Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

20
Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Transcript of Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Page 1: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Long Line Modeling IssuesRev. 2.2

SRWG Meeting

March 9, 2011

R. Peter Mackin, P.E.

Page 2: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

• Basic Transmission Line Models • (from Stevenson, Elements of Power System

Analysis, 4th Edition)

• Short Transmission Line:– Up to 50 miles

Background

Z = R + jX

Page 3: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

• Medium-length Transmission Line:– 50 miles to 150 miles

Background

Z = R + jXY2

Y2

Page 4: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

• Long Transmission Line:– Greater than 150 miles– Lumped parameters cannot be used

accurately to represent these lines– Accurate representation requires the use of

hyperbolic functions

Background

Y tanh(γl/2)2 γl/2

Y’2

=

sinh(γl) γl

Z’ = ZY’2

Page 5: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

The Issue

• For long transmission lines (greater than say 150 miles), using the per mile impedance times the line length in miles can result in an inaccurate representation of the transmission line.

• For these long lines, it is better to use the “long line” equations that involve hyperbolic functions to calculate the line impedance.

• A couple of examples that illustrate the problem are given below.

Page 6: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #1

• Assume a new 500 kV line with the following parameters– 200 miles long– Horizontal conductor configuration

• 32’ phase spacing, 35’ minimum clearance to ground

• 3 – 1780 ACSR 84/19 “Chukar” conductors per phase

• 18” triangular bundle

Page 7: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #1• The table below shows the impedances for this line calculated using either

the PowerWorld Transmission Line Parameter Calculator (TLPC) ver. 1.0 or Aspen Line Constants.

• The PowerWorld TLPC uses “Long Line” equations to calculate more accurate values of impedance and admittance for longer lines.

• Aspen Line Constants calculates a “per mile” impedance and then multiplies this value by the line length in miles to determine the line impedance and admittance.

Source Line Length (mi.) Calculation R (p.u.) X (p.u.) B (p.u.) Comment

PowerWorld TLPC 1.0 200 Long Line Parameters 0.001540 0.041579 3.953540Aspen Line Constants 200 Per Mile Line Parameters 0.001468 0.042723 4.082248

PowerWorld TLPC 1.0 120 Long Line Parameters 0.000958 0.025397 2.350851PowerWorld TLPC 1.0 80 Long Line Parameters 0.000646 0.017026 1.562865

Total 0.001604 0.042423 3.913716Totals are NOT equal to 200 mile long line above

Aspen Line Constants 120 Per Mile Line Parameters 0.000881 0.025634 2.449349Aspen Line Constants 80 Per Mile Line Parameters 0.000587 0.017089 1.632899

Total 0.001468 0.042723 4.082248Totals are equal to 200 mile long line above

Page 8: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #1• The example below shows the effects of the different impedance

assumptions on the flow on this hypothetical line.• The first power flow plot shows the flows on the line when using the

“long line” impedance and admittance.• The second power flow plot shows the flows on the line in the first

plot when a new bus is added 60% of the total line distance from TESTBUS1.

• The third power flow plot shows the flows on the line when using inaccurate “per mile” impedance and admittance method used by Aspen Line Constants.

• The fourth power flow plot shows the flows on the line in the third plot when a new bus is added 60% of the total line distance from TESTBUS1.

Page 9: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #1

• This power flow plot shows the flows on the line when using the “long line” impedance and admittance.

Long Line Parameters

Parallel Paths

Page 10: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

• This power flow plot shows the flows on the line in the first plot when a new bus is added 60% of the total line distance from TESTBUS1.

Long Line Parameters

Example #1

Parallel Paths

Page 11: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Per Mile Line Parameters

• This power flow plot shows the flows on the line when using inaccurate “per mile” impedance and admittance method used by Aspen Line Constants.

Example #1

Parallel Paths

Page 12: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

• This power flow plot shows the flows on the line in the third plot when a new bus is added 60% of the total line distance from TESTBUS1.

Per Mile Line Parameters

Example #1

Parallel Paths

Page 13: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #1 Conclusions

• As shown, “long line” impedance and admittance values provide the most accurate results for long lines. This conclusion can be observed by noting that the line flows before and after adding an intermediate bus to a line are almost exactly the same.

• Using “per mile” impedance and admittance values are not as accurate. This fact is demonstrated by the addition of an intermediate bus to the line using these parameters. As shown in the third and fourth power flow plots, the flow on the line is not the same in both cases (even though it should be).

Page 14: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #2• The first power flow plot shows the line flows on a 200 mile long 500 kV

line that is modeled as 5 series pi sections of 40 miles each.• The second power flow plot shows the line flows on a 200 mile long 500

kV line that is correctly modeled as 1 long line compensated segment (i.e., using PowerWorld Transcalc).

• The third power flow plot shows the line flows on a 200 mile long 500 kV line modeled as 1 Pi segment (incorrectly modeled using per mile impedances times line length in miles).

• The fourth power flow plot shows the line flows on a 200 mile long 500 kV line that was originally modeled using long line compensated impedances (Example #2, Plot #2), but is now split into two equal segments without recalculating the segment impedances. (This example is different than Example #1 in that the long line compensated impedances were simply divided in half. In example #1 the long line impedances were recalculated when adding the intermediate bus.)

Page 15: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

200 Miles of 500 kV line modeled as 5

series Pi sections of 40 Miles each

The first power flow plot shows the line flows on a 200 mile long 500 kV line that is modeled as 5 series pi sections of 40 miles each.

Parallel Paths

Page 16: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

200 Miles of 500 kV line modeled as 1

long-line compensated

segment

The second power flow plot shows the line flows on a 200 mile long 500 kV line that is correctly modeled as 1 long line compensated segment (i.e., using PowerWorld Transcalc).

Parallel Paths

Page 17: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

200 Miles of 500 kV line modeled as 1 Pi segment (Incorrectly

Modeled)

The third power flow plot shows the line flows on a 200 mile long 500 kV line modeled as 1 Pi segment (incorrectly modeled using per mile impedances times line length in miles).

Parallel Paths

Page 18: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

200 Miles of 500 kV line split into two segments without

recalculating the long line impedances

The fourth power flow plot shows the line flows on a 200 mile long 500 kV line that was originally modeled using long line compensated impedances (Example #2, Plot #2), but is now split into two equal segments without recalculating the segment impedances. (This example is different than Example #1 in that the long line compensated impedances were simply divided in half. In example #1 the long line impedances were recalculated when adding the intermediate bus.)

Parallel Paths

Page 19: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Example #2 Conclusions• GE PSLF properly corrects impedances for long lines if the line is

split into multiple short segments (compare Plots #1 and #2).• Incorrectly modeling a long line using per mile impedances times

line length in miles results in slightly different (and incorrect) flows on the modeled line.

• If you add an intermediate bus to a long line, you must recalculate the new line impedances. You cannot just multiply the impedances by the ratio of the distance to the next bus divided by the total line length. This conclusion applies whether the original impedance was calculated using long line compensated impedances or “per mile” impedances.

Page 20: Long Line Modeling Issues Rev. 2.2 SRWG Meeting March 9, 2011 R. Peter Mackin, P.E.

Questions?