MRC CONNECTED LOAD AND HVAC SURVEY

23
H. LEE MOFFITT CANCER CENTER MRC CONNECTED LOAD AND HVAC SURVEY 12902 USF MAGNOLIA DRIVE TAMPA, FLORIDA CERTIFIED TEST; ADJUST; BALANCE REPORT ARCHITECT: NOT APPLICABLE ENGINEER: NOT APPLICABLE CONTRACTOR: NOT APPLICABLE PROJECT # P3604 DATE: 09/09/2021 Phone: 813-621-5888 Fax: 813-621-5885

Transcript of MRC CONNECTED LOAD AND HVAC SURVEY

Page 1: MRC CONNECTED LOAD AND HVAC SURVEY

H. LEE MOFFITT CANCER CENTERMRC CONNECTED LOAD AND HVAC SURVEY

12902 USF MAGNOLIA DRIVE TAMPA, FLORIDA

CERTIFIED TEST; ADJUST; BALANCE REPORT

ARCHITECT: NOT APPLICABLE

ENGINEER: NOT APPLICABLE

CONTRACTOR: NOT APPLICABLE

PROJECT # P3604

DATE: 09/09/2021

Phone: 813-621-5888 Fax: 813-621-5885

Page 2: MRC CONNECTED LOAD AND HVAC SURVEY

Table of Contents

Report Summary 1Instrument List 2Abbreviations 3Air Handling Unit 4Balance Valve 21

Page 3: MRC CONNECTED LOAD AND HVAC SURVEY

September 9, 2021

H. Lee MoffittMRC Connected Load & HVAC Survey12902 USF Magnolia DriveTampa, Florida

General: The data contained in this report has been accumulated from the equipment and systems

actually installed at the project. The results of our testing and balancing service are documented in

the following report. All measurements and procedures follow the 2019-Ninth Edition of the

Procedural Standard for Testing, Adjusting, and Balancing of Environmental Systems published by

the National Environmental Balancing Bureau and are true and correct as of our test date and are

within the limits of field error.

Ceiling mounted grilles and registers were measured using a calibrated flow hood or

traverse method. Sidewall grilles and registers were measured using a rotating vane anemometer,

digital anemometer, or flow hood. There were no adjustments made to the HVAC systems. The

data was measured and recorded to document existing conditions.

We believe this report is self-explanatory in its entirety. However, if any questions arise;

please do not hesitate to contact us.

Pro-Tech Diversified Services, Inc.

1

Page 4: MRC CONNECTED LOAD AND HVAC SURVEY

INSTRUMENTATION LIST

Model Number Serial Number Calibration Date

EBT-731 04/26/21

EBT-731 04/26/21

RVA801

73181406

73181406

A05266 10/12/20

HM-680 70748148 10/28/20

RH-390 180813979 10/09/20

EA10 120802154 09/23/20

325 44160607WS 09/22/20

MT-200 B184B5012P 09/23/20

160-18

N/A

160-24

N/A

160-36

N/A

160-48

N/A

Instrument

TSI Balometer

TSI Micromanometer

TSI Rotating Vane Anemometer

TSI Hydronic Manometer

Extech Digital Psychrometer

Extech Digital Thermometer

Fluke Current – Current Clamp Meter

Nidec-Shimpo Tachometer

Fuji FSCS Ultrasonic Flow Meter

Dwyer 18” Standard Airfoil Tube

Dwyer 24” Standard Pitot Tube

Dwyer 36” Standard Airfoil Tube

Dwyer 48” Standard Pitot Tube

Dwyer 60” Standard Airfoil Tube 160-60

N/A

FSCS N0F0843T 11/30/20

2

Page 5: MRC CONNECTED LOAD AND HVAC SURVEY

ABBREVIATIONS

ADJ ADJUSTABLE

AHU AIR HANDLING UNIT

BHP BRAKE HORSEPOWER

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CRU COMPUTER ROOM UNIT

D.D. DIRECT DRIVE

EP ELECTRONICALLY PROTECTED

ERV ENERGY RECOVERY VENTILATOR

EXIST EXISTING

FCU FAN COIL UNIT

FPB FAN POWERED BOX

FPM FEET PER MINUTE

FT FEET

GPM GALLONS PER MINUTE

HD HEAD

HP HORSEPOWER

HPU HEAT PUMP UNIT

HZ HERTZ

MUA MAKE UP AIR

MAU MAKE-UP AIR UNIT

MED MEDIUM

N/A NO ACCESS

N/G NOT GIVEN

O/A OUTSIDE AIR

OAU OUTSIDE AIR UNIT

OBD OPPOSED BLADE DAMPER

OED OPEN END DUCT

PPM PARTS PER MILLION

R/A RETURN AIR

RH RELATIVE HUMIDITY

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

S/A SUPPLY AIR

SP STATIC PRESSURE

SPD SPEED

TP THERMALLY PROTECTED

VFD VARIABLE FREQUENCY DRIVE

VFPM VELOCITY FEET PER MINUTE

VSC VARIABLE SPEED CONTROL

WG WATER GAUGE

WSAC WATER SOURCE AIR CONDITIONER

WSCRU WATER SOURCE COMPUTER ROOM UNIT

WSHP WATER SOURCE HEAT PUMP

3

Page 6: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 2-8

Unit DataUnit Manufacturer McQuayUnit Model Number M5L1340HUnit Serial Number 3ZK00437-04Unit Discharge UPBLAST

Final Test DataVFD at Final test 60.0 HZ

Test DataSupply Air Actual 17285 CFMOutside Air Actual 17285 CFM

Electrical Test DataAHU 2-8/Supply Fan

Motor Volts T1-T2 474Motor Volts T2-T3 473Motor Volts T1-T3 473Motor Amps T1 20.8Motor Amps T2 20.7Motor Amps T3 20.7

Coil Air Test DataAHU 2-8/Cooling Coil-01

Actual Coil Airflow 17285 CFM

TemperatureAHU 2-8/Cooling Coil-01

ENT Air DB Temp Actual 73.7 Deg FENT Air WB Temp Actual 64.0 Deg FLVG Air DB Temp Actual 51.5 Deg FLVG Air WB Temp Actual 50.4 Deg FSensible Capacity Actual 416,344 BTU/HRTotal Capacity Actual 683,708 BTU/HR

Motor DataAHU 2-8/Supply Fan

Manufacturer BaldorFrame 284TNameplate HP 25.00Operating BHP 17.34Nameplate RPM 1760Actual RPM 1784Phase 3Nameplate Volts 230/460Hertz 60FL Amps 31Corrected FLA 30.1Service Factor 1.15Efficiency % 0.917Power Factor 0.83VFD @ Final Test 60.0 Hz

Sheave DataAHU 2-8/Supply Fan

Drive Type BeltMotor Sheave MFG Not LegibleMotor Sheave Model Not LegibleMotor Sheave Diam. 7-1/4 in.Motor Sheave Bore 1-7/8 in.Sheave Open Turns FIXEDFan Sheave MFG Not LegibleFan Sheave Model Not LegibleFan Sheave Diam. 8-1/4 in.Fan Sheave Bore 2-7/16 in.Number of Belts 2Belt Manufacturer CarlisleBelt Size BX66Sheave Center Line 23.5 in.Actual Fan RPM 1531

Coil Water Test DataAHU 2-8/Cooling Coil-01

Coil GPM Actual 104.3EWT Actual 44.2 Deg FLWT Actual 51.5 Deg FWater Delta T Actual 7.3 Deg FCoil Inlet PSI Actual 78.0Coil Outlet PSI Actual 65.1Coil DP Actual 29.8 Ft. H20Ultrasonic Reading 104.3 GPM

Filter DataAHU 2-8/SF Filter Bank

Manufacturer KOCHFilter Type PleatedFilter Quantity - Size 1 10

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 4

Page 7: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 2-8

Filter DataAHU 2-8/SF Filter Bank

Filter Dimensions - Size 1 24x24x2Filter Quantity - Size 2 10Filter Dimensions - Size 2 24x24x4

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 2-8/SPP-01

Test PressuresPre Filter SP In -0.07 in. w.c.Pre Filter SP Out -0.29 in. w.c.Cooling Coil SP In -0.54 in. w.c.Cooling Coil SP Out -2.84 in. w.c.Heating Coil SP In -0.29 in. w.c.Heating Coil SP Out -0.54 in. w.c.Supply Fan SP In -2.84 in. w.c.Supply Fan SP Out 0.71 in. w.c.ESP Actual 0.78 in. w.c.TSP Actual 3.55 in. w.c.

Static Pressure Profile

ESP Actual 0.78TSP Actual 3.55

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 5

Page 8: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 2-8/Main Supply

Traverse Data Points

Ductwork DataHeight 38.0 in.Width 42.00 in.Air Flow Area 11.08 sq. ft.Location of Holes 1 Bottom

Traverse SummaryCFM Design N/GCFM Actual 17285Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 7Readings Per Row 7Total Readings 49Sum of Readings 76450Average Velocity 1560 FPMStatic Pressure 0.47 Inches w.c.Air Temperature 65.5 Deg FFan Speed/RPM 1531

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 6

Page 9: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-2

Unit DataUnit Manufacturer CarrierUnit Model Number 39ED 48Unit Serial Number 3888 T 12745Unit Discharge UPBLAST

Test DataSupply Air Actual 10156 CFMOutside Air Actual 940 CFMReturn Air Actual 9216 CFMO/A Damper Pos 24 % open

Electrical Test DataAHU 3-2 /Supply Fan

Motor Volts T1-T2 474Motor Volts T2-T3 474Motor Volts T1-T3 473Motor Amps T1 22.5Motor Amps T2 22.6Motor Amps T3 22.6

Coil Air Test DataAHU 3-2 /Cooling Coil-01

Actual Coil Airflow 10156 CFM

TemperatureAHU 3-2 /Cooling Coil-01

ENT Air DB Temp Actual 74.6 Deg FENT Air WB Temp Actual 65.6 Deg FLVG Air DB Temp Actual 54.8 Deg FLVG Air WB Temp Actual 54.1 Deg FSensible Capacity Actual 218,181 BTU/HRTotal Capacity Actual 358,304 BTU/HR

Motor DataAHU 3-2 /Supply Fan

Manufacturer MagnatekFrame 286TNameplate HP 30.00Operating BHP 18.85Nameplate RPM 1750Actual RPM 1774Phase 3Nameplate Volts 230/460Hertz 60FL Amps 37Corrected FLA 35.9Service Factor 1.15Efficiency % 0.883Power Factor 0.860

Sheave DataAHU 3-2 /Supply Fan

Drive Type BeltMotor Sheave MFG T.B. WoodsMotor Sheave Model 11.0x2B-SKMotor Sheave Diam. 11 in.Motor Sheave Bore SK1-7/8 in.Sheave Open Turns FIXEDFan Sheave MFG T.B. WoodsFan Sheave Model 13.6x2B-SKFan Sheave Diam. 13.6 in.Fan Sheave Bore SK2-7/16 in.Number of Belts 2Belt Manufacturer CarlisleBelt Size B97Sheave Center Line 30.0 in.Actual Fan RPM 1442

Coil Water Test DataAHU 3-2 /Cooling Coil-01

Coil GPM Actual 92.3EWT Actual 44.2 Deg FLWT Actual 59.9 Deg FWater Delta T Actual 15.7 Deg FCoil Inlet PSI Actual 62.0Coil Outlet PSI Actual 51.5Coil DP Actual 24.2 Ft. H20Ultrasonic Reading 92.3 GPM

Filter DataAHU 3-2 /SF Filter Bank

Manufacturer AAFFilter Type PleatedFilter Quantity - Size 1 15Filter Dimensions - Size 1 24x24x2

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 7

Page 10: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-2

Filter DataAHU 3-2 /SF Filter Bank

Filter Quantity - Size 2 3Filter Dimensions - Size 2 20x24x2

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-2 /SPP-01

Test PressuresPre Filter SP In -0.03 in. w.c.Pre Filter SP Out -0.09 in. w.c.Cooling Coil SP In -0.09 in. w.c.Cooling Coil SP Out -0.27 in. w.c.Supply Fan SP In -0.27 in. w.c.Supply Fan SP Out 0.85 in. w.c.ESP Actual 0.88 in. w.c.TSP Actual 1.12 in. w.c.

Static Pressure Profile

ESP Actual 0.88TSP Actual 1.12

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 8

Page 11: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-2 /Main Return (From 2nd Floor)

Traverse Data Points

Ductwork DataHeight 18.0 in.Width 54.00 in.Air Flow Area 6.75 sq. ft.Location of Holes 1 Bottom

Traverse SummaryCFM Design N/GCFM Actual 3719Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 7Readings Per Row 4Total Readings 28Sum of Readings 15421Average Velocity 551 FPMStatic Pressure -0.04 Inches w.c.Air Temperature 74.1 Deg FFan Speed/RPM 1442

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 9

Page 12: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-2 /Main Return (From 3rd Floor)

Traverse Data Points

Ductwork DataHeight 18.0 in.Width 54.00 in.Air Flow Area 6.75 sq. ft.Location of Holes 1 Bottom

Traverse SummaryCFM Design N/GCFM Actual 3227Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 7Readings Per Row 4Total Readings 28Sum of Readings 13390Average Velocity 478 FPMStatic Pressure -0.04 Inches w.c.Air Temperature 74.4 Deg FFan Speed/RPM 1442

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 10

Page 13: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-2 /Outside Air Intake

Traverse Data Points

Ductwork DataHeight 16.0 in.Width 24.00 in.Air Flow Area 2.67 sq. ft.Location of Holes 1 Bottom

Traverse SummaryCFM Design N/GCFM Actual 940Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 5Readings Per Row 4Total Readings 20Sum of Readings 7049Average Velocity 352 FPMStatic Pressure -0.03 Inches w.c.Air Temperature 75.2 Deg FFan Speed/RPM 1442

System/Unit Area Served Inlet Type Size AK Factor

Design Reading

Prelim Reading

Final Reading

Final VFPM

% Final Deviation

Inlet-01 3049 EXIST 24X24 3.83 N/G 2270 2270 592Totals: - - - 0 2270 2270 - 0

AHU 3-2 Return Inlet Summary

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 11

Page 14: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-3A

Log: AHU 3-3A/Supply Fan 9/1/2021 Roddy Quinones No Access to the motor information.

Unit DataUnit Manufacturer Trane

Unit Model Number BCH090G1A0A3M07R2200ACBC100

Unit Serial Number T07B08949Unit Discharge HORIZONTAL

Test DataSupply Air Actual 3269 CFMOutside Air Actual 368 CFMReturn Air Actual 2902 CFMTotal Outlet Readings 3269 CFMO/A Damper Pos 100 % open

Electrical Test DataAHU 3-3A/Supply Fan

Motor Volts T1-T2 474Motor Volts T2-T3 474Motor Volts T1-T3 473Motor Amps T1 3.4Motor Amps T2 3.4Motor Amps T3 3.6

Coil Air Test DataAHU 3-3A/Cooling Coil-01

Actual Coil Airflow 3269 CFM

TemperatureAHU 3-3A/Cooling Coil-01

ENT Air DB Temp Actual 75.3 Deg FENT Air WB Temp Actual 64.4 Deg FLVG Air DB Temp Actual 54.6 Deg FLVG Air WB Temp Actual 54.1 Deg FSensible Capacity Actual 73,420 BTU/HRTotal Capacity Actual 101944 BTU/HR

Motor DataAHU 3-3A/Supply Fan

Manufacturer No AccessFrame No AccessNameplate HP 3.00Nameplate RPM No AccessActual RPM No AccessPhase 3Hertz 60FL Amps 4.3Corrected FLA 4.2

Sheave DataAHU 3-3A/Supply Fan

Drive Type BeltActual Fan RPM No Access

Filter DataAHU 3-3A/SF Filter Bank

Manufacturer KOCHFilter Type PleatedFilter Quantity - Size 1 6Filter Dimensions - Size 1 16x20x2

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 12

Page 15: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-3A/SPP-01

Test PressuresPre Filter SP In -0.39 in. w.c.Pre Filter SP Out -0.65 in. w.c.Cooling Coil SP In -0.65 in. w.c.Cooling Coil SP Out -1.19 in. w.c.Supply Fan SP In -1.19 in. w.c.Supply Fan SP Out 0.34 in. w.c.ESP Actual 0.73 in. w.c.TSP Actual 1.53 in. w.c.

Static Pressure Profile

ESP Actual 0.73TSP Actual 1.53

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 13

Page 16: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-3A/Outside Air Intake

Traverse Data Points

Ductwork DataDiameter 12.00 in.Air Flow Area 0.79 sq. ft.

Traverse SummaryCFM Design N/GCFM Actual 368Test Instrument AirfoilType of Traverse RoundNumber Of Rows 2Readings Per Row 8Total Readings 16Sum of Readings 7453Average Velocity 466 FPMStatic Pressure -0.31 Inches w.c.Air Temperature 74.8 Deg F

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 14

Page 17: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

System/Unit Mfg. Model Valve Position

Size Design GPM

Indicated Flow

Valve-01 ARMSTRONG CBV 3.2 1-1/2 N/GTotals: - - - - - -

AHU 3-3A Balance Valve Summary

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 15

Page 18: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-5

Unit DataUnit Manufacturer McQuayUnit Model Number LSL114DVUnit Serial Number 32K0036-04Unit Discharge UPBLAST

Test DataSupply Air Actual 4983 CFMOutside Air Actual 331 CFMReturn Air Actual 4652 CFMO/A Damper Pos 20 % open

Electrical Test DataAHU 3-5/Supply Fan

Motor Volts T1-T2 473Motor Volts T2-T3 474Motor Volts T1-T3 473Motor Amps T1 5.7Motor Amps T2 5.7Motor Amps T3 5.6

Coil Air Test DataAHU 3-5/Cooling Coil-01

Actual Coil Airflow 4983 CFM

TemperatureAHU 3-5/Cooling Coil-01

ENT Air DB Temp Actual 77.5 Deg FENT Air WB Temp Actual 65.9 Deg FLVG Air DB Temp Actual 55.3 Deg FLVG Air WB Temp Actual 54.6 Deg FSensible Capacity Actual 120,026 BTU/HRTotal Capacity Actual 174,231 BTU/HR

Motor DataAHU 3-5/Supply Fan

Manufacturer BaldorFrame 213TNameplate HP 7.50Operating BHP 4.53Nameplate RPM 1760Actual RPM 1783Phase 3Nameplate Volts 230/460Hertz 60FL Amps 9.3Corrected FLA 9.0Service Factor 1.15Efficiency % 0.91Power Factor 0.80

Sheave DataAHU 3-5/Supply Fan

Drive Type BeltMotor Sheave MFG BrowningMotor Sheave Model 2VP60Motor Sheave Diam. 6 in.Motor Sheave Bore 1-3/8 in.Sheave Open Turns 4.5Fan Sheave MFG BrowningFan Sheave Model 2BK95HFan Sheave Diam. 9-1/2 in.Fan Sheave Bore H1-7/16 in.Number of Belts 2Belt Manufacturer GatesBelt Size BX65Sheave Center Line 21.5 in.Actual Fan RPM 1089

Coil Water Test DataAHU 3-5/Cooling Coil-01

Coil GPM Actual 49.5EWT Actual 44.2 Deg FLWT Actual 52.4 Deg FWater Delta T Actual 8.2 Deg FCoil Inlet PSI Actual 70.1Coil Outlet PSI Actual 67.2Coil DP Actual 6.7 Ft. H20

Filter DataAHU 3-5/SF Filter Bank

Manufacturer KOCHFilter Type PleatedFilter Quantity - Size 1 8Filter Dimensions - Size 1 20x25x2

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 16

Page 19: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-5

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-5/SPP-01

Test PressuresPre Filter SP In -0.22 in. w.c.Pre Filter SP Out -0.62 in. w.c.Cooling Coil SP In -0.61 in. w.c.Cooling Coil SP Out -1.01 in. w.c.Supply Fan SP In -1.01 in. w.c.Supply Fan SP Out 1.11 in. w.c.ESP Actual 1.33 in. w.c.TSP Actual 2.12 in. w.c.

Static Pressure Profile

ESP Actual 1.33TSP Actual 2.12

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 17

Page 20: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-5/Main Supply

Traverse Data Points

Ductwork DataHeight 18.0 in.Width 44.00 in.Air Flow Area 5.50 sq. ft.Location of Holes 1 Right

Traverse SummaryCFM Design N/GCFM Actual 4983Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 4Readings Per Row 7Total Readings 28Sum of Readings 25371Average Velocity 906 FPMStatic Pressure 0.98 Inches w.c.Air Temperature 65.1 Deg FFan Speed/RPM 1089

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 18

Page 21: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-5/Outside Air Intake

Traverse Data Points

Ductwork DataHeight 10.0 in.Width 10.00 in.Air Flow Area 0.69 sq. ft.Location of Holes 1 Bottom

Traverse SummaryCFM Design N/GCFM Actual 331Test Instrument AirfoilType of Traverse RectangleNumber Of Rows 3Readings Per Row 3Total Readings 9Sum of Readings 4321Average Velocity 480 FPMStatic Pressure -0.15 Inches w.c.Air Temperature 75.0 Deg FFan Speed/RPM 1089

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 19

Page 22: MRC CONNECTED LOAD AND HVAC SURVEY

Air Handling UnitPROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

System/Unit Mfg. Model Valve Position

Size Design GPM

Indicated Flow

Valve-01 ARMSTRONG CBV 4.0 2.00 N/G 49.5Totals: - - - - - -

AHU 3-5 Balance Valve Summary

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 20

Page 23: MRC CONNECTED LOAD AND HVAC SURVEY

Balance ValvePROJECT:LOCATION:

MRC Connected Load and HVAC SurveyTampa, FLP3604PROJECT #:

DATE:CONTACT:

9/9/2021Steven Mullins

Tested By: Roddy QuinonesDate: 9/1/2021

SYSTEM/UNIT: AHU 3-3A/Valve-01

Unit DataService CHILLED WATERMfg. ARMSTRONGModel CBVSize 1-1/2 INCHDesign GPM N/G

Test DataValve Position 3.2

Tested By: Roddy QuinonesDate: 9/2/2021

SYSTEM/UNIT: AHU 3-5/Valve-01

Unit DataService CHILLED WATERMfg. ARMSTRONGModel CBVSize 2.00 INCHDesign GPM N/G

Test DataValve DP Actual 4.55 Ft. H2oValve Position 4.0Indicated Flow 49.5 GPM

Pro-Tech Diversified Services, Inc.Professionals delivering Performance 21