Low Vacuum in Condenser
-
Upload
charu-chhabra -
Category
Documents
-
view
220 -
download
0
Transcript of Low Vacuum in Condenser
-
7/27/2019 Low Vacuum in Condenser
1/6
SUBJECT : LOW VACUUM IN CONDENSER
PROJECT : NORTH CHENNAI/ UNIT-2
PROBLEM :
Vacuum gradually worsened at above site, from 0.892 Ksc at fullload to 0.763 Ksc (150 MW) over 30 days from 17.05.03 to
19.06.03. All efforts, including water tightness test and condenser
tube cleaning was ineffective. A summary of relevant datasubmitted for study is as tabulated below:
Time Date LoadMW
Vacuum
ksc
HotWell
CWInlet
temp
(L)/(R)
CWOutlet
temp
(L)/(R)
CWF Bay
level
(M)
Remarks
1300 17.05.03 210 -0.892 49 32 32 41 40 8.4
1100 22.05.03 210 -0.863 54 34 34 44 43 8.0
1400 27.05.03 210 -0.800 58 35 35 45 45 8.0
1100 02.06.03 200 -0.799 60 35 35 45 44 7.5
0900 07.06.03 100 -0.791 60 36 36 42 42 6.6
0400 12.06.03 150 -0.78 60 37 37 43 43 6.21800 19.06.03 150 -0.763 59 37 37 45 44 6.5
1000 22.06.03 194 -0.759 63 35 35 46 45 6.2
1000 27.06.03 183 -0.763 62 37 37 47 46 6.7
ONEvac.
pump in
service(Unit 2
only)
1600 27.06.03 155 -0.762 64.8 38 38 47 46 6.7 TWO
vac
pumps
Air exhausted from vacuum pumps was exceeding 150 Kg/hr. (Second
vacuum pump was installed for unit 1. The air piping was extended to
unit-2 from unit-1.)
-
7/27/2019 Low Vacuum in Condenser
2/6
ANALYSIS
It was decided to check with Helium leak detector. Helium leak
detection instrument was used, From 22.07.03 to 24.07.03, tocheck the following:
? LP Cylinder : Bursting diaphragms, glands of LP seals,parting plane, Neck weld, LP BP downstream piping.
? Extraction piping: LPH 1 and LPH 2 piping and shell.?
Hot well stand pipes & CEP suction and impulse lines? Vacuum pump and main ejector? Flash tanks and drain coolerReadings were obtained at LP parting plane (corner), ejector air inlet
valve bonnet, ejector drain isolation flange, condenser manhole and
two bursting diaphragms. However, ingress was not high.
Condenser vacuum & CW inlet and outlet sea water systems
were thermally mapped (Fig. 1 shows condenser, Fig.2 shows vacuum
pumps) using a laser non-contact thermometer. From this,
we could see that mixing of inlet and outlet seawater was
taking place -- poor condenser performance due to reduced flow
through CW tubes. (Observe how temp. of flow reversal side is
higher than outlet). Also observe that temp. of air to vacuum
-
7/27/2019 Low Vacuum in Condenser
3/6
pump is getting sub-cooled only in one half. (In Ennore TPS unit 3,
similar behavior was observed. Inspection had revealed heavy
corrosion of parting plate of inlet/outlet water box. After
correction, in Ennore vacuum went to full value and exhaust temp
came down to 45 Deg C at low loads.)
CONCLUSION
TNEB was advised to make temporary sealing with suitable agent,
(M-Seal) etc at identified air ingress points till unit could be shut
down. To find a long-term solution they were advised:
1.To service the components showing air ingress and makeairtight.
2.Reduce the seal water temp of vacuum pump.3.Inspect and confirm seawater CW mixing at parting plate of
inlet/outlet water box. Make necessary corrections to stop
this in unit 2 and other units of North Chennai.
4.Monitor the thermal and flow behavior (DT, TTD and CWwaterbox temperatures; DP and flow across each waterbox)
of all condensers and water boxes of the running units.
5.Make provision for sacrificial anode in CW system to preventcorrosion due to seawater.
-
7/27/2019 Low Vacuum in Condenser
4/6
Note:
To understand condenser performance DT, TTD, DP and flow must
be watched:
DT = CW outlet temp CW inlet temp (difference in
temperature between CW inlet and outlet should be about 8-10 deg
C at full load of 210 MW. More means less CW flow, less could
mean mixing: confirm this by seeing TTD values also.)
TTD = Hot well temp - CW outlet temp
(TTD values of 5-6 deg C are normal. Values above 10 indicate
worsening condenser performance. 20 or more means very poor
heat exchange possibly due to fouling of condenser tubes or mixing
of inlet and outlet CW.)
DP and FLOW: Higher motor currents in axial flow CW pumps could
mean restrictions in discharge flow due to choking in debris filter,
and higher DP across CW tubes may mean choking in the tubes.
-
7/27/2019 Low Vacuum in Condenser
5/6
-
7/27/2019 Low Vacuum in Condenser
6/6