LLPD CatalogueLine Lightning Protec on Devices for Medium-Voltage Networks
2017
Streamer Interna onal AGSwiss company based in Chur, Switzerland
Innova onand Solu on oriented
Streamer is a specialist for innova ve solu ons which improve the reliability of medium and high voltage electrical networks. Streamer invests more than 10% of its turnover every year in three different R&D centers:• St. Petersburg, Russia - in coopera on with the State Polytechnical University of St. Petersburg;• Moscow, Russia - for the development of electronic products;• Chur, Switzerland - in coopera on with University of Applied Sciences Rapperswil
The cer fica ons of our products are made in the best laboratories worldwide: CESI, CEPRI and STRI and meet the latest interna onal standards (IEC, GOST).- CESI (ITALY) - STRI (SWEDEN) - CEPRI (PRC)
Product range1. Lightning protec on from 6 to 40 kVA unique lightning protec on solu on for overhead line: Line Lightning Protec on Devices (LLPDs) with EasyQuench (EQ) technology that has been invented and patented by Streamer. More than 1 million of LLPDs have been installed worldwide (Russia, China, Indonesia, Malaysia, Thailand, Brazil, UAE, Iran, Vietnam, Switzerland, Germany etc.).2. Fault Passage Indicators (FPI) A complete range of Fault Passage Indicators (FPI) for overhead lines and underground cables. Thanks to these products, our customers are able to reduce dras cally the outage's me due to transient and permanent faults.Streamer is the only manufacturer having a complete range with mobile devices, pole mounted or conductor mounted solu on.3. Transformer drying solu onTRANSEC is an online drying solu on for oil insulated transformer of all sizes. It can be installed, operated and regenerated while the Transformer is running and opera onal. It pumps the transformer oil con nuously through its cylinders and thereby extract the moisture smoothly from the paper.Due to the robust design and it`s opera on principle, TRANSEC is the most cost-efficient drying solu on for Transformer!
• 20 years of experience.
• 1.2 Million lightning protec on devices installed.
• Installa on in more than 15 countries.
• Tested in CESI, EPRI, STRI, CEPRI.
Key points
Groupe E (Switzerland)SIG (Switzerland)Romande Energie Holding SA (Switzerland)BKW (Switzerland)Repower (Switzerland)LAPP Insulators (Germany)Sicame Group (France)China Southern Power Grid (China)State Grid Corpora on of China (China)Electricity Genera ng Authority of Thailand (Thailand)Tenaga Nasional Berhad (Malaysia)Perusahaan Listrik Negara (Indonesia)VietNam Electricity (Vietnam)
Customers listDagupan Electric (Philippines)Electronet (New Zealand)Saudi Aramco (Saudi Arabia)Federal Electricity & Water Authority (UAE)Dubai Electricity & Water Authority (UAE)Iran Power Genera on and Transmission Company (Iran)Botswana Power Corpora on (Botswana)Rio Grande Energia (Brazil)CPFL Energia (Brazil)Celesc (Brazil)AES Sul (Brazil)PJSC ROSSETI (Russia)LUKOIL (Russia)GAZPROM (Russia)
Tests
2
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
www.streamer-electric.com 3
EasyQuench is a new and unique technology, developed and improved since 1996 by Streamer. Products featuring EasyQuench System, protect overhead lines against direct and indirect lightning strikes. LLPD prevent breakage of conductors, insulators and outages (trips) caused by lightning. According to their opera ng principle, Line Lightning Protec on Devices (LLPDs) do not require ground lead nor ground rod. Therefore, devices work perfectly in areas with high soil resis vity. Overvoltage discharge is ensured through conduc vity of the pole and the cross-arm. Life expectancy is 20 years.
EASYQUENCHTECHNOLOGY
Diagram of discharge ini a on
Diagram of discharge comple on
The EasyQuench principleEasyQuench LLPDs are made of a series of metal electrodes and gaps embedded in a silicon rubber housing.
The lower terminal of the device is connected to the cross arm, while the upper is placed at a certain distance from the conductor. An air gap separates the upper terminal and the line.
When a lightning overvoltage occurs on the line, the air gap is sparked over. While lightning overvoltage is being discharged through the air gap and the device, ensuring protec on of the line, the air gap conduc vity is strongly reduced due to air ioniza on. The device is then directly connected to the line on the upper terminal.
Lightning Protec on Solu ons
In case of the appearance of a follow current (short circuit) it will be quenched in less than half a cycle (<10ms) by the Mul -Chamber System.In fact, follow current arc will be divided into a big amount of small arcs between electrodes. Arcs will heat up air within chambers. Due to air expansion, arcs are elongated and weakened. At follow (alterna ve) current first zero crossing, the arc will ex nguish. A er this quenching opera on, the connec on between the conductor and the earth, through LLPD is finally cut. The voltage and the current on the line are back in normal condi on. No short circuit will be sensed by control relays. No outages will be no ced from consumer side.
Efficiency • Protect sensi ve components• Avoid outages on the line• No grounding to adjust to
Cost saving• No maintenance required• One me investment• 20 years life expectancy
1. Silicon rubbershape2. Intermediateelectrodes
3. Arc quenchingchamber4. Arc5. Plasma jet
SAdC20z SAi20z SAdS15z SAdM35z
4
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Glossary
BFO – Back Flashover – a flashover of phase-to-earth insula onresul ng from a lightning strike to that part of the system whichis normally at earth poten al
IOV – Induced Overvoltage – an overvoltage in the network that is induced by a lightning strike that does not strike directly any part of the network
MPFC – Maximum Prospec ve Fault Current – the highestelectric current which can exist in a par cular electrical system under short-circuitcondi ons without any protec ve or current-limi ng device. It is determinedby the voltage and impedance of the supply system
MOA – Metal-Oxide Arrester – a surge arrester u lizing valveelements fabricated from nonlinear resistance metal-oxide materials
PMT – Pole-Mounted Transformer – A distribu on transformerthat provides the final voltage transforma on in the electric power distribu onsystem, stepping down the voltage used in the distribu on lines to the levelused by the customer, and is located on a pole of an overhead line
LLPD – Line Lightning Protec on Device DLS – Direct Lightning Stroke – a lightning striking a componentof the network such as the conductor, tower or substa on equipment
CFO – Cri cal Flashover Voltage – the amplitude of voltageof a given waveshape that, under specified condi ons, causes flashoverthrough the surrounding medium on 50% of the voltage applica ons
Surge Arrester – a protec ve device for limi ng surge voltageson equipment by discharging or bypassing surge current around the protecteddevice, without any power frequency current flowing to ground, and is capableof repea ng these func ons as repeatedly
IPC – Insulated Piercing Clamp
www.streamer-electric.com 5
Index
SAdS15z SAdC20z
SAiC20z.4W
SAd21z SAdM35z
Accessories
SAi15z/SAi20z
SAdS10zSAdC10z
p. 8
p. 18
p. 14
p. 22
p. 34
p. 44
p. 40
p. 26 p. 30
6
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Selec on Guide LLPD
Sourceof lightning
issuesI D choose SAD.xxx,D-LLPDs includeall benefits of i-LLPDs
MPFC<1,5 kA MPFC<5 kA
SAdM35zSASAi15z SAi20z SAdS15z SAd21zSAdC20z
choose SAI.xxx
Suspension SuspensionCompact
Nosolu on
NO
NOYESYES YES
12 kV – 17.5 kV 17.5 kV – 24 kV
Su
SSAdS10zSAdC10z
SuspensionCompact
1up to 12 kV 26.4 kV – 40.5 kV
Highest voltagefor equipment*
Highest voltagefor equipment*
* according to IEC 60038
12 kV – 17.5 kV 17.5 kV – 24 kV
Nosolu on
NO
www.streamer-electric.com 7
1,5 kA<MPFC<5 kA
Highest voltagefor equipment*
up to 24 kV
SAdC20z.4W
Overall Dimensions1. EQ system2. End fi ng withthe a achment point3. Terminal electrode
Test Cer ficatesLaboratoryTest
High current impulsewithstand CESI (Milan, Italy)
CESI (Milan, Italy)Lightning dischargecapability
CESI (Milan, Italy)Standard lightningimpulse sparkover
CESI (Milan, Italy)Housing impulsewithstand
CESI (Milan, Italy)Temperature cycling,Salt and mist
CESI (Milan, Italy)Vibra ons
Maximumprospec ve faultcurrent
STRI (Witness testin Streamer’slaboratory)
1
2
3
FeaturesIOV protec onPreven on of conductors and insulatorsbreakageDLS endurance
253
205
R8
36
SAi15z/SAi20zLine Lightning Protec onDevice for OverheadLines up to 24 kV
LLPD SAi20z is intended for protec on of overhead lines with nominal voltage up to 24 kV against induced overvoltages and their deleterious consequences
8
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Agai
nst I
ndire
ct Li
ghtn
ing
Installa on1 piece per pole with phase alterna on for ensuring reliable protec on of an overhead line against IOV.LLPD SAi20z must be installed with an air gap between its terminal electrode and conductor clamp. In order to select the proper value of the gap, please refer to the table.
Insulator’sCFO (kV)
SAi20z: Air gap (mm)
6 to 17.5 kV Highestvoltage for equipment
17.5 to 24 kV Highestvoltage for equipment
< 100100110125150180
4045556580
60607590
Contact usContact us Contact us
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
1.5 1.550±10 70±1011038
12050
2.465310
2.465310
02010000.451 visual verifica on per year
17.5 24SAi15z SAi20z
Reference: SAI.020.Z.WW/920
Performance specifica on and characteris cs
SAI.015.Z.WW/920
Agai
nst i
ndire
ct li
ghtn
ing
www.streamer-electric.com 9
PIN insula on (L-BAR cross-arms)Using BPD.38 bracket
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
Using BLD.091 andBTE.113 brackets
10
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
POST / PIN-POST insula on (U-sec on cross-arms)Using BCL.141 bracket
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
Using BPD.23 bracket
M24nut(not included)
MAX permissible thread size is M24!
Agai
nst i
ndire
ct li
ghtn
ing
www.streamer-electric.com 11
TENSION insula onUsing BPD.38 bracket
HRN.0838(for more informa on, please,refer to Electrode pages)
12
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Agai
nst i
ndire
ct li
ghtn
ingUsing BCL.141 bracket
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
TENSION insula on (installa on in jumper)
www.streamer-electric.com 13
115
4
Overall Dimensions
1. Module A with EQ system2. Module B with EQ system3. Insula ng load-bearingframe
4. A achment point5. Terminal electrodewith indicator
423
284
248
SAiC20z.4WLine Lightning Protec onDevice for OverheadLines up to 24 kV
LLPD SAiC20z.4W is intended for protec on of overhead lines with nominal voltage up to 24 kV against induced overvoltages and their deleterious consequences
FeaturesIOV protec onPreven on of conductors and insulatorsbreakageDLS endurance
14
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Performance specifica on and characteris cs
Insulator’sCFO (kV)
SAiC20z.4W: Air gap (mm)
6 to 17 kV Highest voltagefor equipment
18 to 24 kV Highest voltagefor equipment
< 120120140160180200
4045556580
Contact us
60607590
Contact usContact us
Reference: SAI.C20.Z.4W/920
Agai
nst i
ndire
ct li
ghtn
ing
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
570±1016050
2.465310
02010002.51 visual verifica on per year
24
Installa on1 piece per pole with phase alterna on for ensuring reliable protec on of an overhead line against IOV.LLPD SAiC20z.4W must be installed with an air gap between its terminal electrode and conductor clamp. In order to select the proper value of the gap, please refer to the table.
www.streamer-electric.com 15
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029 + EPC.100b. CCi90.4531 + EPC.100c. CCi90.6531 + EPC.100
Possible op ons
PIN / POST insula onUsing BCL.190 bracket
16
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
TENSION insula onUsing BCL.190 bracket
Agai
nst i
ndire
ct li
ghtn
ing
www.streamer-electric.com 17
DLS protec on of overhead power linesPreven on of conductors and insulatorsbreakageDLS endurance
1
4
2
Overall Dimensions
Features
1. EQ system2. Insula ng load-bearingframe
3. Terminal electrode4. A achment point
3SAdC10zLine Lightning Protec onDevice for Overhead Linesup to 24 kV
LLPD SAdC10z is intended for the protec on of overhead lines with the highest voltage for equipment up to 12 kV and high short-circuit currents against direct lightning strikes, back flashovers and induced overvoltages, as well as their deleterious consequences.
278
R223
423
12
18
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Performance specifica on and characteris cs
Reference: SAD.C10.Z.WW/920
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
550±1012028
2.4653010
02010001.11 visual verifica on per year
12
Installa on
3 pieces per pole for ensuring comprehensive protec on of an overhead line against DLS, BFO and IOV.For more details, please refer to Installa on pages.
Overview
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
www.streamer-electric.com 19
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.653
Possible op ons
PIN insula onUsing BPD.38.SP bracket
20
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
(for more informa on, please,refer to Conductor clamp pages)
HRN.0038.WW
Possible op ons
TENSION insula onUsing BPD.38.SP bracket
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
www.streamer-electric.com 21
DLS protec on of overhead power linesPreven on of conductors and insulatorsbreakageDLS endurance
2
43
5
6
1
Overall Dimensions
Features1. EQ system2. Insula ng load-bearingframe3. Terminal electrode4. A achment point
5. Horn electrode6. Air gap7. Auxiliary electrode with one me glass indicator8. Suspension compositeinsulator (not included)
7
8SAdS10zLine Lightning Protec onDevice for OverheadLines up to 24 kV
LLPD SAdS10z is intended for the protec on of overhead lines with the highest voltage for equip-ment up to 12 kV and high short-circuit currents against direct lightning strikes, back flashovers and induced overvolt-ages, as well as their deleterious consequences.
40...60
170.
..22
0
277 451
22
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Agai
nst I
ndire
ct a
nd D
irect
Ligh
tnin
g
Performance specifica on and characteris cs
3 pieces per pole for ensuring comprehensive protec on of an overhead line against DLS, BFO and IOV.For more details, please refer to Installa on pages.
Installa onOverview
Reference: SAD.S10.Z.WW/920
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
550±1012028
2.4653010
02010001.51 visual verifica on per year
12
www.streamer-electric.com 23
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029 + EPC.100b. CCi90.4531 + EPC.100c. CCi90.6531 + EPC.100
Possible op ons
PIN / POST / TENSION insula onUsing BTA.155 bracket
Possible op ons
24
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
PIN / POST / TENSION insula onUsing addi onal cross-arm PCF.800 + bracket BTA.156
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
Possible op ons
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029 + EPC.100b. CCi90.4531 + EPC.100c. CCi90.6531 + EPC.100
Possible op ons
www.streamer-electric.com 25
1
4
6
2
9
3 85 7
Overall Dimensions
Features
1. Module A with EQ system2. Module B with EQ system3. Insula ng load-bearingframe4. Electrodes5. Air gap
6. A achment point of module A7. A achment point of module B8. Auxiliary electrode withone me glass indicator9. Composite insulator (notincluded)
170
min
460
40...6040max
M10
82
SAdS15zLine Lightning Protec onDevice for Overhead Linesup to 17.5 kV
LLPD SAdS15z is intended for pro-tec on of overhead lines with the highest voltage for equipment up to 17.5 kV and high short-circuit currents against direct ligh ng strikes, back flashovers and induced overvoltages, as well as their deleterious consequences.
• DLS protec on ofoverhead power lines• Preven on of conductors and insulatorsbreakage• DLS endurance
26
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Performance specifica on and characteris cs
Insulator’sCFO (kV)
SAd15z:Air gap, mm
SAdS15z: power frequencywithstand voltage, kV
< 140160180200220240
6570758085
Contact us80-100
100-120120-140140-160160-180
Contact us5560657075
Contact us
Installa onOverview1 piece per phase for each circuit on one pole for ensuring comprehensive protec on of an overhead line against DLS, BFO and IOV.
LLPD SAdS15z must be installed with an air gap between upper and lower elec-trodes. In order to select the proper value of the gap, please refer to the table.
Reference: SAD.S15.Z.WW/920
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
560±2014038
2.4653010
02010002.81 visual verifica on per year
17.5
www.streamer-electric.com 27
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
Possible op ons
PIN / POST insula onUsing BTA.155 bracket (for more informa on, please, refer to Brackets pages)
Agai
nst I
ndire
ct a
nd D
irect
Ligh
tnin
g
28
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
Possible op ons
Using addi onal cross-arm PCF.800 + BTA.156 bracket
PIN / POST insula on
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
www.streamer-electric.com 29
DLS protec on of overhead power linesPreven on of conductors and insulatorsbreakageDLS endurance
115
4
Overall Dimensions
Features
1. Module A with EQ system2. Module B with EQ system3. Insula ng load-bearingframe
4. A achment point5. Terminal electrodewith indicator
423
284
248
SAdC20zLine Lightning Protec onDevice for OverheadLines up to 24 kV
LLPD SAdC20z is intended for pro-tec on of overhead lines with nominal voltage up to 24 kV against direct lightning strikes, back flashovers, induced over-voltages and their deleterious consequences
30
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Agai
nst I
ndire
ct a
nd D
irect
Ligh
tnin
g
Performance specifica on and characteris cs
Insulator’sCFO (kV)
SAdC20z: Air gap (mm)
6 to 17 kV Highest voltagefor equipment
18 to 24 kV Highest voltagefor equipment
< 120120140160180200
4045556580
Contact us
60607590
Contact usContact us
1 piece per phase for each circuit on one pole for ensuring comprehensive protec on of an overhead line against DLS, BFO and IOV.LLPD SAdC20z must be installed with an air gap between upper and lower electrodes. In order to select the proper value of the gap, please address to the table.
Installa onOverview
Reference: SAD.C20.Z.WW/920
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
570±1016050
2.465310
02010002.51 visual verifica on per year
24
www.streamer-electric.com 31
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029 + EPC.100b. CCi90.4531 + EPC.100c. CCi90.6531 + EPC.100
Possible op ons
PIN / POST insula onUsing BCL.190 bracket
32
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
TENSION insula onUsing BCL.190 bracket
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
www.streamer-electric.com 33
1
5
4
3
2
Overall Dimensions
Features1. SAd21z, which is a “ring”with EQ system integratedwith a PPS loadbearingframe2. Electrode with indicator3. Air gap
4. Horn electrode(see Electrode page)5. Addi onal compositeinsulator
DLS protec onPreven on of conductors and insulatorsbreakageDLS endurance
485
22066
70max
SAd21zLine Lightning Protec onDevice for OverheadLines up to 24 kV
LLPD SAd21z is intended for pro-tec on of overhead lines with nominal voltage up to 24 kV against direct ligh ng strikes, back flashovers, induced over-voltages and their deleterious consequences
34
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Performance specifica on and characteris cs
Installa onOverview
Insulator’sCFO (kV)
SAd21z: Air gap (mm)6 to 17 kV Highest voltage
for equipment18 to 24 kV Highest voltage
for equipment
< 120120140160180200
4045556580
Contact us
60607090
Contact usContact us
1 piece per phase each circuit on one pole for ensuring comprehensive protec on of an overhead line against DLS, BFO and IOV.LLPD SAd21z must be installed with an air gap between its electrode and horn elec-trode. In order to select the proper value of the gap, please address to the table.
Reference: SAD.021.Z.WW/920
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
570±1016050
2.4653010
02010002.21 visual verifica on per year
24
www.streamer-electric.com 35
Using BTA.155 bracketPIN / POST insula on
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
Possible op ons
36
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
PIN / POST insula onUsing addi onal cross-arm PCF.800 + BTA.156 bracket
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
Possible op ons
www.streamer-electric.com 37
TENSION / SUSPENSION insula onUsing BTA.155 bracket
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
Possible op ons
38
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
TENSION / SUSPENSION insula onUsing addi onal cross-arm PCF.800 + BTA.156 bracket
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
(for more informa on, please,refer to Jumpers page)Jumper for conductor clamps:
JUM.017Jumper for IPCs:
JUM.C17 JUM.S16
Possible op ons
www.streamer-electric.com 39
Overall Dimensions
Features
1. Upper “ring” with EQsystem integrated with aPPS load-bearing frame2. Upper electrode3. Air gap
4. Lower “ring” with EQsystem integrated with a PPSload-bearing frame5. Lower electrode with indicator6. A achment point
4
5
6
2
3
Upper ring / Lower ring
DLS protec onPreven on of conductors and insulatorsbreakageDLS endurance
M12
82
461
100
SAdM35zLine Lightning Protec onDevice for OverheadLines up to 40.5 kV
LLPD SAdM35z is intended for protec on of overhead lines with nominal voltage up to 40.5 kV against direct ligh ng strikes, back flashovers, induced over-voltages and their deleterious consequences
40
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Insulator’s CFO (kV) SAdM35z: Air gap (mm)
< 180180200220240260
120140160180200
Contact us 1 piece per phase for each circuit on one pole for ensuring comprehensive protec on of an overhead line against DLS, BFO.LLPD SAdM35z must be installed with an air gap between upper and lower electrodes. In order to select the proper value of the gap, please refer to the table.
Performance specifica on and characteris cs
Installa onOverview
Reference: SAD.M35.Z.WW/920
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
* According to IEC 60038, ** According to IEC 60071-1., *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
ELECTRICAL LINE PARAMETERSHighest voltage for equipment*, kVMaximum prospec ve fault current, kAExternal air gap, mm
Power frequency withstand voltage**, kV50% flashover voltage, kV
LIGHTNING PARAMETERS
GENERAL PARAMETERS
Lightning discharge capability (200 μs)***, CHigh current impulse (4/10 μs), kAMaximum fault quenching lightning current (1/50 μs), kAMinimum withstand amount of opera ons
Addi onal power losses on the line, %Average life me expectancy, yearsUV resistance****, hWeightMaintenance
5150±3023080
2.4653010
02010005.31 visual verifica on per year
40.5
www.streamer-electric.com 41
SUSPENSION insula onNo extra bracketsare required
(for more informa on, please,refer to Conductor clamp pages)
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
3. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
Possible op ons
PIN / POST insula onUsing BTA.155 bracket
(for more informa on, please,refer to Jumpers page)
JUM.S35
Possible op ons
42
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
TENSION insula on (with addi onal / exis ng string of cap-and-pin insulators)Using BTA.100 bracket
TENSION insula on (with addi onal / exis ng string of cap-and-pin insulators)Using BTA.155 bracket
Agai
nst i
ndire
ct a
nd d
irect
ligh
tnin
g
www.streamer-electric.com 43
Conductor clampsNon-piercing clamps for bare conductors
Conductor clamp CB90.0006.SSReference: CB90.0006.SS
6
Stainless steel-
Minimum externaldiameterof a conductor, mm
15Maximum externaldiameterof a conductor, mmMaterialCoa ngWeight, kg 0.14
18
9
Stainless steel-
Maximum externaldiameterof a conductor, mmMaterialCoa ngWeight, kg
Reference: CB90.0009.SS
0.15
24
18
Stainless steel
0.16-
Maximum externaldiameterof a conductor, mmMaterialCoa ngWeight, kg
Reference: CB90.0018.SS
Conductor clamp CB90.0009.SS
Conductor clamp CB90.0018.SS
Cond
ucto
r Cla
mps
25
44
3
4435
9
132
M8
132
9
3
41
2535
44
M8
132
9
3
44
2535
44
M8
Minimum externaldiameterof a conductor, mm
Minimum externaldiameterof a conductor, mm
44
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Conductor clampsPiercing clamps for covered conductors
Reference: CC90.2509.SSConductor clamp CC90.2509.SS
Reference: CC90.2518.SSConductor clamp CC90.2518.SS
18
9
2.5
Stainlesssteel
-
Maximum externaldiameterof a conductor, mm
Material
Coa ngWeight, kg
Maximum thickness ofinsula on layer, mm
0.15
24
18
2.5
Stainlesssteel
-
Maximum externaldiameterof a conductor, mm
Material
Coa ngWeight, kg
Maximum thickness ofinsula on layer, mm
0.16
Cond
ucto
r Cla
mps
132
9
25
45
3
35
44
M8
132
25
9
35
45
44
3
M8
Minimum externaldiameterof a conductor, mm
Minimum externaldiameterof a conductor, mm
www.streamer-electric.com 45
Conductor clampsInsulated piercing clamps (IPC) for covered conductors
Insulated piercing clamp CCi90.3029
Insulated piercing clamp CCi90.4531
Insulated piercing clamp CCi90.6531
29
3.0
0.25
Stainless steel
-
Maximum external diameterof a conductor, mm
Material
Coa ng
Weight, kg
Maximum thickness ofinsula on layer, mm
31
4.5
0.30
Stainless steel
-
Maximum external diameterof a conductor, mm
Material
Coa ng
Weight, kg
Maximum thickness ofinsula on layer, mm
31
6.5
0.35
Stainless steel
-
Maximum external diameterof a conductor, mm
Material
Coa ng
Weight, kg
Maximum thickness ofinsula on layer, mm
Reference: CCi90.3029.WW
Reference: CCi90.4531.WW
Reference: CCi90.6531.WW
Cond
ucto
r Cla
mps
8556
147
8556
147
8556
147
46
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Horn electrodes for LLPDsHorn electrode HRN.0838
Horn electrode HRN.1238
Horn electrode HRN.1638
Reference: HRN.0838.WW
Reference: HRN.1238.WW
Reference: HRN.1638.WW
75
40
Steel
HDG, 75 μm
Horn electrode length, mm
Material
Coa ng
Weight, kg
Maximum external diameterof a insulators’ end fi ng, mm
0.77
115
40
Steel
HDG, 75 μm
Horn electrode length, mm
Material
Coa ng
Weight, kg
Maximum external diameterof a insulators’ end fi ng, mm
0.81
155
40
Steel
HDG, 75 μm
Horn electrode length, mm
Material
Coa ng
Weight, kg
Maximum external diameterof a insulators’ end fi ng, mm
0.86
Horn
Ele
ctro
des
266
90
30
M10
40max
63
266
130
30
M10
40max
63
266
170
30
M10
40max
63
www.streamer-electric.com 47
For LLPDs up to 24 kVAccessories for installa on for covered conductors
Jumper JUM.C17
JUM.017.15JUM.017.17JUM.017.20JUM.017.22JUM.017.25
Reference Length, mTerminal 1
connec onop ons
JUM.C17.15JUM.С17.17JUM.С17.20JUM.С17.22JUM.С17.25
1.501.752.002.252.50
CCi90.3029CCi90.4531CCi90.6531
Terminal 2 connec on
op ons
Compositeinsulator’send fi ng,17 mm hole
1.5Terminal 1
Terminal 2
Jumper JUM.017
Reference Length, mTerminal 1 connec on
op ons1.501.752.002.252.50
CC90.2509.SSCC90.2518.SS
Terminal 2 connec on
op ons
Compositeinsulator’send fi ng,17 mm hole
Terminal 1
Terminal 2
Jum
pers
Thickness ofinsula on layer,
mm
1.5
Thickness ofinsula on layer,
mm
JUM.S16.WW
Jumper JUM.S16
Reference Length, mTerminal 1 connec on
op ons
3.00(length to be
adjusted on site)
free end forCCi90.3029CCi90.4531CCi90.6531
Terminal 2 connec on
op ons
Compositeinsulator’send fi ng,17 mm hole
Terminal 1
Terminal 2
1.5
Thickness ofinsula on layer,
mm
48
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
For 40.5 kV LLPDs
Terminal 1
Terminal 2
JUM.017.15JUM.017.17JUM.017.20JUM.017.22JUM.017.25
Jumper JUM.017
Reference Length, mTerminal 1 connec on
op ons1.501.752.002.252.50
CB90.0006.SSCB90.0009.SSCB90.0018.SS
Terminal 2 connec on
op ons
Compositeinsulator’send fi ng,17 mm hole
Accessories for installa on for BARE conductors
Jum
pers
1.5
Thickness ofinsula on layer,
mm
JUM.S35.WW
Jumper JUM.S35
Reference Length, mTerminal 1 connec on
op ons
3.00(length to be
adjusted on site)
free end forCCi90.3029CCi90.4531CCi90.6531
Terminal 2 connec on
op ons
Compositeinsulator’send fi ng,17 mm hole
Terminal 1
Terminal 2
2.5
Thickness ofinsula on layer,
mm
www.streamer-electric.com 49
IndicatorsOne- me indica on of LLPD opera on
Possible op ons
Indicator SGI.142
For CB90.00XX and CC90.25XX ranges
1. Conductor clamp for bare conductors:a. CB90.0006.SSb. CB90.0009.SSc. CB90.0018.SS
2. Conductor clamp for covered conductors:a. CC90.2509.SSb. CC90.2518.SS
(for more informa on, please,refer to Conductor clamp pages)
Weight, kg
Compa bility
Reference: SGI.142.WW
CC90.2509.SSCC90.2518.SS
0.13
CB90.0006.SSCB90.0009.SSCB90.0018.SS
Indi
cato
rs
26
131
173
M8
50
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
IndicatorsOne- me indica on of LLPD opera on
Possible op ons
Indicator bent SGI.142.B
For CCi90.XXXX range
1. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
(for more informa on, please,refer to Conductor clamp pages)
Weight, kg
Compa bility
Reference: SGI.142.B. WW
0.15
ССi90.3029.WWССi90.4531.WWССi90.6531.WW
Indi
cato
rs
26
M8
126
149
87
www.streamer-electric.com 51
Elec
trod
e
100
100
10
2x45
2x45 R10
Electrode
Possible op ons
Electrode EPC.100
For CCi90.XXXX range
1. IPC (insulated piercing clamp):a. CCi90.3029b. CCi90.4531c. CCi90.6531
(for more informa on, please,refer to Conductor clamp pages)
ССi90.3029.WWССi90.4531.WWССi90.6531.WW
Weight, kg
Compa bility
0.12
Reference: EPC.100.WW
52
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Brac
kets
155x120
Steel
1.17Zn, HDG 75 μm
Reference: BCL.141.WW
Maximum permissiblesize of a cross-arm, mm
MaterialCoa ngWeight, kg
Bracket BCL.141Brackets
Reference: BCL.190.WW
155150
HDG, 75 μm
1.8
17
Permissible sizeof cross-arm, mm:Width (W)Height (H)
Zinc coa ng
Weight, kg
Diameter of a holein composite insulator’send fi ng, mm
Bracket BCL.19014
0 m
ax 249
65371
160
35
70
170
577
130max
170
M12
103
170
70
222
160
www.streamer-electric.com 53
Brac
kets Bracket BLD.91
90x90
SteelZn, HDG 75 μm0.66
Maximum permissiblesize of the L-bar, mm
MaterialCoa ngWeight, kg
Reference: BLD.091.WW
Bracket BPD.38Reference: BPD.038.WW
38
SteelZn, HDG 75 μm0.2
Maximum externaldiameter of a pin, mm
MaterialCoa ngWeight, kg
23
Steel
0.35Zn, HDG 75 μm
Reference: BPD.023.WW
Maximum diameterof insulator’s pin, mm
MaterialCoa ngWeight, kg
Bracket BPD.23
Brackets
30
110
660
174
90
44
135
40
M12
21
5
M10
66
6
12538max
54
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
Brac
kets
Reference: BTA.155.WWBracket BTA.155
Brackets
155120
HDG, 75 μm
1.8
17
Permissible sizeof cross-arm, mm:Width (W)Height (H)
Zinc coa ng
Weight, kg
Diameter of a holein composite insulator’sendfi ng, mm
Bracket BTA.100Reference: BTA.100.WW
120-150260-300
HDG, 75 μm
2
Permissible sizeof cross-arm,mm:Width (W)Height (H)
Zinc coa ng
Weight, kg
65
75
260
160
200
170
70
40
M16
M12
250
M12
400
www.streamer-electric.com 55
Brac
kets
Reference: BTA.156.WW
HDG, 75 μm
1.8
17
18
Diameter of a holein addi onalcross-arm, mm
Zinc coa ng
Weight, kg
Diameter of a holein composite insulator’send fi ng, mm
Bracket BTA.156
Bracket BTE.113
SteelZn, HDG 75 μm0.13
MaterialCoa ngWeight, kg
Reference: BTE.113.WW
Brackets
30
R818.5
143.5
R155.
5
18.52526
30
R814R153.5
113
114
80
M16
160
M16
40
60
32
52
56
Line Lightning Protec on Devices Catalogue 2017
Streamer Interna onal AG
800
400
576
40
40
18Weight, kg
Compa bility: SAdS15zSAd21zSAdM35z
10
Brac
kets
Reference: PCF.800.WWFor SAdS15z, SAd21z, SAdM35z
Addi onal cross-arm PCF.800
Instala on
Brackets
Op on 1: using metalmoun ng band
3 bands per 1 bracket
Op on 2: Two wood screwsin the upper and lower partsof the bracket, plus 2 bands
for be er reliability
2 bands per 1 bracket
Suitable wood screws:
Washer(DIN 125)
Quan ty,pcs
12 2+22+22+2
1616
Wood scre(DIN 571)
12х10016х80
16х100
www.streamer-electric.com 57