Extech Digital Thermometer
Fluke Current – Current Clamp Meter
Nidec-Shimpo Tachometer
Fuji FSCS Ultrasonic Flow Meter
Dwyer 18” Standard Airfoil Tube
Dwyer 24” Standard Pitot Tube
Dwyer 36” Standard Airfoil Tube
Dwyer 48” Standard Pitot Tube
Dwyer 60” Standard Airfoil Tube 160-60
N/A
FSCS N0F0843T 11/30/20
2
ABBREVIATIONS
ADJ ADJUSTABLE
AHU AIR HANDLING UNIT
BHP BRAKE HORSEPOWER
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CRU COMPUTER ROOM UNIT
D.D. DIRECT DRIVE
EP ELECTRONICALLY PROTECTED
ERV ENERGY RECOVERY VENTILATOR
EXIST EXISTING
FCU FAN COIL UNIT
FPB FAN POWERED BOX
FPM FEET PER MINUTE
FT FEET
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
HPU HEAT PUMP UNIT
HZ HERTZ
MUA MAKE UP AIR
MAU MAKE-UP AIR UNIT
MED MEDIUM
N/A NO ACCESS
N/G NOT GIVEN
O/A OUTSIDE AIR
OAU OUTSIDE AIR UNIT
OBD OPPOSED BLADE DAMPER
OED OPEN END DUCT
PPM PARTS PER MILLION
R/A RETURN AIR
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
S/A SUPPLY AIR
SP STATIC PRESSURE
SPD SPEED
TP THERMALLY PROTECTED
VFD VARIABLE FREQUENCY DRIVE
VFPM VELOCITY FEET PER MINUTE
VSC VARIABLE SPEED CONTROL
WG WATER GAUGE
WSAC WATER SOURCE AIR CONDITIONER
WSCRU WATER SOURCE COMPUTER ROOM UNIT
WSHP WATER SOURCE HEAT PUMP
3
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 2-8
Unit DataUnit Manufacturer McQuayUnit Model Number M5L1340HUnit Serial Number 3ZK00437-04Unit Discharge UPBLAST
Final Test DataVFD at Final test 60.0 HZ
Test DataSupply Air Actual 17285 CFMOutside Air Actual 17285 CFM
Electrical Test DataAHU 2-8/Supply Fan
Motor Volts T1-T2 474Motor Volts T2-T3 473Motor Volts T1-T3 473Motor Amps T1 20.8Motor Amps T2 20.7Motor Amps T3 20.7
Coil Air Test DataAHU 2-8/Cooling Coil-01
Actual Coil Airflow 17285 CFM
TemperatureAHU 2-8/Cooling Coil-01
ENT Air DB Temp Actual 73.7 Deg FENT Air WB Temp Actual 64.0 Deg FLVG Air DB Temp Actual 51.5 Deg FLVG Air WB Temp Actual 50.4 Deg FSensible Capacity Actual 416,344 BTU/HRTotal Capacity Actual 683,708 BTU/HR
Motor DataAHU 2-8/Supply Fan
Manufacturer BaldorFrame 284TNameplate HP 25.00Operating BHP 17.34Nameplate RPM 1760Actual RPM 1784Phase 3Nameplate Volts 230/460Hertz 60FL Amps 31Corrected FLA 30.1Service Factor 1.15Efficiency % 0.917Power Factor 0.83VFD @ Final Test 60.0 Hz
Sheave DataAHU 2-8/Supply Fan
Drive Type BeltMotor Sheave MFG Not LegibleMotor Sheave Model Not LegibleMotor Sheave Diam. 7-1/4 in.Motor Sheave Bore 1-7/8 in.Sheave Open Turns FIXEDFan Sheave MFG Not LegibleFan Sheave Model Not LegibleFan Sheave Diam. 8-1/4 in.Fan Sheave Bore 2-7/16 in.Number of Belts 2Belt Manufacturer CarlisleBelt Size BX66Sheave Center Line 23.5 in.Actual Fan RPM 1531
Coil Water Test DataAHU 2-8/Cooling Coil-01
Coil GPM Actual 104.3EWT Actual 44.2 Deg FLWT Actual 51.5 Deg FWater Delta T Actual 7.3 Deg FCoil Inlet PSI Actual 78.0Coil Outlet PSI Actual 65.1Coil DP Actual 29.8 Ft. H20Ultrasonic Reading 104.3 GPM
Filter DataAHU 2-8/SF Filter Bank
Manufacturer KOCHFilter Type PleatedFilter Quantity - Size 1 10
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 4
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 2-8
Filter DataAHU 2-8/SF Filter Bank
Filter Dimensions - Size 1 24x24x2Filter Quantity - Size 2 10Filter Dimensions - Size 2 24x24x4
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 2-8/SPP-01
Test PressuresPre Filter SP In -0.07 in. w.c.Pre Filter SP Out -0.29 in. w.c.Cooling Coil SP In -0.54 in. w.c.Cooling Coil SP Out -2.84 in. w.c.Heating Coil SP In -0.29 in. w.c.Heating Coil SP Out -0.54 in. w.c.Supply Fan SP In -2.84 in. w.c.Supply Fan SP Out 0.71 in. w.c.ESP Actual 0.78 in. w.c.TSP Actual 3.55 in. w.c.
Static Pressure Profile
ESP Actual 0.78TSP Actual 3.55
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 5
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 2-8/Main Supply
Traverse Data Points
Ductwork DataHeight 38.0 in.Width 42.00 in.Air Flow Area 11.08 sq. ft.Location of Holes 1 Bottom
Traverse SummaryCFM Design N/GCFM Actual 17285Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 7Readings Per Row 7Total Readings 49Sum of Readings 76450Average Velocity 1560 FPMStatic Pressure 0.47 Inches w.c.Air Temperature 65.5 Deg FFan Speed/RPM 1531
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 6
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-2
Unit DataUnit Manufacturer CarrierUnit Model Number 39ED 48Unit Serial Number 3888 T 12745Unit Discharge UPBLAST
Test DataSupply Air Actual 10156 CFMOutside Air Actual 940 CFMReturn Air Actual 9216 CFMO/A Damper Pos 24 % open
Electrical Test DataAHU 3-2 /Supply Fan
Motor Volts T1-T2 474Motor Volts T2-T3 474Motor Volts T1-T3 473Motor Amps T1 22.5Motor Amps T2 22.6Motor Amps T3 22.6
Coil Air Test DataAHU 3-2 /Cooling Coil-01
Actual Coil Airflow 10156 CFM
TemperatureAHU 3-2 /Cooling Coil-01
ENT Air DB Temp Actual 74.6 Deg FENT Air WB Temp Actual 65.6 Deg FLVG Air DB Temp Actual 54.8 Deg FLVG Air WB Temp Actual 54.1 Deg FSensible Capacity Actual 218,181 BTU/HRTotal Capacity Actual 358,304 BTU/HR
Motor DataAHU 3-2 /Supply Fan
Manufacturer MagnatekFrame 286TNameplate HP 30.00Operating BHP 18.85Nameplate RPM 1750Actual RPM 1774Phase 3Nameplate Volts 230/460Hertz 60FL Amps 37Corrected FLA 35.9Service Factor 1.15Efficiency % 0.883Power Factor 0.860
Sheave DataAHU 3-2 /Supply Fan
Drive Type BeltMotor Sheave MFG T.B. WoodsMotor Sheave Model 11.0x2B-SKMotor Sheave Diam. 11 in.Motor Sheave Bore SK1-7/8 in.Sheave Open Turns FIXEDFan Sheave MFG T.B. WoodsFan Sheave Model 13.6x2B-SKFan Sheave Diam. 13.6 in.Fan Sheave Bore SK2-7/16 in.Number of Belts 2Belt Manufacturer CarlisleBelt Size B97Sheave Center Line 30.0 in.Actual Fan RPM 1442
Coil Water Test DataAHU 3-2 /Cooling Coil-01
Coil GPM Actual 92.3EWT Actual 44.2 Deg FLWT Actual 59.9 Deg FWater Delta T Actual 15.7 Deg FCoil Inlet PSI Actual 62.0Coil Outlet PSI Actual 51.5Coil DP Actual 24.2 Ft. H20Ultrasonic Reading 92.3 GPM
Filter DataAHU 3-2 /SF Filter Bank
Manufacturer AAFFilter Type PleatedFilter Quantity - Size 1 15Filter Dimensions - Size 1 24x24x2
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 7
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-2
Filter DataAHU 3-2 /SF Filter Bank
Filter Quantity - Size 2 3Filter Dimensions - Size 2 20x24x2
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-2 /SPP-01
Test PressuresPre Filter SP In -0.03 in. w.c.Pre Filter SP Out -0.09 in. w.c.Cooling Coil SP In -0.09 in. w.c.Cooling Coil SP Out -0.27 in. w.c.Supply Fan SP In -0.27 in. w.c.Supply Fan SP Out 0.85 in. w.c.ESP Actual 0.88 in. w.c.TSP Actual 1.12 in. w.c.
Static Pressure Profile
ESP Actual 0.88TSP Actual 1.12
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 8
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-2 /Main Return (From 2nd Floor)
Traverse Data Points
Ductwork DataHeight 18.0 in.Width 54.00 in.Air Flow Area 6.75 sq. ft.Location of Holes 1 Bottom
Traverse SummaryCFM Design N/GCFM Actual 3719Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 7Readings Per Row 4Total Readings 28Sum of Readings 15421Average Velocity 551 FPMStatic Pressure -0.04 Inches w.c.Air Temperature 74.1 Deg FFan Speed/RPM 1442
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 9
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-2 /Main Return (From 3rd Floor)
Traverse Data Points
Ductwork DataHeight 18.0 in.Width 54.00 in.Air Flow Area 6.75 sq. ft.Location of Holes 1 Bottom
Traverse SummaryCFM Design N/GCFM Actual 3227Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 7Readings Per Row 4Total Readings 28Sum of Readings 13390Average Velocity 478 FPMStatic Pressure -0.04 Inches w.c.Air Temperature 74.4 Deg FFan Speed/RPM 1442
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 10
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-2 /Outside Air Intake
Traverse Data Points
Ductwork DataHeight 16.0 in.Width 24.00 in.Air Flow Area 2.67 sq. ft.Location of Holes 1 Bottom
Traverse SummaryCFM Design N/GCFM Actual 940Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 5Readings Per Row 4Total Readings 20Sum of Readings 7049Average Velocity 352 FPMStatic Pressure -0.03 Inches w.c.Air Temperature 75.2 Deg FFan Speed/RPM 1442
System/Unit Area Served Inlet Type Size AK Factor
Design Reading
Prelim Reading
Final Reading
Final VFPM
% Final Deviation
Inlet-01 3049 EXIST 24X24 3.83 N/G 2270 2270 592Totals: - - - 0 2270 2270 - 0
AHU 3-2 Return Inlet Summary
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 11
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-3A
Log: AHU 3-3A/Supply Fan 9/1/2021 Roddy Quinones No Access to the motor information.
Unit DataUnit Manufacturer Trane
Unit Model Number BCH090G1A0A3M07R2200ACBC100
Unit Serial Number T07B08949Unit Discharge HORIZONTAL
Test DataSupply Air Actual 3269 CFMOutside Air Actual 368 CFMReturn Air Actual 2902 CFMTotal Outlet Readings 3269 CFMO/A Damper Pos 100 % open
Electrical Test DataAHU 3-3A/Supply Fan
Motor Volts T1-T2 474Motor Volts T2-T3 474Motor Volts T1-T3 473Motor Amps T1 3.4Motor Amps T2 3.4Motor Amps T3 3.6
Coil Air Test DataAHU 3-3A/Cooling Coil-01
Actual Coil Airflow 3269 CFM
TemperatureAHU 3-3A/Cooling Coil-01
ENT Air DB Temp Actual 75.3 Deg FENT Air WB Temp Actual 64.4 Deg FLVG Air DB Temp Actual 54.6 Deg FLVG Air WB Temp Actual 54.1 Deg FSensible Capacity Actual 73,420 BTU/HRTotal Capacity Actual 101944 BTU/HR
Motor DataAHU 3-3A/Supply Fan
Manufacturer No AccessFrame No AccessNameplate HP 3.00Nameplate RPM No AccessActual RPM No AccessPhase 3Hertz 60FL Amps 4.3Corrected FLA 4.2
Sheave DataAHU 3-3A/Supply Fan
Drive Type BeltActual Fan RPM No Access
Filter DataAHU 3-3A/SF Filter Bank
Manufacturer KOCHFilter Type PleatedFilter Quantity - Size 1 6Filter Dimensions - Size 1 16x20x2
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 12
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-3A/SPP-01
Test PressuresPre Filter SP In -0.39 in. w.c.Pre Filter SP Out -0.65 in. w.c.Cooling Coil SP In -0.65 in. w.c.Cooling Coil SP Out -1.19 in. w.c.Supply Fan SP In -1.19 in. w.c.Supply Fan SP Out 0.34 in. w.c.ESP Actual 0.73 in. w.c.TSP Actual 1.53 in. w.c.
Static Pressure Profile
ESP Actual 0.73TSP Actual 1.53
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 13
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-3A/Outside Air Intake
Traverse Data Points
Ductwork DataDiameter 12.00 in.Air Flow Area 0.79 sq. ft.
Traverse SummaryCFM Design N/GCFM Actual 368Test Instrument AirfoilType of Traverse RoundNumber Of Rows 2Readings Per Row 8Total Readings 16Sum of Readings 7453Average Velocity 466 FPMStatic Pressure -0.31 Inches w.c.Air Temperature 74.8 Deg F
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 14
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
System/Unit Mfg. Model Valve Position
Size Design GPM
Indicated Flow
Valve-01 ARMSTRONG CBV 3.2 1-1/2 N/GTotals: - - - - - -
AHU 3-3A Balance Valve Summary
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 15
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-5
Unit DataUnit Manufacturer McQuayUnit Model Number LSL114DVUnit Serial Number 32K0036-04Unit Discharge UPBLAST
Test DataSupply Air Actual 4983 CFMOutside Air Actual 331 CFMReturn Air Actual 4652 CFMO/A Damper Pos 20 % open
Electrical Test DataAHU 3-5/Supply Fan
Motor Volts T1-T2 473Motor Volts T2-T3 474Motor Volts T1-T3 473Motor Amps T1 5.7Motor Amps T2 5.7Motor Amps T3 5.6
Coil Air Test DataAHU 3-5/Cooling Coil-01
Actual Coil Airflow 4983 CFM
TemperatureAHU 3-5/Cooling Coil-01
ENT Air DB Temp Actual 77.5 Deg FENT Air WB Temp Actual 65.9 Deg FLVG Air DB Temp Actual 55.3 Deg FLVG Air WB Temp Actual 54.6 Deg FSensible Capacity Actual 120,026 BTU/HRTotal Capacity Actual 174,231 BTU/HR
Motor DataAHU 3-5/Supply Fan
Manufacturer BaldorFrame 213TNameplate HP 7.50Operating BHP 4.53Nameplate RPM 1760Actual RPM 1783Phase 3Nameplate Volts 230/460Hertz 60FL Amps 9.3Corrected FLA 9.0Service Factor 1.15Efficiency % 0.91Power Factor 0.80
Sheave DataAHU 3-5/Supply Fan
Drive Type BeltMotor Sheave MFG BrowningMotor Sheave Model 2VP60Motor Sheave Diam. 6 in.Motor Sheave Bore 1-3/8 in.Sheave Open Turns 4.5Fan Sheave MFG BrowningFan Sheave Model 2BK95HFan Sheave Diam. 9-1/2 in.Fan Sheave Bore H1-7/16 in.Number of Belts 2Belt Manufacturer GatesBelt Size BX65Sheave Center Line 21.5 in.Actual Fan RPM 1089
Coil Water Test DataAHU 3-5/Cooling Coil-01
Coil GPM Actual 49.5EWT Actual 44.2 Deg FLWT Actual 52.4 Deg FWater Delta T Actual 8.2 Deg FCoil Inlet PSI Actual 70.1Coil Outlet PSI Actual 67.2Coil DP Actual 6.7 Ft. H20
Filter DataAHU 3-5/SF Filter Bank
Manufacturer KOCHFilter Type PleatedFilter Quantity - Size 1 8Filter Dimensions - Size 1 20x25x2
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 16
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-5
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-5/SPP-01
Test PressuresPre Filter SP In -0.22 in. w.c.Pre Filter SP Out -0.62 in. w.c.Cooling Coil SP In -0.61 in. w.c.Cooling Coil SP Out -1.01 in. w.c.Supply Fan SP In -1.01 in. w.c.Supply Fan SP Out 1.11 in. w.c.ESP Actual 1.33 in. w.c.TSP Actual 2.12 in. w.c.
Static Pressure Profile
ESP Actual 1.33TSP Actual 2.12
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 17
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-5/Main Supply
Traverse Data Points
Ductwork DataHeight 18.0 in.Width 44.00 in.Air Flow Area 5.50 sq. ft.Location of Holes 1 Right
Traverse SummaryCFM Design N/GCFM Actual 4983Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 4Readings Per Row 7Total Readings 28Sum of Readings 25371Average Velocity 906 FPMStatic Pressure 0.98 Inches w.c.Air Temperature 65.1 Deg FFan Speed/RPM 1089
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 18
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-5/Outside Air Intake
Traverse Data Points
Ductwork DataHeight 10.0 in.Width 10.00 in.Air Flow Area 0.69 sq. ft.Location of Holes 1 Bottom
Traverse SummaryCFM Design N/GCFM Actual 331Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 3Readings Per Row 3Total Readings 9Sum of Readings 4321Average Velocity 480 FPMStatic Pressure -0.15 Inches w.c.Air Temperature 75.0 Deg FFan Speed/RPM 1089
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 19
Air Handling UnitPROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
System/Unit Mfg. Model Valve Position
Size Design GPM
Indicated Flow
Valve-01 ARMSTRONG CBV 4.0 2.00 N/G 49.5Totals: - - - - - -
AHU 3-5 Balance Valve Summary
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 20
Balance ValvePROJECT:LOCATION:
MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:
DATE:CONTACT:
9/9/2021Steven Mullins
Tested By: Roddy QuinonesDate: 9/1/2021
SYSTEM/UNIT: AHU 3-3A/Valve-01
Unit DataService CHILLED WATERMfg. ARMSTRONGModel CBVSize 1-1/2 INCHDesign GPM N/G
Test DataValve Position 3.2
Tested By: Roddy QuinonesDate: 9/2/2021
SYSTEM/UNIT: AHU 3-5/Valve-01
Unit DataService CHILLED WATERMfg. ARMSTRONGModel CBVSize 2.00 INCHDesign GPM N/G
Test DataValve DP Actual 4.55 Ft. H2oValve Position 4.0Indicated Flow 49.5 GPM
Pro-Tech Diversified Services, Inc.Professionals delivering Performance 21