Managing Building Moisture

download Managing Building Moisture

of 53

Transcript of Managing Building Moisture

  • 7/31/2019 Managing Building Moisture

    1/53

    Managing BuildingMoisture

  • 7/31/2019 Managing Building Moisture

    2/53

    American Standard Inc. 1998

    SYS-AM-15 i

    Managing BuildingMoisture

    by Dennis Stanke, staff engineer

    La Crosse, Wisconsin

    Bruce Bradway, senior airside applications engineer

    Lexington, Kentucky

    with Art Hallstrom, airside applications engineering manager

    Lexington Kentucky

    Nan Bailey, information designer

    La Crosse, Wisconsin

    Special thanks to: J. David Odom III, vice president CH2M Hill and his staff in

    Orlando, Florida, for permission to adapt text and illustrations from the

    CH2M Hill manual Preventing Indoor Air Quality Problems in Hot,

    Humid Climates: Design and Construction Guidelines, CH2M Hill,

    1996.

  • 7/31/2019 Managing Building Moisture

    3/53

    ii American Standard Inc. 1998SYS-AM-15

    Contents

    Preface ......................................................................................................... iv

    Introduction ............................................................................................. 1

    Good Reasons for Dry Buildings ........................................ 2Better Indoor Air Quality/Better Health ......................................................2

    Reduced Building System Deterioration ................................................... 3

    More Comfortable Space Conditions ......................................................... 3

    Moisture Sources ............................................................................... 4

    Liquid-Water Sources ............................................................................. 4Weather .................................................................................................. 5

    Ground Water ......................................................................................... 5

    Interior Leaks.......................................................................................... 6

    Cleaning ................................................................................................. 6

    Water-Vapor Sources ...................................................................................6

    Vapor-Pressure Diffusion ........................................................................ 7

    People .................................................................................................. 10

    Evaporation .......................................................................................... 10

    Combustion .......................................................................................... 12

    Infiltration .............................................................................................. 12

    Ventilation ............................................................................................. 14

    Condensation ............................................................................................. 15

    Moisture and Building Envelope ....................................... 17Prevent Liquid-Water Intrusion ................................................................17

    Minimize Vapor-Pressure Diffusion .........................................................17

    Minimize Infiltration ................................................................................... 18

    Summary ..................................................................................................... 20

    Moisture and Occupied Spaces ......................................... 21Minimize Liquid-Water Sources ...............................................................21

    Prevent Unplanned Condensation ........................................................... 21

    Dehumidify Spaces .................................................................................... 22

    Account for All Loads............................................................................23

    Part-Load Control ................................................................................. 23

    Unoccupied Control .............................................................................. 24

    System Monitoring ................................................................................25

    Summary ..................................................................................................... 25

  • 7/31/2019 Managing Building Moisture

    4/53

    American Standard Inc. 1998

    SYS-AM-15 iii

    Contents

    Equipment-Room Moisture ....................................................26Minimize Moisture Sources ...................................................................... 26

    Prevent Unplanned Condensation ........................................................... 27

    Raise Surface Temperature and Vapor Seal ........................................ 27

    Lower Equipment-Room Dew Point ..................................................... 27

    Dehumidify Ventilation Air ........................................................................28

    Equipment-Room Design Examples ........................................................30

    A Poor Design: Negative Pressurization ..............................................30

    A Better Design: Positive Return-Air Pressurization ............................32

    Best Design: Positive Supply-Air Pressurization ..................................34

    Summary ..................................................................................................... 35

    Moisture and Chillers ................................................................... 36

    Moisture and Air-Handling Units .......................................37Condensate Collection Pans ....................................................................37

    Size Coil to Limit Carryover ..................................................................37

    Slope to Prevent Standing Water ......................................................... 38

    Drain to Prevent Flooding.....................................................................39

    Drain-Line Seals ......................................................................................... 39

    External Condensation .............................................................................. 41

    Seal Penetrations and Joints................................................................ 42

    Improve Unit Insulation .........................................................................43

    Internal Condensation ............................................................................... 45Seal Unit Penetrations and Joints ........................................................ 46

    Lower Equipment-Room Dew Point ..................................................... 46

    In Conclusion ....................................................................................... 47Acknowledgments ................................................................................ 47

  • 7/31/2019 Managing Building Moisture

    5/53

    iv American Standard Inc. 1998SYS-AM-15

    Preface

    Uncontrolled moisture within a building can contribute to structural damage,

    occupant discomfort and unacceptable indoor air quality. Moisture is often

    overlooked or underestimated during HVAC system design and operation, and it

    can cause significant problems in the building envelope, occupied spaces and

    mechanical-equipment rooms.

    This manual helps HVAC system designers identify and quantify moisture

    sources. It also presents moisture-management techniques related to the

    building envelope, the occupied space and the mechanical-equipment room.

    Moisture problems can occur in buildings in any geographic location. The

    solutions identified in this manual apply to building-moisture management in any

    climate; however, the concepts are especially applicable for buildings located inhumid climates.

    The Trane Company, in proposing these system design and application

    concepts, assumes no responsibility for the performance or desirability of any

    resulting system design. System design is the prerogative and responsibility of

    the system designer.

  • 7/31/2019 Managing Building Moisture

    6/53

    American Standard Inc. 1998

    SYS-AM-15 1

    Introduction

    Uncontrolled moisture in buildings can cause serious problems for building

    occupants, furnishings and structure. Microbial growth, encouraged by high

    relative humidity, leads to poor indoor air quality and building deterioration.

    Poor IAQ results in discomfort, health problems and could ultimately lower

    productivity and spawn lawsuits. Uncontrolled moisture can also stain wall

    surfaces, damage paint, corrode metal surfaces and accelerate the deterioration

    of building furnishings and structural materials. Buildings located in climates with

    long periods of high ambient temperature and high, absolute humidity (hot,

    humid climates) are particularly prone to uncontrolled moisture. Figure 1

    illustrates humid climate and fringe climate regions within the U.S.

    Figure 1 Hot, Humid Climates

    This manual discusses design considerations and HVAC operating techniques

    that help control moisture within occupied buildings once it enters the building. l

  • 7/31/2019 Managing Building Moisture

    7/53

    American Standard Inc. 1998

    2 SYS-AM-15

    Good Reasons forDry Buildings

    Controlling building moisture takes time and money. How do building

    occupants and building owners benefit from these expenditures?

    Better Indoor Air Quality/Better HealthBuilding components (walls, floors and ceilings) and building furnishings (wall

    coverings, carpets, furniture and stored materials) provide ideal amplification

    sites for microbial growth. Microbial growthfungi, bacteria and dust mites, for

    instancecan produce odors, allergens, and in some cases, toxins.

    Odors cause discomfort and long-term exposure to allergens and toxins can lead

    to health problems such as asthma and lung disease. Also, musty-smelling

    buildings cannot command high rent or a high resale price.

    For microbial growth to occur, certain conditions must be present

    w A source of food

    w Temperature between 40F100F

    w Adequate moisture, usually 70% RH or higher

    w A source of mold or mildew spores

    These conditions can certainly be present in a building. Materials used in

    building construction, building furnishings, stored materials (books and papers)

    and accumulated dirt can all become food sources for microbial growth. Typical

    indoor temperatures fall in the middle of the microbial growth temperature range.

    Uncontrolled, indoor relative humidity can easily rise above the 70% RH needed

    to encourage microbial growth, especially in hot, humid climates. Spores, ofcourse, are present everywhere in both indoor and outdoor air as well as in

    building materials and furnishings.

    Of the four conditions for microbial growth, relative humidity is most easily

    controlled. Maintaining indoor relative humidity below 60% RH, as required by

    ASHRAE 62-1989 (Figure 2), limits the potential for microbial growth in buildings.

    Figure 2 ASHRAE-Recommended Humidity Levels

  • 7/31/2019 Managing Building Moisture

    8/53

    American Standard Inc. 1998

    SYS-AM-15 3

    Good Reasons forDry Buildings

    Reduced Building System DeteriorationThe same fungi (mold and mildew) that cause people discomfort and/or harm

    can also cause building materials, furnishings and structure to prematurely

    corrode and/or degenerate. Premature failure of walls, ceilings and floors and

    irreversible damage to carpets, wall coverings and furnishings can result.

    The same rationale holds true for the air handling equipment and duct system.

    Wet insulation can lead to corrosion and/or deterioration, shortening the useful

    life and effectiveness of the air-distribution system.

    Deterioration in buildings increases maintenance and operation costs. Figure 3

    illustrates the relationship between the effects of relative humidity and building

    operation, maintenance and repair costs. Maintenance includes normal cleaning

    and periodic replacement of damaged furnishings, such as moldy carpet and

    wallpaper. Building operational costs include the cost of energy.

    Figure 3 Humidity and Building Costs

    More Comfortable Space ConditionsControlling indoor relative humidity to an acceptable level results in consistent

    thermal comfort within the occupied spaces. Thermal comfort reduces occupant

    complaints and improves worker productivity, and increases both rental potential

    and market value. l

  • 7/31/2019 Managing Building Moisture

    9/53

    American Standard Inc. 1998

    4 SYS-AM-15

    Moisture Sources

    Moisture enters the building as liquid water or as water vapor. It causes trouble

    in either form and changes readily from vapor to liquid through condensation. It

    must be properly managed to avoid trouble. Lets look at possible moisture

    sources and techniques to minimize the impact of each.

    Liquid-Water SourcesLiquid water damages furnishings and building structure, supports microbial

    growth and provides surface wetness for evaporation, a source of water vapor

    and increased indoor moisture load. Common liquid-water sources include the

    weather (rain, fog and snow), ground water, leaking pipes and equipment, and

    wet cleaning processes (see Figure 4). Perhaps the most troublesome source of

    liquid water, condensed water vapor, is discussed separately on the following

    pages.

    Figure 4 Common Liquid-Water Sources in Buildings

  • 7/31/2019 Managing Building Moisture

    10/53

    American Standard Inc. 1998

    SYS-AM-15 5

    Moisture Sources

    Weather

    During building construction, prior to completion of the roof and walls, building

    materials and the partially completed building structure may become saturated

    with rainwater or snow. Protect building materials from rain, snow and

    condensation (which can form inside equipment wrapped with a vapor retarder

    such as plastic) during construction. For best results, store materials within

    covered structures. If materials become wet, dry them quickly and completely or

    replace them. Mold can grow within 24 hours on wet materials. Discard visibly

    moldy materials and replace with new, dry materials.

    During normal operation, rain may enter the building structure through roof and

    wall leaks or openings. Design windows and walls to minimize leakage and

    control water with internal drainage schemes. Roof design and construction

    practices must result in a leakproof membrane that drains properly. Roofs need

    proper maintenance to assure long-term integrity. Repair leaky walls and roofs

    quickly to prevent water damage and to avoid high latent loads indoors.

    The outdoor intake airflow may entrain rain droplets or snowflakes and carry

    them into the duct system. Design outdoor air intakes to limit rainwater

    entrainment, using rain hoods and moisture eliminators sized to avoid high intake

    velocity. If the design allows water droplets to penetrate the intake, provide for

    indoor drainage (drain pans for instance); in other words, manage the water flow

    once it enters the building.

    Rain hoods and moisture eliminators cannot stop entrained snow. Prevent

    possible filter damage or internal flooding using a heating coil to melt the snow ora large plenum to allow the snow to settle, melt and evaporate before it reaches

    the filters.

    Fog also enters the building through the outdoor air intake. Fog droplets, too

    small to stop at a louver or moisture eliminator, usually evaporate quickly within

    the HVAC system, causing little or no surface wetting. However, the evaporated

    droplets certainly add to the indoor moisture load and must be accounted for in

    the design and operation of the system.

    Ground Water

    Ground water may seep into the building through very small cracks in basement

    walls and floors. Be sure that surface water and subsurface water drains away

    from the building, not toward it. Design the floor to limit water intrusion via cracks

    and joints. Manage any water that penetrates the floor using proper slopes and

    drains.

  • 7/31/2019 Managing Building Moisture

    11/53

    American Standard Inc. 1998

    6 SYS-AM-15

    Interior Leaks

    Leaking appliances, valves and pipes can quickly wet large areas of interior

    structure. Liquid water within walls and concealed areas, through capillary action

    and surface tension, can travel long distances and result in widespread, long-

    term wetting.

    Plan and follow maintenance procedures to assure speedy location and repair of

    any water leaks within the building. Accidental spills and floods should be

    cleaned up quickly. If porous materials become wet, dry them completely within

    24 hours or consider replacing them.

    Cleaning

    Cleaning processes, such as floor mopping and carpet shampooing, result in

    large wet areas. Carpet shampooing in particular increases moisture content in

    carpet fibers (and in the accumulated dirt beneath the carpet).

    Use wet cleaning processes cautiously (or not at all). Take steps to dry wet-

    cleaned surfaces within 24 hours. For shampooed carpets, assure speedy

    evaporation by providing adequate air motion and dehumidification during drying.

    If a cooling coil controlled by a thermostat provides the necessary

    dehumidification, auxiliary heat may be needed to maintain a sufficient cooling

    coil load for continuous dehumidifying capacity.

    Water-Vapor SourcesA high indoor water-vapor level elevates the indoor dew point and relative

    humidity, and it contributes to the latent load on HVAC equipment. High dew

    point increases the likelihood of unplanned condensation; high relative humidity

    can result in occupant discomfort, increased dust mite population, and

    accelerated microbial growth. HVAC-equipment capacity must match total (latent

    plus sensible) load.

    Common water-vapor sources in buildings (see Figure 5) include vapor-pressure

    diffusion from outside, evaporation from people, wet surfaces and processes,

    generation from combustion, infiltration from outside and introduction from

    outside via ventilation airflow.

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    12/53

    American Standard Inc. 1998

    SYS-AM-15 7

    Figure 5 Common Water-Vapor Sources

    Vapor-Pressure Diffusion

    Water vapor moves through solid materials in direct proportion to the difference

    in vapor pressure between the opposite sides of the material and the resistance

    of the material to water-vapor flow (the permeance of the material).

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    13/53

    American Standard Inc. 1998

    8 SYS-AM-15

    The moisture load (grains of water per hour) added to a building from outside

    by vapor-pressure diffusion can be found using Equation 1.

    Equation 1

    Wp = P A (VPo VPi)

    Where

    Wp = moisture load (gr/h)

    P = permeance factor (gr/h ft2 in. Hg)

    A = surface area (ft2)

    VPo = outdoor vapor pressure (in. Hg)

    VPi = indoor vapor pressure (in. Hg)

    The table below (from 1997 ASHRAE Fundamentals Handbook) shows

    permeance factors for some common construction materials. The permeance

    factor for a composite wall (Pc) can be found as the reciprocal of the sum of

    permeance reciprocals.

    Common Construction Materials Permeance*

    hardwood siding (1/8") 11.00

    air space (1.0") 120.00

    polyethylene vapor retarder (0.002") 0.16

    insulating board sheathing (1.0") 50.00

    fibrous insulation (6.0") 19.00

    gypsum wallboard (3/8") 50.00

    paint, commercial latex 6.28

    vinyl wallpaper 0.23

    *Permeance factor = gr/h ft2 in. Hg

    Consider a composite wall that includes wallboard (P = 50), fibrous insulation

    (P = 19), exterior sheathing (P = 50), and hardboard siding (P = 11), and has a

    high composite permeance [Pc = 1 (1 50 + 1 19 +1 50 + 1 11) = 5.448];

    i.e. water vapor can diffuse through the wall quite readily. The same composite

    wall with a polyethylene vapor retarder (P = 0.16), has a much lower its

    composite permeance (Pc = 0.155); i.e. water-vapor diffusion through this wall is

    much more difficult.

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    14/53

    American Standard Inc. 1998

    SYS-AM-15 9

    Figure 6 shows the composite walls described above. On a hot, humid day in

    Jacksonville, outdoor water-vapor pressure exceeds indoor water-vapor pressure

    more significantly (VPo VPi = 1.03 - 0.39 = 0.64 in. Hg) than on a cooler day

    (VPo VPi = 0.60 0.39 = 0.21 in. Hg).

    Applying the permeable wall structure (Pc = 5.435) to a small building with

    4000 ft2 of exterior wall surface, and solving Equation 1, we find that the moisture

    load due to vapor-pressure diffusion can be quite high (Wp = 5.448 4000 0.64

    = 13,900 gr/h) on the hot day and lower on the cooler day (Wp = 5.448 4000

    0.21 = 4580 gr/h).

    Adding a vapor retarder results in a less permeable wall structure (Pc = 0.155)

    and significantly lower moisture load on both the hot day (Wp = 0.155 4000 0.64 = 400 gr/h) and on the cooler day (Wp = 0.155 4000 0.21 = 130 gr/h).

    As this example illustrates, moisture load due to vapor-pressure diffusion can be

    significant through a simple wall. The addition of an exterior vapor barrier

    reduces it considerably but cannot eliminate it.

    Use a vapor retarder in floors, walls and ceilings to minimize moisture transfer

    due to vapor-pressure diffusion. Locate the vapor retarder within walls and

    ceilings, near the warm side, to avoid unplanned condensation within the

    structure.

    Moisture Sources

    Figure 6 Vapor Diffusion Through Wall Structure

  • 7/31/2019 Managing Building Moisture

    15/53

    American Standard Inc. 1998

    10 SYS-AM-15

    In humid climates and other predominantly cooling climates, use low-

    permeance materials near the outside surface (the warm side) to keep

    summertime outdoor water vapor away from cold, interior surfaces. When the

    building includes an attic, be sure to include a continuous vapor retarder on the

    attic side of the insulation.

    In mixed climates, for buildings with low wintertime inside relative humidity

    (35% RH or less), use low-permeance materials near the outside surface, as

    recommended for cooling climates.

    In predominantly heating climates, use low-permeance materials near the inside

    surface (the warm side) to keep wintertime indoor water vapor away from cold

    exterior surfaces.

    People

    Building occupants produce water vapor at different rates, depending upon their

    activity level, via respiration and perspiration. According to the 1997 ASHRAE

    Fundamentals Handbook, an adult working at a desk introduces a latent load of

    155 Btu/h, and an active athlete contributes 1000 Btu/h.

    Since water vapor contains approximately 0.14 Btu/gr, an office worker

    contributes 1100 gr/h (Wo = 155 / 0.14) to the indoor moisture load while a

    volleyball player contributes approximately 7100 gr/h (Wo = 1000 / 0.14).

    Although it can be significant, many designers erroneously consider respirationas the sole source of moisture load in buildings. Design the HVAC system and

    equipment with sufficient capacity to satisfy the total moisture load, including the

    people-related moisture load as one of many sources.

    Evaporation

    Wet surfaces add moisture to indoor air through evaporation. Evaporation occurs

    when the air vapor pressure (VPa) is less than the vapor pressure of the

    saturated air at the wet surface (VPs).

    Wet surfaces, found throughout the building, may be planned (pools, aquariums

    and fountains) or unplanned (such as leaky pipes and unplanned condensation).

    Cooking processes and live plants add water vapor via evaporation. On rainy orsnowy days, building occupants carry a significant amount of moisture into the

    building on their shoes and clothing.

    Equation 2 can be used to calculate the moisture load due to evaporation from

    liquid-water surfaces.

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    16/53

    American Standard Inc. 1998

    SYS-AM-15 11

    Equation 2

    We = H A (VPsVPa) 7000/1060

    Where

    We = moisture load from evaporation (gr/h)

    H = latent heat transfer rate (Btu/h ft2 in. Hg, see Figure 7)

    A = water surface area (ft2)

    VPs = saturated vapor pressure of air at the water surface

    temperature (in. Hg)

    VPa = vapor pressure of space air (in. Hg)

    7000 = definition of grains (gr/lb)

    1060 = latent heat of vaporization at 75F (Btu/lb)

    Figure 7 shows latent heat transfer rate (H) related to air stream velocity. For

    example, a large aquarium in an office with typical 50-fpm transverse airflow

    (perpendicular to surface) transfers latent heat to the air at a rate of (H = 250

    Btu/h ft2 in. Hg). If the space is 72F, 50% RH (VPa = 0.39), and 8 ft2 of water

    surface at 78F (VPs = 0.96 in. wg) is exposed, the evaporation moisture load

    can be found using Equation 2 (We = 250 8 0.57 7000 / 1060 = 7500 gr/h).

    In another example, a 4-ft diameter puddle (A = 12.5 ft2) of condensate at 80F

    (VPs = 1.03) on the floor of an equipment room at 85F, 50% RH (VPa = 0.60),

    contributes 8900 gr/h (We = 250 12.5 0.43 7000 / 1060) to the equipment

    room.

    Figure 7 Latent Heat Transfer from Water Surface

    (with respect to the research by W.H. Carrier in 1918)

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    17/53

    American Standard Inc. 1998

    12 SYS-AM-15

    Depending on the situation, moisture load due to evaporation from water

    surfaces may be significant. Design the HVAC system with sufficient capacity to

    satisfy the moisture load from all sources, including evaporation from planned

    water surfaces (pools and fountains) and predictable liquid-water sources

    (rainwater in entryways, shampooed carpets). Minimize unplanned evaporation

    sources (liquid water from leaky pipes, leaky roofs, and spills) by quickly

    eliminating the source and removing the liquid water.

    Combustion

    Combustion liberates water vapor. Remember from high-school chemistry: the

    two products of complete combustion are carbon dioxide (CO2) and water (H2O).Equation 3 can be used to calculate the rate of moisture generation from an

    open gas flame. Open-flame heaters, boilers and appliances, as well as open-

    flame cooking surfaces, can produce significant water vapor.

    Indoor combustion processes must be considered when calculating indoor

    moisture load. If an unvented gas griddle consumes natural gas at a known rate

    (G = 6.7 ft3/h), the combustion moisture load can be easily found (Wc = 6.7 650

    = 4400 gr/h).

    Equation 3

    Wc = G K

    WhereWc = moisture load from combustion (gr/h)

    G = gas firing rate (ft3/h)

    K = 650 gr/ft3 for natural gas

    1300 gr/ft3 for propane

    If possible, use vented combustion processes to eliminate combustion moisture

    load and other products of combustion. Dehumidify to remove moisture from

    unvented combustion processes within the building.

    Infiltration

    No building is airtight. Outdoor air enters (infiltration) and indoor air leaves

    (exfiltration) via countless little openings in the building envelope as well as large

    intentional openings such as doors and windows.

    Driven by differential pressures imposed by mechanical ventilation, wind and

    stack effect, the infiltration (exfiltration) air carries water vapor with it. Air passes

    through any available penetration in wall, floor or ceiling.

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    18/53

    American Standard Inc. 1998

    SYS-AM-15 13

    Elevator shafts act as chimneys, reducing pressure on lower floors. Gaps can

    be found at wall-floor or wall-ceiling joints, between wallboard and electrical

    fixtures on perimeter walls, at electrical wire and conduit penetrations, at pipe

    and duct penetrations, and at window and door penetrations. Air also comes

    and goes through open exterior doorways and windows. Whenever an exterior

    door opens in Florida, cooled indoor air spills out of the building at floor level,

    only to be replaced by an inflow of warm, moist air at door-top level.

    How much water vapor moves with the air? Building moisture load due to

    infiltration can be calculated using Equation 4.

    Equation 4

    Wi = A r 60 Va (HRo HRi)

    Where

    Wi = moisture load due to infiltration (gr/h)

    A = area of opening (ft2)

    r = density of outdoor air (lb/ft3)

    60 = minutes per hour (m/h)

    Va = air velocity through opening (fpm)

    HRo = outdoor air humidity ratio (gr/lb)

    HRi = indoor air humidity ratio (gr/lb)

    Equation 4 includes air velocity and the total area of all openings in the envelope.

    Values for these variables may be estimated, either at normal or extreme

    differential (inside-to-outside) building pressure. However, it may be more

    practical to estimate total envelope airflow (Qe = A Va) as follows.

    Building tightness specifications often rate building leakage at a differential

    pressure of 0.30 in. wc. At a positive differential pressure of 0.30, the 1997

    ASHRAE Fundamentals Handbook, Chapter 25, estimates typical exfiltration

    airflow per square foot of exterior wall surface for tight, average and leaky walls

    (Q = 0.10, 0.30 and 0.60 cfm/ft2, respectively).

    If we assume an exponential relationship between differential pressure and

    airflow (Q = k P0.65), established statistically by various researchers, we can find

    the flow coefficient (k) for each wall construction category, as shown in Figure 8.

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    19/53

    American Standard Inc. 1998

    14 SYS-AM-15

    Figure 8 Leakage Airflow

    Assuming our example building in Jacksonville uses average wall construction

    and operates at a slightly negative pressure (DP = 0.05 in. wc.), we can calculate

    infiltration airflow (Q = 0.66 (0.05)0.65 = 0.094 cfm/ft2) per square foot of exterior

    wall surface or total infiltration through the envelope (Qe = Q Ae = 0.094 4000

    = 376 cfm).

    In Jacksonville, Florida, when outdoor conditions are hot (96F, 80% RH, HRo =

    156 gr/lb) and indoor conditions are comfortable (72F, 50% RH, HRi = 58 gr/lb),

    we can use Equation 4 (with A Va = Qe) to calculate the infiltration moisture load

    (Wi = 376 0.069 60 (156 58) = 153,000 gr/h).

    Even very low infiltration airflow can contribute significantly to moisture load and

    must be considered during design. Seal air leaks due to cracks/gaps/holes

    where air and moisture can enter, paying particular attention to wall penetrations.

    In hot, humid climates, design to minimize infiltration by maintaining indoor

    spaces at a slightly higher static pressure than outdoor atmospheric pressure;

    operate with positive building pressure.

    Ventilation

    HVAC equipment draws in outdoor air for ventilation and to replace indoor air

    removed by exhaust fans and combustion processes. Ventilation air can contain

    considerable moisture, especially in hot, humid climates. Water vapor in the

    ventilation air often represents the single largest source of moisture in a building.

    We can use ventilation airflow (Qv = A Va) in Equation 4 to find ventilation

    moisture load Wv.

    Given ventilation airflow (Qv = 2000 cfm), ventilation moisture load on a hot,

    humid day in Jacksonville can be calculated (Wv = 2000 0.069 60 (156 58)

    = 820,000 gr/h).

    Moisture Sources

    Finding Worst Case

    Design Condition

    Most designers use the ambient

    weather data presented in the

    1997 ASHRAE Fundamentals

    Handbook to determine total

    cooling load due to ventilation.

    Traditionally, designers used peak

    dry-bulb temperature and mean-

    coincident wet-bulb temperature

    as worst-case design condition.

    A designer in Jacksonville, using

    the 0.4% annual peak dry bulb

    (96F) and mean coincident wet

    bulb (76F) from 1997 ASHRAE

    Fundamentals Handbook, can first

    find outdoor and indoor air

    enthalpy (ho = 39.2 and hi = 26.4

    Btu/lb, respectively), then find the

    associated air conditioning load.

    For our example building,

    ventilation air adds 9.6 tons

    (Qt = 4.5 2000 (39.2 26.4)/

    12000 = 9.6) to the building air

    conditioning load at this design

    condition. Is this the worst-case

    ventilation air load? No!

    The 1997 ASHRAE Fundamentals

    Handbookalso presents annual

    peak dew point and mean

    coincident dry-bulb temperatures.

    Using the 0.4% annual-peak dew

    point (76F) and mean coincident

    dry-bulb (84F) temperatures,

    both outdoor air enthalpy (ho =

    41.6 Btu/lb) and ventilation load

    (Qt = 11.4 tons) increase.

    Ventilation air on a warm, rainy

    day represents more total coolingload than the same volume of

    ventilation air on a hot, sunny day.

  • 7/31/2019 Managing Building Moisture

    20/53

    American Standard Inc. 1998

    SYS-AM-15 15

    Contrast the moisture load in Jacksonville to that in Denver. On a typical hot day

    in Denver, each pound of ambient air at 93F, 10% RH contains only 24 grains

    of water vapor. Again, given ventilation airflow (Qv = 2000 cfm), ventilation

    moisture load can be calculated using Equation 4 (Wv = 2000 0.071 60

    (24 58) = -290,000 gr/h). Note that a negative ventilation moisture load results.

    In Denver, ventilation air can actually remove moisture from the building rather

    than add it.

    Most designers use ambient weather data (see side-bar) to estimate ventilation

    air conditions and ventilation moisture load. Ambient weather data describes

    historical conditions in a general geographical region. However, local ventilation-

    air moisture content may be even higher than indicated by ambient conditions.

    For instance, a roof-mounted intake in Jacksonville may introduce very warm air

    (110F) with very high moisture content (170 gr/lb or more), especially when the

    sun reappears after a rain shower. Since outdoor airflow cannot be lower than

    the minimum required for proper ventilation, the air introduced for ventilation

    must be dehumidified.

    Select and operate HVAC equipment and systems to dehumidify the ventilation

    air at all load conditions.

    CondensationCondensate forms whenever moist air contacts a surface at a temperature below

    the dew point (Figure 9).

    Figure 9 Surface Condensation

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    21/53

    American Standard Inc. 1998

    16 SYS-AM-15

    Inside the exterior walls, water vapor can enter by vapor-pressure diffusion, by

    exfiltration or infiltration, or by evaporation from liquid-water leaksraising

    internal dew point.

    In occupied spaces during the cooling season, a supply-air duct or chilled-water

    pipe behind an interior wall may cool the wall surface below dew point. The

    concrete beneath carpeted floors may be very cool compared with average

    space temperature. During the heating season, indoor water vapor can easily

    condense on cold windows, cold wall surfaces within the space, and inside the

    exterior wall structure.

    The mechanical equipment room offers many cold surfaces for the formation of

    unplanned condensate, especially during the cooling season. The outsidesurfaces of air handlers and supply-air ducts, water chillers, chilled-water and

    return-water pipes, and condensate drain pipes all operate at low temperatures.

    If the equipment room is not conditioned, equipment-room dew point may be

    very, very high, especially in hot, humid climates.

    Inside the air handler, surface temperature approaches supply air temperature. If

    design philosophy results in a high equipment-room dew point, any air leaks into

    the air handler downstream of the cooling coil may cause significant

    condensation and flooding inside the air handler.

    To avoid unplanned condensation in any location, either raise the surface

    temperature or lower the air dew point or both. No other alternative exists.

    In summary, many sources of moisture in buildings must be considered. Some

    can be eliminated, others can be minimized, but none can be ignored during

    building design and operation. l

    Moisture Sources

  • 7/31/2019 Managing Building Moisture

    22/53

    American Standard Inc. 1998

    SYS-AM-15 17

    Four major building elements must be designed and operated properly to

    minimize the impact of moisture in the building

    w Envelope

    w Occupied spaces

    w Equipment room

    w HVAC equipment

    Lets start with the building envelope.

    Unwanted, unplanned condensate forms inside walls and ceilings if the dew

    point of the internal air exceeds the coldest surface temperature. Since water

    vapor can enter the wall cavity by evaporation, vapor-pressure diffusion or

    infiltration, all three of these potential water-vapor sources must be managed toprevent unplanned condensation.

    Prevent Liquid-Water IntrusionWater vapor inside the building envelope structure increases if evaporation from

    liquid water occurs. Design and construct exterior walls to keep liquid water out.

    Liquid water includes not only rainwater and melted snow, but also ground water,

    water from leaky pipes and unplanned condensation. Use a water barrier near

    the outside surface of exterior walls to keep the rain and snow out. Design the

    roof to drain freely and to be watertight. Be sure to drain ground water away from

    the building. Seal all envelope penetrations. Seal underground wall-floor systemsand wall-floor joints.

    Minimize Vapor-Pressure DiffusionSince the indoor-to-outdoor temperature difference cannot be controlled,

    condensation prevention relies on low moisture content (low dew point) within the

    walls. In addition to sealing against liquid water, design to limit water-vapor

    diffusion into the wallcondensation occurs if moist air can penetrate to a cold

    surface.

    Use a vapor retarder on the warm side. Warm side (as mentioned above) in

    cooling and mixed climates means the outdoor side of the ceiling or the wallstructure; in heating climates, it means the indoor side. Do not use two vapor

    retardersone on the warm side and one on the cold side. Moisture trapped

    between the two vapor retarders cannot escape and condenses inside the ceiling

    or the wall at the cold surface. Also, include a sealed vapor retarder in the ceiling

    of the top floor: in heating climates use a vapor retarder on the space-side, and

    in cooling climates use one on the attic side.

    Moisture andBuilding Envelope

  • 7/31/2019 Managing Building Moisture

    23/53

    American Standard Inc. 1998

    18 SYS-AM-15

    Figure 10 Comparison of Humid Climate Walls

    Avoid low-permeance wall finishes (e.g. vinyl wall coverings and latex paint) on

    perimeter walls and ceilings in cooling climates; condensation and mold growth

    are commonly found behind perimeter wall coverings in Floridas buildings.

    Minimize InfiltrationSince all air contains water vapor, design the wall structure to limit the movement

    of moist air into interstitial wall cavities. In cooling and mixed climates, limit

    infiltration of outdoor air (the predominant source of moisture) into the building

    structure using an airflow or weather barrier near the exterior surface of

    perimeter walls.

    Figure 10 shows both a poor design and a good design for exterior walls in

    cooling or mixed climates. The poor design allows water vapor to penetrate to the

    interior wall. The good design limits vapor-pressure diffusion with a warm-side

    vapor retarder and outdoor air infiltration with an exterior weather barrier.

    Design and operate buildings to assure that indoor static pressure exceeds

    outdoor static pressure. Positive building pressure minimizes outdoor infiltration

    air, while maximizing exfiltration of low-dew-point indoor air into wall cavities.

    Moisture andBuilding Envelope

  • 7/31/2019 Managing Building Moisture

    24/53

    American Standard Inc. 1998

    SYS-AM-15 19

    Design the building so that the air-handling system can maintain a slight

    positive pressure in all portions of the building, including not only the envelope

    walls but also the occupied spaces and the equipment room. Positive building

    pressure prevents infiltration due to mechanical system operation (powered

    exhaust) and minimizes infiltration due to wind and stack effect. Remember,

    makeup airflow must always exceed the airflow needed to replace exhausted

    air and combustion air (for any open combustion processes) in order to

    maintain positive building pressure. Trane Application Manual AM-CON-17

    provides helpful recommendations related to building pressurization control.

    Lower dew point and prevent condensation within the perimeter wall structure

    by maximizing vapor-pressure diffusion out of the wall while minimizing moist

    air infiltration into the wall.

    As Figure 11 illustrates, without a warm-side vapor retarder, outdoor water

    vapor diffuses into the wall structure. And, operating the building at a negative

    pressure, with no exterior air barrier, encourages moist airflow through the wall

    and into the space. On the other hand, using highly permeable materials on the

    cold side and low permeability materials on the warm side maximizes vapor-

    pressure diffusion out of the wall (into the space). Operating with positive building

    pressure and using an external air barrier encourages dry indoor airflow through

    the wall structure to outdoors.

    Moisture andBuilding Envelope

    Figure 11 Humid Climate Wall Operation

  • 7/31/2019 Managing Building Moisture

    25/53

    American Standard Inc. 1998

    20 SYS-AM-15

    During the winter in heating climates, indoor moisture sources predominate. It

    seems logical to operate with negative building pressure to avoid forcing moist

    indoor air into the walls. However, negative indoor pressure increases the

    infiltration of very cold outdoor air, possibly resulting in drafts, cold spots,

    temperature stratification and discomfort.

    Operating with positive indoor pressure, on the other hand, results in exfiltration

    of moist indoor air into the perimeter walls. Condensation within the wall structure

    results. Very low outdoor-air vapor pressure eventually drives water vapor out for

    the wall, but repeated freeze/thaw cycles can cause serious mechanical

    damage, especially within masonry walls.

    Proper air distribution plays an important role in uniform building pressurization.Air-distribution systems must be balanced after installation and should be

    balanced periodically throughout the life of the building, especially after changes

    in building use or after system alterations.

    SummaryUse water barriers and internal drainage to minimize liquid-water penetration and

    eliminate water accumulation inside wall structures. Use a vapor retarder on the

    warm side of perimeter walls to minimize vapor-pressure diffusion. Do not use a

    vapor retarder (either purposely or accidentally) on the cold side of perimeter

    walls. Use an air (weather) barrier on the outside to minimize infiltration due to

    wind and stack effect and liquid-water penetration. Maintain positive buildingpressure in cooling climates to eliminate infiltration due to mechanical system

    operation.

    In summary, buildings in humid and predominately cooling climates should be

    designed and operated to be slightly positive. Buildings in heating climates are

    comfortable if positive, but may suffer structural damage in winter. Some

    designers and operators maintain slightly positive summertime pressure and

    slightly negative pressure during transitional seasons and in the winter. l

    Moisture andBuilding Envelope

  • 7/31/2019 Managing Building Moisture

    26/53

    American Standard Inc. 1998

    SYS-AM-15 21

    Now, lets turn from the building envelope to the occupied spaces. The

    occupied spaces inside the building should also be designed and operated

    properly to minimize the impact of moisture.

    According to ASHRAE 62-89 requirements, relative humidity in occupied spaces

    should be maintained below 60% RH at all load conditions. Moisture enters the

    occupied space by a number of paths, increasing space dew point, relative

    humidity and moisture load. Moisture entry can be minimized, but it cannot be

    stopped. Therefore, spaces must be designed to minimize moisture load and

    control relative humidity to 60% RH or less at all load conditions.

    Minimize Liquid-Water SourcesUnplanned liquid water within the occupied space can damage furnishings and

    promote microbial growth. It also evaporates, adding unplanned moisture load to

    the indoor air and raising both dew point and relative humidity.

    Design and install window systems that minimize leakage. Keep the windows

    closed during rain showers. As mentioned above, fix leaky pipes or appliances

    and dry accidental spills within 24 hours. If possible, avoid carpet shampooing; if

    unavoidable, be sure to dry shampooed carpets quickly while maintaining control

    of space relative humidity. This might mean adding heat to the space to assure

    adequate latent cooling capacity while drying.

    Prevent Unplanned CondensationWater vapor in the air cannot be eliminated, but keeping space dew point lower

    than space surface temperature can prevent condensation within the space.

    Minimize vapor-pressure diffusion using properly placed vapor retarders.

    Minimize unnecessary wet surfaces (evaporation) within the space. Eliminate

    unvented combustion processes. To minimize outdoor air infiltration, maintain

    positive space pressure in cooling climates and design entryways (using entry

    tunnels or airlock vestibules) to prevent excessive air-exchange. Do not

    introduce untreated outdoor air for space ventilation.

    Eliminate cold surfaces. Raise surface temperature by adding heat wherenecessary, or avoid cold-surface/moist-air contact by insulating surfaces from

    potential heat sinks and applying a vapor retarder on the warm side. Finally,

    Moisture andOccupied Spaces

  • 7/31/2019 Managing Building Moisture

    27/53

    American Standard Inc. 1998

    22 SYS-AM-15

    lower space dew point by removing water vapor. Account for all moisture

    sources that cannot be eliminated and design the HVAC system with sufficient

    dehumidification capacity for full-load operation and with proven control schemes

    capable of maintaining relative humidity below 60% RH at all operating

    conditions.

    Dehumidify SpacesSince moisture enters the space continuously, it must be removed continuously

    to maintain relative humidity below 60% RH. As Figure 12 illustrates, moisture

    can be removed from the occupied space in two ways: direct dehumidification

    within the space, or by replacing moist return air with dry supply air.

    Direct dehumidification, commonly applied in residential basements, simply uses

    a local dehumidifiera fan and cold and warm coils in seriesto remove water

    vapor from space air.

    Large buildings more commonly use return airflow to physically carry water vapor

    away from the space. Air supplied to the space must be dry enough to absorb the

    water vapor entering the spacesupply air dew point must be low. As local

    moisture sources add water vapor to the space, average space dew point can be

    maintained by adding sufficiently dry supply air. Space air absorbs the water

    vapor produced within the space (the latent load) and return air carries it away.

    Supply air is commonly dehumidified in one of two ways: by passing it through a

    cold coil or by passing it over a desiccant material, usually mounted on a rotatingwheel. A cold coil dehumidifies as entering-air water vapor condenses on the coil

    surface and flows down a drain. A desiccant material dehumidifies as entering-air

    water vapor adsorbs onto the desiccant surface and is then rejected to a

    separate regeneration air stream.

    Moisture andOccupied Spaces

    Figure 12 Two Space Dehumidification Methods

  • 7/31/2019 Managing Building Moisture

    28/53

    American Standard Inc. 1998

    SYS-AM-15 23

    Account for All Loads

    High, local dew points can occur indoors. Near an exterior door in a Florida

    school, for instance, water vapor enters whenever the door opens, and the door

    may open quite often. Local dew point in the entryway rises considerably. This

    moisture, and all locally introduced moisture, must be removed by the

    dehumidification system. Account for all moisture loads, not just people loads,

    when designing (sizing) the dehumidification system and the part-load control

    system.

    Select central dehumidification equipment with sufficient capacity to dehumidify

    at worst-case conditions. For moisture load, worst-case conditions usually occur

    on a cool rainy day. The 1997 ASHRAE Fundamentals Handbooknow includes

    values for both design-dry-bulb/mean-coincident-wet-bulb and design-dew-point/

    mean-coincident-dry-bulb to help designers size equipment properly.

    Remember that local, ventilation-air moisture content may be even higher than

    ambient conditions indicate. A sun-baked roof after a rain shower can add

    significantly to moisture load.

    Part-Load Control

    An HVAC system sized for the sensible design load usually has sufficient

    capacity to adequately remove moisture at both design and part load. However,

    if not properly controlled at part load, the system may not maintain space

    conditions below 60% RH.

    For instance, a 15-ton packaged rooftop, modulated by a thermostat (a sensible

    temperature controller), may maintain both sensible temperature and relative

    humidity in a classroom very well on a summer day. On a cool, rainy day,

    however, the thermostat modulates both the sensible and latent capacity of the

    rooftop unit. Although it maintains sensible temperature, the thermostat allows

    space relative humidity to rise unacceptably.

    Some HVAC systems, VAV for instance, can provide central dehumidification and

    control space relative humidity over a wide range of loads without actually

    sensing it space thermostats control temperature by modulating the flow of

    very dry air to the spaces. Other HVAC systems, like the constant-volume rooftop

    system mentioned above, cannot assure indirect relative humidity control.

    Rather, relative humidity must be sensed to allow active modulation of cooling

    capacity for dehumidification as well as sensible temperature control.

    Moisture andOccupied Spaces

  • 7/31/2019 Managing Building Moisture

    29/53

    American Standard Inc. 1998

    24 SYS-AM-15

    Systems that deliberately separate space temperature control from space

    moisture control require both a thermostat and a humidistat. A classroom unit

    ventilator, for instance, can use a thermostat to modulate the cooling coil and

    control sensible temperature and a humidistat to sense relative humidity. If the

    space exceeds 60% RH, cooling coil capacity increases to maximum and the

    thermostat modulates a tempering or reheat coil to maintain sensible

    temperature.

    Note that part-load humidity control with cold coils usually requires supply-air

    tempering to avoid overcooling the spaces. The boiler or some other source of

    heat must be available at part-load operating conditions to add heat to the cool,

    dry supply air. On the other hand, when using a desiccant-based dehumidifier,

    the adsorption process heats the supply air; a chiller or some other source ofcooling must be available at all load conditions to remove heat from the warm,

    dry supply air.

    Some central system controls actually reset supply air temperature upward at

    sensible part-load conditions, often resulting in very poor control of space relative

    humidity. Warm supply air contains more moisture than cold supply air. It cannot

    lower average space relative humidity nearly as well as supply air at design

    temperature. Especially in cooling climates, be sure that supply-air-temperature-

    reset schemes include high-humidity override techniques (return-air humidity

    sensing, for instance) to limit the amount of reset operation.

    Unoccupied ControlDesign and operate to keep indoor spaces dry at all times, not just during

    occupied periods. Monitor building humidity during weekend and night setback

    cycles, and automatically operate the dehumidification system to maintain space

    humidity below 60% RH. Unoccupied dehumidification helps limit microbial

    growth and dust mite populations. (Although the people leave the building on

    weekends, the microorganisms do not!) It also helps avoid long dehumidification

    pull-down times after the unoccupied period. Indoor relative humidity conditions

    return to normal quickly. Carpet, furniture and other porous materials do not

    store moisture during unoccupied hours if low vapor pressure is maintained.

    Unoccupied dehumidification is particularly important for schools in hot, humid

    climates. When the children leave the building at 3:00 p.m., significant water

    vapor can enter the space via door-opening infiltration. If the dehumidification

    system turns off at 3:00 p.m. too, space dew point rises and unplanned

    condensation can easily occur. Allow continued dehumidification system

    operation after the occupants leave.

    Moisture andOccupied Spaces

  • 7/31/2019 Managing Building Moisture

    30/53

    American Standard Inc. 1998

    SYS-AM-15 25

    System Monitoring

    Modern building control systems can monitor and log both equipment and

    space conditions. Use trend-logging features to monitor changes in space

    humidity, building pressure, outdoor airflow and temperatures throughout the

    system. Observed changes in these variables may be useful when diagnosing

    perceived or potential building problems. For instance, high relative humidity

    might indicate negative building pressurization (a system malfunction),

    deteriorated window or door seals, open loading-dock doors, pipe or roof

    leaks, or other equipment failures.

    SummaryDesign and operate the HVAC system, especially during periods of partial

    sensible cooling load, to maintain indoor relative humidity below 60% RH, i.e.

    pressurize and dehumidify. l

    Moisture andOccupied Spaces

  • 7/31/2019 Managing Building Moisture

    31/53

    American Standard Inc. 1998

    26 SYS-AM-15

    In addition to the building envelope and the occupied spaces, proper design

    and operation of another key building element, the equipment room, must be

    considered.

    Many building designers place the building HVAC components together in a

    mechanical equipment room. Some equipment rooms include only chillers,

    others include only air handling units, while still others include chillers, air

    handlers and a variety of other equipment. Regardless of equipment-room

    contents, improper design related to moisture can result in many costly

    problems.

    Equipment rusts, wood rots, insulation deteriorates, water pools on the floor and

    may invade other parts of the building. Microorganisms bloom, resulting in odors,irritants and further deterioration of materials. To avoid or at least minimize these

    problems, as with the envelope and the occupied spaces, certain basic design

    principles apply.

    Minimize Moisture SourcesDo not allow rain or snow to enter the equipment room. Minimize open water. Do

    not allow condensate from air handlers to run freely across the floor. Fix leaky

    pipes and valves. Design the equipment room to avoid unplanned condensation

    on cold surfaces.

    Minimize unvented combustion appliances or processes within the equipmentroom; combustion generates water vapor. Also, for all combustion processes

    (vented or unvented), convey makeup air directly from outside to each process

    using ducts; do not use the equipment room as a makeup-air plenum for

    combustion processes. A negative-pressure equipment room leads to unplanned

    condensation.

    Minimize vapor-pressure diffusion into the equipment room by insulating

    perimeter walls and using a low-permeability vapor retarder on the warm side, as

    described for the building envelope.

    Minimize infiltration due to wind and stack effect. Eliminate infiltration due to

    mechanical exhaust (or leaky negative return ducts) by pressurizing the

    equipment room, preferably using dry supply air. Especially in hot, humidclimates, outdoor-air dew point can be extremely highdo not allow untreated

    outdoor air to enter the equipment room, either accidentally or by design.

    Equipment-Room Moisture

  • 7/31/2019 Managing Building Moisture

    32/53

    American Standard Inc. 1998

    SYS-AM-15 27

    Prevent Unplanned CondensationCondensation occurs whenever air dew point exceeds surface temperature.

    Design and operate the equipment as appropriate to raise exposed surface

    temperatures and/or lower equipment-room dew point. Remember, the cold

    surface location within the equipment room is irrelevantan air handler with a

    warm, dry exterior, for example, may generate significant unplanned

    condensation on interior airstream surfaces.

    Raise Surface Temperature and Vapor Seal

    Cold surfaces abound within the equipment room. Some can be heated, but

    most must be insulated and vapor-sealed.

    For instance, condensate drain pipes, chilled water pipes (both leaving and

    return), even condenser water pipes may contain liquid at temperatures well

    below room dew point. These pipes must be insulated and sealed with a vapor

    retarder on the warm side. Water valves and other associated devices must also

    be insulated and vapor-sealed. Insulation alone raises surface temperature, but

    not interior temperaturesat some location within the insulation, a cold surface

    still exists. To prevent condensation inside the insulation, vapor-pressure

    diffusion into the insulation must be minimized using a vapor retarder.

    Most equipment-room surfaces can be insulated and vapor-sealed adequately,

    but some must be heated above dew point. The sections below discuss specific

    solutions.

    Lower Equipment-Room Dew Point

    Process-side temperatures within the equipment room cannot be changed.

    Supply-air, chilled-water and drain-line condensate temperatures all depend on

    loads and design criteria, not condensation prevention. To avoid unplanned

    condensation throughout the equipment room, lower the equipment-room dew

    point. Insulation can then raise room-side surface temperature above the

    equipment-room dew point and vapor retarders can keep most moisture away

    from cold surfaces within the insulation.

    Some insulation materials inherently form an effective vapor barrier without the

    addition of a separate vapor-retarding material. One square foot of chillerinsulation, for instance, with a permeance factor of 0.30 gr/h ft2 in. Hg, allows

    less than 0.23 gr/h to diffuse into the insulation more than adequate vapor

    diffusion protection, provided the joints are well-sealed.

    Equipment-Room Moisture

  • 7/31/2019 Managing Building Moisture

    33/53

    American Standard Inc. 1998

    28 SYS-AM-15

    Figure 13 Pressurize to Avoid Condensation

    Figure 13 shows a cold condensate drain, first in an unconditioned equipment

    room; then in an equipment room pressurized by a return air fan. In the first

    room, open to outdoor air, a very high dew point results in unplanned condensate

    formation on the uninsulated-pipe surface. Simply replacing the moisture-laden

    outdoor air in the space with drier return air lowers dew point in the second room.

    The dew point could have been lowered further using supply air rather than

    return air to pressurize the room.

    Some designers refer to this measure as conditioning the equipment room.However, conditioning usually implies controlling one or more variables to

    maintain a set point. Simply pressurizing the room slightly with either return or

    supply air can lower equipment-room dew point significantly. Both sensible

    temperature and dew point float as supply (or return) air conditions change and

    room loads vary. No variables are directly controlled, so strictly speaking, the

    room is not conditioned. Pressurized more accurately describes an equipment

    room with low dew point. During construction and normal operation, equipment-

    room pressurization solves most moisture problems, including internal

    condensation. (See side-bar.)

    Dehumidify Ventilation AirLets examine dehumidification of ventilation air in more detail. Only two air-dehumidification methods need to be considered: desiccant dehumidification and

    cold-coil dehumidification.

    A desiccant dehumidification unit (Figure 14) incorporates a desiccant material

    mounted on a rotating wheel. Warm, moist outdoor air enters the rotating wheel.

    Some portion of the water vapor adsorbs onto the desiccant surface. As the

    rotating wheel turns, the moisture-laden portion moves into the regeneration air

    Equipment-Room Moisture

    During Construction

    Air handlers are often operated at

    full capacity (wild coils with

    very cold, chilled water) providing

    cooling and dehumidification for

    the construction crew. If the

    equipment room is open to

    outside, high-dew-point

    conditions, and chilled water is

    supplied at low-surface, design

    temperatures; wet insulation,

    internal flooding and generalwater damage due to unwanted

    condensation often results.

    If at all possible, close the

    equipment-room envelope prior to

    operating the air handler

    properly pressurizing the room to

    lower its dew point. Reset the

    chilled-water temperature as high

    as possible during construction

    (i.e., 55F) to raise equipment-

    room surface tempertures.

    Dont allow construction-phase

    operation to ruin a well-designed

    equipment room before the

    building is even finished.

  • 7/31/2019 Managing Building Moisture

    34/53

    American Standard Inc. 1998

    SYS-AM-15 29

    Equipment-Room Moisture

    stream. Hot air (either heated outdoor air or heated return air) drives the

    adsorbed water vapor from the desiccant material, drying or regenerating it.

    The wheel rotates the regenerated material into the outdoor air stream again and

    the process repeats. Since the hot desiccant raises the temperature of the

    leaving dehumidified outdoor air, it must be cooled (usually by mechanical and/or

    evaporative cooling) before it can be delivered to the occupied spaces.

    Figure 14 Desiccant Dehumidification

    A cold coil dehumidifies simply by presenting a cold surface for controlled

    condensation. As warm, moist outdoor air (or a mixture of outdoor and

    recirculated return air) passes through the coil, water vapor condenses on the

    cold coil surface and flows down to the drain pan. Since the cold coil removes

    heat, the dry supply air may be too cold for the space sensible load; the air must

    be tempered (reheated) to avoid overcooling the occupied spaces.

    When using direct refrigerant expansion (DX) to cool the dehumidifying coil,

    simple sensible-temperature-based cycling for capacity control may lead to

    humidity control problems. Coil cycling can lead to wide variations in supply-air

    dew point and loss of dehumidifying capacity during the off cycle. DX

    dehumidifiers should use a thermostat to control sensible temperature (by

    cycling coil capacity or by modulating reheat capacity) and a humidistat toactivate full coil capacity when required for proper dehumidification.

    Some designers dehumidify the outdoor air before it mixes with recirculated

    return air in the air-handler mixing section, removing only ventilation moisture.

    Other designers dehumidify mixed air, removing both ventilation and internally

    generated moisture. Either way, the outdoor moisture load must be removed

    before delivering the ventilation air to the space.

  • 7/31/2019 Managing Building Moisture

    35/53

    American Standard Inc. 1998

    30 SYS-AM-15

    Equipment-Room Design ExamplesEquipment-room designs vary widely. Depending on climate and operation,

    design decisions may differ. The following examples illustrate poor, better, and

    best design practices, especially for equipment rooms in predominantly cooling

    climates.

    A Poor Design: Negative Pressurization

    Equipment rooms designed to operate at a negative pressure with respect to

    outdoor pressure (unconditioned rooms) commonly encounter unplanned

    condensation on all cold surfaces. As a result of infiltration, the dew point simply

    rises too high. Avoid designing negative-pressure equipment rooms that use theroom as an intake plenum for outdoor air. Also, avoid other poor, though

    common, design practices illustrated in Figure 15.

    Key Elements Of Poor Design

    Liquid-Water Sources

    D Rain water easily penetrates the outdoor air louver.

    D No trapping allows flooding inside the air handler and leakage onto the floor.

    D Condensate from drain pan runs across the floor.

    Water-Vapor Sources

    D Exterior walls with no vapor retarder allow unimpeded flow of water vapor

    from outside.

    D Without an outdoor air duct, the equipment room operates at a negative

    pressure to induce ventilation airflow, resulting in significant infiltration.

    D By design, outdoor air for ventilation enters the equipment room through

    louvers in the equipment-room wall, bringing moist outdoor air with it.

    Unplanned Condensation

    D Condensate forms on uninsulated pipes and puddles on the floor.

    D Condensate forms on the air handler exterior.

    D Condensate forms on the interior insulation of poorly-sealed supply ducts.

    D Condensate forms inside the air handler.

    Unplanned condensation occurs in a negatively pressurized equipment room

    despite surface insulation and sealing. Any small air leak in air-handling units or

    ducts, or any small break in piping insulation or vapor retarders, results in

    condensate. Do not design equipment rooms that can become negatively

    pressurized.

    Equipment-Room Moisture

  • 7/31/2019 Managing Building Moisture

    36/53

    American Standard Inc. 1998

    SYS-AM-15 31

    Equipment-Room Moisture

    Figure 15 Poor Equipment-Room Design

  • 7/31/2019 Managing Building Moisture

    37/53

    American Standard Inc. 1998

    32 SYS-AM-15

    A Better Design: Positive Return-Air Pressurization

    Pressurizing the equipment room goes a long way toward reducing unplanned

    condensation. One pressurization technique uses return air dumped into the

    equipment room by a return fan. This, of course, can only be accomplished in

    systems that use a return-air fan.

    The dew point in such an equipment room roughly matches the return-air dew

    point. Some designers refer to this design as a conditioned equipment room,

    since air returns from conditioned spaces. This level of moisture effectively

    avoids unplanned condensation on external surfaces. However, local moisture

    sources may still elevate equipment-room dew point to an unacceptably high

    level during many operating hours. Although the better design illustrated in

    Figure 16 resolves some problems, it fails to address others.

    Key Elements Of Better Design

    Diminished Liquid-Water Sources

    C A rain hood protects the intake from rain intrusion.

    C No open water tanks in the room.

    D Poor trapping allows flooding inside the air handler and leakage onto the floor.

    C Condensate drain-line guides condensate to a sanitary drain.

    Diminished Water-Vapor Sources

    D Exterior walls with no vapor retarder allow unimpeded flow of water vapor

    from outside.C Return air fan assures positive room pressure (return-air positive), to

    eliminate the infiltration moisture load, but return-air moisture content

    contributes to the equipment-room dew point.

    C Ventilation air, ducted directly to unit, adds no equipment-room moisture load.

    Unplanned Condensation

    C Well-insulated, sealed pipes prevent condensation.

    C Well-insulated air handler limits surface condensation.

    C Well-sealed supply ducts prevent condensation inside insulation.

    D Condensate still forms inside the air handler since high-dew-point air can leak

    into the unit.

    When using powered exhaust or relief fans in the equipment room, duct returnair to the air handler and use the best design approach described below. Do not

    use the equipment room a negative return plenum. Again, an equipment room

    under negative pressure can be subject to extensive infiltration of untreated,

    moist outdoor air. Using the return fan to pressurize an equipment room

    eliminates outdoor-air infiltration.

    Equipment-Room Moisture

  • 7/31/2019 Managing Building Moisture

    38/53

    American Standard Inc. 1998

    SYS-AM-15 33

    Equipment-Room Moisture

    Figure 16 Better Equipment-Room Design

  • 7/31/2019 Managing Building Moisture

    39/53

    American Standard Inc. 1998

    34 SYS-AM-15

    Best Design: Positive Supply-Air Pressurization

    An equipment room pressurized with supply air (supply-air positive) offers the

    best solution. Although conditioned by cool, dry supply air, equipment-room

    temperature can float. No controls (thermostats or humidistats) are needed to

    modulate the pressurizing supply airflow. Dry airflow into the equipment room

    (see side-bar) limits infiltration and ventilation moisture load by simply filling the

    space with low-dew-point air. Therefore, this design avoids the problems of

    unplanned condensate formation.

    Key Elements Of Best Design

    No Liquid-Water SourcesC A rain hood protects the intake from rain intrusion.

    C Proper trapping prevents internal flooding.

    C Condensate drain line guides condensate to a sanitary floor drain.

    Minimum Water-Vapor Sources

    C A vapor retarder on the warm side of exterior walls minimizes moisture load

    due to vapor-pressure diffusion from outside.

    C Low-volume supply airflow assures positive room pressure (supply air

    positive), eliminating infiltration moisture load and decreasing equipment-

    room dew point.

    C Ventilation air ducted to the unit adds no moisture load to the equipment room.

    No Unplanned Condensation

    C Well-insulated, sealed pipes prevent condensation.

    C Well-insulated air handler prevents surface condensation.

    C Well-sealed supply ducts prevent condensation inside the insulation.

    C A low equipment-room dew point combined with well-sealed air-handler joints

    prevent condensate formation inside the air handler.

    The supply airflow needed to pressurize the equipment room varies greatly. Very

    low airflow may be enough to maintain sufficient static pressure (0.10 to 0.20

    in. wc), especially if good, exterior wall construction limits exfiltration through

    cracks and openings.

    Some designers actually control temperature and/or humidity to truly condition

    interior equipment rooms. However, environmentally controlled equipment rooms

    must be designed carefully. Avoid sensible-temperature control schemes that

    allow dew point to float. Maintaining sensible temperature cannot assure proper

    dew-point control. Also, remember that a low dry-bulb temperature in the

    Equipment-Room Moisture

    How Much Air?

    Based on wall construction, the

    volume of dry supply air needed

    to pressurize an equipment room

    can be estimated using Figure 8.

    Assuming that an average wall

    and a positive pressure of 0.10

    in. wg negates wind effects, we

    can estimate leakage [Q = 0.66

    (0.10)0.65= 0.15 cfm/ft2]. If the

    exterior wall area is 1800 ft2

    , theleakage flow rate is only 270 cfm.

    Of course, depending upon

    equipment room heat sources,

    high dry bulb temperatures may

    result. In other words, additional

    airflow may be needed to lower

    equipment room dry bulb

    temperatures to an acceptable

    value.

  • 7/31/2019 Managing Building Moisture

    40/53

    American Standard Inc. 1998

    SYS-AM-15 35

    equipment room means lower surface temperatures. Ideally, a controlled

    equipment room would sense and maintain dew point, while maintaining sensible

    temperature below a high limit.

    SummaryEquipment rooms need special design and operational attention to avoid

    problems due to unplanned condensate. Do not use the equipment room as an

    outdoor air plenum. Duct outdoor air directly to the air handler.

    Consider pressurizing the equipment room with return air if the system uses a

    return fan. Better yet, consider pressurizing and dehumidifying the equipmentroom with a small volume of supply air. The simplest, most effective method to

    resolve all equipment-room condensate problems is to pressurize the equipment

    room with supply air. l

    Equipment-Room Moisture

    Figure 17 Best Equipment-Room Design

  • 7/31/2019 Managing Building Moisture

    41/53

    American Standard Inc. 1998

    36 SYS-AM-15

    HVAC equipment, both water chillers and air-handling units, must be selected,

    applied and operated properly with regard to moisture. First, lets discuss the

    water chillers. An operating water chiller develops cold surfaces. Uninsulated or

    insulated-but-unsealed chiller surfaces exposed to moist air lead to unplanned

    condensate. Chiller condensation problems can be attacked on three fronts:

    surface heating, surface insulating and sealing, and lowering equipment-room

    dew point.

    The dew point in a ventilated, unconditioned mechanical room cannot be

    decreased; therefore, cold surfaces must be insulated or heated. Some cold

    surfaces, valve handles for instance, cannot be insulated. Increased air motion

    may add sufficient heat by convection to raise the temperature of a cold chiller

    surface above surrounding dew point (see Figure 18). In some cases air motionalone is insufficient for very cold spots. A small heater can be used to raise

    surface temperature above ambient dew point and prevent condensate

    formation.

    Cold chiller surfaces are often insulated to increase efficiency. Insulation can

    adequately raise exposed surface temperatures above the dew point of the

    equipment room, but merely adding insulation between warm, moist air and a

    cold surface cannot prevent condensation.

    If significant moisture penetrates (permeates) the insulation, it eventually

    encounters a surface temperature lower than dew point. Without a vapor

    retarder, moisture permeates the insulation until it encounters a cold enough

    temperature, then condenses. The insulation must be sealed with a low-permeability vapor retarder applied on the warm side. Alternatively, insulation

    with low permeability (0.30 gr/h ft2 in. Hg), if well sealed, eliminates harmful

    condensation within the insulation.

    Of course, lowering equipment-room dew point significantly reduces all

    unplanned chiller condensation. If possible, pressurize the equipment room with

    supply air. l

    Figure 18 Raise Surface Temperature

    Moisture and Chillers

  • 7/31/2019 Managing Building Moisture

    42/53

  • 7/31/2019 Managing Building Moisture

    43/53

    American Standard Inc. 1998

    38 SYS-AM-15

    To prevent carryover, do not exceed the maximum allowable coil-face velocity.

    Coil geometry (fin type, shape and spacing) and allowable face velocity

    determine required drain pan length. Below the velocity limit, water droplets on

    the coil surface flow down the coil into the drain panthe air stream can blow

    droplets from the coil, but it cannot carry them beyond the drain pan. Above the

    velocity limit, however, the air stream carries water droplets beyond the drain pan

    and deposits it on downstream air-handler and duct surfaces.

    Specify coil size to assure that air stream velocity falls below the maximum

    allowable coil face velocity. Clean the coils regularly: dirty coils cause local high-

    velocity jets and high-velocity jets lead to carryover beyond the drain pan. Re-

    evaluate coil performance if airflow requirements change. Increased airflow

    across the coil face may increase face velocity above the carryover limit. Consultmanufacturers literature for maximum coil-face velocity limits.

    Slope to Prevent Standing Water

    Collected condensate must not be allowed to accumulate in the air-handler drain

    pan. Standing water results in microbial growth (microbial slime). The drain pan

    must be properly sloped and properly connected to a drain system to assure

    speedy, complete drainage with the fan on or off.

    Design or specify drain pans that slope in two planes, as shown in Figure 20. A

    flat pan retains water. A single-plane sloped pan with one drain connection limits

    the volume of water retained; some water hangs up in the low corners. A dual-

    plane sloped pan assures that all water drains out. Be sure to place the drain

    connection at lowest point of the pan. Even a very small slope assures complete

    drainage when the pan slopes in two planes. Remember, proper drain pan slope

    depends not only on design but also on installation: the unit must be level. Be

    sure to install the air-handling unit according to the manufacturers

    recommended instructions and within the tolerance specified for levelness.

    Moisture andAir-Handling Units

    Figure 20 Drain Pan Designs

  • 7/31/2019 Managing Building Moisture

    44/53

    American Standard Inc. 1998

    SYS-AM-15 39

    Drain to Prevent Flooding

    If collected condensate cannot drain through the drain connection, it spills over

    the top of the drain pan and floods the air-handling unit and duct system.

    Microbial growth as well as equipment and building damage can result from

    internal flooding. Proper condensate drainage depends on drain-pan slope,

    drain-connection size and maintenance, and, as explained below, drain-seal

    design and maintenance.

    Condensate forms at a high rate when very moist air enters the coil (as much as

    5 gpm on a 100-ft2 coil). To assure speedy drainage without drain-pan overflow,

    do not reduce the drain-pipe diameter to be smaller than the drain connection

    provided by the manufacturer. The equipment manufacturer selects the drain

    connection size to accommodate the maximum condensate flow at extreme

    conditions. Reducing its diameter may result in slower drainage and drain-pan

    overflow.

    Wet coils help clean particles from the air stream. Condensate flow keeps the

    coils relatively clean, but dirt accumulates in the drain pan. Accumulated dirt

    increases the likelihood of restricted or blocked condensate flow and subsequent

    flooding. Be sure to inspect drain pans on a regular basis and clean if necessary.

    Drain-Line SealsAfter collecting in the drain pan, condensate exits the air handler via the drain

    connection, passes through a drain seal, then follows the drain line to a sanitaryfloor drain. Faulty drain seals result in more moisture-related problems than any

    other air handler element. Improper design, installation or maintenance of the

    drain seal can cause water droplet carryover or internal flooding within the air-

    handling unit. Although some designers use other sealing devices, simple

    P-traps seal the vast majority of air-handler drain pans.

    Moisture andAir-Handling Units

  • 7/31/2019 Managing Building Moisture

    45/53

    American Standard Inc. 1998

    40 SYS-AM-15

    Figure 21 Blow-Thru Trapping

    Blow-thru designs positively pressurize the drain-pan surface with respect to the

    equipment room (Figure 21). Supply air pushes condensate through the trap,

    eliminating any concern for water droplet carryover due to trap operation, but

    raising a concern for maintaining the internal-to-external air seal. Without an air

    seal, supply air can flow out of the unit into the equipment room, creating a small

    supply-air leak. Inadequate trap depth (D) allows casing pressure to force all

    water out of the trap destroying the seal.

    Specify a trap depth no less than the casing static pressure (CP) plus a safety

    margin to allow for final, as-installed balancing (D = d + CP + 1 in. wg). Specify a

    total trap height (T) no less than the trap depth plus an installation safety margin(T = D + 1 in. wg).

    Moisture andAir-Handling Units

    Figure 22 Draw-Thru Trapping

  • 7/31/2019 Managing Building Moisture

    46/53

    American Standard Inc. 1998

    SYS-AM-15 41

    Draw-thru designs negatively pressurize the drain-pan surface (Figure 22).

    Equipment-room air pushes condensate through the trap toward the drain pan.

    With insufficient total trap height (T), the trap contains adequate water to

    maintain the air seal but not enough to allow water flow. Consequently, the drain

    pan overflows and floods the inside of the air handler. With insufficient trap depth

    (D), equipment-room pressure pushes trap water into the drain pan. High velocity

    air flows into the drain pan throwing water droplets into the supply air stream,

    causing carryover, due to trap spitting or geysering. Also, the high-velocity

    airflow prevents water flow through the drain opening, causing drain-pan overflow

    and internal flooding.

    Each time the draw-thru fan starts, the trap must be primed (contain water).

    Without a water seal, a properly designed trap operates as though it hasinsufficient trap depth: it spits and causes internal flooding. Specify the trap head

    (H) no less than the negative casing pressure (CP) plus a 1 in. wg safety margin

    (H= 1+CP). Specify trap depth (D) no less than half the trap head (D = H + d).

    Total trap height (T) is the sum of installed head and depth (T = H+D). Inspect

    traps regularly and prime when necessary, especially just before the cooling

    season begins.

    Moisture andAir-Handling Units

    Plan for proper trapping: the unit must be mounted high enough above the floor

    to allow for the recommended total trap height (T) and trap depth (D). Countless

    air-handler installations include crudely chopped holes in concrete floors; proper

    trap dimensions were considered as an afterthought, after flooding or carryover

    problems resulted in service expense and building damage. Follow the trap

    design guidelines discussed above.

    Remember, even a well-designed trap, if plugged, causes drain-pan overflow and

    internal flooding. Inspect traps regularly. Clean and prime if necessary. Do not

    gang drain pans at different surface pressures on the same trap. Use shutoff

    values, not traps, to seal maintenance-only drains.

    External CondensationSupply air downstream of the cooling coil and in the supply ducts can be very

    cold. The coil itself can be even colder; chilled-water temperature may be 45F or

    lower. Therefore, external air-handler surfaces and supply-duct surface

    temperatures may also be very low unless adequately insulated. If high dewpoint air can contact these cold surfaces, unplanned external condensation

    (sweating) occurs, leading to equipment-room flooding, unit discoloration and

    damage (corrosion and deterioration), possible building damage, and increased

    potential for microbial growth.

  • 7/31/2019 Managing Building Moisture

    47/53

    American Standard Inc. 1998

    42 SYS-AM-15

    Seal Penetrations and Joints

    A supply air leak from the air-handling unit or supply duct causes a very cold

    local surface, a cold spot. In a high-dew-point equipment room (negative

    pressure, unconditioned), water vapor from the air condenses readily at the cold

    spot. Unplanned, liquid water results. Design the pressurized sections of the air

    handler and the supply ducts to minimize leakage of cold supply air.

    Each penetration of the air handler represents a potential supply air leak. Specify

    airtight seals (Figure 23) at all air handler penetration points, including pipe

    penetrations at the coils (both heating and cooling), unused maintenance-only

    drain openings, and any penetrations for electrical wiring.

    Figure 23 Seal Pipe Penetrations

    All air-handling units include access doors and panels. Poorly sealed doors and

    panels result in supply air leakage. Some units use individual sections, joined at

    the factory or in the field, to form the air handler. Each joint downstream of the

    fan represents a potential supply air leak.

    Gasket all access panels, door openings and inspection windows in positive-

    pressure sections. Seal all joints between sections (Figure 24). Note that draw-

    thru air handlers usually include fewer pressurized sections than blow-thru

    configurations, so fewer joints need sea