Micom P740

download Micom P740

of 18

Transcript of Micom P740

  • 8/11/2019 Micom P740

    1/18

    15.10 NUMERICAL BUSBAR PROTECTION

    SCHEMES

    The application of numerical relay technology to busbar

    protection has lagged behind that of other protection

    functions. Static technology is still usual for such

    schemes, but numerical technology is now readily

    available. The very latest developments in the

    technology are included, such as extensive use of a data

    bus to link the various units involved, and fault tolerance

    against loss of a particular link by providing multiple

    communications paths. The development process hasbeen very rigorous, because the requirements for busbar

    protection in respect of immunity to maloperation are

    very high.

    The philosophy adopted is one of distributed processing of

    the measured values, as shown in Figure 15.20. Feeders

    each have their own processing unit, which collects

    together information on the state of the feeder (currents,

    voltages, CB and isolator status, etc.) and communicates

    it over high-speed fibre-optic data links to a central unit.

    For large substations, more than one central unit may be

    used, while in the case of small installations, all of theunits can be co-located, leading to the appearance of a

    traditional centralised architecture.

    For simple feeders, interface units at a bay may be used

    with the data transmitted to a single centrally

    located peripheral unit. The central unit performs the

    calculations required for the protection functions.

    Available protection functions are:

    a. protection

    b. backup overcurrent protection

    c. breaker failure

    d. dead zone protection

    In addition, monitoring functions such as CB and isolator

    monitoring, disturbance recording and transformersupervision are provided.

    Because of the distributed topology used,

    synchronisation of the measurements taken by theperipheral units is of vital importance. A high stability

    numerically-controlled oscillator is fitted in each of the

    central and peripheral units, with time synchronisation

    between them. In the event of loss of thesynchronisation signal, the high stability of the oscillatorin the affected feeder unit(s) enables processing of the

    incoming data to continue without significant errors

    until synchronisation can be restored.

    The peripheral units have responsibility for collecting the

    required data, such as voltages and currents, and

    processing it into digital form for onwards transmissionto the central unit. Modelling of the CT response is

    included, to eliminate errors caused by effects such as CTsaturation. Disturbance recording for the monitored

    feeder is implemented, for later download as required.

    Because each peripheral unit is concerned only with anindividual feeder, the protection algorithms must reside

    in the central unit.

    The differential protection algorithm can be much more

    sophisticated than with earlier technology, due to

    improvements in processing power. In addition tocalculating the sum of the measured currents, the

    algorithm can also evaluate differences betweensuccessive current samples, since a large change above a

    threshold may indicate a fault the threshold being

    chosen such that normal load changes, apart from inrushconditions do not exceed the threshold. The same

    15

    BusbarProt

    ection

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 2 5 1

    Figure 15.20: Architecture for numerical protection scheme

    Personal

    Computer

    PU

    CT

    CBPU CB

    CT

    PU CB

    CT

    Feeder 1 Feeder 2

    CU

    Central Unit

    PU

    Fibre optic link

    System Communication Network

    PU: Peripheral Unit

    CU: Central Unit

    CB

    CT

    Chap15-232-253 17/06/02 9:54 Page 251

  • 8/11/2019 Micom P740

    2/18

    considerations can also be applied to the phase angles ofcurrents, and incremental changes in them.

    One advantage gained from the use of numericaltechnology is the ability to easily re-configure theprotection to cater for changes in configuration of thesubstation. For example, addition of an extra feeder

    involves the addition of an extra peripheral unit, thefibre-optic connection to the central unit and entry viathe MMI of the new configuration into the central unit.Figure 15.21 illustrates the latest numerical technologyemployed.

    15.10.1 Reliability Considerations

    In considering the introduction of numerical busbarprotection schemes, users have been concerned withreliability issues such as security and availability.Conventional high impedance schemes have been one of

    the main protection schemes used for busbar protection.The basic measuring element is simple in concept andhas few components. Calculation of stability limits andother setting parameters is straightforward and schemeperformance can be predicted without the need forcostly testing. Practically, high impedance schemes haveproved to be a very reliable form of protection.

    In contrast, modern numerical schemes are morecomplex with a much greater range of facilities and amuch high component count. Based on low impedancebias techniques, and with a greater range of facilities toset, setting calculations can also be more complex.

    However, studies of the comparative reliability of

    conventional high impedance schemes and modernnumerical schemes have shown that assessing relativereliability is not quite so simple as it might appear. Thenumerical scheme has two advantages over its oldercounterpart:

    a. there is a reduction in the number of externalcomponents such as switching and other auxiliaryrelays, many of the functions of which areperformed internally within the softwarealgorithms

    b. numerical schemes include sophisticatedmonitoring features which provide alarm facilities

    if the scheme is faulty. In certain cases, simulationof the scheme functions can be performed on linefrom the CT inputs through to the tripping outputsand thus scheme functions can be checked on aregular basis to ensure a full operational mode isavailable at all times

    Reliability analyses using fault tree analysis methodshave examined issues of dependability (e.g. the ability tooperate when required) and security (e.g. the ability notto provide spurious/indiscriminate operation). Theseanalyses have shown that:

    a. dependability of numerical schemes is better thanconventional high impedance schemes

    b. security of numerical and conventional highimpedance schemes are comparable

    In addition, an important feature of numerical schemesis the in-built monitoring system. This considerablyimproves the potential availability of numerical schemescompared to conventional schemes as faults within theequipment and its operational state can be detected andalarmed. With the conventional scheme, failure to re-instate the scheme correctly after maintenance may notbe detected until the scheme is required to operate. Inthis situation, its effective availability is zero until it isdetected and repaired.

    15.11 REFERENCES

    15.1 The Behaviour of Current Transformers subjectedto Transient Asymmetric Currents and theEffects on Associated Protective Relays. J.W.Hodgkiss. CIGRE Paper Number 329, Session15-25 June 1960.

    15

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 2 5 2

    Figure 15.21: Busbar protection relay using thelatest numerical technology (MiCOM P740 range)

    BusbarProt

    ection

    Chap15-232-253 17/06/02 9:54 Page 252

  • 8/11/2019 Micom P740

    3/18

    The MiCOM P740 numerical busbar protection

    scheme provides complete protection for all

    types of extra / ultra high voltage busbar

    configurations.

    Built on a number of innovative techniques,

    including CT saturation detection and dynamic

    topology processing algorithms, the P740 offers

    a unique combination of security, speed and

    sensitivity.

    With a typical operating time of 15ms, the P740

    protection is one of the fastest in its class and

    meets the most stringent requirements of extra /

    ultra high voltage transmission systems.

    The substation replica processing algorithms

    ensure that P740 adapts to the dynamically

    changing topology of the busbar.

    The MiCOM P740 busbar differential protectionscheme can be engineered to provide a

    centralized or a distributed architecture. It also

    supports easy maintenance, operation and future

    expansion of the busbar.

    Customer benefits

    Fast fault trip(typically 15ms)

    Adaptable to any busbarconfiguration.

    Can operate with differenttypes of CT.

    Fibre optic cable used forcommunication betweenCentral and Peripheral Units:- Ensures high

    communication speed- Eliminates insulation

    problems

    AREVA T&D

    MiCOM P740Numerical Busbar Protection

    PROTECTION

    MiCOM P741 in 80TE

    MiCOM P743 in 60TE

    MiCOM P742 in 40TE

  • 8/11/2019 Micom P740

    4/18

    APPLICATION

    The MiCOM P740 numerical busbar protection scheme

    has been designed to protect a wide range of busbar

    configurations. The modular scheme comprises of three

    relays:

    Central Unit - P741

    Peripheral Unit - P742 / P743

    These units, interconnected using optic fibre cables

    together with the topology configurator software allow

    application to all types of busbar configurations.

    The Central Unit co-ordinates the scheme, receiving

    signals from all the peripheral units associated with the

    protected busbars and acting on these signals, initiating

    a buszone protection trip when necessary. A single

    Central Unit can accommodate upto,

    8 Zones

    28 Peripheral Units

    One Peripheral Unit is associated with each

    CT location, usually one per incomer/feeder and one

    or two for each bus coupler/bus section, depending on

    number of CT (1 or 2). The Peripheral Units acquire

    the analogue signals from the associated CT and the

    binary signals from the auxiliary contacts of circuit

    breakers and isolators.The Peripheral Units also

    incorporate the main circuit breaker failure logic

    together with backup protection.

    The difference between the P742 and P743 is in the

    number of I/O that each can accommodate. The P743

    allows for increased I/O, this is particularly useful in

    double busbar applications. Especially where single

    pole breakers and transfer busbar are employed, in

    these applications the I/O requirements are large in

    comparison to those required for a single busbar

    application where a P742 may be more suitable.

    2>3

    Complete flexibility to suitany busbar configuration

    P740 scheme

    applied for protecting

    double busbar with transfer bus

    BB1

    Central UnitOptical fibre Peripheral UnitsPeripheral Units

    BB2

    BB3

    BB4

    TransferBus

    2 P742 or2 P743

    P742 P743 P741 P742P743

    PROTECTION

    FUNCTIONS

    OVERVIEW P74 P74 P743

    87BB / P Phase segregated biased current - -differential high speed busbar protection

    87BB / N Sensitive earth fault bias current controlled - -busbar protection

    87 CZ Check zone element (supervision) - -50 / 51 / P Phase overcurrent protection (2 stages) - 50 / 51 / N Earth overcurrent protection (2 stages) - 50ST Dead zone protection (short zone between CTs and CBs) - -CTS Current transformer supervision 50BF Breaker failure protection (LBB) ISL Isolator discrepancy alarm -

    Fibre optic signalling channel Digital inputs 8 16 24

    Output relays 8 8 21

    Front communication port (RS232) Rear communication port (RS485) Time synchronisation port (IRIG-B) * option - -

    * Refer data sheet for model selection

  • 8/11/2019 Micom P740

    5/18

    MANAGEMENT FUNCTIONS

    In addition to the protection and control elements, the

    P740 scheme provides a wide range of measurement,

    monitoring, post fault analysis and self-diagnostic

    features:

    Circuit breaker control

    Trip circuit supervision (using PSL)

    On-line measurement

    Plant status monitoring 4 alternative setting groups

    Programmable scheme logic (PSL)

    Sequence of event recording (SOE)

    Comprehensive disturbance recording (waveform

    capture)

    User configurable LEDs

    Local and remote communication ports

    Time synchronisation

    Fully customisable menu texts

    Multi level password protection

    Test facilities

    Power-up diagnostics and continuous self-monitoring

    of relay.

    User friendly setting and analysis software

    Speed, Sensitive & Secure:P740 the ultimate in busbar protection

    X

    /

    /

    / /

    Fault records

    Measurements

    PSL

    Local

    Communication

    Remote

    comm. port

    Busbar protection scheme

    Peripheral Unit P742 / P743

    LEDsBinaryInput / output

    Self monitoring

    50/

    51/P

    50/

    51/N

    50ST

    Disturbance

    Record

    Fibre optic

    signaling

    channel

    50BF CTS

    Fault records

    Measurements

    PSL

    Local

    Communication

    Remote

    comm. port

    Busbar protection schemeCentral Unit P741

    LEDsBinaryInput / output

    Self monitoring

    87BB

    / P

    87BB

    / N 87CZ

    Disturbance

    Record

    Fibre optic

    signaling

    channel

    50BF CTS

    ISL

    FUNCTIONAL OVERVIEW

    (Description of ANSI code nos. see Protection Function Overview)

  • 8/11/2019 Micom P740

    6/18

    The P740 employs biased differential algorithms, in

    which the differential current is compared with a bias

    current. This characteristic ensures stability of the

    protection for external fault even with differing CT

    tolerances and errors which otherwise could lead to

    spurious operation.

    To increase the security of the differential protection,

    the biased differential element is supervised by a

    global check zone element. This ensures stability

    even under erroneous status of the auxiliary contact of

    plant isolators and circuit breakers.

    The MiCOM P740 also employs an innovative, ultra

    high-speed, secure CT saturation detection

    algorithm. This ensures stability when CTs become

    saturated, particularly under external fault conditions.

    This algorithm combine a simulation of the flux built up

    in the core of the CTs with a recursive consistence

    variation control.This technique can detect CT

    saturation in less than 2ms.

    4>5

    i (t)bias

    I > 2Di3 in

    i2i1

    I > 1D

    Ispe

    rcenta

    gebias

    -k=20t

    o90%

    Tripping

    Area

    Restrain

    area

    i (t)diff nodeDifferential current : = + + i n1 2 iii 3 + ....... +

    i (t)diffOperating current : = = i

    i (t)diff

    i (t)bias i 1 i 2 i 3 i nRestraining current : =+ + + ....... + = i

    i (t)diff node

    Universal on-line topology processing

    Bias differential characteristics

    CT saturation detection

    To ensure adaptability of the relay to any type of

    busbar configuration the P740 is built with a universal

    topology processing algorithm. This algorithm

    determines the optimum tripping zone on-line based

    on the status of the plant isolator and breakers.

    This ensures that minimum part of the busbar is

    isolated for any fault in it.

    BUSBAR DIFFERENTIAL PROTECTION

    The primary protection element of the P740 scheme is

    the phase segregated biased current differential

    protection. The technique is based on the numerical

    application of Kirchoff's Law for the selective detection

    and ultra high-speed isolation of a faulty section of the

    busbar.

    The analysis is carried out in the Central Unit (CU)

    which communicates with the Peripheral Unit (PU) to

    get the current flowing in individual circuits and to

    implement the tripping of circuits as decided by it.

    This reliable, high speed communication is achieved

    via a direct optical connection utilising a 2.5 Mbps

    data rate.

  • 8/11/2019 Micom P740

    7/18

    DUAL CHARACTERISTICS

    To provide stability for severe through faults and at the

    same time detect low current internal faults, the P740

    is equipped with dual characteristics. One phase

    segregated differential protection and another

    sensitive earth current differential protection.

    MULTIPLE TRIPPING CRITERIA

    The MiCOM P740 maintains the highest level of

    stability, under all conditions including a hardware

    failure and incoherent signals applied from external

    plant equipment or generated by power system.

    Any tripping order must therefore be made conditional

    on the simultaneous occurrence of 5 or 6 criteria:

    > Magnitude criteria; confirmation of two simultaneous

    thresholds per zone:

    Exceeding the bias slope characteristic (k)

    Exceeding differential operating current threshold

    (ID>2).

    > Exceeding the supervision threshold (ID>1).

    > Signal quality criteria:

    No CT saturation detected

    Current variation detected on at least two

    Peripheral Units

    > Time or angular criterion.

    The measurement elements on 2 samples taken at

    1200 Hz. A first sample for the initial measurement

    and a second sample for tr ip confirmation.

    > Check zone supervision.

    The zone element(s) are only permitted to trip if the

    order is confirmed by the check zone element.

    > Local criteria (optional)

    The Peripheral Units can be set to only authorise

    tripping if there is confirmation by local overcurrent

    criteria.

    DEAD ZONE OR BLIND SPOTPROTECTION

    The current transformers surrounding the busbars

    define the limits of the main zones. When the circuit

    breaker is opened a dead zone or blind spot is created

    between the CB and the associated CT. The P740

    detects this condition automatically and provides

    protection for this zone also.

    CONTINUOUS SUPERVISION

    OF CURRENT CIRCUITS

    The P740 detects any abnormality in the current circuit

    by continuously monitoring it. Under normal operating

    conditions the differential current will be negligible. An

    anomaly is detected by a threshold, ID>1, which can

    be set to alarm from 1% of the primary basis current

    (Ibp).

    DIFFERENTIAL CURRENT SETTING

    When switching operations are carried out in the

    substation, incorrect topology replicas may occur. In

    this case, a differential current appears. The

    differential elements of the MiCOM P740 are allowed

    to operate only if the differential current reaches a

    threshold ID>2which is set above the highest load

    current.

    ADDITIONAL ULTRA HIGH SPEEDEXTERNAL FAULT BLOCKING

    The ultra high-speed saturation detection is carried out

    in each PU and can generate a control signal from the

    moment of the first sample (0.4 ms).

    Dual characteristics

    PU1connectedto BB1

    PU2 not connected to BB1= Activation

    of Dead Zone protection

    CB OpenCB Closed

    Dead Zone

    BB1

    Intertrip contact

    to other end

    ID>2

    Trip

    ISID>1

    idiff

    Perce

    ntage

    bias-

    k

    IDN>2Restrain

    Trip

    IIDN>1

    ibias

    ibias

    idiff

    Percentage

    bias- kN

    SEF Block threshold

    kNmin =0.2

    BlockEnable

    Restrain

    SN

    Dead zone protection

  • 8/11/2019 Micom P740

    8/18

    6>7

    Programmable scheme

    logic editor (MiCOM S1)

    PHASE OVERCURRENT ANDEARTH FAULT PROTECTION

    Two independent stages each of phase overcurrent and

    earth fault protection is provided in the Peripheral Units.

    These elements provide backup protection for the

    individual circuits.

    The two stages can be programmed as:

    > First stage can be programmed as definite time (DT)

    delay or one of the nine inverse time (IDMT) curves

    (IEC/UK and IEEE/US).

    > Second stage can only be programmed as definite

    time.

    CIRCUIT BREAKER FAILUREPROTECTION (LBB)

    The MiCOM P740 busbar protection scheme can work

    in co-ordination with external breaker failure

    protection relays. In this configuration, the receipt of an

    external breaker failure information results in tripping of

    all the adjacent circuit breakers, via the topological

    recognition system knowing which breaker is connected

    to which zone.

    The P740 also offers an in-built integrated solution

    for breaker failure protection. This requires all

    Peripheral Units to receive a duplication of the trip

    commands generated in their associated bay.

    In general the Breaker Failure protection must be

    executed on a per phase basis which involves the

    possibility of receiving tripping orders on a per pole

    basis.

    CURRENT TRANSFORMERMISMATCH CORRECTION

    The MiCOM P740 can correct mismatch between

    current transformer ratios over a very wide range up

    to 40. Its associated user interface provides a range

    between 1 A and 30,000 A primary.

    Since the current transformer ratings in a substation

    may be of mixed ratios, the MiCOM P740 enables a

    common base current to be defined, irrespective of

    the feeder section concerned.

    The settings on the Central Unit are all adjusted to this

    common current, known as the primary base current (Ibp).

    ISOLATION AND MAINTENANCEOPERATING MODE

    For ease of operation or maintenance of the busbar

    protection system, the Central Unit and the Peripheral

    Units can receive specific commands designed to

    allow system testing or other intervention without any

    danger of unwanted tripping.

    In the Central Unit, a centralized command to isolate

    the busbars at two levels can be applied selectively

    zone wise:

    > Differential protection (87 BB) in monitoring mode

    (measurements active and tripping deactivated).The

    Breaker Failure protection remains operational.

    > Differential protection (87 BB) and Circuit Breaker

    Failure protection (50 BF) in monitoring mode.The

    additional local protection functions (51, 51N, etc...)

    remain operational.

    A selective two-level command may be applied

    selectively for each Peripheral Units:

    > Maintenance of bay(s) for human intervention.

    In this state, all I/O are deactivated.The busbarprotection is still in service, but the CB of the feeder

    in service can not be tripped.

    > Intervention on the equipment for maintenance and

    testing.

    PROGRAMMABLE SCHEME LOGIC

    Powerful programmable scheme logic (PSL) allows the

    user to customize the protection and control functions.

    It is also used to programme the functionality of the

    optically isolated inputs, relay outputs and LED

    indications.The programmable scheme logic

    comprises of gate logic and general purpose timers.

    The gate logic includes OR, AND and majority gate

    functions, with the ability to invert the inputs and

    outputs, and provide feedback.The programmable

    scheme logic is configured using the graphical MiCOM

    S1 PC based support software.

    PLANT STATUS

    Checks and monitoring of the plant status can be

    made, and an alarm raised for any discrepancy

    conditions between the open and closed auxiliary

    contacts of the isolators and circuit breakers.

  • 8/11/2019 Micom P740

    9/18

    MEASUREMENTAND RECORDING FACILITIES

    The P740 series relays are capable of measuring and

    storing the values associated with a fault. All the

    events, faults records and disturbance records are time

    tagged to 1 ms using an internal real time clock. An

    optional IRIG-B port is also provided for accurate time

    synchronization. A lithium battery provides a back up

    for the real time clock and all records in the event of

    supply failure.

    MEASUREMENTS

    The measurements provided, which may be viewed in

    primary or secondary values, can be accessed via

    the back lit liquid crystal display. They are also

    accessible via the communication ports. The following

    instantaneous parameters can be viewed:

    > Central unit (P741

    Differential current Idiff / phase / zone

    Bias current Ibias / phase / zone

    Check zone Idiff / phase> Peripheral units (P742 & P743)

    Phase currents IA IB IC

    Neutral current IN

    Sequence currents

    Frequency

    EVENT RECORDER

    Up to 250 time tagged event records are stored in

    battery backed memory, and can be extracted via the

    communication port or be viewed on the front panel

    display.

    FAULT RECORDER

    Records of the last 5 faults are stored in the

    battery-backed memory of both the Central and

    Peripheral Units.

    Each fault record includes:

    > Indication of the faulty zone (CU + PU)

    > Protection element operated

    > Active setting group

    > Fault duration

    > Currents and frequency (PU)

    > Faulty zone differential and bias current (CU)

    DISTURBANCE RECORDER

    The Central and Peripheral units of the P740 have

    independent disturbance recording facility. The

    Peripheral Units can record 4 analogue and 32 digital

    channels, whereas the Central unit stores 8 analogue

    and 32 digital channels in addition to 1 time channel.

    > Specific analogue channels Ibias / Idiff (CU)

    IA, IB, IC, IN (PU)

    > Maximum duration of one record and number of

    records

    1.2s per record and 8 records (CU)

    up to 10.5s per record and minimum of

    20 records (PU)

    Disturbance records can be extracted from the relay

    via the remote communications and saved in the

    COMTRADE format. These records may be examined

    using MiCOM S1 or any other standard COMTRADE

    viewer.

    Disturbance record viewed in MiCOM S1

  • 8/11/2019 Micom P740

    10/18

    LOCAL AND REMOTECOMMUNICATIONS

    Two communication ports are available as standard; a rear

    port providing remote communications and a front port

    providing local communications.

    The front RS232 port has been designed for use with MiCOM

    S1, which fully supports functions within the relay by providing

    the ability to programme the settings off-line, configure the

    programmable scheme logic, extract and view event,

    disturbance and fault records, view the measurement

    information dynamically and perform control functions (using

    Courier protocol).

    The default remote communications is Courier / K-bus and can

    be converted to IEC60870-5-103.

    DIAGNOSTICS

    Automatic tests performed including power-on diagnostics andcontinuous self-monitoring ensures a high degree of reliability.

    The results of the self-test functions are stored in battery

    backed memory. Test features available on the user interface

    provide examination of input quantities, states of the digital

    inputs and relay outputs. A local monitor port provides digital

    outputs, selected from a prescribed list of signals, including the

    status of protection elements.

    HARDWARE

    All models within the MiCOM P740 series relays include:

    > A back-lit liquid crystal display

    > 12 LEDs

    > Optional IRIG-B port (CU),

    > RS232 (front port) & RS485 (rear port),

    > Fibre optic connection from the CU to the PUs,

    > Download/monitor port,> Battery (supervised),

    > N/O and C/O watchdog contacts

    > Supervised +48 V field voltage

    > Dual rated CT inputs 1A/5A

    > Universal opto inputs with progammable voltage threshold

    The optically isolated inputs are independent and may be

    powered from the +48V field voltage.

    Our policy is one of continuous development. Accordinglythe design of our products may change at any time. Whilstevery effort is made to produce up to date literature, thisbrochure should only be regarded as a guide and isintended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application ofany product referred to in it. We cannot be held responsiblefor any reliance on any decisions taken on its contentswithout specific advice.

    AUTOMATION-L3-P740-BR-05.05-1021-GB

    -

    -AREVA

    -2004

    .AREVA

    ,the

    AREVAlogoan

    danya

    lterna

    tivevers

    ion

    there

    ofare

    tra

    demarksan

    dserv

    icemarkso

    fAREVA

    .MiCOM

    isaregis

    tere

    dtra

    demarko

    fAREVA

    .All

    t r a

    d e n a m e s o r

    t r a

    d e m a r k s m e n

    t i o n e

    d h e r e

    i n w

    h e

    t h e r r e g

    i s t e r e

    d o r n o

    t a r e

    t h e p r o p e r t y o

    f t h e

    i r o w n e r s

    3 8 9 1 9 1 9 8 2 R C S

    P A R I S

    P r i n

    t e d i n F r a n c e

    S O N O V I S I O N I

    T E P

    AREVA T&D Worldwide Contact Centre:

    http://www.areva-td.com/contactcentre/

    Tel.: +44 (0) 1785 250 070

    www.areva-td.com

    www.areva-td.com/protectionrelays

    Device Track Record

    >> Low impedance biased differential busbar protection, MBCZ,

    launched in 1988 and over 800 cubicles sold

    >> Over 200 DIFB, medium impedance biased differential busbar

    protection scheme delivered since its launch in 1992.

    >> Medium impedance biased differential busbar protection with linear current

    combination, DIFB CL, launched in 1996. Over 70 cubicles delivered.

    >> Since the launch of the P740, over 50 systems have been delivered.

  • 8/11/2019 Micom P740

    11/18

    Customer benefits This architecture can

    accommodate the mostcomplex substation layouts

    and different CT classesand manufacturers.

    The use of fibre optics forcommunication betweenPeripheral Units and theCentral Unit gives thefollowing advantages:

    - High communicationspeed

    - Eliminates insulationproblems

    Fast fault clearance(Typical tripping time 15 ms).

    >

    T&DEnergy Automation & Information

    MiCOM P740

    Numerical Busbar Protection

    >> The consequences of a faulton the busbars of a powertransmission or distributionnetwork substation may be veryserious. Poor quality of supply toconsumers and damage to theelectrical equipment are veryreal threats.

    ALSTOM has developed a newand fully numerical busbarprotection. The primary

    objectives are to provide totalprotection stability under normaloperating conditions and for allexternal faults, whilst reactingquickly to internal faults. Thisprotection scheme is theMiCOM P740.

    The MiCOM P740 provideshigh-speed protection ( Distributed architecture (up to 1.000 m

    of optical fibre) or in a centralised cubicle.

    > Topological configuration can

    accommodate up to 8 zones.

    > Advanced topological analysis using

    operational research algorithms

    (registered patent).

    > Trip supervision by "check zone"

    element for security.

    > Low CT requirements allow the core

    to be shared with existing protection.> Innovative algorithms for CT

    saturation detection

    (registered patent).

    The minimum permitted saturation

    time is 2 ms for stability.

    > Bias characteristics to maintain

    stability during transient CT responses

    in presence of a significant DC

    component.

    > Security against accidental open

    circuit of CTs by the use of delta

    algorithms.

    > Phase segregation with a separateelement for sensitive earth fault

    detection (high impedance earthed

    networks).

    > Automatic control of the sensitive

    earth fault element by phase elements.

    > User-friendly interface for operation

    and commissioning staff including

    two levels of maintenance.

    Our products>

    > >

  • 8/11/2019 Micom P740

    12/18

    Main protection functions

    > Architecture

    The architecture of the numerical

    differential busbar protection is builtaround a P741 Central Unit (CU) whichgathers and processes all the analoguemeasurements from the P742 and P743Peripheral Units (PU) via direct fibreoptic connections.It is possible to protect:

    8 zones.

    32 Peripheral Units per Central Unit.

    > Protection

    > Central Unit (P741)

    Busbar bias differential protection. Check Zone protection

    Breaker Fail protection

    (general 3 poles trip).

    > Peripheral Units (P742/3)

    Dead zone protection (short zone

    between CTs and circuit-breakers).

    Non directional Overcurrent

    protection.

    - Phase fault (2 stages).

    - Earth fault (2 stages).

    Breaker Fail protection

    (single or three pole retrip).

    Busbar protection

    The operation of the MiCOM P740 isbased on the numerical application ofKirchoff's Law for the selective detectionand ultra high-speed isolation of afaulty section of a busbar.

    > Universal topologicalprocessing algorithms

    The MiCOM P740 uses new universalalgorithms based on operational

    research which create, in real time,architectures of up to 8 zones.

    > Stabilisation againstCT saturation

    One of the most important objectives ofa differential busbar protection is toensure stability when CTs becomesaturated, particularly under externalfault conditions.In order to avoid this risk ofmaloperation, the MiCOM P740 usesinnovative ultra high-speed algorithmsbased on signal consistence variationmodel (registered patent).

    > Bias characteristic

    The operation of the MiCOM P740 isbased on an algorithm with acharacteristic (see figure 2) in which the

    differential current is compared with abias value.The purpose of this characteristic is toensure the stability of the protection

    when there is an external fault, differingCT tolerances and errors whichotherwise would lead to spuriousdetection of an in-zone fault.

    > Global supervision by

    check zone element

    One of the most frequent causes of themaloperation of busbar protectionschemes is an error in actual plantstatus. This leads to the production of adifferential current.

    2

    Models available

    Features P741 P742 P743

    CentralUnit

    PeripheralUnit

    Peripheral

    Unit87BB/P

    87BB/N

    87CZ

    50/51/P

    50/51/N

    CTS

    50BF

    8 Opto Universal Inputs, 8 Output relays(MiCOM 16case, 80 TE)

    16 Opto Universal Inputs, 8 Output relays(MiCOM 8case, 40 TE)

    24 Opto Universal Inputs, 21 Output relays

    (MiCOM 12case, 60 TE)

    Phase segregated currentdifferential busbar protection

    Sensitive earth fault busbar protectionCheck zone element (Supervision)

    Phase Overcurrent protection

    Earth Overcurrent protection

    Current transformers supervision

    Breaker fail protectionLocal single orthree pole re-tripGeneral three poleback-trip

    Fibre Optic signalling channels

    Figure 1

    Double Busbarwith transfer bus

    BB1

    CentralUnitOptical Fibre Peripheral UnitsPeripheral Units

    BB2

    BB3

    BB4

    TransferBus

    2 P742or

    P743

    P742 P743 P741 P742P743

  • 8/11/2019 Micom P740

    13/18

    However, if all currents of the wholesubstation are taken into account, theirsum will remain null if a fault is notpresent, irrespective of the error in plantstatus/position.Consequently, the tripping order for azone element is conditional on theoperation of a check zone element.The main advantage of this element isthe total insensitivity to defectiveauxiliary contacts.

    > Dead zone or Blind spot

    The current transformers surrounding thebusbars define the limits of the mainzones. When the circuit breaker isopened a dead zone or blind spot isautomatically created between the CBand the associated CT.

    > Continuous supervision of thecurrent circuits by

    measurement of thedifferential current value

    Under normal operating conditions thedifferential current will be negligible. Ananomaly is detected by a threshold,ID>1, which can be set to alarm from1% of the primary basis current (Ibp).

    > Differential current setting

    When switching operations are carriedout in the substation, incorrect topologyreplicas may occur. In this case, adifferential current appears.The differential elements of the MiCOMP740 are allowed to operate only if thedifferential current reaches a thresholdID>2 which is set above the highest loadcurrent.

    > Stabilisation of the protectionin the event of CT saturationfor external fault

    One main quality of the MiCOM P740is its ability to detect CT saturation in

    less than 2 ms.The signal processing algorithmsimplemented in the MiCOM P740combine a simulation of the flux built upin the core of the CTs with a recursiveconsistence variation control(registered patent).

    > Additional ultra high speedexternal fault blocking

    The ultra high-speed saturation detectionis carried out in each PU and cangenerate a control signal from themoment of the first sample (0.4 ms).

    > Dual characteristics

    The MiCOM P740 offers phase-segregated protection and a separateelement for earth fault detection.

    > Multiple tripping criteria

    The MiCOM P740 maintains the highestlevel of stability, under all conditionsincluding:

    > A hardware failure

    > Incoherence of signals applied from

    external plant or generated by the

    power system.

    > Any tripping order must therefore be

    made conditional on the simultaneous

    occurrence of 5 or 6 criteria:

    > Magnitude criteria; confirmation of

    two simultaneous thresholds per zone:

    Exceeding the bias slopecharacteristic (k)

    Exceeding differential operating

    current threshold (ID>2).

    > Exceeding the supervision threshold

    (ID>1).

    > Signal quality criteria:

    No CT saturation detected

    Current variation detected on at

    least two Peripheral Units

    No discrepancy detected.

    > Time or angular criterion.

    The measurement elements on 2samples taken at 1200 Hz.

    A first sample for the initial

    measurement and a second sample

    for trip confirmation.> Check zone supervision.

    The zone element(s) are only

    permitted to trip if the order is

    confirmed by the check zone element.> Local criteria (optional)

    The Peripheral Units can be set to

    only authorise tripping if there isconfirmation by local overcurrent

    criteria.

    Additional protection

    The following back-up protectionfunctions are implemented locally in thePeripheral Units (P742/P743).

    > Phase and Earth Faultovercurrent protection either

    Definite Time (DT) or IDMT(IEC/UK, IEEE/US curves)

    Two independent stages are availablefor phase and earth:

    > First stage (I>1 or IN>1) can be

    programmed as Definite Time (DT)

    delay or dependant on one of nine

    inverse time (IDMT) curves

    (IEC/UK and IEEE/US).

    > Second stage (I>2 or IN>2) can only

    be programmed as definite time.

    > External Breaker Failureprotection from the busbarprotection system

    The usual 50 BF relay is totallyindependent of the others and thecontrol connection with the busbarprotection system is hardwired. Receiptof an external 50BF information resultsin tripping of all the adjacent circuitbreakers, via the topological recognitionsystem knowing which breaker isconnected to which zone.

    > Internal breaker failureprotection in the busbarprotection system

    Some operators prefer an integratedsolution, which requires all PeripheralUnits to receive a duplication of the tripcommands generated in their associatedbay.In general the Breaker Failure protectionmust be executed on a per phase basis

    which involves the possibility ofreceiving tripping orders on a per pole

    basis.

    i (t)bias

    I > 2Di3 in

    i2i1

    I > 1DIs

    perce

    ntage

    bias

    -k=2

    0to9

    0%

    TrippingArea

    Restrainarea

    i (t)diff nodeDifferential current : = + + i n1 2 iii 3+ ....... +i (t)diffOperating current : = = i

    i (t)diff

    i (t)bias i 1 i 2 i 3 i nRestraining current : = + + + ....... + = i

    i (t)diff node

    3

    Figure 2

    Biascharacteristic

  • 8/11/2019 Micom P740

    14/18

    4

    Matching CT Transformer ratios

    > Balancing protection

    The MiCOM P740 can correct mismatch

    between current transformer ratios overa very wide range up to 40. Itsassociated user interface provides arange between 1 A and 30,000 Aprimary.

    > Common base ratio

    Since the current transformer ratings ina substation may be of mixed ratios, theMiCOM P740 enables a common basecurrent to be defined, irrespective of thefeeder section concerned. The settingson the CU are all adjusted to this

    common current, known as the primarybasis current (Ibp).

    Isolation and downgradedoperating mode

    For ease of operation or maintenance ofthe busbar protection system, theCentral Unit and the Peripheral Unitscan receive specific commands designedto allow system testing or otherintervention without any danger of

    unwanted tripping.

    > Central Unit - CU (P741)

    A central command to isolate thebusbars at two levels can be appliedselectively zone by zone.

    > Differential protection (87 BB) in

    monitoring mode (measurements

    active and tripping deactivated).

    The Breaker Failure protection

    remains operational.

    > Differential protection (87 BB) and

    Circuit Breaker Failure protection

    (50 BF) in monitoring mode. The

    additional local protection functions

    (51, 51N, etc...) remain operational.

    > Peripheral Units - PU(P742 and P743)

    A selective two-level command may beapplied selectively for each PU.

    > Maintenance of bay(s) for human

    intervention. In this state,

    all I/O are deactivated.

    The busbar protection is still in

    service, but the CB of the feeder in

    service can not be tripped.

    > Intervention on the equipment for

    maintenance and testing.

    Control

    > Circuit breaker control

    The circuit breaker control is availablefrom the front panel user interface, orthe optically isolated inputs.

    > Programmable scheme logic

    Powerful Programmable Scheme Logic(PSL) allows the user to customise theprotection and control functions. It isalso used to program the functionality ofthe optically isolated inputs, relayoutputs and LED indications.The PSL uses up to 256 logic gates and8 timers and is configured using thegraphical MiCOM S1 PC basedsoftware as illustrated in Figure 3.

    > Independent protection

    settings groups

    The settings are divided into twocategories: protection settings and

    control and configuration settings. Foursettings groups are provided for theprotection settings to allow differentoperating conditions and adaptiverelaying.

    Measurement and recording

    facilities

    The P740 series relays are capable ofmeasuring and storing the valuesassociated with a fault. All the events,faults records and disturbance records

    are time tagged to 1 ms using aninternal real time clock. An IRIG-B portis also provided for accurate timesynchronisation.

    A lithium battery provides a back up forthe real time clock and all records in theevent of supply failure.

    > Measurements

    The measurements provided, which maybe viewed in primary or secondary

    values, can be accessed via the back litliquid crystal display. They are also

    accessible via the communication ports.

    > Instantaneous measurements

    > Central unit (P741) Differential current

    Idiff/phase/zone Bias Current

    Ibias/phase/zone Check zone

    Idiff/phase

    > Peripheral units (P742 & P743) Phase currents IA IB IC

    Neutral currentIN

    Frequency f

    Figure 3

    Programmable Scheme Logic

  • 8/11/2019 Micom P740

    15/18

    Post fault analysis

    > Event recorder

    Up to 250 time tagged event recordsare stored in battery backed memory,and can be extracted via thecommunication port or be viewed on thefront panel display.

    > Fault recorder

    Records of the last 5 faults are stored inthe battery-backed memory.

    Each fault record includes: Indication of the faulted phase Indication of the faulted zone (CU) Protection element operated Active setting group Fault duration Currents and frequency (PU) Faulty zone differential and

    bias current (CU)

    > Disturbance Recorder

    The internal disturbance recorder storeson non-volatile memory: 8 analogue channels

    ibias/idiff (CU) iA, iB, iC, iN (PU)

    32 digital channels 1 time channel Data is sampled 12 times a cycle 20 (PU) & 8 (CU) disturbance records Max. duration of each record for

    PU: 10.5 s & CU: 600 ms All channels and trigger sources user

    configured (PU)

    Disturbance records can be extractedfrom the relay via the remotecommunications and saved in theCOMTRADE format.

    These records may be examined usingMiCOM S1 or COMTRADE viewer.

    Plant status

    Checks and monitoring of the plantstatus can be made, and an alarmraised for any discrepancy conditionsbetween the open and closed auxiliarycontacts of the isolators and circuitbreakers.

    Local communications port

    All the relays are equipped with a localcommunications port on the front face.The PUs are also accessible from onecentral point via the protectioncommunication channel, i.e. via theP741 Central Unit.

    The local communication port is

    designed to be used with MiCOM S1. Itdeals with the local functions and allowsthe user to program bay settings and toconfigure the PSL. Extraction and

    viewing of events, disturbance recordingand the fault records is also possible.

    Supervision & diagnostics

    Continuous self monitoring Continuous local supervision of

    current transformers by zero-sequence current control

    Continuous central supervision ofcurrent circuits by measurement of thedifferential current(circuitry fault detection)

    Trip circuit supervision(using specific PSL)

    Power-up diagnostics Test facilities

    Diagnostics

    Continous self-checking gives a high

    degree of reliability. The results of theself-test functions are saved in thebattery-backed memory.The test features available on the userinterface provide the status of the inputquantities, the digital inputs, the relayoutputs and selected internal logic.

    A local monitor port providing digitaloutputs, selected from a prescribed listof signals, including the status ofprotection elements may be used inconjunction with test equipment.

    Hardware description

    All models within the MiCOM P740series relays include: A back-lit liquid crystal display 12 LEDs Optional IRIG-B port (CU), RS232 Port, Fibre optic connection from

    the CU to the PUs, Download/monitor port, Battery (supervised), N/O and C/O watchdog contacts Supervised +48 V field voltage

    Dual rated CT inputs 1A/5A

    The hardware variation between theMiCOM P740 series relay models are:

    (1) Universal voltage range opto-inputs(2) N/O: Normally Open

    C/O: Change Over

    The opto inputs are independent, andmay be energised from any substationbattery voltage, or from the 48V-field

    voltage.

    User interface

    The front panel user interface comprises:

    (1) A 2 x 16 characters backlitLCD display(2) Four fixed LEDs(3) Eight user programmable LEDs(4) Menu navigation and data

    entry keys(5) READ and CLEAR keys

    to view alarms(6) An upper cover identifying

    the product name.(7) A lower cover concealing the front

    RS232 port & parallel port -download/monitoring port andbattery compartment.

    (8) Facility for fitting a security

    lead seal

    5

    P741 P742 P743

    Relay

    Outputs (2)

    Opto

    -inputs (1)8 16 24

    6 N/O 6 N/O 15 N/O

    2 C/O 2 C/O 6 C/O

    12

    3

    4

    5

    6

    78

  • 8/11/2019 Micom P740

    16/18

    The user interface and menu text areavailable in English, French, German

    and Spanish as standard. Labelssupplied with the device allow tocustomise the LEDs descriptions.

    A user selectable default displayprovides measurement information,time/date, protection functions andplant reference information. The abilityto customise the menu text and alarmtext is also supported.

    > Password Protection

    Password protection may beindependently applied to the front userinterface, to the front communicationsport and to the rear communicationport. Two levels of password protectionare available providing access to thecontrols and settings respectively.

    Software support

    WindowsTM 98/ME/2000/NT compatible.MiCOM S1 software which comprises:

    Settings editor Programmable Scheme Logic editor Menu text editor Display of fault diagnostics and

    measurements Disturbance recorder viewer

    Technical data

    > Nominal Operating time

    Typic 15 ms to energisation of CB tripcoil (including relay contact closure).

    > Ratings

    > Inputs

    AC Current (In)

    1 A / 5 A Dual rated

    Frequency 50/60 Hz 5Hz

    Auxiliary Voltage (Vx)

    > Outputs

    Field Voltage 48 Vdc

    (current limit: 112 mA)> Optocoupled digital inputs

    Maximum voltage input

    (any setting): 300V dc

    > Burdens

    > P741

    With 8 comms. boards

    37 to 41 W

    With 5 comms. boards

    25 to 29 W

    > P742: 16 to 23 W

    > P743: 22 to 32 W

    > Optical fibre connection

    850nm, ST connectors Multi-mode fibre 62.5/125

    Data rate: 2.5 Mbits

    Maximum lenght: 1000 m

    > Front communication port

    Multi core Cable 15 m maxi.

    Connector RS232 DTE

    9 pins D-type Female

    Protocol Courier

    Isolation ELV for local access

    > IRIG-B Port

    Carrier signal

    Amplitude modulated

    Connection BNC

    50 coaxial cable

    > Download/monitor port

    This is a 25 pin D-type female connector

    located on the front user interface and is

    specially designed for test purposes and

    software download.

    > Internal Battery

    Battery type: AA, 3.6V

    6

    A = Clearance holesB = Mounting holes

    23.25

    159.00

    10.30

    168.0

    0

    177.00

    Front view

    Side view30.00

    240.00Incl. wiring

    Secondary cover (when fitted)

    116.55 142.45

    155.40 129.50305.50

    A B A B B A

    A B B AB A

    12 off holes Dia. 3.4

    303.50

    309.60

    157.5 max

    177.0(4U)

    483 (19 rack)

    Sealingstrip

    All dimensions in mm

    CC CA

    Operating range (V)

    24 - 48 19 - 65 -

    48 - 110 37 - 150 24 - 110

    110 - 250 87 - 300 80 - 265

    Nominal

    (V) DC

    >

    Figure 4 Case size MiCOM P741 (80TE)

  • 8/11/2019 Micom P740

    17/18

    7

    7

    Central Unit (CU)

    Vx aux rating

    Communication boards

    Hardware options

    1

    24 - 48Vdc

    48 - 125Vdc (30 - 100Vac)

    110 - 250Vdc (100 - 240Vac)

    1 communication board (up to 4 peripheral units)2 communication boards (up to 8 peripheral units)

    Standard version 1IRIG-B input 2

    3 communication boards (up to 12 peripheral units)4 communication boards (up to 16 peripheral units)

    5 communication boards (up to 20 peripheral units)6 communication boards (up to 24 peripheral units)7 communication boards (up to 28 peripheral units)8 communication boards (up to 32 peripheral units)

    1

    2

    3

    1

    MiCOM P 4

    P741:

    23

    4

    5678

    A 1A 0 0* **

    Central Unit,8 opto inputs, 8 outputs,Size 16" case (80 TE)

    Information required with order

    Peripheral Units (PU)

    Vx aux rating

    In rating

    2

    24 - 48Vdc

    48 - 125V dc (30 - 100V ac)

    110 - 250Vdc (100 - 240Vac)

    1

    2

    3

    Peripheral Unit,16 opto inputs, 8 outputs,Size 8" case (40 TE)

    Peripheral Unit,24 opto inputs, 21 outputs,Size 12" case (60 TE)

    3

    P742:

    P743:

    1 & 5 A - 1 1 0 V 1

    Without analogue inputs 0

    7MiCOM P 4 A 1 * *0A1

    23.30 155.40

    181.30202.00

    10.35

    159.00 168.00

    8 off holes Dia. 3.4

    A B B A

    A B B A

    Flush mounting panel

    Note: If mounting plateis required use flushmounting cut out dimensions

    200.00

    All dimensions in mm

    Front view

    177.00

    206.00 30.00Side view

    240.00Incl. wiring

    Secondary cover (when fitted)

    157.5 max

    177.0(4U)

    483 (19"rack)

    Sealing strip

    Panel cut-out detailA = Clearance holesB = Mounting holes

    A = Clearance holesB = Mounting holes

    23.25

    159.00

    10.30

    168.0

    0

    177.00

    Front view

    Side view30.00

    240.00Incl. wiring

    Secondary cover (when fitted)

    116.55 142.45

    155.40 129.50305.50

    A B A B B A

    A B B AB A

    12 off holes Dia. 3.4

    303.50

    309.60

    157.5 max

    177.0(4U)

    483 (19 rack)

    Sealingstrip

    All dimensions in mm

    > Case

    The MiCOM relays are housed in aspecially designed case providing ahigh density of functionality within theproduct, a customisable user interface,and additional functions/informationconcealed by upper an lower covers.

    Physical protection of the front paneluser interface and prevention of casualaccess is provided by an optionaltransparent front cover, which can befitted or omitted according to choicesince the front panel has been designed

    to IP52 protection against dust andwater.

    The case is suitable for either rack orpanel mounting as shown in figures4,5 and 6.

    > P741 MiCOM 80TE

    > P742 MiCOM 40TE

    > P743 MiCOM 60TE

    > Weight

    P741(with 8 comms. boards):

    7.6 kg

    P741

    (with 1 comms. board):

    6.2 kg

    P742

    7.5 kg

    P743

    9.2 kg

    >

    Figure 5 Case size MiCOM P742 (40TE) Figure 6 Case size MiCOM P743 (60TE)

  • 8/11/2019 Micom P740

    18/18

    ALSTOM Track Record -

    Busbar protection

    >> Low impedance biased differentialbusbar protection (MBCZ)launched in 1988.Over 6.522 units delivered.

    >> Over 211 medium impedancebiased differential busbarprotection (DIFB) delivered sincelaunching in 1992.

    >> Medium impedance biaseddifferential busbar protection withlinear current combination

    (DIFB CL). Over 73 cubiclesdelivered since 1996.

    Our policy is one of continuous development. Accordingly the design of our products may change at any time.Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for

    information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it.We cannot be held responsible for any reliance on any decisions taken on its contents without specific advise.

    South East Asia

    Tel.: +65 67 49 07 77 - Fax: +65 68 41 95 55

    Pacific

    Tel.: +65 67 49 07 77 - Fax: +65 68 46 17 95China

    Tel.: +86 10 64 10 62 88 - Fax: +86 10 64 10 62 64

    India

    Tel.: +91 11 26 44 99 07 - Fax: +91 11 26 44 94 47

    North America

    Tel.: +1 (484) 766-8100 - Fax: +1 (484) 766-8150

    Central America

    Tel.: +52 55 11 01 07 00 - Fax: +52 55 26 24 04 93

    South America

    Tel.: +55 11 30 69 08 01 - Fax: +55 11 30 69 07 93

    France

    Tel.: +33 1 40 89 66 00 - Fax: +33 1 40 89 67 19

    British Isles

    Tel.: +44 (0) 1785 27 41 08 - Fax: +44 (0) 1785 27 45 74

    Northern Europe

    Tel.: +49 69 66 32 11 51 - Fax: +49 69 66 32 21 54

    Central Europe & Western Asia

    Tel.: +48 22 850 96 00 - Fax: +48 22 654 55 90

    Near & Middle East

    Tel.: +971 6 556 3971 - Fax: +971 6 556 5133

    Mediterranean, North & West Africa

    Tel.: +33 1 41 49 20 00 - Fax: +33 1 41 49 24 23

    Southern & Eastern Africa

    Tel.: +27 11 82 05 111 - Fax: +27 11 82 05 220

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    PAPERRTS

    CTS

    0V

    RX

    TX

    SERIALPORT

    8

    9

    7

    4

    6

    5

    3

    2

    CONNECTED

    DATA READY

    TO-T7

    DO-D7

    0V

    RESETEXTERNAL

    ACKNOWLEDGE

    DOWNLOADCOMMAND

    DATA

    DOWNLOADTEST/

    17

    20,21,23,2411,12,15,13,

    19,18,22,25

    NOT

    1 SK1

    14

    2-9

    16

    10

    1

    E16SCN

    E18

    SK2

    E17

    C9

    OPTO 5 C10

    OPTO 3

    OPTO 4

    OPTO 1

    OPTO 2

    C8

    C7

    C6

    C5

    C4

    C3

    C1

    C2

    A18

    A16

    A17

    A15

    A14

    A12

    A13

    A10

    A11

    A7

    A8

    A9

    A6

    A5

    C14

    A4

    A3

    A2

    A1

    C17

    C18

    C16

    C15

    C12

    C13

    C11

    CONNECTION

    OPTO 16

    COMMON

    OPTO 15

    OPTO 14

    OPTO 13

    OPTO 12

    OPTO 11

    OPTO 7

    OPTO 10

    OPTO 9

    CONNECTIONCOMMON

    OPTO 8

    OPTO 6D8

    D7

    D10

    D9

    D12

    D11

    D13

    D16

    D18

    D17

    D14

    D15

    WATCHDOG

    WATCHDOG

    D2

    D5

    D6

    D4

    D3

    E13

    E14

    D1

    E12

    E11

    48V DC FIELDVOLTAGE OUT

    -

    -

    +

    +

    +

    -

    E10

    E9

    E8

    E2

    E7

    E1

    COMMUNICATIONFIBRE OPTIC

    CURR DIFF

    RX2

    RX1

    TX2

    TX1

    CASEEARTH

    DIRECTION OF FORWARD CURRENT FLOW

    NOTE 2.

    C

    B

    AS2 S1

    P2 P1

    NI

    B12

    B11

    B10

    B9

    1A

    5A

    1A

    B5

    CI

    B8

    B6

    B7

    BI

    B4

    B3

    B2

    5A

    1A

    5A

    1A

    PHASE ROTATION

    A

    C B

    I A

    B1 5A

    AUX SUPPLYAC OR DC Vx

    MiCOM P742 (PART)

    MiCOM P742 (PART)

    POWER SUPPLY VERSION 24-48V (NOMINAL) D .C. ONLY*

    CONTACT

    CONTACT

    RELAY 8

    RELAY 7

    RELAY 6

    RELAY 5

    RELAY 4

    TRIP A

    TRIP B

    TRIP C

    EIA485/KBUS

    PORT

    Busbar protectionPeripheral UnitP742

    C.T. SHORTING LINKS

    50 OHM BNC CONNECTOR

    PIN TERMINAL (P.C.B. TYPE)

    9-WAY & 25-WAY FEMALE D-TYPE SOCKET ANSI31_7

    (b)

    1.

    NOTES

    (a)

    2.C.T. CONNECTION S ARE SHOWN 1ACONNECTED AND ARE TYPICAL ONLY.

    3. THIS RELAY SHOULD BE ASSIGNED TOANY TRIP TO ENSURE CORRECT

    OPERATION OF THE PROTECTIVE RELAY.

    4. OPTO INPUTS 1 & 2 MUST BE USED FORSETTING GROUP CHANGES IF THIS OPTION

    IS SELECTED IN THE RELAY MENU.

    Figure 7 System overview of the P742 relay