Manual Sicam Fcm

82
SICAM Feeder Condition Monitor 1.0 Manual E50417-H8940-C509-A1 Preface Table of Contents Delivery 1 Introduction 2 Hardware Components and Drawings 3 Device Functions 4 Technical Data 5 Connection Diagrams 6 Parameterization A Modbus Registers B Index

description

Power Design

Transcript of Manual Sicam Fcm

Page 1: Manual Sicam Fcm

SICAMFeeder Condition Monitor

1.0

Manual

I

H

D

T

C

P

M

I

E50417-H8940-C509-A1

Preface Table of Contents Delivery 1ntroduction 2ardware Components and Drawings 3evice Functions 4echnical Data 5onnection Diagrams 6arameterization Aodbus Registers B

ndex

Page 2: Manual Sicam Fcm

NOTEFor your own safety, please observe the warnings and safety instructions contained in this manual..

Disclaimer of LiabilityThis document has been subjected to rigorous technical review before being published. It is revised at regular intervals, and any modifications and amendments are included in the subsequent issues. The content of this doc-ument has been compiled for information purposes only. Although Siemens AG has made best efforts to keep the document as precise and up-to-date as possible, Siemens AG shall not assume any liability for defects and damage which result through use of the information contained herein. This content does not form part of a contract or of business relations; nor does it change these. All obligations of Siemens AG are stated in the relevant contractual agreements.Siemens AG reserves the right to revise this document from time to time..Document version: E50417-H8940-C509-A1.02Release status: 06.2013Version of the product described: 1.0

CopyrightCopyright © Siemens AG 2013. All rights reserved The disclosure, duplication, distribution and editing of this document, or utili-zation and communication of the content are not permitted, unless autho-rized in writing. All rights, including rights created by patent grant or registra-tion of a utility model or a design, are reserved. Registered TrademarksSICAM® is a registered trademark of Siemens AG. Any unauthorized use is illegal. All other designations in this document can be trademarks whose use by third parties for their own purposes can infringe the rights of the owner..

Page 3: Manual Sicam Fcm

Preface

Purpose of the Manual

This manual describes the functions and operation of 6MD2320 devices. In particular, you will find:

• Information regarding the configuration of the device and a description of the device functions 4.1 Fault Detection

• Compilation of the Technical Data 5.1 Device Technical Data

• Compilation of the most significant data for advanced users A.1 Parameterization

and B.1 Modbus Registers

Target Audience

Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-tenance of automation, selective protection and control equipment, and operating personnel in electrical instal-lations and power plants.

Scope

This manual applies to SICAM Feeder Condition Monitor (FCM) 6MD2320, firmware version V 1.X.

Additional Support

Should further information on the system SICAM be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens represen-tative.

Support

For more information, please contact our customer support center.

Phone: +49 (180) 524 84 37

Fax: +49 (180) 524 24 71

(Charges depending on the provider)

E-mail: [email protected]

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

3

Page 4: Manual Sicam Fcm

Preface

Training Courses

The SICAM FCM as a user-friendly product does not require individual trainings but it will be part of diverse SICAM RTU trainings.

If you are interested in our current training program, please contact our Training Center.

Siemens Power Academy

Humboldt Street 59

90459 Nuremberg

Phone: +49 (911) 433-7415

Fax: +49 (911) 433-7929

E-mail: [email protected]

Internet: http://www.siemens.com/power-academy

Safety Information

This manual is not a complete index of all safety measures required for operation of the equipment (module, device). However, it comprises important information that must be noted for purposes of personal safety, as well as in order to avoid material damage. Information is highlighted and illustrated as follows according to the degree of danger.

DANGERDANGER means that death or severe injury will result if the measures specified are not taken.

✧ Comply with all instructions, in order to avoid death or severe injuries.

WARNINGWARNING means that death or severe injury may result if the measures specified are not taken.

✧ Comply with all instructions, in order to avoid death or severe injuries.

CAUTIONCAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.

✧ Comply with all instructions, in order to avoid medium-severe or slight injuries.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

4

Page 5: Manual Sicam Fcm

Preface

Qualified Electrical Engineering Personnel

Only qualified electrical engineering personnel may commission and operate the equipment (module, device) described in this document. Qualified electrical engineering personnel in the sense of this manual are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, iso-late, ground and label devices, systems and circuits according to the standards of safety engineering.

Use as Prescribed

The equipment (device, module) may only be used for such applications as set out in the catalogs and the tech-nical description, and only in combination with third-party equipment recommended and approved by Siemens.

Problem-free and safe operation of the product depends on the following:

• Proper transport

• Proper storage, setup, and installation

• Proper operation and maintenance

When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper action is not taken, death, severe injury, or property damage can result.

• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected (capacitors can still be charged).

• Equipment with exposed current transformer circuits must not be operated.

• The limit values stated in the document may not be exceeded. This must also be considered during testing and commissioning.

Indication of Conformity

This product complies with the directive of the Council of the European Communities on harmonization of the laws of the Member States relating to electromagnetic com-patibility (EMC Council Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low Voltage Directive 2006/95/EC). This conformity has been proved by tests performed according to the Council Directive in accordance with the generic standards EN 61000-6-2 and EN 61000-6-4 (for EMC directive) and with the standard EN 61010-1 (for Low Voltage Directive) by Siemens AG. This device is designed and manufactured for application in an industrial environment. The product conforms with the international standard of IEC 61326-1.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

5

Page 6: Manual Sicam Fcm

Preface

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

6

Page 7: Manual Sicam Fcm

Table of Contents

Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

1 Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

1.1 Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

2 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

3 Hardware Components and Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

3.1 Hardware Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

3.2 Terminal Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

3.3 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

4 Device Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

4.1 Fault Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

4.2 Determination of Fault Direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

4.3 Direction Determination of Phase Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

4.4 Directional Earth Fault (Compensated/Resonant Earthed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

4.5 Directional Earth Fault (Isolated Earthed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

4.6 Inrush-Current Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

4.7 Voltage Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

4.8 Fault Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

4.9 Fault Reset Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

4.10 Measurements and Derived Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

4.11 RTC Synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

4.12 Archive Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

5 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

5.1 Device Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

6 Connection Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

6.1 Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

6.2 Installing the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

A Parameterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

A.1 Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38

A.2 Parameterizing the User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

A.3 Editing the Device Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42

B Modbus Registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43

B.1 Modbus Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

7

Page 8: Manual Sicam Fcm

Table of Contents

B.2 Implementation of Modbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

B.3 Bit Type Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

B.4 Register Type Data - Holding Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

B.5 Register Type Data - Input Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

B.6 Register Type Data - Analog Input Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

B.7 Register Type Data - Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

B.8 Register Type Data - Trailing Pointers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

8

Page 9: Manual Sicam Fcm

1 Delivery

1.1 Delivery 10

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

9

Page 10: Manual Sicam Fcm

Delivery1.1 Delivery

1.1 Delivery

Delivery Note

The SICAM FCM device is delivered in a cardboard box containing the Siemens logo.

Contents of Delivery• 1 SICAM FCM device

• 1 document with safety instructions

DANGERDanger of explosion of the battery.

Noncompliance with the safety instructions means that death, severe injuries or considerable material damages can occur.

✧ Do not throw the SICAM FCM device containing a battery into a fire.

WARNINGWarning about battery disposal.

Noncompliance with the safety instructions means that severe injuries or considerable material damages can occur.

✧ When discharged, or when properly secured against short-circuit, lithium batteries can be disposed of through retailers or at depots run by competent organizations (for example, in Germany GRS collection points).

NOTE

The lithium batteries in the equipment are subject to special provision 188/A45 of the dangerous goods regu-lations of the different transport modes (as in edition 2003, lithium content and tests of UN Manual of Tests and Criteria).

This is only valid for the original battery or original spare batteries. For general transport security by shipment as freight: Electric equipment is only to be sent as freight if shut off.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

10

Page 11: Manual Sicam Fcm

2 Introduction

2.1 Overview 12

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

11

Page 12: Manual Sicam Fcm

Introduction2.1 Overview

2.1 Overview.

SICAM Feeder Condition Monitor (FCM) is an Intelligent Electronic Device (IED) used for detecting and indi-cating short-circuits or earth faults with and without directional information. SICAM FCM accurately monitors, measures, and displays electrical variables and performs the condition monitoring task in a medium-voltage distribution grid. SICAM FCM is typically used in the medium-voltage secondary substation that ranges from greater than 1 kV up to 36 kV.

SICAM FCM measures the TRMS (True r.m.s value) for alternating voltage, alternating current, and power fre-quency. SICAM FCM calculates the active power (P), reactive power (Q), apparent power (S), power factor (cos Φ), and phase angle.

SICAM FCM consists of the following hardware components:

• 3 current inputs

• 3 voltage inputs

• 1 digital input

• 1 communication interface (Modbus RTU)

Figure 2-1 SICAM FCM Block Diagram

Applications

SICAM FCM is used in the medium-voltage energy distribution grid:

• As a fault indicator in the medium-voltage secondary substations

• As a directional and non-directional short-circuit detection and ground-fault detection

• As a simple power quality meter in various applications

Flush Mounting

SICAM FCM can be flush mounted in the panel and operated inside an enclosed dry room.

To mount SICAM FCM in the panel, follow the procedure:

• Cut a hole in the Ring Main Unit (RMU) panel measuring 92.0 + 0.8 mm x 45.0 + 0.8 mm (W x H).

• Carry out all required internal wiring connections.

For more information about terminal diagrams, refer to 3.2 Terminal Diagram

• Flush SICAM FCM into the panel and lock with the clamps.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

12

Page 13: Manual Sicam Fcm

Introduction2.1 Overview

Ordering Information

Use the following ordering information to order SICAM FCM and other related accessories.

For example, MLFB: 6MD2320-1AA00-1AA0

Figure 2-2 Ordering Information of SICAM FCM

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

13

Page 14: Manual Sicam Fcm

Introduction2.1 Overview

Battery Freshness Seal Mode

NOTE

Battery Freshness Mode (BFM) enhances the battery life of the device. BFM keeps the battery from discharging until the device is plugged in and used for the first time and preserves the battery life. When the device is shipped, BFM is enabled to avoid the discharge of the battery power during shipping and storage.

To operate the device with the battery power for the first time, you disable the BFM by supplying an auxiliary power to the device. Before storage, it is always recommended that you enable BFM of the device to avoid discharge of battery after use. During installation and commissioning, the BFM is automatically disabled once powered-on from an external power supply.

Accessories

You can download the current version of the SICAM FCM manual from www.siemens.com/powerquality

Typical Ordering Com-binations

MLFB Number

Use Case

Neutral-point treatment

Neutral-point treatment

Sensors avail-able

Solid/low resis-tant

Isolated/ com-pensated

with 1 A trans-ducer

SICAM FCM

Fault indica-tor with di-rectional in-formation and mea-surements of V, I, F, P, Q, S, cos Φ, power direc-tion

6MD2320-1AA00-1AA0

1 x 1 x 1 x 1 x

Phase-current sensor

Type 225 mV at 300 A, IEC 60044-8split core; window di-ameter 52 mm

6MD2320-0GA00-1AA0

– 3 x 2 x –

Core balance current sensor

Type 225 mV at 60 A, IEC 60044-8split core; window di-ameter 110 mm

6MD2320-0AF00-1AA0

– – 1 x –

1 A adaptor 3 inputs 1 A into low-power signal

6MD2320-0AA10-1AA0

– – – 1 x

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

14

Page 15: Manual Sicam Fcm

3 Hardware Components and Drawings

3.1 Hardware Components 16

3.2 Terminal Diagram 17

3.3 Dimensional Drawings 19

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

15

Page 16: Manual Sicam Fcm

Hardware Components and Drawings3.1 Hardware Components

3.1 Hardware Components.

In this manual, SICAM FCM is also referred as "Device".

• Microcontroller - The device uses a low-power ARM MCU which includes high-precision 16-bit ADCs.

• Battery - The device contains a battery with 3.6 V and a capacity of 1.2-Ah. When the main power supply fails, the battery is used to operate the device.

• LCD - LCD is used to view real-time values, events, archives, and device parameters.

• Keypads - The 4 navigation keys are used to navigate the device application software and select the desired parameters. The functions of navigation keys are specific to different LCD screens.

• LEDs - The device consists of 3 LEDs which indicate the status of the process.

- FAULT (Red) - Indicates when any distribution-grid fault is detected

- COM (Yellow) - Indicates that the communication is active between Modbus and the device

- RUN (Green) - Indicates the healthy condition of the device and running on the main power supply

• Digital Input - The device consists of 1 digital input for resetting the fault indication.

Figure 3-1 SICAM FCM Hardware Block Diagram

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

16

Page 17: Manual Sicam Fcm

Hardware Components and Drawings3.2 Terminal Diagram

3.2 Terminal Diagram.

The terminal diagram is located on top of the housing and displays the terminal numbers and terminals.

Figure 3-2 Terminal Diagram

Table 3-1 Terminal Specifications

Terminal Number Terminal Name Description(1) NC Not connected(2) N(-)/~ Supply voltage(3) L(+)/~ Supply voltage(4) COM Common(5) A/- Tx

(6) B/+ Rx

(7) NC Not connected(8) NC(9) NC Not connected(10) NC(11) DI1(-) Digital input (12) DI1(+) Digital input (13) A/I1 Phase current I1 (14) A/I1(15) B/I2/IE Phase current I2 or

Earth current IE (16) B/I2/IE(17) C/I3 Phase current I3 (18) C/I3(19) V1 Voltage input V1 (20) V1N+ Neutral(21) V2 Voltage input V2

(22) V2N+ Neutral(23) V3 Voltage input V3

(24) V3N+ Neutral+ indicates V1N, V2N, V3N are internally shorted

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

17

Page 18: Manual Sicam Fcm

Hardware Components and Drawings3.2 Terminal Diagram

Terminal Connections

You can connect the device terminals with a wire of cross-section ranging from 0.75 mm2 to 2.5 mm2. Use the following options to connect the terminals:

• Spring-cage connection

Spring-cage connection is used to connect the upper row of terminals. For example, from terminal 1 to terminal 12.

• Screw connection

Screw connection is used to connect the bottom row of terminals. For example, from terminal 13 to termi-nal 24.

The following tables shows the technical details of the different connection methods.

Table 3-2 Spring-Cage Connection

Table 3-3 Screw Connection

Connection Elements SpecificationsConnection method Spring cageConductor size (solid) 4 mm2

Conductor size (stranded) 2.5 mm2

Stripping length 8 mmAWG (max) 12AWG (min) 24

Connection Elements SpecificationsConnection method Screw connectionConductor size (solid) 1.5 mm2

Conductor size (stranded) 1.5 mm2

Stripping length 8 mmAWG (max) 16AWG (min) 26Torque 0.5 NmScrewdriver size 3/32 inch or 2.5 mm

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

18

Page 19: Manual Sicam Fcm

Hardware Components and Drawings3.3 Dimensional Drawings

3.3 Dimensional Drawings.

This chapter shows the dimensional drawings and different views of SICAM FCM.

Rear View

Figure 3-3 Rear View with Terminals

Front View

Figure 3-4 Front View

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

19

Page 20: Manual Sicam Fcm

Hardware Components and Drawings3.3 Dimensional Drawings

Isometric View

Figure 3-5 Isometric View

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

20

Page 21: Manual Sicam Fcm

4 Device Functions

4.1 Fault Detection 22

4.2 Determination of Fault Direction 22

4.3 Direction Determination of Phase Elements 23

4.4 Directional Earth Fault (Compensated/Resonant Earthed) 23

4.5 Directional Earth Fault (Isolated Earthed) 24

4.6 Inrush-Current Detection 25

4.7 Voltage Alerts 26

4.8 Fault Indication 26

4.9 Fault Reset Modes 26

4.10 Measurements and Derived Values 27

4.11 RTC Synchronization 27

4.12 Archive Logging 27

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

21

Page 22: Manual Sicam Fcm

Device Functions4.1 Fault Detection

4.1 Fault Detection.

The device determines the fault based on the following criteria:

• Overcurrent detection for phase currents (I>>) and earth current (INE >)

• Earth current and neutral-point displacement voltage (IE > and VE) for resonant earthed/isolated grid

where, VNE is an internally calculated value.

The device allows individual settings of time delays for phase and earth currents. If any of the above criteria is met, the device identifies the nature of the fault and determines the direction using the sampled values of the relevant voltage and current.

For more information on fault-detection parameters, see Figure A-3 and refer to the Fault Parameters > Phase Fault Detection menu and to the Fault Parameters > Earth Fault Detection menu.

4.2 Determination of Fault Direction.

The fault direction for the phase faults are determined by calculating the phase angles between the fault current and the corresponding phase-to-phase voltages. If the fault occurred is more than one phase and if the phase angles of the corresponding voltages cannot be measured accurately, the previously stored voltage phase-angle data is used to compute the fault direction.

Pickup Measuring Element1 2 3 E

1 I1 V2 - V3 – – – – – – 2 – – I2 V3 - V1 – – – –3 – – – – I3 V1 - V2 – –E – – – – – – – VNE

#

1, E I1 V2 - V3 – – – – IE VNE#

2, E – – I2 V3 - V1 – – IE VNE#

3, E – – – – I3 V1 - V2 IE VNE#

1, 2 I1 V2 - V3 I2 V3 - V1 – – – –2, 3 – – I2 V3 - V1 I3 V1 - V2 – –1, 3 I1 V2 - V3 – – I3 V1 - V2 – –1, 2, E I1 V2 - V3 I2 V3 - V1 – – IE VNE

#

2, 3, E – – I2 V3 - V1 I3 V1 - V2 IE VNE#

1, 3, E I1 V2 - V3 – – I3 V1 - V2 IE VNE#

1, 2, 3 I1 V2 - V3 I2 V3 - V1 I3 V1 - V2 – -1, 2, 3, E I1 V2 - V3 I2 V3- V1 I3 V1 - V2 IE VNE

#

VNE# = V1+ V2 + V3 depending on the connection types of voltages

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

22

Page 23: Manual Sicam Fcm

Device Functions4.3 Direction Determination of Phase Elements

4.3 Direction Determination of Phase Elements.

In SICAM FCM, the directional overcurrent element operates for any faults either in the forward direction or in the reverse direction. The forward direction refers to the power flow away from the busbar and the reverse di-rection refers to the power flow towards the busbar.

The directional determination of phase elements works in the quadrature connection to prevent the loss of po-larizing quantity for close-in phase faults. Each current element has a direction by a voltage derived from the other 2 phases. This connection introduces a 900 phase jump (current leading voltage) between reference volt-ages and operating quantities (currents). A fault is determined to be in the selected direction if its phase rela-tionship lies within a quadrant of ± 850 on either side of the characteristic angle, which is hard-coded as +450.

Figure 4-1 Direction Determination of Phase Elements

4.4 Directional Earth Fault (Compensated/Resonant Earthed).

In compensated/resonant earthed grid, the arc-suppression coil is configured to match the capacitive charging currents, such that when an earth fault occurs the negligible fault current flows through the coil. The character-istic angle is set to 00 and a boundary of +900 is used to detect the direction of the resistive component within the residual currents.

The measuring element circuit is subjected to cosine component of the zero-sequence current for directly mea-suring the real current due to losses. The characteristic angle is set to 00.

Calculate the active power (P) and if the value is falling in the 1st and the 4th quadrant, then the direction is forward. If the active power (P) is falling in the 2nd and 3rd quadrant, then the direction is shown as reverse.

For more information on directional earth fault parameters (compensated/resonant earthed), see Figure A-4 and refer to the Process Parameters > Earth Connection menu.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

23

Page 24: Manual Sicam Fcm

Device Functions4.5 Directional Earth Fault (Isolated Earthed)

Figure 4-2 Directional Earth Fault (Compensated/Resonant Earthed)

4.5 Directional Earth Fault (Isolated Earthed).

During earth-fault on isolated distribution grid, no fault path is detected and subsequently no fault-current flows. The phase-to-neutral capacitive charging current of the healthy phases for the entire grid is supplied through the fault path. This produces a current that is used to detect the presence of the earth fault. It appears as a residual current which lags the residual voltage by 900 and the characteristic angle is -900.

Calculate the reactive power (Q) and if the value is falling in the 1st and the 2nd quadrant, then the direction is forward. If the reactive power (Q) is falling in the 3rd and 4th quadrant, then the direction is shown as reverse.

For more information on directional earth-fault parameters (isolated earthed), see Figure A-4 and refer to the Process Parameters > Earth Connection menu.

Figure 4-3 Directional Earth Fault Isolated Earthed

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

24

Page 25: Manual Sicam Fcm

Device Functions4.6 Inrush-Current Detection

4.6 Inrush-Current Detection.

SICAM FCM detects the presence of high levels of 2nd harmonic current which is indicative, for example, for a transformer inrush current. If the 2nd harmonic current is greater than 10 % of the fundamental, then the device does not issue an indication for any detected fault in the grid for a duration of less than 2 seconds.

The detection enable flag for earth and phase controls the protection algorithm. These flags are disabled if the settings value of phase and earth are set to zero respectively.

The inrush-current detection function starts when the current exceeds the set values (I>> for I1, I2, and I3 and IE> for IE).

If the fault current persists for the respective time setting (tI>> for phases, tIE for earth), the inrush-current block-ing function checks for the inrush current. The inrush current is detected by analyzing the magnitude of 2nd harmonic component of phase vectors. The inrush current is detected if any of the 2nd harmonic component of phase vector exceeds 10 % of the I>> setting.

If the inrush current is present the detection function blocks the inrush-current detection to generate an indica-tion. If the inrush current is present for more than 2 seconds, the function is disabled and the inrush-current detection function is allowed to generate an indication. The detection function blocks both the phase and earth fault detection.

Figure 4-4 Inrush-Current Detection Logic Diagram

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

25

Page 26: Manual Sicam Fcm

Device Functions4.7 Voltage Alerts

4.7 Voltage Alerts.

The device displays overvoltage and undervoltage alarms as well as warnings when it is connected to a grid. The 2 threshold voltages of Vmax and Vmin provide alarms and warnings which are displayed and communicated via Modbus. The device maintains a hysteresis band of 2 % for indicating undervoltage and overvoltage alarms and warning. The alert screens on the HMI are displayed once the thresholds are exceeded and are cleared once the voltages are restored back to normal.

For more information on voltage alerts parameters, see Figure A-3 and Overvoltage Alarm and Fault Param-eters > Undervoltage Warning and Undervoltage Alarm menu.

4.8 Fault Indication.

When the device detects a fault, the following components are activated:

• LED - The red LED is turned on and indicates a fault

• LCD - Displays current and voltage values with the fault type and fault information sent via Modbus

• Modbus - Fault type and additional fault information will be sent to the RTU

NOTE

If any fault is detected, the red LED flashes for every 1 second. In case, SICAM FCM is not powered through auxiliary supply, the device reaches to sleep mode and the communication with RTU is disconnected. In the sleep mode, you can press any one of the key to view the events. After 8 hours of sleep mode, the device needs a power on from a power supply.

In the sleep mode, the fault reset and the effect of changes made in parameters can take few minutes.

NOTE

Under sub zero temperature -20 0 celsius, the LCD display can take up to 2 minutes to start or display the data.

4.9 Fault Reset Modes.

After the fault indication, you can reset the fault status of device through any one of the following modes:

• Auto reset as per user-defined time settings. see Figure A-3and refer to Fault Parameters > Auto Reset Time menu.

• Digital input

• HMI selection from menu

• RS485/Modbus interface

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

26

Page 27: Manual Sicam Fcm

Device Functions4.10 Measurements and Derived Values

4.10 Measurements and Derived Values.

The device internally calculates and displays the derived values. The following table shows the measured values and derived values of the device when it is connected to the medium-voltage grid.

Table 4-1 Measurements and Derived Values

NOTE

The phase current measurements I1, I2, I3 may vary by 1 A for the measured range from 5 A to 40 A. The earth current measurement IE may vary by 0.3 A for the measured range from 1 A to 8 A.

4.11 RTC Synchronization.

SICAM FCM provides an internal real-time clock. In order to get an external time synchronization, use Modbus for the accurate time stamp of events. The real-time clock synchronization is mandatory for a valid time stamp.

The device needs a time synchronization, whenever it resumes from the sleep mode to ensure correct time and date. Also a time and date update is required when the device is powered on after 8 hours of sleep mode.

4.12 Archive Logging.

An archive log is composed of:

• Event logs

The device stores 20 faults as event logs on the non-volatile memory. The event logs consists of time stamp and fault current values. It is designed as a ring buffer where in a new fault will always over write the oldest stored event.

• Trailing Pointers

The minimum and maximum values of current and voltage are archived at every 15 minutes, 30 minutes, 45 minutes, 1 hour, 24 hours, 1 month, and 1 year.

For more information on parameters of archive logging, see Figure A-3 and refer to Events and Trailing Point-ers menu.

NOTE

Whenever the device is powered on or it resumes from the sleep mode, the date and time display format would be 01-01-2012, 00:00:00. The Modbus registers for date and time is set as invalid.

Measurements Derived ValuesPhase I1, phase I2, phase I3 IE and 2nd harmonic of phase currentPhase I1, phase IE, phase I3 I2 and 2nd harmonic of phase current Phase V1, V2, V3 –Frequency (I1) 50 Hz/60 Hz –– Active power, reactive power, apparent power – Cos Φ (power factor)– Phase angle

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

27

Page 28: Manual Sicam Fcm

Device Functions4.12 Archive Logging

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

28

Page 29: Manual Sicam Fcm

5 Technical Data

5.1 Device Technical Data 30

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

29

Page 30: Manual Sicam Fcm

Technical Data5.1 Device Technical Data

5.1 Device Technical Data

Technical Data

Measuring Inputs for Voltage

Measuring Inputs for Current

Measured Value Accuracy

Communications

Medium-voltage distribution >1 kV to 36 kVFrequency range 45 Hz to 65 HzSupply voltage range DC 24 V to DC

60 V (±10%)AC 230 V (±20%)

Integrated backup battery Battery lifetime for 15 years including 1000 hour LED flashing and 1000 hour display

Voltage ph-n AC 3.25/√3 V, AC 100/√3 VClassical voltage transformer AC 100/√3 VLow-power voltage transformer AC 3.25/√3 V

Low-power current transformer (phase current) 5 A to 2000 A Low-power current transformer (earth current) 1 A to 60 A

Measured variable Accuracy Class Dependence to IEC 61557- 12:2007-08 (K55) (In Percentage)

Voltage V 1Current I 1Apparent power (S) 3Reactive power (Q) 3Active power (P) 3Aggregated reactive power 3Aggregated active power 3Total power factor PF total 2Frequency F 1

RS485 interfaceElectrical interface RS485Connection type Connection type terminal block with spring type terminalsSupported communication protocol Modbus RTUFunctionality SlaveBaud rate (bps) 2400, 4800, 9600, 19200, 38400, 57600, 115200

Default value: 115200 bpsData format 8N1, 8E1, 8O1

Default value: 8N1Supported address area 1 to 247

Default value: 1

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

30

Page 31: Manual Sicam Fcm

Technical Data5.1 Device Technical Data

Digital Inputs

Dimensions

Environment

Protection Device Class

NOTE

When the main power supply fails, the device is switched on with an internal battery and in this mode, the device has limited functionality.

Number 1External operating voltage DC 24 V - 60 V

Type of fixing Flush mountingCut-out (W x H) 92 +0.8 mm x 45 +0.8 mmOverall depth 99.5 mmPermissible switch panel thickness for installation ≤ 4 mmMounting position HorizontalWeight ≤ 500 g

Operating temperature range -300C to +700CStorage temperature range -400C to +850CHumidity range 0 to 95%, non-condensing Altitude above sea level Maximum up to 2000 m

Device front IP 40Device rear IP 20

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

31

Page 32: Manual Sicam Fcm

Technical Data5.1 Device Technical Data

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

32

Page 33: Manual Sicam Fcm

6 Connection Diagrams

6.1 Connection Diagrams 34

6.2 Installing the Device 36

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

33

Page 34: Manual Sicam Fcm

Connection Diagrams6.1 Connection Diagrams

6.1 Connection Diagrams.

This chapter describes about the various connection diagrams and how the device can be connected in the medium-voltage grid.

Fault Passage Indicator

SICAM FCM can be used as a dedicated Fault Passage Indicator (FPI) by using only the 3 current inputs and no directional fault information is provided.

Figure 6-1 SICAM FCM as Fault Passage Indicator

Fault Detector

SICAM FCM can be used as a fault detector by providing fault information with directional information. The device can be operated when it is additionally connected to the low-power voltage transformer (3.25/√ 3 V or 100/√ 3 V) in the medium-voltage grid. By using this connection, SICAM FCM also provides all the measured and calculated measurands.

3- Low-Power Voltage Transformer, 3-Low-Power Current Transformer

The device is connected to the voltage inputs V1, V2, V3 through low-power voltage transformers of 3.25/√ 3 V or 100/√ 3 V of medium-voltage grid. The 3-low power current measurement sensors are connected to I1, I2, I3. This schematics is used for solidly grounded system and the IE value is derived.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

34

rmares
Rectangle
Page 35: Manual Sicam Fcm

Connection Diagrams6.1 Connection Diagrams

Figure 6-2 SICAM FCM as Fault Detector – 3-Low-Power Voltage Transformer and Current Transformer with 3-Phase Current

3-Low-Power Voltage Transformer, 2-Phase Current, and Sensitive Earth Current Sensor

The device is connected to the voltage inputs V1, V2, V3 through low-power voltage transformers of 3.25/√ 3 V or 100/√ 3 V of medium-voltage grid. The 3-low power current measurement sensors are connected to I1, IE, I3 with IE connected to the sensitive earth current sensors. This schematics is used for isolated and resonant grounded system and the I2 value is derived.

Figure 6-3 SICAM FCM as Fault Detector – 3-Low-Power Voltage Transformer with 2-Phase Current and Sensitive Earth Current Sensor

NOTE

During electrical installation, all the rules and regulations of power systems is observed.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

35

rmares
Rectangle
Page 36: Manual Sicam Fcm

Connection Diagrams6.2 Installing the Device

6.2 Installing the Device.

✧ Use the correct polarity before connecting to an auxiliary DC voltage.

✧ Check and verify all terminals for the proper connections.

✧ Check the polarities and phase connections of all instrument transformers.

✧ Before energizing with supply voltage, place the device in the operating environment for at least 2 hours to avoid humidity and condensation problems.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

36

Page 37: Manual Sicam Fcm

A Parameterization

A.1 Parameterization 38

A.2 Parameterizing the User Interface 39

A.3 Editing the Device Settings 42

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

37

Page 38: Manual Sicam Fcm

ParameterizationA.1 Parameterization

A.1 Parameterization.

This appendix describes about the various parameters menu and the possible parameters settings that can be executed via HMI. Parameters can also be set remotely by using the RS485/Modbus interface and the param-eters are stored in the respective Modbus registers. For more information about Modbus, refer to B.1 Modbus Registers

Display and User Controls

The device menu screen contains the following user interface elements:

Figure A-1 Default LCD screen with Display and User Controls

• Header - The header area displays the title, status of feeder.

• Display - The display area shows the default measured values such as phase currents, phase voltages, power factor, and frequency.

• Footer - The footer area contains the keypads. Keypads allow you to navigate the menus by selecting a value or editing the device settings. The following functions are assigned to the navigation keys:

- BFM - Press the BFM menu to enable the Battery Freshness Mode (BFM). For more information, see 2.1 Overview and refer to Battery Freshness Seal Mode

- MENU - Calls the main menu

- OK - Opens submenu from the selected main menu

- Save - Permanently saves the last set value and returns from edit mode to display mode

- Edit - Opens edit mode of the device settings

- ↑↓ - The up and down arrow is used to move the cursor. It is also used to scroll within the menu list and for selecting or entering numerical values

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

38

Page 39: Manual Sicam Fcm

ParameterizationA.2 Parameterizing the User Interface

A.2 Parameterizing the User Interface.

This chapter describes about the default menu and the possible parameters settings that you can perform in the HMI.

Default Screen

The default screen displays the phase current I1, I2, I3, IE, V1, V2, V3 values, and frequency. By navigating the keys, you can view active power, reactive power, and apparent power. The default screen also displays the power flow direction and status of the feeder.

Figure A-2 Default Screen

Parameterization Menu Structure

The parameterization menu structure displays the main menu and the relevant submenu functions.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

39

Page 40: Manual Sicam Fcm

ParameterizationA.2 Parameterizing the User Interface

Figure A-3 Parameters Menu Structure

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

40

Page 41: Manual Sicam Fcm

ParameterizationA.2 Parameterizing the User Interface

Figure A-4 Parameters Menu Structure

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

41

Page 42: Manual Sicam Fcm

ParameterizationA.3 Editing the Device Settings

A.3 Editing the Device Settings.

This chapter describes you with an example on how to edit and set the device parameters.

To edit the phase protection values settings:

• From the default LCD screen, select MENU>. The MENU screen appears.

• Navigate to FAULT PARAMETERS menu and press OK>. The PHASE FAULT DETECTION I>> screen appears.

• In the PHASE FAULT DETECTION I>> screen, navigate to PHASE FAULT DETECTION I>>, press OK>. TheSAVED I >> screen appears.

• In the SAVED I >> screen, press Edit>. The New I>> screen appears.

• In the NEW I >> screen, press up arrow or down arrow to set the New I>> value within the provided range.

• Press Save> to save the new PHASE FAULT DETECTION I>> value.

NOTE

To navigate from one value to another value, use the left arrow and right arrow for entering the values, press up arrow and down arrow. For example, from 0 A to 1000 A.

• Press <Esc if you want to cancel the edit mode and return to display mode, all the saved values are dis-carded.

Figure A-5 Editing Phase Protection Settings

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

42

Page 43: Manual Sicam Fcm

B Modbus Registers

B.1 Modbus Registers 44

B.2 Implementation of Modbus Protocol 45

B.3 Bit Type Data 51

B.4 Register Type Data - Holding Registers 53

B.5 Register Type Data - Input Registers 63

B.6 Register Type Data - Analog Input Registers 69

B.7 Register Type Data - Events 74

B.8 Register Type Data - Trailing Pointers 78

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

43

Page 44: Manual Sicam Fcm

Modbus RegistersB.1 Modbus Registers

B.1 Modbus Registers

Introduction

Modbus is a fieldbus which is used to exchange data between programmable logic controllers (PLCs) and other devices via the communication protocols. The communication protocol is typically based upon the master/slave system over a serial line (RS485).

Modbus is a master/slave communication. The Modbus master requests data from the slaves which are con-nected to the bus. The slaves answer to the request from the master. The device works as Modbus Slave and supports communication via RS485. Regardless of the transmission mode, the communication cycle and con-tents remain the same. The message frame contains the following format:

• Device address

• Function code

• 8-bit data bytes

• Error Checking

The Modbus data models are classified as follow:

• Bit type data

- Discrete Input

- Coil

• Register type data

- Input Register

- Holding Register

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

44

Page 45: Manual Sicam Fcm

Modbus RegistersB.2 Implementation of Modbus Protocol

B.2 Implementation of Modbus Protocol .

The device operates as a Modbus Remote Terminal Unit (RTU) slave.

Modbus Function Codes

If the device receives an unsupported function code, it returns the exception code response as 01.

Data Package Format

Table B-1 Communication Settings

Table B-2 Modbus Parameters

In the SICAM FCM, the data-byte standard setting is as follows:

• 1 start bit

• 8 data bits (LSB first)

• 1 parity bit (Odd/Even/None)

• 1 stop bit

Modbus Data

The device supports the following data types:

• Bit type data (Discrete Inputs/Coil)

• Register type data

The following abbreviations are used for the register names:

For more information about bit type data - coil, refer to B.3 Bit Type Data.

Function Code Function as per Modbus Specification Description01 Read coils Bit access to BIT-AREA02 Read discrete inputs Bit access to BIT-AREA03 Read holding registers 16-bit access to REGISTER-AREA04 Read input registers 16-bit access to REGISTER-AREA05 Write single coil Bit access to BIT-AREA06 Write single register 16-bit access to REGISTER-AREA15 Write multiple coils Bit access to BIT-AREA16 Write multiple registers 16-bit access to REGISTER-AREA

Baud rate (bps) 2400, 4800, 9600, 19200, 38400, 57600, 115200Parity O/E/N

Modbus ID 1 to 2470 - Broadcast 248 - 255 Special

Modbus type RTU

Input Registers Inp-RegHolding Registers Hold-Reg

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

45

Page 46: Manual Sicam Fcm

Modbus RegistersB.2 Implementation of Modbus Protocol

Table B-3 Bit Type Data - Coil

For more information about bit type data - discrete, refer to B.3 Bit Type Data.

Table B-4 Bit Type Data - Discrete

For more information about holding registers, refer to B.4 Register Type Data - Holding Registers.

Table B-5 Holding Registers

Address Modbus Data Type Parameters Access1 Coil Activate test mode R/W2 Coil Reset device (Reserved) R/W3 Coil Reset fault R/W4 Coil Intermittent earth fault counter reset R/W5 Coil Binary output A (Reserved) R/W6 Coil Binary output B (Reserved) R/W7 Coil Clear data available status R/W8 Coil Clear event database R/W

Address Modbus Data Type

Parameters Access

1 Discrete Input Status data/Data available R2 Discrete Input Test mode activated R3 Discrete Input Overcurrent (I>>) without direction indication R4 Discrete Input Earth fault tripping (IE>) R5 Discrete Input Overvoltage warning R6 Discrete Input Overvoltage alarm R7 Discrete Input Undervoltage warning R8 Discrete Input Undervoltage alarm R9 Discrete Input I>> direction A R10 Discrete Input I>> direction B R11 Discrete Input IE> direction A R12 Discrete Input IE> direction B R13 Discrete Input Forward (A) power-flow direction of I1 R14 Discrete Input Reverse (B) power-flow direction of I1 R15 Discrete Input Forward (A) power-flow direction of I2 R16 Discrete Input Reverse (B) power-flow direction of I2 R17 Discrete Input Forward (A) power-flow direction of I3 R18 Discrete Input Reverse (B) power-flow direction of I3 R19 Discrete Input Time synchronization required R

Address Min/Max Value Parameters Default Unit Type1 Modbus frame configuration – – uInt162 0 - 6 Modbus baud rate 6 bps uInt164 1 - 247 Modbus ID 1 – uInt165 - 8 Date and time – – uInt169 0 - 1 Grid frequency 50 Hz uInt1610 10 - 360 Primary voltage 220 1/10 kV uInt1611 0, 50 - 2000 Overcurrent trip value (I >>) 400 A uInt1612 4 - 6000 Overcurrent response time (tI >>) 4 ms uInt1613 0 - 1000 Earth fault trip value (IE>) 60 A uInt16

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

46

Page 47: Manual Sicam Fcm

Modbus RegistersB.2 Implementation of Modbus Protocol

For more information about register type data – input registers, refer to B.5 Register Type Data - Input Registers

Table B-6 Input Registers

14 4 - 6000 Earth fault response time (tIE >) 16 ms uInt1616 0 - 2 Earth point treatment Solid – uInt1617 0 - 1 Language Deutsche – uInt1618 0 - 1 Voltage transformer secondary/Low-

power voltage transformer3.25/√3 V AC V uInt16

19 0 - 2 Date type (DD-MM-YYYY) – uInt1620 0 - 1 Time type 1 (24 hour) – uInt1621 0 - 10 VMax Alarm 0 % uInt1622 0 - 10 VMax Warning 0 % uInt1623 0 - 10 VMin Alarm 0 % uInt1624 0 - 10 VMin Warning 0 % uInt1625 0 - 100 Neutral displacement voltage VNE> 0 % uInt1626 4 - 6000 Neutral displacement time tVNE> 16 ms uInt1627 0 - 80 Auto reset time 80 ms uInt16

Address Min/Max Value Parameters Unit Type1000 0 - 9999 Phase current I1 A uInt161001 0 - 9999 Phase current I2 A uInt161002 0 - 9999 Phase current I3 A uInt161003 0 - 9999 Earth current IE A uInt161004 0 - 65535 Voltage V12 V uInt161005 0 - 65535 Voltage V23 V uInt161006 0 - 65535 Voltage V31 V uInt161007 0 - 65535 Voltage V1 V uInt161008 0 - 65535 Voltage V2 V uInt161009 0 - 65535 Voltage V3 V uInt161010 0 - 65535 Displacement Voltage VNE V uInt161011 0 - 3599 Phase angle I1 1/10° uInt161012 0 - 3599 Phase angle I2 1/10° uInt161013 0 - 3599 Phase angle I3 1/10° uInt161014 0 - 3599 Phase angle IE 1/10° uInt161015 0 - 3599 Phase angle V12 1/10° uInt161016 0 - 3599 Phase angle V23 1/10° uInt161017 0 - 3599 Phase angle V31 1/10° uInt161018 0 - 3599 Phase angle V1 1/10° uInt161019 0 - 3599 Phase angle V2 1/10° uInt161020 0 - 3599 Phase angle V3 1/10° uInt161021 0 - 3599 Phase angle VNE 1/10° uInt161022, 1027, 1031

0 - 65535 Apparent power phase 1, Apparent power phase 2, Apparent power phase 3

kVA uInt16

1023, 1028, 1032

-32768 to 32767 Active power phase 1, Active power phase 2, Active power phase 3

kW sInt16

1024, 1029, 1033

-32768 to 32767 Reactive power phase 1, Reactive power phase 2, Reactive power phase 3

kVAR sInt16

Address Min/Max Value Parameters Default Unit Type

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

47

Page 48: Manual Sicam Fcm

Modbus RegistersB.2 Implementation of Modbus Protocol

For more information about register type data - analog input registers, refer to B.6 Register Type Data - Analog Input Registers.

Table B-7 Analog Input Registers

For more information about register type data – events, refer to B.7 Register Type Data - Events.

1025, 1030, 1034

-1000 to 1000 Power factor phase 1, Power factor phase 2, Power factor phase 3

1/1000 sInt16

1026 0 - 65535 Frequency 1/10 Hz uInt161035, 1036, 1037

Dir A, Dir B Load flow direction 1, Load flow direc-tion 2, Load flow direction 3

Address Min/Max Value Parameters Unit Type1 – Last reset type – uInt162 0 - 59999 Last reset time (milliseconds) ms uInt163 0 - 23

0 - 59Last reset time (hours and minutes) h and min uInt16

4 1 - 121 - 31

Last reset time (month and date) month and date uInt16

5 12 - 99 Last reset time (year) year uInt166 – Overvoltage alarm type – uInt167 – Overvoltage alarm time (milliseconds) ms uInt168 – Overvoltage alarm time (hours and

minutes)h and min uInt16

9 – Overvoltage alarm time (month and date)

month and date uInt16

10 – Overvoltage alarm time (year) year uInt1611 – Overvoltage warning type – uInt1612 – Overvoltage warning time (millisec-

onds)ms uInt16

13 – Overvoltage warning time (hours and minutes)

h and min uInt16

14 – Overvoltage warning time (month and date)

month and date uInt16

15 – Overvoltage warning time (year) year uInt1616 – Undervoltage alarm type – uInt1617 – Undervoltage alarm time (millisec-

onds)ms uInt16

18 – Undervoltage alarm time (hours and minutes)

h and min uInt16

19 – Undervoltage alarm time (month and date)

month and date uInt16

20 – Undervoltage alarm time (year) year uInt1621 – Undervoltage warning type – uInt1622 – Undervoltage warning time (millisec-

onds)ms uInt16

23 – Undervoltage warning time (hours and minutes)

h and min uInt16

24 – Undervoltage warning time (month and date)

month and date uInt16

25 – Undervoltage warning time (year) year uInt16

Address Min/Max Value Parameters Unit Type

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

48

Page 49: Manual Sicam Fcm

Modbus RegistersB.2 Implementation of Modbus Protocol

Table B-8 Events

Read or write accesses to any addresses beyond the defined address cause the exception code 02. If any value that is written beyond the range of value cause the exception code 03. The modified values contained in the registers are saved during a device reset.

For more information about register type data - trailing pointers, refer to B.8 Register Type Data - Trailing Point-ers.

Table B-9 Trailing Pointers

Address Modbus Data Type

Parameters Unit Type

299 0 - 65535 Intermittent earth fault counter – uInt16300 0 - 65535 Event counter – uInt16301 - 491 0 - 65535 Event type – uInt16302 - 492 0 - 59999 Time in milliseconds ms uInt16303 - 493 0 - 23

0 - 59Time in hours and minutes h and min uInt16

304 - 494 1 - 311 - 12

Time in month and date month and date uInt16

305 - 495 12 - 99 Time in year year uInt16306 - 496 0 - 9999 Phase current I1 A uInt16307 - 497 0 - 9999 Phase current I2 A uInt16308 - 498 0 - 9999 Phase current I3 A uInt16309 - 499 0 - 9999 Phase current IE A uInt16310 - 500 Inp-Reg Reserved – uInt16

Address Modbus Data Type

Parameters Unit Type

101 - 104105 - 107108 - 110111 - 113

Inp-Reg I1, I2, I3, IE (min) 15 minutesP1, P2, P3 (min) 15 minutesQ1, Q2, Q3 (min) 15 minutesS1, S2, S3 (min) 15 minutes

A uInt16

114 - 117118 - 120121 - 123124 - 126

Inp-Reg I1, I2, I3, IE (max) 15 minutesP1, P2, P3 (max) 15 minutesQ1, Q2, Q3 (max) 15 minutesS1, S2, S3 (max) 15 minutes

A uInt16

127 - 130131 - 133134 - 136137 - 139

Inp-Reg I1, I2, I3, IE (min) 30 minutesP1, P2, P3 (min) 30 minutesQ1, Q2, Q3 (min) 30 minutesS1, S2, S3 (min) 30 minutes

A uInt16

140 - 143144 - 146147 - 149150 - 152

Inp-Reg I1, I2, I3, IE (max) 30 minutesP1, P2, P3 (max) 30 minutesQ1, Q2, Q3 (max) 30 minutesS1, S2, S3 (max) 30 minutes

A uInt16

153 - 156157 - 159160 - 162163 - 165

Inp-Reg I1, I2, I3, IE (min) 45 minutesP1, P2, P3 (min) 45 minutesQ1, Q2, Q3 (min) 45 minutesS1, S2, S3 (min) 45 minutes

A uInt16

166 - 169170 - 172173 - 175176 - 178

Inp-Reg I1, I2, I3, IE (max) 45 minutesP1, P2, P3 (max) 45 minutesQ1, Q2, Q3 (max) 45 minutesS1, S2, S3 (max) 45 minutes

A uInt16

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

49

Page 50: Manual Sicam Fcm

Modbus RegistersB.2 Implementation of Modbus Protocol

179 - 182183 - 185186 - 188189 - 191

Inp-Reg I1, I2, I3, IE (min) 60 minutesP1, P2, P3 (min) 60 minutesQ1, Q2, Q3 (min) 60 minutesS1, S2, S3 (min) 60 minutes

A uInt16

192 - 195196 - 198199 - 201202 - 204

Inp-Reg I1, I2, I3, IE (max) 60 minutesP1, P2, P3 (max) 60 minutesQ1, Q2, Q3 (max) 60 minutesS1, S2, S3 (max) 60 minutes

A uInt16

205 - 208209 - 211212 - 214215 - 217

Inp-Reg I1, I2, I3, IE (min) 24 hourP1, P2, P3 (min) 24 hourQ1, Q2, Q3 (min) 24 hourS1, S2, S3 (min) 24 hour

A uInt16

218 - 221222 - 224225 - 227228 - 230

Inp-Reg I1, I2, I3, IE (max) 24 hourP1, P2, P3 (max) 24 hourQ1, Q2, Q3 (max) 24 hourS1, S2, S3 (max) 24 hour

A uInt16

231 - 234235 - 237238 - 240241 - 243

Inp-Reg I1, I2, I3, IE (min) 1 monthP1, P2, P3 (min) 1 monthQ1, Q2, Q3 (min) 1 monthS1, S2, S3 (min) 1 month

A uInt16

244 - 247248 - 250251 - 253254 - 256

Inp-Reg I1, I2, I3, IE (max) 1 monthP1, P2, P3 (max) 1 monthQ1, Q2, Q3 (max) 1 monthS1, S2, S3 (max) 1 month

A uInt16

257 - 260261 - 263264 - 266267 - 269

Inp-Reg I1, I2, I3, IE (min) 1 yearP1, P2, P3 (min) 1 yearQ1, Q2, Q3 (min) 1 yearS1, S2, S3 (min) 1 year

A uInt16

270 - 273274 - 276277 - 279280 - 282

Inp-Reg I1, I2, I3, IE (max) 1 yearP1, P2, P3 (max) 1 yearQ1, Q2, Q3 (max) 1 yearS1, S2, S3 (max) 1 year

A uInt16

Address Modbus Data Type

Parameters Unit Type

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

50

Page 51: Manual Sicam Fcm

Modbus RegistersB.3 Bit Type Data

B.3 Bit Type Data.

Table B-10 Bit Type Data - Coil

Table B-11 Bit Type Data - Discrete

Bit Type Address Data DescriptionActivate test mode 1 1 Setting to 1 activates the incorporated self-testReset device 2 - ReservedReset fault 3 1 Setting to 1 deactivates the LED event indicator

and tripped event-related relays. It also resets the register for the events and display.The device sets the bit automatically to 0

Intermittent earth fault counter reset

4 – Setting to 1 resets the intermittent earth fault counter to zeroThe device sets the bit automatically to 0

Binary output A 5 – ReservedBinary output B 6 – ReservedClear data available status 7 1 Delete the available status of the dataClear event database 8 1 Delete the event database

Bit Type Address Data DescriptionStatus data/Data available 1 1

0New data availableNo new data availableThe bit is set to 1 on occurrence of IE>, I >>, ov-ervoltage alarm or undervoltage alarm. The status data can be cleared if the user sets the value of Bit type data - Coil, Clear data avail-able status

Self test activated 2 10

Incorporated test mode activatedIncorporated test mode not activated

Overcurrent (I>>) 3 10

Overcurrent indication detectedNo overcurrent indication detected

Earth fault tripping (IE>) 4 10

IE> indication detectedNo IE> indication occurred

Overvoltage warning (V>) 5 10

Overvoltage warning detectedNo overvoltage warning detected

Overvoltage alarm 6 10

Overvoltage alarm detectedNo overvoltage alarm detected

Undervoltage warning (V<) 7 10

Undervoltage warning detectedNo undervoltage warning detected

Undervoltage alarm 8 10

Undervoltage alarm detectedNo undervoltage alarm detected

I>> direction A 9 10

Overcurrent direction A detectedNo overcurrent direction A detected

I>> direction B 10 10

Overcurrent direction B detectedNo overcurrent direction B detected

IE> direction A 11 10

Earth current direction A detectedNo Earth current direction A detected

IE> direction B 12 10

Earth current direction B detectedNo earth current direction B detected

Forward (A) power-flow di-rection of I1

13 10

Forward (A) power-flow direction of I1Power-flow direction of I1 is not forward (A)

Reverse (B) power-flow di-rection of I1

14 10

Reverse (B) power-flow direction of I1Power-flow direction of I1 is not reverse (B)

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

51

Page 52: Manual Sicam Fcm

Modbus RegistersB.3 Bit Type Data

Forward (A) power-flow di-rection of I2

15 10

Forward (A) power-flow direction of I2Power-flow direction of I2 is not forward (A)

Reverse (B) power-flow di-rection of I2

16 10

Reverse (B) power-flow direction of I2Power-flow direction of I2 is not reverse (B)

Forward (A) power-flow di-rection of I3

17 10

Forward (A) power-flow direction of I3Power-flow direction of I3 is not forward (A)

Reverse (B) power-flow di-rection of I3

18 10

Reverse (B) power-flow direction of I3Power-flow direction of I3 is not reverse (B)

Time synchronization re-quired

19 10

No time synchronization in last 24 hoursDevice is in time synchronization

Bit Type Address Data Description

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

52

Page 53: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

B.4 Register Type Data - Holding Registers

Modbus Frame Configuration

(Address 1) This register defines the modbus frame configuration.

Modbus Baud Rate

(Address 2) This register defines the modbus baud rate.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Odd/Even Stop bits Parity Not used Not used27 26 25 24 Not used 22 21 20

Format Bit DescriptionParity 1

0Parity check switched on Parity check switched off

Odd/Even 10

Odd mode (with parity check switched on) Even mode (with parity check switched on)

Default Parity: None Stop bits: 1

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 6Baud rate (bps) 0

123456

2400 4800 9600 19200 38400 57600 115200

Default 6 115200 bps

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

53

Page 54: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Modbus ID

(Address 4) This register defines the modbus ID.

Date and Time

(Address 5 - 8) The format used for date and time complies with EN60870-5- 4:1993. It consists of 4 successive registers for writing in one request and uses the function code 16.

(Address 5)

Table B-12 Date and Time - Seconds

(Address 6)

Table B-13 Date and Time - Hours/Minutes

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 1 - 247Default 1

Bit 15 14 13 12 11 10 9 8Milliseconds215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Milliseconds27 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 59999 msDefault 0

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Hours 215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Minutes27 26 25 24 23 22 21 20

HoursFormat 5-bit unsigned integer Unit hRange 0 - 23

Minutes Format 6-bit unsigned integerUnit MinutesRange 0 - 59

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

54

Page 55: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

(Address 7)

Table B-14 Date and Time - Date/Month

(Address 8)

Table B-15 Date and Time - Year

Bit 15 14 13 12 11 10 9 8RES3 Month215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Day of week Date27 26 25 24 23 22 21 20

MonthFormat 4-bit unsigned integerUnit MonthRange 1 - 12

Day of weekFormat 3-bit unsigned integer Unit DayRange 1 - 7

Date Format 5-bit unsigned integerUnit DateRange 1 - 31

RES3 Reserved

Bit 15 14 13 12 11 10 9 8RES5215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0RES4 Year27 26 25 24 23 22 21 20

RES5 Reserved

Year Format 7-bit unsigned integerUnit YearRange 12 - 99

For example, if modbus value is read as:12 = Year 201299 = Year 2099

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

55

Page 56: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Grid Frequency

(Address 9) This register defines the grid frequency.

Primary Voltage

(Address 10) This register contains the primary voltage.

Overcurrent Trip Value (I >>)

(Address 11) This register defines the trip value for overcurrent detection for short-circuits.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Not used Grid FREQ27 26 25 24 23 22 21 20

Format BitGrid FREQ 0

150 Hz grid frequency 60 Hz grid frequency

Default 0 50 Hz

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit 1/10 kVRange 10 - 360Default 220

For example, if modbus value is read as:10 = 1.0 kV115 = 11.5 kV

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit ARange 0, 50 - 2000

When 0 is selected, then the protection function is disabled

Default 400

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

56

Page 57: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Overcurrent Response Time (tI >>)

(Address 12) This register defines the minimum time necessary for an overcurrent to exist and to make the device to indicate the fault.

Earth Fault Trip Value (IE >)

(Address 13) This register defines the earth current value for a earth-fault protection.

Earth Fault Response Time (tIE>)

(Address 14) This register defines the minimum time required for an earth fault to exist and allow the device to indicate a fault.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit msRange 4 - 6000Default 4

For example, if modbus value is read as:4 = 40 ms1050 = 10500 ms

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit ARange 0 - 1000 (earth fault settings)

When 0 is selected, then the protection function is disabledDefault 60

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Not used Not used27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit msRange 4 - 6000Default 16

For example, if modbus value is read as:4 = 40 ms1050 = 10500 ms

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

57

Page 58: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Earth Point Treatment

(Address 16) This register defines the earth point treatment method.

Language

(Address 17) This register defines the device language.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Earth point

treatmentEarth point treatment

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 2

0 = Solid1 = Isolated2 = Resonant

Default 0 = Solid

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Not used Language27 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 1

0 = English1 = Deutsche

Default 1 = Deutsche

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

58

Page 59: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Voltage Transformer Secondary/Low-Power Voltage Transformer

(Address 18) This register contains the selected low-power voltage transformer/voltage transformer secondary voltages.

Date Type

(Address 19) This register defines the date type.

Table B-16

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Voltage

Transform-er Second-ary/Low-Power Voltage Transform-er

Voltage Transform-er Second-ary/Low-Power Voltage Transform-er

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 1

0 = 3.25/√3 V AC 1 = 100/√3 V AC

Default 0 = 3.25/√3 V AC

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Date Type Date Type27 26 25 24 23 22 21 20

Format 2-bit unsigned integerRange 0 = DD-MM-YYYY

1 = MM-DD-YYYY2 = YYYY-MM-DD

Default 0 = DD-MM-YYYY

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

59

Page 60: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Time Type

(Address 20) This register defines the time type.

VMax Alarm

(Address 21) This register defines the maximum threshold voltage that you can set for providing an alarm. It is expressed in percentage (%) of primary voltage.

VMax Warning

(Address 22) This register defines the maximum threshold voltage that you can set for providing a warning. It is expressed in percentage (%) of primary voltage.

Refer to, VMax Alarm

VMin Alarm

(Address 23) This register defines the minimum threshold voltage that you can set for providing an alarm. It is expressed in percentage (%) of primary voltage.

Refer to, VMax Alarm and the format used is 16-bit signed integer.

VMin Warning

(Address 24) This register defines the minimum threshold voltage that you can set for providing a warning. It is expressed in percentage (%) of primary voltage.

Refer to, VMax Alarm and the format used is 16-bit signed integer.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Not used Time Type27 26 25 24 23 22 21 20

Format 1-bit unsigned integerRange 0 = 12 hour format

1 = 24 hour formatDefault 1 = 24 hour format

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 10 % of primary voltageDefault 0

When 0 is selected, then the Vmax Alarm is disabled

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

60

Page 61: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

Neutral Displacement Voltage VNE>

(Address 25) This register defines the neutral displacement voltage and it is expressed in percentage (%).

Neutral Displacement Time tVNE>

(Address 26) This register defines the neutral displacement time and it is expressed in milliseconds.

Auto Reset Time

(Address 27) This register defines the auto reset time and it is expressed in hours. The value is multiple of 0.5 hours (30 minutes).

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit VRange 0 - 100% of primary voltage

When 0 is selected then the function is disabledDefault 0

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit msRange 4 - 6000Default 16

For example, if modbus value is read as:4 = 40 ms1050 = 10500 ms

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit 1/10 hoursRange 0 - 80Default 80

For example, if modbus value is read as:15 = 1.5 hours80 = 8.0 hours

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

61

Page 62: Manual Sicam Fcm

Modbus RegistersB.4 Register Type Data - Holding Registers

NOTE

If the voltage VNE exceeds its magnitude threshold VNE>, the timer tVNE> is incremented. If any time during the activity, the magnitude falls below the threshold value VNE>, timer tVNE> is reset.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

62

Page 63: Manual Sicam Fcm

Modbus RegistersB.5 Register Type Data - Input Registers

B.5 Register Type Data - Input Registers

Phase Current I1

(Address 1000) This register contains the phase current I1.

Phase Current I2

(Address 1001) This register contains the phase current I2.

Refer to, Phase current I1.

Phase Current I3

(Address 1002) This register contains the phase current I3.

Refer to, Phase current I1.

Earth Current IE

(Address 1003) This register contains the actual earth current value IE.

Refer to, Phase current I1.

Voltage V12

(Address 1004) This register contains the actual voltage V12.

Voltage V23

(Address 1005) This register contains the actual voltage V23.

Refer to, Voltage V12.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit ARange 0 - 9999

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit VRange 0 - 65535

For example, if modbus value is read as:10 = 1.0 kV115 = 11.5 kV

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

63

Page 64: Manual Sicam Fcm

Modbus RegistersB.5 Register Type Data - Input Registers

Voltage V31

(Address 1006) This register contains the actual voltage V31.

Refer to, Voltage V12.

Voltage V1

(Address 1007) This register contains the actual voltage value of phase 1-to-earth.

Refer to, Voltage V12.

Voltage V2

(Address 1008) This register contains the actual voltage value of phase 2-to-earth.

Refer to, Voltage V12.

Voltage V3

(Address 1009) This register contains the actual voltage value of phase 3-to-earth.

Refer to, Voltage V12.

Displacement Voltage VNE

(Address 1010) This register contains the displacement voltage value VNE.

Refer to, Voltage V12.

Phase Angle I1

(Address 1011) This register contains the phase angle I1.

The value is indicated in steps of 1/100.

Phase Angle I2

(Address 1012) This register contains the phase angle I2.

Refer to, Phase Angle I1.

Phase Angle I3

(Address 1013) This register contains the phase angle I3.

Refer to, Phase Angle I1.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit 1/100 Range 0 to 3599

For example, if modbus value is read as:905 = 90.50

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

64

Page 65: Manual Sicam Fcm

Modbus RegistersB.5 Register Type Data - Input Registers

Phase Angle IE

(Address 1014) This register contains the phase angle IE.

Refer to, Phase Angle I1.

Phase Angle V12

(Address 1015) This register contains the phase angle V12.

Refer to, Phase Angle I1.

Phase Angle V23

(Address 1016) This register contains the phase angle V23.

Refer to, Phase Angle I1.

Phase Angle V31

(Address 1017) This register contains the phase angle V31.

Refer to, Phase Angle I1.

Phase Angle V1

(Address 1018) This register contains the phase angle V1.

Refer to, Phase Angle I1.

Phase Angle V2

(Address 1019) This register contains the phase angle V2.

Refer to, Phase Angle I1.

Phase Angle V3

(Address 1020) This register contains the phase angle V3.

Refer to, Phase Angle I1.

Phase Angle VE

(Address 1021) This register contains the phase angle VE.

Refer to, Phase Angle I1.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

65

Page 66: Manual Sicam Fcm

Modbus RegistersB.5 Register Type Data - Input Registers

Apparent Power Phase 1

(Address 1022) This register contains the apparent power phase 1.

Active Power Phase 1

(Address 1023) This register contains the active power phase 1.

Reactive Power Phase 1

(Address 1024) This register contains the reactive power phase 1.

Power Factor Phase 1 (Cos ϕ )

(Address 1025) This register contains the power factor phase 1 (cos ϕ) in 1/1000.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit kVA Range 0 - 65535

Bit 15 14 13 12 11 10 9 8- 215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit signed integerUnit kW Range −32768 to 32767

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit signed integerUnit kVARRange −32768 to 32767

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit signed integerUnit 1/1000Range −1000 to 1000

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

66

Page 67: Manual Sicam Fcm

Modbus RegistersB.5 Register Type Data - Input Registers

Frequency Phase 1

(Address 1026) This register contains the frequency phase 1 in 1/10 Hz.

Apparent Power Phase 2

(Address 1027) This register contains the apparent power phase 2.

Refer to, Apparent power phase 1.

Active Power Phase 2

(Address 1028) This register contains the active power phase 2.

Refer to, Active power phase 1.

Reactive Power Phase 2

(Address 1029) This register contains the reactive power phase 2.

Refer to, Reactive power phase 1.

Power Factor Phase 2

(Address 1030) This register contains the power factor phase 2.

Refer to, Power factor phase 1.

Apparent Power Phase 3

(Address 1031) This register contains the apparent power phase 3.

Refer to, Apparent power phase 1.

Active Power Phase 3

(Address 1032) This register contains the active power phase 3.

Refer to, Active power phase 1.

Reactive Power Phase 3

(Address 1033) This register contains the reactive power phase 3.

Refer to, Reactive power phase 1.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit 1/10 HzRange 0 to 65535

For example, if modbus value is read as:502 = 50.2 Hz

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

67

Page 68: Manual Sicam Fcm

Modbus RegistersB.5 Register Type Data - Input Registers

Power Factor Phase 3

(Address 1034) This register contains the actual power factor phase 3

Refer to, Power factor phase 1.

Load Flow Direction of I1

(Address 1035) This register contains the load flow direction of I1.

Load Flow Direction of I2

(Address 1036) This register contains the load flow direction of I2.

Refer to, Load flow direction of I1.

Load Flow Direction of I3

(Address 1037) This register contains the load flow direction of I3.

Refer to, Load flow direction of I1.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used DIR B DIR A27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit -Bit type DIR A = Load flow direction: A

DIR B = Load flow direction: B Data 01 = Load flow direction A

10 = Load flow direction B11 = Load flow direction not determined

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

68

Page 69: Manual Sicam Fcm

Modbus RegistersB.6 Register Type Data - Analog Input Registers

B.6 Register Type Data - Analog Input Registers

Last Reset Type

(Address 1) This register contains the last reset type.

Last Reset Time (Milliseconds)

(Address 2) This register contains the last reset time in milliseconds.

Last Reset Time (Hours and Minutes)

(Address 3) This register contains the last reset time in hours and minutes.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Auto (self)

ResetModbus Reset

HMI Reset BI Reset Not used

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit –Range –

Bit 15 14 13 12 11 10 9 8Milliseconds215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Milliseconds27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit msRange 0 - 59999

Bit 15 14 13 12 11 10 9 8Hours215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Minutes27 26 25 24 23 22 21 20

Format 8-bit unsigned integerUnit hRange 0 - 23

Format 8-bit unsigned integerUnit minRange 0 - 59

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

69

Page 70: Manual Sicam Fcm

Modbus RegistersB.6 Register Type Data - Analog Input Registers

Last Reset Time (Month and Date)

(Address 4) This register contains the last reset time in month and date.

Last Reset Time (Year)

(Address 5) This register contains the last reset time in year.

Overvoltage Alarm Type

(Address 6) This register defines the phase in which the overvoltage alarm is occurred.

Bit 15 14 13 12 11 10 9 8Month215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Date27 26 25 24 23 22 21 20

Format 8-bit unsigned integerUnit MonthRange 1 - 12

Format 8-bit unsigned integerUnit DateRange 1 - 31

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Year27 26 25 24 23 22 21 20

Format 8-bit unsigned integerUnit YearRange 12 - 99

For example, if modbus value is read as:12 = Year 201299 = Year 2099

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used V3 V2 V1

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit –Range –

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

70

Page 71: Manual Sicam Fcm

Modbus RegistersB.6 Register Type Data - Analog Input Registers

Overvoltage Alarm Time (Milliseconds)

(Address 7) This register contains the alarm time in milliseconds.

Refer to, Last reset time (Milliseconds).

Overvoltage Alarm Time (Hours and Minutes)

(Address 8) This register contains the alarm time in hours and minutes.

Refer to, Last reset time (Hours and Minutes).

Overvoltage Alarm Time (Month and Date)

(Address 9) This register contains the alarm time in month and date.

Refer to, Last reset time (Month and Date).

Overvoltage Alarm Time (Year)

(Address 10) This register contains the overvoltage alarm time in year.

Refer to, Last reset time (Year).

Overvoltage Warning Type

(Address 11) This register defines the phase in which the overvoltage warning is occurred.

Overvoltage Warning Time (Milliseconds)

(Address 12) This register contains the overvoltage warning time in milliseconds.

Refer to, Last reset time (Milliseconds).

Overvoltage Warning Time (Hours and Minutes)

(Address 13) This register contains the overvoltage warning time in hours and minutes.

Refer to, Last reset time (Hours and Minutes).

Overvoltage Warning Time (Month and Date)

(Address 14) This register contains the overvoltage warning time in month and date.

Refer to, Last reset time (Month and Date).

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used V3 V2 V1

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit –Range –

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

71

Page 72: Manual Sicam Fcm

Modbus RegistersB.6 Register Type Data - Analog Input Registers

Overvoltage Warning Time (Year)

(Address 15) This register contains the overvoltage warning time in year.

Refer to, Last reset time (Year).

Undervoltage Alarm Type

(Address 16) This register defines the phase in which the undervoltage alarm is occurred.

Undervoltage Alarm Time (Milliseconds)

(Address 17) This register contains the undervoltage alarm time in milliseconds.

Refer to, Last reset time (Milliseconds).

Undervoltage Alarm Time (Hours and Minutes)

(Address 18) This register contains the undervoltage alarm time in hours and minutes.

Refer to, Last reset time (Hours and Minutes).

Undervoltage Alarm Time (Month and Date)

(Address 19) This register contains the undervoltage alarm time in month and date.

Refer to, Last reset time (Month and Date).

Undervoltage Alarm Time (Year)

(Address 20) This register contains the undervoltage alarm time in year.

Refer to, Last reset time (Year).

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used V3 V2 V1

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit –Range –

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

72

Page 73: Manual Sicam Fcm

Modbus RegistersB.6 Register Type Data - Analog Input Registers

Undervoltage Warning Type

(Address 21) This register defines the phase in which the undervoltage warning is occurred.

Undervoltage Warning Time (Milliseconds)

(Address 22) This register contains the undervoltage warning time in milliseconds.

Refer to, Last reset time (Milliseconds).

Undervoltage Warning Time (Hours and Minutes)

(Address 23) This register contains the undervoltage warning time in hours and minutes.

Refer to, Last reset time (Hours and Minutes).

Undervoltage Warning Time (Month and Date)

(Address 24) This register contains the undervoltage warning time in month and date.

Refer to, Last reset time (Month and Date).

Undervoltage Warning Time (Year)

(Address 25) This register contains the undervoltage warning time in year.

Refer to, Last reset time (Year).

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used V3 V2 V1

27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit –Range –

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

73

Page 74: Manual Sicam Fcm

Modbus RegistersB.7 Register Type Data - Events

B.7 Register Type Data - Events

Intermittent Earth Fault Counter

(Address 299) This register contains a counter which increments when an intermittent earth fault occurs. This counter gets reset when a fault reset is triggered and helps you to understand the behavior of earth faults during a fault scenario.

Event Counter

(Address 300) This register contains a counter which is automatically incremented each time when a new event occurs. It can be used for checking the sequence of events.

If the event counter value is zero, it means that the database is empty or no event is added.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Not used Not used Not used Not used27 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 65535

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 65535

Address Modbus Data Type Parameters Unit Type301 - 491 Inp-Reg Event type – uInt16302 - 492 Inp-Reg Time in milliseconds ms uInt16303 - 493 Inp-Reg Time in hours and minutes h and min uInt16304 - 494 Inp-Reg Time in date and month date and month uInt16305 - 495 Inp-Reg Time in year year uInt16306 - 496 Inp-Reg Phase current I1 A uInt16307 - 497 Inp-Reg Phase current I2 A uInt16308 - 498 Inp-Reg Phase current I3 A uInt16309 - 499 Inp-Reg Phase current IE A uInt16310 - 500 Inp-Reg Reserved – uInt16

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

74

Page 75: Manual Sicam Fcm

Modbus RegistersB.7 Register Type Data - Events

Event Type

(Address 301, 311, …., 491) This register contains the event type. If IE > bit is active, the earth fault is detected. For fault in phases, the respective I1, I2, and I3 bit is activated. At the time of fault, the direction of fault is rep-resented by the respective bits for each phase.

Time in Milliseconds

(Address 302, 312, …., 492) This register contains the time in milliseconds.

Time in Hours and Minutes

(Address 303, 313, …., 493) This register contains the time in hours and minutes.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used I>>(For-

ward A)I>>(Re-verse B)

IE>(For-ward A)

IE>(Re-verse B)

215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used I3>> I2>> I1>> IE>27 26 25 24 23 22 21 20

Format 16-bit unsigned integerRange 0 - 65535

Bit 15 14 13 12 11 10 9 8Milliseconds215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Milliseconds27 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit msRange 0 - 59999

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Hours

215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Minutes

27 26 25 24 23 22 21 20

Format 5-bit unsigned integerUnit hRange 0 - 23

Format 6-bit unsigned integerUnit minRange 0 - 59

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

75

Page 76: Manual Sicam Fcm

Modbus RegistersB.7 Register Type Data - Events

Time in Month and Date

(Address 304, 314, …., 494) This register contains the time in month and date.

Time in Year

(Address 305, 315, …., 495) This register contains the time in year.

Phase Current I1

(Address 306, 316, …., 496) This register contains the fault current in I1.

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Month

215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Not used Not used Not used Date

27 26 25 24 23 22 21 20

Format 5-bit unsigned integerUnit DateRange 1 - 31

Format 4-bit unsigned integerUnit MonthRange 1 - 12

Bit 15 14 13 12 11 10 9 8Not used Not used Not used Not used Not used Not used Not used Not used215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 0Not used Year27 26 25 24 23 22 21 20

Format 7-bit unsigned integerUnit YearRange 12 - 99

For example, if modbus value is read as:12 = Year 201299 = Year 2099

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit ARange 0 - 9999

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

76

Page 77: Manual Sicam Fcm

Modbus RegistersB.7 Register Type Data - Events

Phase Current I2

(Address 307, 317, …., 497) This register contains the fault current in I2.

Refer Phase current I1.

Phase Current I3

(Address 308, 318, …., 498) This register contains the fault current in I3.

Refer Phase current I1.

Earth Current IE

(Address 309, 319, …., 499) This register contains the fault earth current in IE.

Refer Phase current I1.

Reserved

(Address 310 - 500) These registers are reserved.

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

77

Page 78: Manual Sicam Fcm

Modbus RegistersB.8 Register Type Data - Trailing Pointers

B.8 Register Type Data - Trailing Pointers.

(Address 101 - 282) This register stores the minimum value, and maximum value of I1, I2, I3, IE, P, Q, and S values for the respective phases at regular intervals. The interval ranges from 15 minutes, 30 minutes, 45 min-utes, 60 minutes, 24 hours, 1 month, and 1 year.

Table B-17 Trailing Pointers

Phase Current I1

(Address, see Table B-17) This register contains the minimum value and maximum values of phase current I1 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Phase Current I2

(Address, see Table B-17) This register contains the minimum value and maximum values of phase current I2 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Phase current I1.

Phase Current I3

(Address, see Table B-17) This register contains the minimum value and maximum values of phase current I3 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Phase current I1.

Parame-ters

15 Minutes 30 Minutes 45 Minutes 60 Minutes 24 Hours 1 Month 1 Year

Min value

Min value

Min value

Min value

Min value

Max value

Min value

Max value

Min value

Max value

Min value

Max value

Min value

Max value

I1 101 114 127 140 153 166 179 192 205 218 231 244 257 270I2 102 115 128 141 154 167 180 193 206 219 232 245 258 271I3 103 116 129 142 155 168 181 194 207 220 233 246 259 272IE 104 117 130 143 156 169 182 195 208 221 234 247 260 273P1 105 118 131 144 157 170 183 196 209 222 235 248 261 274P2 106 119 132 145 158 171 184 197 210 223 236 249 262 275P3 107 120 133 146 159 172 185 198 211 224 237 250 263 276Q1 108 121 134 147 160 173 186 199 212 225 238 251 264 277Q2 109 122 135 148 161 174 187 200 213 226 239 252 265 278Q3 110 123 136 149 162 175 188 201 214 227 240 253 266 279S1 111 124 137 150 163 176 189 202 215 228 241 254 267 280S2 112 125 138 151 164 177 190 203 216 229 242 255 268 281S3 113 126 139 152 165 178 191 204 217 230 243 256 269 282

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit ARange 0 - 9999

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

78

Page 79: Manual Sicam Fcm

Modbus RegistersB.8 Register Type Data - Trailing Pointers

Earth Current IE

(Address, see Table B-17) This register contains the minimum value and maximum values of phase current IE measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Phase current I1.

NOTE

Trailing pointers feature is enabled only after the Modbus time synchronization happens between the device clock and RTU.

Active Power P1 for Phase 1

(Address, see Table B-17) This register contains the minimum value and maximum values of active power for phase 1 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Active Power P2 for Phase 2

(Address, see Table B-17) This register contains the minimum value and maximum values of active power for phase 2 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Active Power for phase 1.

Active Power P3 for Phase 3

(Address, see Table B-17) This register contains the minimum value and maximum values of active power for phase 3 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Active Power for phase 1.

Reactive Power Q1 for Phase 1

(Address, see Table B-17) This register contains the minimum value and maximum values of reactive power for phase 1 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit kWRange −32768 to 32767

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit kVARRange −32768 to 32767

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

79

Page 80: Manual Sicam Fcm

Modbus RegistersB.8 Register Type Data - Trailing Pointers

Reactive Power Q2 for Phase 2

(Address, see Table B-17) This register contains the minimum value and maximum values of reactive power for phase 2 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year resepectively.

Refer to, Reactive Power Q for phase 1.

Reactive Power Q3 for Phase 3

(Address, see Table B-17) This register contains the minimum value and maximum values of reactive power for phase 3 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year resepectively.

Refer to, Reactive Power Q for phase 1.

Apparent Power S1 for Phase 1

(Address, see Table B-17) This register contains the minimum value and maximum values of apparent power for phase 1measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Apparent Power S2 for Phase 2

(Address, see Table B-17) This register contains the minimum value and maximum values of apparent power for phase 2 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Apparent Power S for phase 1.

Apparent Power S3 for Phase 3

(Address, see Table B-17) This register contains the minimum value and maximum values of apparent power for phase 3 measured at every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.

Refer to, Apparent Power S for phase 1.

Bit 15 14 13 12 11 10 9 8215 214 213 212 211 210 29 28

Bit 7 6 5 4 3 2 1 027 26 25 24 23 22 21 20

Format 16-bit unsigned integerUnit kVARange 0 - 65535

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

80

Page 81: Manual Sicam Fcm

Index

AAccessories 14Analog input registers 48Applications 12Archive logging 27Auto reset time 61

BBattery 16Battery freshness seal mode 14Bit type data - coil 51Bit type data - discrete 51

CCommunication settings 45Communications 30Connection diagrams 34

DData package format 45Date type 59Derived values 27Digital input 16Digital inputs 31Dimensions 31Directional earth fault 23

EEarth fault response time (tIE>) 57Earth fault trip value (IE>) 57Earth point treatment 58Environment 31Event counter 74Event type 74Events 49

FFault indication 26Fault passage indicator 34Fault reset modes 26Flush mounting 12Front view 19

GGrid frequency 55

HHolding registers 46, 53

IIED 12Input registers 47Inrush-current detection 25Intermittent earth fault counter 74Isometric view 19

KKeypads 16

LLanguage 58LED 16

MMeasured value accuracy 30Measuring inputs for current 30Measuring inputs for voltage 30Medium voltage 12Modbus baud rate 53

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

81

Page 82: Manual Sicam Fcm

Modbus data 45Modbus frame configuration 53Modbus function codes 45Modbus ID 54Modbus parameters 45Modbus Registers 44

NNeutral displacement time tVNE> 61Neutral displacement voltage VNE> 61

OOrdering information 13Overcurrent response time (tI >>) 57Overcurrent trip value (I >>) 56

PPanel 12Parameterization menu structure 39Parameters 16PLC 44Power factor 12Primary voltage 56Protection device class 31

RRear view 19RTC synchronization 27

SScrew connection 18Spring-cage connection 18

TTechnical data 30Terminal diagram 17Time in hours and minutes 75Time in milliseconds 75Time in month and date 76Time in year 76Time type 59Trailing pointers 49, 78

UUser interface 39

VVMax alarm 60Voltage alerts 26Voltage transformer secondary/Low-power voltage

transformer 58

SICAM Feeder Condition Monitor, ManualE50417-H8940-C509-A1, Edition 06.2013

82