    EASYPAT 1600 PAT TESTER

    MARTINDALEELECTRIC

    Trusted by professionals

    INSTRUCTIONS

    16th Edition Testers

    All-in-ones

    Calibration Equipment

    Continuity Testers

    Electricians kits

    Full Calibration & Repair Service

    Fuse Finders

    Digital Clamp Meters

    Digital Multimeters

    Microwave Leakage Detectors

    Motor Maintenance Equipment

    Non-trip loop testers

    Pat testers & Accessories

    Phase rotation

    Proving units

    Socket Testers

    Thermometers & Probes

    Test Leads

    Voltage Indicators

    and

    Specialist Metrohm testers (4 & 5kV)

    Specialist Drummond testers

    http://www.pattesters.co.uk/
  • 8/10/2019 Martindale Epat1600 Manual 59

    2/8

    2 15

    SAFETY INFORMATION: Always read before proceeding.

    WARNING

    These instructions contain information and warnings that are necessary forsafe operation and maintenance of the EasyPat. It is recommended that you

    read the instructions carefully and ensure the contents are understood.Failure to understand the instructions and comply with warnings andinstructions herein can result in serious injury, damage or even death.

    In order to avoid the danger of electrical shock, it is important that propersafety measures are taken when working with voltages exceeding 30V ACrms, 42V AC peak or 60V DC. Never exceed the maximum allowable inputlevel for each function and range. Refer to the specifications for maximuminputs. Never touch exposed wiring, connections or live circuits.

    The EasyPat must only be used in conditions and for the purpose which ithas been constructed. Attention should be paid to safety instructions,technical specifications and use of the EastPat in dry surroundings.

    Always inspect your meter, test leads and accessories for any sign ofdamage before use. If any abnormal conditions exist (e.g: broken test leads,cracked case, display not reading, etc.), do not attempt to use it. Do not

    expose it to direct sunlight, excessive temperature or moisture.

    Keep these instructions for future reference. Updated instructions andproduct information are available at: www.martindale-electric.co.uk

    SYMBOLS:

    Equipment complies with relevant EU Directives

    AC (Alternating Current)

    Ground

    Direct Current

    Equipment protected by Double Insulation (Class II)

    Caution - refer to accompanying documents

    Caution - risk of electric shock

  • 8/10/2019 Martindale Epat1600 Manual 59

    3/8

    14 3

    CONTENTS

    1 Introduction

    1.1 Description

    1.2 Earth / Continuity (8A and 25A)

    1.3 Earth / Continuity (100mA)

    1.4 Insulation1.5 Fuse

    1.6 Unpacking & Inspection

    1.7 Spares & Accessories

    2 Specifications

    2.1 Electrical Specification

    2.2 Mechanical Specification

    2.3 Environmental Specification

    3 Operation

    3.1 Earth Continuity (8A and 25A)

    3.2 Earth Continuity (100mA)

    3.3 Insulation

    3.4 Fuse

    3.5 Lead Test

    4 Maintenance4.1 Cleaning4.2 Calibration

    4.3 Repair & Service

    4.4 Storage Conditions

    4.5 Warranty

    USER NOTES

  • 8/10/2019 Martindale Epat1600 Manual 59

    4/8

  • 8/10/2019 Martindale Epat1600 Manual 59

    5/8

    12 5

    Fig. 2 Display of reading (1.00)

    The instrument can be connected to a 230V supply and can test 230V or 110V

    appliances.

    Appliances to be tested should be connected into the appropriate test socket. If the

    appliance has an on/off switch, it should be set to the on position to ensure that theappliance is fully tested.

    If the value for the measured parameter is outside the range of the EasyPat 1600

    then the display will show overrange. This is indicated on the display by a single 1.

    with no following zeros (blank). Figure 3 shows the earth continuity display if the

    measured value is greater than 1.99.

    Fig. 3 Overrange Indication

    NB

    On the earth bond tests, overrange means above 1.99 and is a fail.

    On the insulation test it means above 19.9M and is a pass.On the fuse test it means the appliance is drawing more than a few mA andis a pass.

    3.5 Lead Test

    Ensure the earth wander lead is connected to the EasyPat. The crocodile clip

    however should not be used and must not be connected to the lead under test

    nor any earth path.

    For IEC LeadsPlug the lead into the appropriate EasyPat mains socket. Plug the IEC connector

    into the EasyPat IEC socket.

    For Extension Leads

    Plug the lead into the appropriate EasyPat mains socket. Use the short 230V IEC

    lead EX-332 (or optional 110V LEAD EX-331) to connect the extension lead

    outlet to the EasyPat IEC socket.

    Perform earth continuity and insulation tests as 3.1 & 3.3.

    If earth and insulation tests have successfully passed, unplug the lead under test

    from the EasyPat 1600 mains socket, leaving the IEC connector plugged into the

    lead tester. Connect the lead under test to a live mains socket. Check the

    illumination of Lamp 1 & Lamp 2 against the table printed on the EasyPat front

    panel.

  • 8/10/2019 Martindale Epat1600 Manual 59

    6/8

  • 8/10/2019 Martindale Epat1600 Manual 59

    7/8

  • 8/10/2019 Martindale Epat1600 Manual 59

    8/8

    8 9

    SOCKETS

    Mains: 230V 13A to BS 1363110V 16A to BS4343

    Leadtest: IEC320

    LAMPS

    Over Temperature: Red LED which illuminates when the temperature limit

    for the instrument has been exceeded. LED

    extinguishes when unit cools.

    Lamp 1/ Lamp 2: Red LEDs which illuminate to indicate lead polarity for

    extension lead test facility.

    FUSES

    Plug: 13A 1HBC (Ceramic)Internal: 3.15A (F) 5x20mm, HBC (Ceramic)

    Internal fuse is not user replaceable.

    SAFETY

    EMC: Meets BS EN 50081-1BS EN 50082-1

    LVD: Meets BS EN 61010-1

    2.2 Mechanical Specification

    CASE

    Size: 330x263x144mmMaterial: ABS/PolycarbonateColour: Yellow/ClearWeight: 4kg nominal

    2.3 Environmental Specification

    TEMPERATURE

    Operating: 0 C to 35CStorage: -10 C to 50C

    This instrument has been designed to be used in a clean dry environment.

    Do not use the instrument outdoors in wet conditions.

    2. SPECIFICATIONS

    2.1 Electrical Specification

    Supply Voltage: 230V10% 50/60Hz

    Power Consumption: 10/220VA

    EARTH CONTINUITY TEST (8A & 25A)

    Test Voltage: 6V AC nominal with no loadTest Current: 25A AC nom @ 0.1 (25A)

    8A AC nom @ 0.1 (8A)

    Display Range: 0 - 1.99Accuracy of Indication: 10% of reading 2 digits

    EARTH CONTINUITY TEST (100mA)

    Test Voltage: 130mV DC nominal open circuitTest Current: 100mA DC nominal constant currentRange: 0 - 1.99Accuracy of Indication: 10% of reading 2 digit

    INSULATION TEST

    Test Voltage: 500V DC -0% +20% at 0.5MShort Circuit Current: 1.5mA DC nominalDisplay Range: 0 - 19.9M

    Accuracy Of Indication: 5% of reading 1 digit

    FUSE TEST

    Test Voltage: 6V AC nominal

    Over range threshold: 10k nominalZero range threshold: 800k nominal

    LEADS

    Mains: 1.7M fixed lead, with a 13A moulded plugEarth Continuity: 3M long, detachable lead, heavy duty crocodile/alligator clip.230V IEC Adaptor: 13A BS1363 plug to IEC320 connector, 230mm long.