1 MESCON TECHNOLOGIES, INC. Series SPM PC Programmable Universal Input Monitor USER & OPERATIONAL MANUAL

Transcript of MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ......

Page 1: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

1

MESCON TECHNOLOGIES, INC.

Series SPM

PC Programmable Universal Input Monitor

USER & OPERATIONAL MANUAL

Page 2: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

2

INTRODUCTION................................................................................................................................... 4

SOFTWARE INSTALLATION ............................................................................................................ 4

DOWNLOADING THE SPMCONFIGURATOR FROM WWW.MESCONTEC.COM............... 4

STARTING THE SPMCONFIGURATOR PROGRAM................................................................. 5

Software ................................................................................................................................................. 6

CONFIGURING THE SPM................................................................................................................... 9

Select the Input Sensor. ........................................................................................................................ 9

Choose sensor parameters. ................................................................................................................ 10

Engineering Units selection................................................................................................................ 10

Input range. ......................................................................................................................................... 11

Display scaling. ................................................................................................................................... 11

Decimal Point. ..................................................................................................................................... 11

Burnout Detection............................................................................................................................... 11

Line Frequency selection.................................................................................................................... 12

Damping. ............................................................................................................................................. 12

I.D. Tag................................................................................................................................................ 12

Job........................................................................................................................................................ 12

Message. .............................................................................................................................................. 12

DOWNLOADING THE CONFIGURATION.................................................................................... 13

OTHER FEATURES ............................................................................................................................ 13

Set-Points............................................................................................................................................. 13

Display color........................................................................................................................................ 13

DOCUMENTATION ............................................................................................................................ 14

SPM user identification. ..................................................................................................................... 14

SAVING A CONFIGURATION TO FILE......................................................................................... 14

PRINTING CONFIGURATION AND CALIBRATION INFORMATION................................... 14

INPUT FILTERING - THE SMART WAY ....................................................................................... 15

Damping Factor. ................................................................................................................................. 15

Damping Filter Band. ......................................................................................................................... 16

USER DEFINED TABLES .................................................................................................................. 16

User Defined Table for TEMPERATURE sensors ........................................................................... 16

User Defined Table for General Purpose Inputs ............................................................................... 16

APPLYING THE “USER DEFINED TABLE” FUNCTION ........................................................... 18

CREATING A TABLE FROM A MATH FUNCTION .................................................................... 18

CALLENDAR-VAN-DUSEN APPLICATIONS................................................................................ 18

POLYNOMIAL FUNCTIONS ............................................................................................................ 19

TRIMMING........................................................................................................................................... 20

CONTROL BUTTONS DESCRIPTION:........................................................................................... 21

Page 3: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

3

SPM INTERCONNECTION (WIRING) DIAGRAMS .................................................................... 21

Standard SPM wiring diagram........................................................................................................... 21

SPM with 2 X SPDT Relay Option wiring diagram .......................................................................... 22

SPM with 2 X SPST Relay Option wiring diagram ........................................................................... 23

SPM for AC measurement wiring diagram ....................................................................................... 24

Page 4: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

4

INTRODUCTION

Mescon’s series SPM-4XX indicators feature Mescon’s unique JUST-PC technology. These are

state-of-the-art, microprocessor and flash memory based high-performance digital process indicators.

The SPM series provide new highs in measurement accuracy and stability. The unique and user

friendly SPMconfigurator configuration software facilitates logical and speedy set-up of the

indicators. The PA-400, RS232, serial port Programming Adapter, enables full unit configuration

using a PC. No calibrator or meter are required !!!

The SPM indicators are supplied with input and output reference parameters fully factory calibrated.

For actual operation all that is required is to perform the simple and easy configuration procedure.

SOFTWARE INSTALLATION

CAUTION: Before installing the SPMconfigurator software, it is always advisable to close all other

applications including virus scanners and office suites. Failure to do so may result in the corruption of

certain common files.

Application software may be launched automatically when a computer is started up in three ways;

autoexec.bat file, the config.sys file and by Windows in its startup directory/folder.

For assistance in verifying that no applications are running or to disable the launching of such programs, call Mescon

Technologies, Inc. at 815-464-5004 from 8:00 AM to 5:00 PM Central Time before installing this software.

The SPMconfigurator software may be freely downloaded from Mescon’s web site at:

www.mescontec.com or provided on a CD-ROM. It may be installed on Windows 95, Windows 98

based systems. To install, insert the CD-ROM into the proper drive on your computer and run

“setup.exe”. Follow the on screen instructions for complete installation.

DOWNLOADING THE SPMconfigurator from www.mescontec.com

1. Enter Mescon’s web site at www.mescontec.com.2. Click on the “Downloads” icon, or select it from the menu.

3. Click on the “Software” icon, or select it from the menu.

4. Select the SPMconfigurator program for downloading.

5. Follow the instruction as they appear on the screen and select a location for saving the program

files for future use. Click on “Save” to download the SPMconfigurator to its selected location.

6. Perform the Set-Up procedure, which will open the compressed files and set the program up for

operation. It is always advisable to close all other applications including virus scanners and office

suites. Failure to do so may result in the corruption of certain common files.

Page 5: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

5

STARTING THE SPMconfigurator PROGRAM

1. Connect the PA-400 programming adapter into the proper serial port of the PC.

2. Click on the SPMconfigurator icon to start the program.

3. Remove the SPM front lens. Connect the 5-pin plug of the PA-400 to the 5-pin jack on the SPM.

NOTE: The connector is located on the SPM’s front panel, on the lower right hand corner.

Use a small screwdriver to Connect the plug of the PA-400 to the SPM’s jack

remove the front lens (Notice the correct orientation)

For proper operation of your programming adapter, you may need to verify the serial port to which it is

connected. From the menu bar, select the “Options” menu, click on “Communication” and enter the

correct COM port designation from the pull-down menu. (See Figure 1&2)

Figure 1

plug of PA-400

Page 6: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

6

Figure 2

Software

4. When the connection is made and the program recognizes that the SPM is properly connected to

the serial port, the toolbar icons will become highlighted. Normally, the software is provided

with the “Auto Upload” feature already selected, in which case the unit will automatically

upload its present settings to the PC. However, if this feature was turned off, for whatever

reason, simply click on the “UPLOAD” icon. This will begin the communication process

between the SPM and your PC. Once completed, the SPM’s calibration and configuration

settings will be loaded into your PC.

NOTE: The SPM’s display will blink for as long as it is connected to the PC. (See Figure 3)

Page 7: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

7

Figure 3

Figure 3 is an example of the screen that will be displayed when the user opens the program. From this

point on you must plug in the SPM to the computer for the next screen (See Figure 4) to appear.

Page 8: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

8

Figure 4

In figure 4 you may now observe the current configuration of the connected SPM. It is now possible to

configure the unit with other parameters and apply the changes to the SPM, as needed.

Page 9: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

9

Configuring the SPM

Select the Input Sensor.

Select the input sensor by clicking on the “Select Sensor” button.

From the sensor selection screen choose the proper “TAB” at the top of the screen for the sensor of

your choice. The specific sensor screen will now be presented. (See Figure 5)

Figure 5

Page 10: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

10

Choose sensor parameters.Click on the specific selection box which best define your sensor’s parameters. Click the OK button to return to the main

screen. On the main screen next to the “Select Sensor” box you will find the sensor type that has been selected. (See Figure

6) This serves to confirm the selection made on the previous screen.

Figure 6

Engineering Units selection.

Next, select the “Engineering Units”, where appropriate, from a pull- down menu for both the input

and the displayed data (see figure 7). You may type up to four characters in the displayed engineering

units box. These will only appear in the box when the SPM is connected to the PC but are not part of its

own display.

Figure 7

Page 11: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

11

Input range.

The Input “Zero” value defines the low end of the measurement range for the selected sensor. Enter

the “Zero” value in the appropriate box. Next enter the “Full Scale” value, which defines the high end

of the input range for the selected sensor. (See Figure 8)

Figure 8

Display scaling.

The display can exhibit the input parameters in any reasonable engineering scale. Simply type in the

desired scaled values for the corresponding displayed units in the Display “Zero” and “Full scale”

boxes. The SPM will automatically convert the input into the relevant display units.

Note: if display scaling is not desired, the program will copy the input “Zero” and “Full scale”

entries into the corresponding display boxes.

Note: the scaling feature is not normally applicable to temperature measurements using

standard RTDs or thermocouple sensors. However, should it be desired to provide scaling for

such applications it is possible to do so as follows: from the menu bar, select “Options” /

“General” / “Enable scaling for temperature sensors”. You will now be able to provide scaling

for temperature sensors.

Decimal Point.

Use the pull-down menu to select a decimal point. This will define the decimal point, which will appear

on the display.

Burnout Detection.

This feature is only relevant with the Analog Output option. From the pull down menu, select either

Upscale or Downscale for the desired characteristics. A burnt out sensor will cause the display to show

EEEEE (as in Error).

Page 12: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

12

Line Frequency selection.

From the “Line Frequency” pull-down menu, select either 50Hz or 60Hz for the power line frequency

used at your location. (See Figure 10)

Figure 10

Damping.Next Click on the “Set to Optimal” button to enable the computer to calculate and select the optimal values

for the digital filters which determine the damping factor and the damping filter band for the input signal. (See paragraph

about INPUT FILTERING - THE SMART WAY for more detailed information on this function)

I.D. Tag.You may now type in up to eight alpha-numeric characters for an ID tag description for the unit, to be saved in the SPM’s

memory. (See Figure 11)

Job.

You may now type in up to eight alphanumeric characters of a job title for the unit, to be saved in the

SPM’s memory. (See Figure 11)

Message.

You may now type in up to sixteen alphanumeric characters as a specific message for the unit, to be

saved in the SPM’s memory. (See Figure 11)

Figure 11

Page 13: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

13

DOWNLOADING THE CONFIGURATION

You may now click on the “DOWNLOAD” icon. This will instruct the computer to calculate the

entire new set of reference parameters, and download the new configuration values into the SPM

non-volatile memory.

You may verify the memory contents by clicking on the “VERIFY” icon, or you may select the

“Auto Verify” function from the “option / general” menu. In the verification process the settings are

uploaded from the SPM and are compared to the downloaded ones. If not identical, an error message

will appear. In this case, simply repeat the downloading and verify again.

OTHER FEATURES

The SPM may be purchased with several added features, such as: Analog Output, Alarm set points,

Function keys, Communication, and multi-color display. To configure these feature, when available,

click on the “Select Feature” button. The “Input Feature Selection” menu screen will appear. Only

the available features will be highlighted.

Set-Points

From the “Input Feature Selection” screen, select “Set Points”.

1. Select Alarm on High or Alarm on Low for both set points (1 & 2). This will determine the

direction of the alarm activation on either an increasing or a decreasing input value.

2. Enter the trip point values. Trip ON will determine the value of the input parameter for which the

alarm is activated. Trip OFF will determine the value of the input parameter for which the alarm is

deactivated. The difference between the two is in effect, the Dead Band (or hysteresis).

Alternatively, you may enter the Trip Point and Dead Band values, which will also determine the

Trip ON / Trip OFF values.

3. select the desired relays’ output for the alarm condition, either as Open on alarm or as Close

(Inverse) on alarm.

4. Click the “apply” button to download the set-point configuration, or the “OK” button, to download

the configuration and close the Set Point screen.

Note: For proper operation both set points must be defined and values entered for. If only one alarm

point is needed, make sure to select the other one well out of the known measurement range of the

input sensor.

Display color

From the “Input Feature Selection” screen, select “Display Color”. This menu screen will define the

display color for the various alarm conditions.

The column designated as “ALARM STATUS” indicates the various possible alarm conditions

resulting from the set-point selection.

Click on the color bars under the DISPLAY COLOR column header. The color bars will change their

color instantly, from RED to GREEN to YELOW, indicating the specific display color for that alarm

status. Any sequence or color combination may be selected. To finish, click the “apply” button to

download the color configuration, or the “OK” button, to download the configuration and close the

Display Color screen.

Page 14: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

14

DOCUMENTATION

SPM user identification.The SPM contains several fields, which may be used to specifically identify that individual unit. These include:

I.D. Tag: Up to 8 alphanumeric characters

Job: Up to 8 alphanumeric characters

Message: Up to 16 alphanumeric characters

These fields can be changed or modified at any time. Simply click on the appropriate field and enter the

text. To conclude and save this information, click on the “DOWNLOAD” icon. The information

will be downloaded and stored in the SPM’s memory. This configuration information can be retrieved

at any time just by clicking on the “UPLOAD” icon.

SAVING A CONFIGURATION TO FILE

Any general SPM configuration may be saved into a standard file. This information may be used for

future references, re-loading, and archiving.

To SAVE, click on the “SAVE” icon in the tool bar and specify a file name and directory location

to which the file is to be saved.

Should there be many SPMs that need to be configured with the exact same parameters, the user may

select the ‘Regeneration Enable” option from the “option / general” menu.

To configure a new device with the preloaded parameters, click on the “REGENERATION” icon.

The computer will automatically upload the new SPM calibration parameters, calculate the proper

configuration parameters, then, download them to the SPM’s memory.

PRINTING CONFIGURATION AND CALIBRATION INFORMATION

Click on the tool bar “PRINTER” icon to initiate the printing of the SPM’s configuration and

calibration information. The printed report will include the S/N, the values of the unit’s own input and

output calibration reference codes, configuration reference codes, current time and date, the date of last

configuration and the date of the last calibration. The printed data can provide invaluable information

in systems performance research, error determination and corrections, and “before” and “after”

analysis. (See Table 1)

Page 15: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

15

Table 1.

Configuration and Calibration Information

Device Status

Unit Type: SPM-400

Serial Number: DEMO133

Tag: 970911

Message: Product Intake

Job: Chiller

PO Number: 971210MES

PO Date: Wed, December 17, 1997

Last Configuration Date: Fri, January 16, 1998

Sensor Type: Thermocouple, type K, Standard Mode, Single Input

Input Range and Setup Option

Engineering Units: Fahrenheit

Zero: 0.00

Full Scale: 500.00

Burnout: Upscale

Line Frequency: 60 Hz

Filter

Damping: 15 sec.

Band: 0.44%

Calibration References

Output 4mA: 1782

Output 20mA: 8948

Input mV: 91.289

Input Ohms: 301.023

CJ Temperature: 296.768

Last Calibration Date: Wed, November 19, 1997

Device Program I.D. : 31977.2

printed on: Friday, January 16, 1998, 12:06:17

INPUT FILTERING - THE SMART WAY

Input filtering is of great importance in low level measurement applications. The effect of low pass

filtering is to average out small transients of the input signal, resulting from process and sensor noise,

as well as externally generated electrical noises. To overcome the sluggish response, often associated

with long filter settings, the SPM uses a Selective Filtering technique. By controlling both the damping

factor and the filter band, this method allows the SPM to achieve faster response time for significant

input variation, yet to provide a stable and clear indication of the measured parameter.

Damping Factor.The Damping Factor provides a measure of the time (in seconds) over which the input signal will be averaged. The greater

the Damping Factor, the smoother the indication (and the slower the measurement). Selective Filtering implies that the

damping is only applied over a limited input Band around the input levels where noise is most likely to be present. This is

the Filter Band.

Page 16: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

16

Damping Filter Band.The Filter Band is defined as the band (in % of the input span) for which damping is applied. A 1% Band for a SPM with a

measurement input span of 500°C means that Damping will apply to input variations of 5°C and less. However, changes in

the input of greater than 5°C will be directly reflected in the SPM’s display without a delay.

For most applications it is sensible to assume that wide input spans would require low band settings

and narrow spans would require large band settings. The SPMconfigurator software provides for a

calculated optimal filter setting which is suitable for the majority of applications, accounting for the

specific SPM input span.

To enable the automatic application of this function simply click on the “Set to Optimal” box.

Note: the settings may be changed manually at any time for applications, which may require it.

USER DEFINED TABLES

For applications where the input is non-standard and non-linear, a User Defined Table (UDT) function

provides a simple and convenient way of linearizing an input for which a linearization table is

available.

Two methods are being used for creating “User Defined Tables”. One is for standard temperature

sensors such as thermocouples and RTDs. The other is for inputs such as mV, Volts, mA, resistance

and potentiometers.

The tables must be made in simple text (ASCII) files. These text files may be written in, or transferred

to, any standard text editor. Lines containing notes, memos, comments and descriptions must be

preceded with an asterisk (*). The * signifies to the software that this line is not a part of the

conversion table. The conversion table must only contain numerical values !! No letters, symbols or

other characters are allowed. (See Table 2)

It is a good practice to include a description, references, dates, and other notes relating the specific

application of the conversion table as a heading to the table.

It may also be useful to store the table in a special directory in order to facilitate easy access in future

use.

User Defined Table for TEMPERATURE sensors

A “user defined table” for temperature sensors (thermocouples or RTDs) consists of two columns of

numbers. The left column is a list of numbers representing the input temperatures for which the table is

defined. Temperature values must be defined in °C !!! The second column should display the values of

the actual sensor output in mV, or Ohms.

User Defined Table for General Purpose Inputs

The first column should display the values of the actual sensor output in mV, mA, Volts, Ohms, or %

(for potentiometers). The second column should display the corresponding values in engineering units.

NOTE: scaling may still be applied to the engineering units values.

Page 17: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

17

Table 2.

Example of a user defined table.

*User defined table for

*IRt/c.xxx-K-80F/27C

*Minimum range -70 degrees Celsius

*Maximum range 200 degrees Celsius

*First column degrees Celsius

*Second Column mV

*Delta 10 degrees

*Use with Thermocouple Sensor Type, User defined table

*Created November 7, 1999

-70.00 -2.59

-60.00 -2.26

-50.00 -1.92

-40.00 -1.57

-30.00 -1.20

-20.00 -0.82

-10.00 -0.42

0.00 0.00

10.00 0.44

20.00 0.90

30.00 1.38

40.00 1.90

50.00 2.44

60.00 3.01

70.00 3.62

80.00 4.26

90.00 4.95

100.00 5.67

110.00 6.45

120.00 7.28

130.00 8.16

140.00 9.09

150.00 10.07

160.00 11.09

170.00 12.16

180.00 13.27

190.00 14.40

200.00 15.55

The table’s Input (left) and output (right) values should be separated by at least a single space or TAB.

Page 18: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

18

APPLYING THE “USER DEFINED TABLE” FUNCTION

1. Select the input sensor for the application.

2. From the “transfer function” or “mode” selection box, select the “user defined table” button.

3. Enter the minimum and maximum table input range. (See Figure 13)

4. Enter the table’s complete file name. (See Figure 13)

5. Select the “OK” button.

6. Download the new configuration

The SPM device is now ready to apply the function.

NOTE: The SPM only contains a calculated table matching its parameters. Hence, when uploading the

SPM configuration, the SPMconfigurator may open a dialog box requiring to open the specific UDT

file which is stored in the computer.

Figure 13

CREATING A TABLE FROM A MATH FUNCTION

If your sensor’s transfer function can be described in a mathematical (trigonometric, log, etc.) equation

it is an easy task to convert it into a table. Use any commercial spreadsheet software program, under

Windows, such as Excel or Lotus, in order to generate a table as above. Use the “COPY” and “PASTE”

commands to transfer the table section to any text editor such as “Notepad” and edit the table and text

according to the above instructions.

CALLENDAR-VAN-DUSEN APPLICATIONS

The Callendar-Van-Dusen application provides a set of constants for a third order polynomial equation,

which then approximates the actual Pt-100 RTD’s resistance to a high degree of precision.The specific

RTD needs to be precisely characterized by exact temperature testing, and the coefficients should then

be calculated.

Page 19: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

19

α alpha is the nominal sensitivity coefficient for the RTD, which, for most standard elements will

be about 0.00385 (DIN curve).

β Beta is zero (0) for temperatures >0 degrees C. It is the significant constant for <0 ranges.

δ Delta is the significant coefficient for the higher temperature ranges.

(See Figure 14)

Figure 14

The minimum and maximum values are the temperatures within the values for which the sensor was

supposed to be defined and tested for. The units are always in Degrees C. If the sensor was tested and

defined between -50°C and +450°C you may enter any values down to and including -50°C for the

minimum value and up to +450°C for the maximum value.

You MUST enter a value for Delta or else the program will request it. Typical values will run in the

order of 1.40 to 1.60 for 100Ohms (@ 0 Degrees C) elements. For units with the 0.000385 curve the

typical values are in the order of 1.45 to 1.47.

Once you enter all of the numbers, the SPMconfigurator software will generate the linearization table

for the particular range of the unit. Upon downloading, this table will be entered into the SPM’s

memory.

Note: the calculated values may be verified by using the simulation function (Alt + S), and observing

that the device indeed provides the proper temperatures for the resistance found by the element’s tests,

or vice versa.

POLYNOMIAL FUNCTIONS

Some sensors output may be characterized a by non-linear transfer function. This function may be

described using a multi-order polynomial. If the coefficients of this polynomial are available, the

Page 20: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

20

sensor’s output may be linearized. While in the Input Sensor Selection screen choose “Polynomial..”

then enter the proper coefficients. The function is suitable for up to a 10th order polynom.

TRIMMING

Realizing that sensors aren’t always perfectly matched to their ideal curves, the trimming function

allows the user to fine-tune the SPM calibration to match a specific sensor to its ideally defined

parameters. The trimming function is a smart substitute for the “zero” and “span” adjustment pots.

Trimming may be applied to a low (zero) or a high measurement point (span), much like conventional

“zero” and “span” adjustments.

To enter the trimming screen, click “Device / Trimming…” and the trimming screen will appear. The

screen contains two slide bars, in addition to several control buttons. To apply trimming to the SPM’s

measurement, check the “Trim On” box. The Lock/Unlock toggle dialog buttons will be added to the

“zero” and “span” slide bars and the top display will also exhibit the “<Trim On>” text. Clicking on

“Unlock” will release the function and position the bar in the center of the slide. Adjust the position of

the slide bar to reflect the desired values. The “Trimmed Value” display represents the adjusted value

of the measurement at the current input level. Clicking on “Lock” freezes the trimming position and the

trimmed value and disables that slide box.

Notice: To avoid potential adjustment errors, the “zero” may be adjusted at any input value, however,

the “span” may only be adjusted when the measured input parameter exceeds ~50% of the configured

input range.

Figure 15

Page 21: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

21

CONTROL BUTTONS DESCRIPTION:

OK - Saving / downloading the new setup. Closing the trimming screen.

Cancel - Restores previous setup and closing the trimming screen.

Hint - A few words about the trimming function…

Restore - Restore the previous setup.

Clear - Clear the trimmed values. Restore non-trim operation.

Note: While in the “Trim On” mode, the trimming adjustments are downloaded instantly to the SPM

and the units’ display reflects the trimmed information. It should be noted that the data displayed in the

trimming screen may slightly differ from that of the SPM display due to different filters used in the two

systems.

SPM INTERCONNECTION (WIRING) DIAGRAMS

Standard SPM wiring diagram

Page 22: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

22

SPM with 2 X SPDT Relay Option wiring diagram

Page 23: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

23

SPM with 2 X SPST Relay Option wiring diagram

Page 24: MESCON TECHNOLOGIES, INC. Series SPM USER MANUAL.pdf · MESCON TECHNOLOGIES, INC. Series SPM ... CREATING A TABLE FROM A MATH FUNCTION ... NOTE: The connector is located on the SPM’s

24

SPM for AC measurement wiring diagram