DEVELOPMENT CONTROL REGULATIONS
Southern Region Logistic Projects (Al Wakra Logistic Park, Birkat Al Aawamer, Aba Saleel)
LAND USE TYPE: Logistics and light Industrial Plots PLOT SIZE: Varies Date: 30/08/2015 Rev. 1
PLOT COVERAGE
PLOT COVERAGE WAREHOUSE BUILDING OFFICE LABOUR ACCOMMODATION
SHOWROOMS LANDSCAPING
* Up to 55% coverage of the total Plot Area
* Maximum G + M Height 20m Basement allowable within the approved floor coverage and accounted in FAR unless utilised for parking only.
Not Exceeding 10% of allowable Built Up Area
Maximum of 4% of plot area for the accommodation of workers employed within the plot only
Maximum of 5% of plot area
* Minimum 3.5% of plot to be covered with soft landscaping
FAR = 1.00 * Security guard function to be accommodated in dedicated guard house not exceeding 10m2 or within the main building
* Maximum height G + M, or G+1 or mezzanine level within warehouse (in accordance with development Guidelines)
Maximum G +2 Maximum G+M
Minimum Development Obligation 25% of plot area
* Electrical Substations permitted at sides, front or rear * Maximum Substation height of 4.5m
Mezzanine shall not exceed 80% of office ground floor area
Mezzanine Level not applicable
Mezzanine shall not exceed 80% of showroom ground floor area
Mezzanine Level not applicable
Single or multiple * Parking canopy maximum height Compliant with
-
2
Buildings are allowable subject to MMUP approval
3.5m * Tensile structures preferred or steel structures
MMUP specification and guidelines
Mezzanine level shall not exceed 4.0m in height
Mezzanine shall not exceed 50% of Warehouse ground floor area
SETBACKS
WAREHOUSE BUILDING PLOT > 2000M2
WAREHOUSE BUILDING
2001M2 > PLOT > 5000M2
WAREHOUSE BUILDING
5,001M2 > PLOT
PARKING
Front 6 Meters 12 Meters 20 Meters 1.5 meters
Sides 3 meters 3 meters 6 meters 1.5 meters
Rear 3 meters Not less than 3 meters provided combined front and rear setback is not less than 18m
6 meters 1.5 meters
Additional Requirements
All sites shall provide emergency access in accordance with Fire Safety Standards Minimum Requirements of the Qatar Ministry of Interior Civil Defence Department and NFPA requirements.
SITE DEVELOPMENT
BOUNDARY WALL FENCING SITE ACCESS PARKING MISCELLANEOUS
* Boundary wall compulsory compliant with design criteria. 2.5m high rear and sides and subject to Manateq approval
* Front and side fence compulsory compliant with design criteria at 2.5m and 1.8m respectively in height and subject to Manateq approval
1 or 2 access points permitted along plot frontage, Min. 2 meters from plot corners
1 parking space per 50 m2 of Gross floor area (GFA) office and showroom and 120m2 for Warehouse area
On plot truck and other operational required parking shall be incorporated within the plot to ensure all requisite operational needs are located within the plot
Refuse storage area shall be screened from view in a services Yard.
-
3
AESTHETICS
FINISH MATERIALS COLORS SIGNAGE PROHIBITED
All exterior finish materials compliant with design criteria
Exterior of all buildings to be white, beige or other colours as pre-approved by MMUP.
Free standing sign or sign on Building compliant with design criteria and subject to Manateq Approval
Temporary Buildings including but not limited to porta cabins are prohibited.
DEVELOPMENT PLANNING REQUIREMENTS
1. Design of the project shall contribute to the cohesive and coherent with the Design criteria. 2. Approval of the preliminary Design required by Manateq and all other approvals by respective and prevailing Government Authority
Note: All plots comprise a minimum frontage of 20 metres or greater
-
4
Design Criteria
1 The Tenants Works should be designed to comply with standards applicable in the State of Qatar or such other international standards as will be notified by the Tenant to the Landlord and will comprise the following minimum anticipated standards of construction and design performance to be considered by the investors in developing the facilities:
1.1 General Planning
The following Design Performance Criteria for the facilities is considered as a minimum, shall be designed to comply with latest editions of British Standards, EN Standards, International Building Code (IBC) American Society for Testing and Materials (ASTM) and National Fire Protection Association (NFPA) and must also be compliant to all latest local codes, rules and regulations of the state and including latest edition of QCS. Further to this, the facilities shall comprise the following minimum anticipated standard of construction and design performance to be considered by the investors in developing the facilities;
General Planning The planning for the Project shall provide due consideration to all the required services that are typically expected as best practice in an international/ regional project of this nature and include the following facilities:
1. Appropriate Landscape with automated Irrigation
2. Appropriate perimeter fencing in compliance with Landlord guidelines
3. All essential Public amenities as required by MMUP requirements.
4. Security and Life Safety requirements as per local codes, especially MOI, Civil
Defense, and MMUP regulations
5. All Dry and Wet Utilities including appropriate cooling facilities as per Kahramaa,
QICT, all other relevant Standards and regulations as a minimum.
6. Air Conditioning System for all facilities (offices, Showrooms, labour
accommodation, amenities).
7. Compliance with GSAS in accordance with MOE requirements
8. Carparking for all visitors workers and trucks shall be accommodated on and within
the plot
9. Labour accommodation shall be compliant with MMUP codes and regulations
Architectural
1. Minimum design life of all the building structures shall be 50 years and for all other
facilities including infrastructure shall be 50 years
2. Clear height within the warehouses of 13m as a minimum unless otherwise
approved by MMUP
3. Grid spacing to be maximized with minimum grid not less than 9m spacing
4. Provision for mezzanine offices as required in compliance with MMUP guidelines
5. Provision of showroom not exceeding 5% of plot area as and if applicable
-
5
6. Provision of labour accommodation solely for accommodating workers on the plot
in accordance with MMUP guidelines as and if required at a maximum of 4% of plot
area
7. Plot service SW & SS connection to be to PWA design standard. 8. Potable Water supply connection to be to KAHRAMAA design standard.
Building Material
PRE-ENGINEERED STEEL STRUCTURES (as a minimum) Standard Accessories
No. Description
1 Double Steel Sliding Door Minimum opening size: To be specified
2 Wall Framed opening For windows and Doors
3 Sky light panels
4 Loading Docks for each warehouse facility compliant with relevant international standards. The loading dock shall be sloped down so that the truck level matches with the loading dock level which shall be the edge of the ware house.
Building Material Structure
Ventilated & AC Warehouses
Metal clad with color bond type material or similar with min 50mm insulation Alternate options to be provided
Portal Steel Frame/ PRE-ENGINEERED STEEL STRUCTURES
Chilled & Refrigerated warehouses
Spray foam Insulation (polystyrene/polyurethane) wall, ceiling and floor finish comprising appropriate flammability index, smoke developed index and with U value as required by standards and further dealt below.
Portal Steel Frame/ PRE-ENGINEERED STEEL STRUCTURES
Roads Bitumen or concrete Should be as per ASHGHAL standards and specifications and so to ensure future handover if required
Open Storage yards
Bitumen or concrete ground finish
Perimeter Wall 2.5m high side and rear and 1.8m high front constructed from block work with steel grate comprising a render & painted finish (refer details)
In accordance with Landlord specification and guidelines
Circulation Areas and roads within sub plots
Bitumen or concrete ground finish Should be as per ASHGHAL standards and specifications and so to ensure future handover if required
-
6
1. 0 Open Storage Yards (51 to 65 )
a) Panel Specifications
ROOF PANELS
Single Skin Panels
Profile As per manufacturer Profile
Thickness (mm) 0.7 0.8(minimum)
Material Aluminum
Finish Polyester Painted
Color Standard per client requirement
b) Paint Specifications
Primary Structural Members The primary steel members shall be cleaned and sand blasted with SA 2.5 Swedish Standard painted with multi coat 250 microns DFT epoxy paint system. Secondary Structural Members The secondary steel members such as purlins, girts, eave struts, base angles and gable angles shall be cold formed pre-galvanized materials. The anchor bolts are galvanized.
2. 0 Enclosed Dry (ventilated) Warehouses (24 to 50 )
a) Panel Specifications
ROOF and WALL PANELS
Sandwich Panels
Exterior Skin
Profile As per manufacturer Profile
Minimum Thickness
0.7 mm
Material Aluminum
Finish Polyester Painted
Color Standard
P.U. Core Density 35kg/m3(minimum)
Thickness 50 mm minimum (excluding rib depth)
Interior Skin
Profile Flat
Thickness 0.5 mm(minimum)
Material Aluzinc
Finish Polyester Painted
Color Standard
-
7
b) Paint Specifications
Primary Structural Members The primary steel members shall be cleaned and sand blasted with SA 2.0 Swedish Standard painted with one coat 75 microns DFT epoxy primer. Secondary Structural Members The secondary steel members such as purlins, girts, eave struts, base angles and gable angles shall be cold formed pre-galvanized materials. The anchor bolts are galvanized.
3. 0 Enclosed Air Conditioned Warehouses (23 to 25)
a) Panel Specifications
ROOF and WALL PANELS
Sandwich Panels
Exterior Skin
Profile As per manufacturer Profile
Minimum Thickness
0.7 mm
Material Aluminum
Finish Polyester Painted
Color Standard
P.U. Core Density 35kg/m3
Minimum Thickness
75 mm minimum (excluding rib depth)
Interior Skin
Profile Flat
Thickness 0.5 mm
Material Aluzinc
Finish Polyester Painted
Color Standard
b) Paint Specifications
Primary Structural Members The primary steel members shall be cleaned and sand blasted with SA 2.0 Swedish Standard painted with one coat 75 microns DFT epoxy primer. Secondary Structural Members The secondary steel members such as purlins, girts, eave struts, base angles and gable angles shall be cold formed pre-galvanized materials. The anchor bolts are galvanized.
4. 0 Enclosed Chilled Warehouses (6 to 22)
-
8
a) Panel Specifications
ROOF and WALL PANELS
Sandwich Panels
Exterior Skin
Profile As per manufacturer Profile
Minimum Thickness
0.7 mm
Material Aluminum
Finish Polyester Painted
Color Standard
P.U. Core Density 35kg/m3
Minimum Thickness
100 mm minimum (excluding rib depth)
Interior Skin
Profile Flat
Thickness 0.5 mm
Material Aluzinc
Finish Polyester Painted
Color Standard
Chilled room shall be constructed separately from the main warehouse and shall be tested for air/water tightness.
b) Paint Specifications
Primary Structural Members The primary steel members shall be cleaned and sand blasted with SA 2.0 Swedish Standard painted with one coat 75 microns DFT epoxy primer. Secondary Structural Members The secondary steel members such as purlins, girts, eave struts, base angles and gable angles shall be cold formed pre-galvanized materials. The anchor bolts are galvanized.
5. 0 Enclosed Frozen Warehouses (0 to 5)
a) Panel Specifications
ROOF and WALL PANELS
Sandwich Panels
Exterior Skin
Profile As per manufacturer Profile
Thickness 0.7 mm
Material Aluminum
Finish Polyester Painted
Color Standard
P.U. Core Density 35kg/m3
Minimum Thickness
100 mm minimum (excluding rib depth)
-
9
Interior Skin
Profile Flat
Thickness 0.5 mm
Material Aluzinc
Finish Polyester Painted
Color Standard
Freezer room shall be constructed separately from the main warehouse and shall be tested for air/water tightness.
b) Paint Specifications
Primary Structural Members The primary steel members shall be cleaned and sand blasted with SA 2.0 Swedish Standard painted with one coat 75 microns DFT epoxy primer. Secondary Structural Members The secondary steel members such as purlins, girts, eave struts, base angles and gable angles shall be cold formed pre-galvanized materials. The anchor bolts are galvanized. Structure
1. Design load for the respective buildings and roads as per QCS
2. Roads - Shall not be less than 16m wide corridor with minimum 8m road width and
comprising a load bearing capacity AS PER Industrial standards and as mandated by
ASHGHAL
General (Codes, Loads and Material Specification) Loading for warehouse super structures CODE : MBMA-2006, AISC 2005, AISI 2002, AWS 2006 Design Live Load : 0.75kN / m2 (On Roof) : 0.75kN / m2 (On Frame) Dead Load : As per design STANDARDS (On Roof& Frame) Collateral Load Air conditioned : 0.50 kN / m2 Cold Store : 1.00 kN / m2 No Air Conditioned : 0.10 kN / m2 Wind Speed : 162 KPH (3-second gust), Exposure B, Importance factor = 1.0, Refer to MBMA-2002, Chapter 1, Section 1.4, Page 16 Seismic Loads : Per IBC latest Edition
-
10
Load Combination : As per MBMA-2002 Rainfall Intensity : 68 mm/Hr Temperature load : None Deflection Limits : In accordance with 2002 MSMN
The temperature design shall consider, but not be limited to, seasonal climatic variations, day/night variations, internal/external variations, and exposed/shaded area variations.
Cases Temperature Range (oC)
For Steel Section Average Restraint/Locked-in temperature
As per QCS
Operational temperature (for controlled conditions)
Operational temperature (for uncontrolled conditions)
To be determined by the consultant
Temperature load shall be combined with the appropriate load cases considering the followings:
1. For construction stage: Combine with applicable DL & SDL, construction LL and WL (with 5 yr return period)
2. For operation stage: Combine with all load cases.
Imperfection loads shall be as per the codal requirement.
QCS applies for all structural aspects of the project. All structures will acceptable International Design standards to Client. Thermal Performance
Roof material is available in almost any construction depth to suit all building needs ranging from
65mm to 500mm with corresponding thermal performance. The table below gives average figures
for systems based on specific criteria.
Construction Depth U Value
100mm 0.4 W/m2K
150mm 0.37 W/m2K
200mm Appropriately to be designed based on local
requirements and conditions
250mm Appropriately to be designed based on local
requirements and conditions
-
11
MEP MEP infrastructure and materials utilized on the Plot shall be fully compliant with and in accordance with relevant Authorities design guidelines and specifications hence enable handover to the Authorities for maintenance upon completion. Generally the following additional provisions shall be incorporated;
1. Air Conditioning & Ventilation(as per regional , GCC and ASHRAE standards)
All air conditioning and refrigeration equipment shall operate using environmentally
friendly refrigerant. Ammonia as a refrigerant alternate can be utilized of refrigeration
system serving large cold and freezer rooms.
2. Electrical design shall be in accordance with Kahrama and QCS Specifications, British
Standards, SSL/CIBSE Lighting Guides and generally shall include the following;
a. 11kv network with 415V non-essential distribution systems
b. 415V essential distribution systems (standby and emergency power)
As a minimum, standby/emergency generator power shall be provided for the
following:
Minimum code requirements for life safety Additional loads required by projects operational requirements Particular Client/End User/Operator requirements
Equipment Type
Form of Construction
IP Rating (main
enclosure)
Fault Level Rating
Minimum Thickness
Comment
MV (11kV) Panel
As per Kahrama specification Min. 25% spare
capacity on design load.
LV (415V)- MDB Panel
Form 4b, Type 6
As per Kahrama specification Min. 25% spare
capacity on design load.
SMBD Panel/MCCB Panel Board
Form 3b, Type 2
IP 32 As per QCS specification Min. 25% spare
capacity on design load.
Final Dist. Board
Form 2b As per QCS specification Min. 25% spare
capacity on design load.
MCC Form 3b As per QCS specification Min. 25% spare
capacity on design load.
Outdoor Feeder Pillar
Form 2b IP 56
10kA for 3 secs if fed from SMDB or
25kA for secs if fed from main
LV panel
2.0 mm Min. 10% spare
capacity on design load.
-
12
c. 415V essential distribution systems (uninterrupted power)
As a minimum the following shall be provided with UPS to feed the following:
MDF and IDF rooms Critical IT and other installations as identified by Client/End User Building Control Systems Security, Access control system. Particular Client/End User/Operator requirements CCTV system including associated network switches as per Ministry of
Interior Security Guidelines
d. Maximum Demand Diversification as per Kahrama requirements.
e. Power factor correction of 95%
f. Energy efficient internal and external lighting and control systems.
g. Emergency Lighting and Exit Signage as per QCD requirements.
h. Lightning Protection as per BS EN 62305.
i. Cables and wires to be low smoke and fume type (LSF/LSOH), or fire rated where
required by QCD.
j. Conduits and cable trunking to be galvanized steel. PVC conduits only to be used
where embedded.
k. Street lighting minimum illumination of 5 lux as per ASHGAL and QCS requirements
and Qatar Highway Design Manual.
3. Fire and life safety shall be designed in accordance with NFPA and compliance with the civil
defense authority of the State of Qatar
4. Hydraulics
a. Provision of storm water drainage to the site
b. Potable water reticulation
c. Irrigation
Landscaping All roads shall be landscaped and provided with appropriate Hard and Soft scapes, should aim to reduce heat gain, minimize water consumption, provide suitable imageability for the project area, provide adequate shade for pedestrians, include Native species and landscape strategies including xeriscapesto mitigate sand storms, heats and prevailing winds. Appropriate urban hardscape should be provided in the public realm where ever possible. All of the above design specifications are provided as a minimum and are for purposes for guiding the developer to achieve acceptable standards in the project as per best practice in the GCC region on similar reputed projects.
B) DESIGN CODES:
-
13
c) MATERIAL SPECIFICATIONS
No Components Specifications Minimum yield
strength
1 Built up (Plates)
ASTM A-572 Grade 50 Yst = 34.50 kN/cm (50 ksi) Fy = 34.5 kN/cm
2
2 Hot
Rolled
Angles ASTM A-36 (or equivalent) Fy = 23.5 kN/cm
2
Beams
ASTM A-572, Yst = 34.50 kN/cm (50 ksi) EN-10025, S355 JR. Yst = 35.50 kN/cm OR S275 Yst = 27.50 kN/cm
Fy = 34.5 kN/cm2
3 Cold Form
Galvanized ASTM A-653 GR 50 (G90) or equipment Fy=34.0kN/cm
2
4 Roof panel
Zinc Aluminium Base
ASTM A792 Gr. 40/50 Fy = 30.0 kN/cm2
5 X-Bracing
Rods
ASTM A36
(or equivalent)
Fy = 23.5 kN/cm2
6 Anchor bolts ASTM A36
(or equivalent) Fu = 25.0 kN/cm2
7 High strength Bolts ASTM A325 Type 1
(or equivalent)
Ft = 30.3 kN/cm2
Fu = 72 to 83 kN/cm2
8 Machine Bolts ASTM A 307
(or equivalent)
Ft = 13.8 kN/cm2
Fu = 41.0 kN/cm2
-
14
(A) STANDARD DEFLECTION LIMITS
DESCRIPTION DEFLECTION LIMIT REFERENCES
Frames: Columns and Rafter
Vertical Deflection Drift Horizontal Sway
Span / 180 for RF Span / 90 for Cantilever Height / 45 (for buildings without crane) Height / 60 (for buildings with crane)
As per UBC, 94 Vol.2. Section 2349,862 As per MBMA, Section C 6,8, Page 117 for crane building frames the maximum calculated bare frame drift under MBMA loading recommendations commonly range from H/60 to H/100.
Roofs: Eave Strut, Purlins & Sheeting.
Span / 180
As per UBC, 94 Vol. 2, Section 1643, Page 2-1203.
Wall & Structural Framing : Rails, Wall Sheeting
Span / 120 (for walls with flexible finishes) Span / 240 (for wall with brittle finishes)
As per UBC 94 Vol. 2, Section 1643.2 Page 2-1203.
Flat Roof / Mezzanine
Span / 360 (With Live Load Only) Span / 240 (With Live Load + Dead Load)
As per UBC, 94 Vol.2, Table 16-D, Page. 2-32.
-
15
Aesthetic standards In order to create an attractive, functional development, aesthetic standards have been established. These standards will promote a consistent, orderly appearance that will help preserve property values and provide assurance to tenants and investors about the quality of development that will occur around them. The aesthetic standards address components of a plot plan that will affect the visual quality of the plot as viewed from off-plot locations. In addition, these components affect the experience of on-plot workforce in their everyday lives. Figures 6-62 and 6-63 below illustrate graphic guidelines for plot landscaping, plot wall character and main signage for the logistics, support, & light industrial land Use Zone. For an attractive and consistent appearance throughout the logistics and industrial Zones, each plot should have a distinct front side and back side. In general, the front side should contain the main office and parking within a landscaped setting. The sides and rear of the plot can be more utilitarian and contain loading areas, utility structures and other ancillary uses that are generally screened from view of public roads.
COMPONENT DESIGN STANDARD
Location of Offices
Offices shall be located at the front of the building facing the road. Where Mezzanine office are considered a dedicated and separate entry shall be provided that is distinguished from warehouse structure and is commensurate with commercial office aesthetics.
Outdoor Storage Areas
Any outdoor storage area (including garaged in storage areas and liquid waste storage tanks) shall not be located within the Front setback. Any outdoor storage area must be screened from the road.
Mechanical Equipment & Utility structures
In general, mechanical equipment and utility structures shall be screened from offsite views: At grade water tank and mechanical equipment shall be located to the side and rear of the building. Roof-top water tank and mechanical equipment shall be screened from view and not be visible from the road.
landscaping A landscaping strip with a minimum average width of 1.5 m shall be provided along all road frontages except across vehicle crossings and where a guardhouse is located in the road boundary setback. the landscaping strip must contain:
Minimum 1 tree and one additional tree for every 10m of roads frontage. Where three or more trees are required these trees shall be planted no more than 15m
apart or closer than 5m apart. Trees shall be of a species capable of reaching a minimum height at maturity of 8m and
shall not be less than 1.5 m high at the time of planting. Walls & Fencing
Walls and fences are permitted under the following conditions: On the read and side of the property, solid walls are allowed up to a height of 2.5m however, on the front of the property
and any external boundary solid walls only up to a height of 1.4m above which a tubular metal fence with minimum 80% opacity may be erected. The total height of this barrier shall not be more than 2.5m.
The following types of fences shall not be permitted on any side of the plot: Barbed wire fencing. Corrugated metal sheet fencing.
Foundations of all walls and fences shall be located within the plot boundary
Signage Signage and branding is permitted at designated locations within the plot boundary as follows: Embedded within the boundary wall near the entrances to the plot. On the vertical surface of the main building. On a standalone independent pillar located within the plot (not exceeding the maximum height of the building).
Dimensions of the signage shall be restricted within a rectangular frame of 15m x 3m
Building Faade treatment
Attractive building faade design is required. Architects are encouraged to create simple, timeless design solutions that contribute to a high-quality character:
Buildings shall display variety in forms, material and colour to reflect a style consistent with modern logistics facilities. The office or non-logistics components of the project shall be expressed differently from that of the warehouses. Ancillary buildings and service buildings shall be architecturally treated with colours and materials appropriate to fit within
the architectural style of the main warehouse facilities
-
16
Southern Region Logistic Projects
Figure 6-62: Typical Plot Boundary Wall (Front) with Signage Plot Identification Signage
Plot Identification Signage Elevation View Plot Identification Signage 3D View
Figure 6-63: Typical Plot Boundary Wall (Side & Rear)
Side & Rear Fence Elevation View Side & Rear Fence Street View